CATALOGO ESPECIFICO DE PRODUCTO

RECLOSER TRIFÁSICO – REVAC 36

EFACEC ENERGIA – Máquinas e Equipamentos Eléctricos, S.A. ● Apartado 1018 ● 4466-952 S. Mamede Infesta Portugal
Capital Social 16.800.000 EUR ● Nº Matricula/NIPC 504040847
Catalogo Especifico de Producto : REVAC 36

RECLOSER TRIFÁSICO – REVAC 36

Características Generales
Aparato : Recloser Trifasico – REVAC 36
Nº Polos/aparato : Tripolar
Normas aplicables : IEC 62271-111/IEEE C37.60 /IEC
62271-1
Instalacion : Exterior
Temperatura de operación : -10ºC a 40ºC
Altitud máxima : 4000 m
Tipo de instalacion : Montaje en subestacion
Material de la cuba : Acero inoxidable
Pintura : Standard
Grado de proteccion : IP55
Aisladores : Silicona/polimérico, desmontables
por bushing
Terminales: Cobre niquelado, roscados( M16x60)
Peso : 160 kg
Controlador electronico : RCU 220

Caracteristicas electricas/mecanicas
Tensión nominal : 22.9 kV
Tensión Máxima de diseño : 38 kV
Corriente nominal : 630 A
Corriente de corto-circuito de corta duración : 12.5 kA (3s)
Corriente de cierre del cortocircuito : 31.5 kAp
Frequência nominal : 60 Hz
Nivel de aislamiento a frecuencia Industrial 60Hz-1 min, seco : 70 kVef
Nivel de aislamiento a frecuencia Industrial 60Hz-10 segundos, 60 kVef
húmedo :
Nivel de Aislamiento (BIL) 1,2/50us : 170 kVp
Mecanismo de actuacion : Actuador magnetico
Interrupción del arco eléctrico : Vacío
Aislamiento del medio de interrupción del arco eléctrico: Resina HCEP
Transformadores de corriente de protección : 3
- Relacion de transformacion : 400:1 A
- Precision : 5P20
Sensores de tensión sobre bushing: 6
- Precisión de la amplitud de tensión : ± 2%
- Precisión del ángulo de fase : ± 1°
Operaciones Mecánicas 10000
Tiempo de apertura máxima : 0.05 s
Tiempo de cierre máxima : 0.06 s

Pág. 2/3
Catalogo Especifico de Producto : REVAC 36

Principales componentes:
1. Envolvente de actuadores magneticos
2. Transformadores de corriente
3. Sensores de tension
4. Aisladores de silicona
5. Cuba de acero inoxidable
6. Dispositivo de apertura manual por pertiga y bloqueo mecanico
7. Valvula de sobrepresion
8. Base montaje de pararrayos
9. Conector de puesta a tierra
10. Salida de cables de control
11. Tapa inferior de cuba
12. Contador de operaciones
13. Indicador visual abierto/cerrado
14. Placa de caracteristicas
15. Agujeros para izaje

