Catalogo Especifico de Producto : REVAC 36
Características Generales
Aparato : Recloser Trifasico – REVAC 36
Nº Polos/aparato : Tripolar
Normas aplicables : IEC 62271-111/IEEE C37.60 /IEC
62271-1
Instalacion : Exterior
Temperatura de operación : -10ºC a 40ºC
Altitud máxima : 4000 m
Tipo de instalacion : Montaje en subestacion
Material de la cuba : Acero inoxidable
Pintura : Standard
Grado de proteccion : IP55
Aisladores : Silicona/polimérico, desmontables
por bushing
Terminales: Cobre niquelado, roscados( M16x60)
Peso : 160 kg
Controlador electronico : RCU 220
Caracteristicas electricas/mecanicas
Tensión nominal : 22.9 kV
Tensión Máxima de diseño : 38 kV
Corriente nominal : 630 A
Corriente de corto-circuito de corta duración : 12.5 kA (3s)
Corriente de cierre del cortocircuito : 31.5 kAp
Frequência nominal : 60 Hz
Nivel de aislamiento a frecuencia Industrial 60Hz-1 min, seco : 70 kVef
Nivel de aislamiento a frecuencia Industrial 60Hz-10 segundos, 60 kVef
húmedo :
Nivel de Aislamiento (BIL) 1,2/50us : 170 kVp
Mecanismo de actuacion : Actuador magnetico
Interrupción del arco eléctrico : Vacío
Aislamiento del medio de interrupción del arco eléctrico: Resina HCEP
Transformadores de corriente de protección : 3
- Relacion de transformacion : 400:1 A
- Precision : 5P20
Sensores de tensión sobre bushing: 6
- Precisión de la amplitud de tensión : ± 2%
- Precisión del ángulo de fase : ± 1°
Operaciones Mecánicas 10000
Tiempo de apertura máxima : 0.05 s
Tiempo de cierre máxima : 0.06 s
Pág. 2/3
Catalogo Especifico de Producto : REVAC 36
Principales componentes:
1. Envolvente de actuadores magneticos
2. Transformadores de corriente
3. Sensores de tension
4. Aisladores de silicona
5. Cuba de acero inoxidable
6. Dispositivo de apertura manual por pertiga y bloqueo mecanico
7. Valvula de sobrepresion
8. Base montaje de pararrayos
9. Conector de puesta a tierra
10. Salida de cables de control
11. Tapa inferior de cuba
12. Contador de operaciones
13. Indicador visual abierto/cerrado
14. Placa de caracteristicas
15. Agujeros para izaje
Pág. 3/3
Edition 1
USER INTERFACE
Without local HMI
With alphanumeric HMI
AUTOMATION STUDIO-READY
Integrated configuration and
1 programming
For more information consult the product
datasheet Simplified engineering and handling
RCU 220E
GENERAL ARCHITECTURE
OPERATION
The RCU 220 is designed for three-phase reclosers supporting either three-phase or single-phase tripping, adapting to
different distribution feeder architectures.
Full-featured breaker control with voltage check and optional synchronism check are part of the available function set.
The hit-and-run feature (delayed open/close), select-before-operate, secure hardwired or distributed interlocking and
multi-level control authority sources ensure safe operation of the equipment.
The auto-reclose function supports up to 5 reclose cycles with independently configurable dead times, is ready to
integrate in fuse-saving schemes, and includes a zone sequence coordination feature that enables the coordination with
downstream devices avoiding unnecessary trips by upstream reclosers.
2/12
RCU 220E
The RCU 220 can also operate as a sectionalizer / interrupter controller. The built-in sectionalizer function has the ability
to monitor upstream reclosers or circuit breakers, isolating the affected area during upstream recloser dead time,
counting up to five (5) reclosing cycles before opening. In order to increase selectivity automatic sectionalizing is only
performed after a fault has been detected.
Several independent stages for main fault detection and protection functions enable versatile device applications, in a
true full-scheme design.
For time-graded coordination, the RCU 220 includes both ANSI/IEC standard curves and traditional recloser curves.
Editable time-current curves are also supported, enabling straightforward coordination with all types of interrupting
devices in the network (including legacy equipment, fuses, reclosers programmed with non-standard curves, etc.).
Eight independent setting groups are available and can be interchanged by user command or logic conditions dependent
on system operation.
The RCU 220 can be easily integrated in radial or loop network configurations and includes a flexible loop section isolation
and feeder restoration function that implements a distributed self-healing algorithm based on time intervals and voltage
levels that does not require communications. Upon reconfiguration RCU 220 units are capable of automatically adapting
the control algorithms to the new network topology through flexible settings.
Given the availability of new generation communication networks the self-healing function can be further enhanced with
peer-to-peer GOOSE messaging, providing high-speed and highly reliable operation at all stages of the detection, isolation
and restoration cycle.