Pág. 3/3
Edition 1

2 OPTIONS OF THE CABINET


 Without magnetic actuator
 With magnetic actuator drive

POWER SUPPLY SYSTEM


SUPERVISION
 Battery voltage monitoring
 Periodic battery tests

USER INTERFACE
 Without local HMI
 With alphanumeric HMI

IEC 61131-3 PROGRAMMING


 General purposes SoftPLC

EMBEDDED HMI SERVER


 Web interface, HMI with vector diagrams

OVERHEAD SWITCHGEAR CONTROLLER MULTIPLE COMMUNICATION


PROTOCOLS
RCU 220E is a recloser/ sectionalizer The RCU 220E also provides open
 IEC 61850
controller that targets protection and IEC 61131-3 programming and full
control of distribution assets together with IEC 61850 communication capabilities  DNP 3
conventional RTU-functionality. It comes enabling fast and selective distributed  IEC 60870-5-101/103/104
in a compact cabinet and includes all peer-to-peer schemes, integration with  Several serial or IP communication
necessary components for recloser centralized feeder control and monitoring protocols are available
application, standing out the RCU 2201 as systems, adaptive schemes for variable
the main control module. power flows or innovative plug-and-
play/ engineering approaches. Despite MULTIPLE COMMUNICATION
The RCU 220E provides not only reclosing OPTIONS
the added-value of advanced functionality
function but also feeder isolation and
and flexibility, RCU 220E is a cost-effective  GPRS/3G/4G
restoration algorithms for loop/ring
controller, carefully designed for integration
configurations. The automatic loop  Radio
with multiple recloser/ interrupter vendors,
restoration control has the advantage of not
easy installation and straightforward  Several Ethernet options
requiring communication capabilities to
configuration and management.
isolate faulty sections and restore power to
unaffected segments. EMBEDDED FUNCTIONS FOR
SECURITY OF ENCLOSURE

AUTOMATION STUDIO-READY
 Integrated configuration and
1 programming
For more information consult the product
datasheet  Simplified engineering and handling
RCU 220E

GENERAL ARCHITECTURE

OPERATION
The RCU 220 is designed for three-phase reclosers supporting either three-phase or single-phase tripping, adapting to
different distribution feeder architectures.

Single-phase trip by three-phase recloser

Full-featured breaker control with voltage check and optional synchronism check are part of the available function set.
The hit-and-run feature (delayed open/close), select-before-operate, secure hardwired or distributed interlocking and
multi-level control authority sources ensure safe operation of the equipment.
The auto-reclose function supports up to 5 reclose cycles with independently configurable dead times, is ready to
integrate in fuse-saving schemes, and includes a zone sequence coordination feature that enables the coordination with
downstream devices avoiding unnecessary trips by upstream reclosers.

2/12
RCU 220E

The RCU 220 can also operate as a sectionalizer / interrupter controller. The built-in sectionalizer function has the ability
to monitor upstream reclosers or circuit breakers, isolating the affected area during upstream recloser dead time,
counting up to five (5) reclosing cycles before opening. In order to increase selectivity automatic sectionalizing is only
performed after a fault has been detected.

Typical scheme of sectionalizer control application

Several independent stages for main fault detection and protection functions enable versatile device applications, in a
true full-scheme design.
For time-graded coordination, the RCU 220 includes both ANSI/IEC standard curves and traditional recloser curves.
Editable time-current curves are also supported, enabling straightforward coordination with all types of interrupting
devices in the network (including legacy equipment, fuses, reclosers programmed with non-standard curves, etc.).
Eight independent setting groups are available and can be interchanged by user command or logic conditions dependent
on system operation.

The RCU 220 can be easily integrated in radial or loop network configurations and includes a flexible loop section isolation
and feeder restoration function that implements a distributed self-healing algorithm based on time intervals and voltage
levels that does not require communications. Upon reconfiguration RCU 220 units are capable of automatically adapting
the control algorithms to the new network topology through flexible settings.

Typical loop/ring feeder configuration

Given the availability of new generation communication networks the self-healing function can be further enhanced with
peer-to-peer GOOSE messaging, providing high-speed and highly reliable operation at all stages of the detection, isolation
and restoration cycle.

3/12
RCU 220E

FUNCTIONS

Sectionalizer Recloser
Protection ANSI IEC 61850
(Directional) Phase Overcurrent 50/51/67   PTOC/RDIR
(Directional) Earth-Fault Overcurrent 50N/51N/67N   PTOC/RDIR
(Directional) Negative Sequence Overcurrent 46/67 (1) (1) PTOC/RDIR
Cold Load Pickup  
Inrush Restraint  
Editable Time-Current-Curves  
Blocking Scheme Logic 68  
Hot Line Mode  
High Current Lockout  
Switch-Onto-Fault 50HS   RSOF/PIOC
Thermal Overload 49   PTTR
Undercurrent / Loss of Load 37   PTUC
Directional Earth-Fault Overcurrent for Non-Earthed
32N   PSDE
Systems
Directional Power 32 (1) (1) PDOP/PDUP
Phase Undervoltage 27   PTUV
Phase Overvoltage 59   PTOV
Residual Overvoltage 59N (1) (1) PTOV
Negative Sequence Overvoltage 47 (1) (1) PTOV
Underfrequency 81 (1) (1) PTUF
Overfrequency 81 (1) (1) PTOF