3/12
RCU 220E
FUNCTIONS
Sectionalizer Recloser
Protection ANSI IEC 61850
(Directional) Phase Overcurrent 50/51/67 PTOC/RDIR
(Directional) Earth-Fault Overcurrent 50N/51N/67N PTOC/RDIR
(Directional) Negative Sequence Overcurrent 46/67 (1) (1) PTOC/RDIR
Cold Load Pickup
Inrush Restraint
Editable Time-Current-Curves
Blocking Scheme Logic 68
Hot Line Mode
High Current Lockout
Switch-Onto-Fault 50HS RSOF/PIOC
Thermal Overload 49 PTTR
Undercurrent / Loss of Load 37 PTUC
Directional Earth-Fault Overcurrent for Non-Earthed
32N PSDE
Systems
Directional Power 32 (1) (1) PDOP/PDUP
Phase Undervoltage 27 PTUV
Phase Overvoltage 59 PTOV
Residual Overvoltage 59N (1) (1) PTOV
Negative Sequence Overvoltage 47 (1) (1) PTOV
Underfrequency 81 (1) (1) PTUF
Overfrequency 81 (1) (1) PTOF
• - Base feature
(1) - Advanced Protection Option
4/12
RCU 220E
Sectionalizer Recloser
Control and Supervision ANSI IEC 61850
Sectionalizer (2)
Three-Phase / Single-Phase Trip Logic 94 /(3) PTRC
Three-Phase / Single-Phase Automatic Reclosure 79 /(3) RREC
Automatic Loop Restoration Control
Voltage Check
Sectionalizer Recloser
Monitoring, Measurement and Metering ANSI IEC 61850
Three-Phase Measurements MMXU/MSQI
MMXU
Statistics
(or user defined)
Metering (4) (4) MMTR
Sags and Swells (4) (4) QVVR
Harmonics (4) (4) MHAI
Fault Locator 21FL (1) (1) RFLO
• - Base feature
(1) - Advanced Protection Option
(2) – Recloser + Sectionalizer Option
(3) – Single-Pole Tripping and Reclosing Option
(4) – Power Quality Option (currently under development)
5/12
RCU 220E
TECHNICAL SPECIFICATIONS
Environmental Conditions
Operating temperature range - 25 °C to + 70 °C
Recommended: - 5 °C to + 55 °C
Relative humidity <95 %
Protection degree IP 55
CE Marking
Electromagnetic compatibility directive Immunity EN 61000-6-2: 2005
EN 61439-1:2011
Emission EN 61000-6-3: 2007 + A1: 2011
EN 61439-1:2011
Low voltage directive EN 61439-1:2011
EN 60255-5: 2001
Insulation Tests
High voltage test 2.5 kV a.c. 1 min. 50 Hz
EN 60255-5
3 kV d.c. 1 min. (power supply)
Impulse voltage test EN 60255-5 5 kV 1.2/50 s, 0.5 J
Insulation resistance test EN 60255-5 > 100 M a 500 V d.c.
6/12
RCU 220E
DIMENSIONS
V1 OPTION, WITHOUT MAGNETIC ACTUATOR DRIVE
7/12
RCU 220E
CONNECTION DIAGRAM
Note: this diagram undertakes an option with resistive voltage inputs and current tori. At the V2 Option, the magnetic actuator
drive and DC/DC converter are placed inside of the cabinet.
8/12
RCU 220E
Male Connector - MS3102A 20-15P Male Connector - MS3102A 28-16P Male Connector - MS3102A 28-16P
XPC1 XPC2 XPC3
standard military type standard military type standard military type
A Power supply input a.c., Phase R Power supply output a.c., Phase A Voltage input U1
F Power supply input a.c., Neutral S Power supply output a.c., Neutral B Voltage input U2
U Earth protection C Voltage input U3
J Output (Pol. +) 48 V d.c. D Common voltage input U1 to U3
E Sin. input OCR Open E Voltage input U4
F Sin. input OCR Closed F Voltage input U5
G Sin. input OCR Blocked G Voltage input U6
M Actuator drive alarm H Common voltage input U4 to U6
H Open control
M Common
K Close control
L Current input I1
N Current input I2
P Current input I3
Q Current input I4
V2 OPTION
Male Connector - MS3102A 20-15P Male Connector - MS3102A 28-16P Male Connector - MS3102A 28-16P
XPC1 XPC2 XPC3
standard military type standard military type standard military type
A Power supply input a.c., Phase R Power supply output a.c., Phase A Voltage input U1
F Power supply input a.c., Neutral S Power supply output a.c., Neutral B Voltage input U2
U Earth protection C Voltage input U3
J Output (Pol. +) 48 V d.c. D Common voltage input U1 to U3
E Sin. Input OCR Open E Voltage input U4
F Sin. Input OCR Closed F Voltage input U5
G Sin. Input OCR Blocked G Voltage input U6
H H Common voltage input U4 to U6
Open control
M
K
Close control
T
L Current input I1
N Current input I2
P Current input I3
Q Current input I4
9/12
RCU 220E
ORDER FORM
RCU 220E-1- A - B - C - D - E - F - G - H
HMI
Not used X
Alphanumeric A
Variant
With magnetic actuator drive V1
Without magnetic actuator drive V2
Power Supply
110 V a.c. 110
230 V a.c. 230
Other – please contact
Cabinet Type
Type 1 – stainless, for aerial applications 1
Other – please contact
SCADA Communication
GPRS G
Radio R
Ethernet 10/100BASE-TX E
Other – please contact 12
Spare
X
Communication Protocols
According to
Table 1 & 2
Table 1, Slave/Server Protocols (up) Code Table 2, Master/Client Protocols (down) Code
None X None X
IEC 60870-5-104/ IEC 60870-5-101 A Modbus E
IEC 61850-8-1 MMS Server and GOOSE Other listed in the Communication Protocols
C
publish/subscribe table, please contact
DNP 3.0 D
Other listed in the Communication
Protocols table, please contact
10/12
RCU 220E
NOTES
11/12
2016-09-23, AS16004189 Rev. 1.0
Due to the continuous development, the characteristics may change without notice. Not valid as a contractual item.