• - Base feature
(1) - Advanced Protection Option

4/12
RCU 220E

Sectionalizer Recloser
Control and Supervision ANSI IEC 61850
Sectionalizer  (2)
Three-Phase / Single-Phase Trip Logic 94 /(3) PTRC
Three-Phase / Single-Phase Automatic Reclosure 79 /(3) RREC
Automatic Loop Restoration Control 

Voltage Check 

Synchronism and Voltage Check 25 (1) RSYN


Broken Conductor Check 46BC (1) (1) RBCD
Open Pole Detection (3) ROPD
Trip Circuit Supervision 74TC   STRC
Fuse Failure / VT Supervision   RVTS
CT Supervision   RCTS
Circuit Breaker Lockout 86   RCBL
Circuit Breaker Control   CSWI
Three-Phase / Single-Phase Circuit Breaker Supervision 52  /(3) XCBR
Circuit Breaker Contact Wear Monitoring  
Power Supply System Supervision  
Programmable Automation GAPC
 
(IEC 61131-3) (or user defined)
• - Base feature
(1) - Advanced Protection Option
(2) – Recloser + Sectionalizer Option
(3) – Single-Pole Tripping and Reclosing Option

Sectionalizer Recloser
Monitoring, Measurement and Metering ANSI IEC 61850
Three-Phase Measurements   MMXU/MSQI
MMXU
Statistics  
(or user defined)
Metering (4) (4) MMTR
Sags and Swells (4) (4) QVVR
Harmonics (4) (4) MHAI
Fault Locator 21FL (1) (1) RFLO

Recording and reporting ANSI IEC 61850


Chronological Event Log  
Disturbance Recorder   RDRE
Power Quality Event Recorder (4) (4)
Load Diagram / Trend Recorder  
Histogram  
Fault Report  

• - Base feature
(1) - Advanced Protection Option
(2) – Recloser + Sectionalizer Option
(3) – Single-Pole Tripping and Reclosing Option
(4) – Power Quality Option (currently under development)

5/12
RCU 220E

TECHNICAL SPECIFICATIONS

A.C. Analogue Current Inputs


Number 4, 4th input with high sensitivity
Standard inputs (1 to 3) Rated current Ir = 1 or 5 A
Operation range [0.05 .. 50] × Ir
500 A for 1 s
Thermal withstand
20 A continuous
Burden < 0.15 VA @ Ir
Sensitive inputs (4th Input) Rated current Ir = 1 or 5 A
Operation range [0.005 .. 5.0] × Ir
250 A for 1 s
Thermal withstand
10 A continuous
Burden < 0.25 VA @ Ir

A.C. Analogue Voltage Inputs


Number 6 via resistive sensors

Environmental Conditions
Operating temperature range - 25 °C to + 70 °C
Recommended: - 5 °C to + 55 °C
Relative humidity <95 %
Protection degree IP 55

CE Marking
Electromagnetic compatibility directive Immunity EN 61000-6-2: 2005
EN 61439-1:2011
Emission EN 61000-6-3: 2007 + A1: 2011
EN 61439-1:2011
Low voltage directive EN 61439-1:2011
EN 60255-5: 2001

Insulation Tests
High voltage test 2.5 kV a.c. 1 min. 50 Hz
EN 60255-5
3 kV d.c. 1 min. (power supply)
Impulse voltage test EN 60255-5 5 kV 1.2/50 s, 0.5 J
Insulation resistance test EN 60255-5 > 100 M a 500 V d.c.

6/12
RCU 220E

DIMENSIONS
V1 OPTION, WITHOUT MAGNETIC ACTUATOR DRIVE

All dimensions in millimetres

V2 OPTION, WITH MAGNETIC ACTUATOR DRIVE

All dimensions in millimetres

7/12
RCU 220E

CONNECTION DIAGRAM

Note: this diagram undertakes an option with resistive voltage inputs and current tori. At the V2 Option, the magnetic actuator
drive and DC/DC converter are placed inside of the cabinet.

8/12
RCU 220E

CONNECTIONS AND CONNECTORS TYPE


V1 OPTION

Male Connector - MS3102A 20-15P Male Connector - MS3102A 28-16P Male Connector - MS3102A 28-16P
XPC1 XPC2 XPC3
standard military type standard military type standard military type
A Power supply input a.c., Phase R Power supply output a.c., Phase A Voltage input U1
F Power supply input a.c., Neutral S Power supply output a.c., Neutral B Voltage input U2
U Earth protection C Voltage input U3
J Output (Pol. +) 48 V d.c. D Common voltage input U1 to U3
E Sin. input OCR Open E Voltage input U4
F Sin. input OCR Closed F Voltage input U5
G Sin. input OCR Blocked G Voltage input U6
M Actuator drive alarm H Common voltage input U4 to U6
H Open control
M Common
K Close control
L Current input I1
N Current input I2
P Current input I3
Q Current input I4

V2 OPTION

Male Connector - MS3102A 20-15P Male Connector - MS3102A 28-16P Male Connector - MS3102A 28-16P
XPC1 XPC2 XPC3
standard military type standard military type standard military type
A Power supply input a.c., Phase R Power supply output a.c., Phase A Voltage input U1
F Power supply input a.c., Neutral S Power supply output a.c., Neutral B Voltage input U2
U Earth protection C Voltage input U3
J Output (Pol. +) 48 V d.c. D Common voltage input U1 to U3
E Sin. Input OCR Open E Voltage input U4
F Sin. Input OCR Closed F Voltage input U5
G Sin. Input OCR Blocked G Voltage input U6
H H Common voltage input U4 to U6
Open control
M
K
Close control
T
L Current input I1
N Current input I2
P Current input I3
Q Current input I4

9/12
RCU 220E

ORDER FORM

RCU 220E-1- A - B - C - D - E - F - G - H
HMI
Not used X
Alphanumeric A

Variant
With magnetic actuator drive V1
Without magnetic actuator drive V2

Power Supply
110 V a.c. 110
230 V a.c. 230
Other – please contact

Cabinet Type
Type 1 – stainless, for aerial applications 1
Other – please contact

Actuator Power Supply


220 V d.c. 220
48 V d.c. 48
Other – please contact

SCADA Communication
GPRS G
Radio R
Ethernet 10/100BASE-TX E
Other – please contact 12

Spare
X

Communication Protocols
According to
Table 1 & 2

Table 1, Slave/Server Protocols (up) Code Table 2, Master/Client Protocols (down) Code
None X None X
IEC 60870-5-104/ IEC 60870-5-101 A Modbus E
IEC 61850-8-1 MMS Server and GOOSE Other listed in the Communication Protocols
C
publish/subscribe table, please contact
DNP 3.0 D
Other listed in the Communication
Protocols table, please contact

10/12
RCU 220E

NOTES

11/12
2016-09-23, AS16004189 Rev. 1.0

Automation Business Unit


Rua Eng. Frederico Ulrich, 4471-907 Moreira Maia, Portugal  Tel. +351 22 940 20 00  Fax +351 22 948 54 28
E-mail: ase.eng@efacec.com  Web: www.efacec.com

Due to the continuous development, the characteristics may change without notice. Not valid as a contractual item.