Professional Documents
Culture Documents
Components Inc.
A laminated bus bar is an electronic package made up of thin, flat metal conductors separated
and bonded together by a dielectric material and sandwiched between outer insulating covers.
The number of layers, size and thickness of conductors, type and thickness of dielectric
material, as well as method of termination depend on the electrical and physical requirements of
the specific application. Input and output terminals can be configured for soldering, mechanical
or connectorized methods of attachment. The outer insulation surface can be used for required
identification and termination designators.
Benefits
♦ Customized modular form for ease of ♦ Low characteristic impedance.
handling and installation.
♦ Superior grounding and shielding
♦ Encapsulated and moisture sealed for capability.
Military/Aerospace applications.
♦ Better heat dissipation because of thin,
♦ High distributed capacitance. wide conductors.
Page 2
Insulation Materials
A variety of materials can be used for insulation between
conductors and for the outer covers. If the bus bar is to
be edge-filled, epoxy glass is recommended for top and
bottom insulators. If it is to be sealed by pinching off the
insulation, we recommend the use of Nomex*.
* Dupont trademark
Page 3
Mounting Holes
The insulated mounting holes of almost any size may be incorporated into laminated bus bars.
However, we recommend the standards shown in the table below. The number of mounting
holes and their placement will depend on the bus bar size and configuration.
Enough metal must be left around the conductor holes to satisfy electrical requirements. A
0.125” / 0.250” insulated hole in a 1.00” wide conductor is shown below.
0.125” 0.250”
0.156” 0.250”
0.180” 0.281”
0.205” 0.312”
Edge Sealing
Depending on the application, exposed conductor edges may be sealed by edge filling or pinch
bonding.
Page 4
Conductor Selection Material
The selection of conductor material is based on electrical requirements and intended methods of
termination:
Copper: The most common material used, due to its excellent electrical and thermal properties.
Aluminum: Due to its excellent weight in volume ratio, (60% of copper), aluminum can be used
where weight is a consideration.
Brass: Often selected where material strength is more important than conductivity.
Conductor Size
A major factor in determining bus bar conductor size,
is the system’s electrical requirements which include
voltage current, temperature rise and voltage drop.
Additionally, many bus bars act as structural
members. They may contain, or act as the interface
for circuit components such as IGBTs, capacitors,
diodes, fuses, etc.
As a general guideline, 300 square mils of copper per amp can be used. When two or more
conductors are laminated together, an allowance should be considered to provide for possible heat
build-up. On average, the cross sectional area of each conductor should be increased by
approximately 7½%, for each bus bar layer.
Conductor Resistance: Bus bar conductor resistance depends on the material used and cross
sectional area. To determine the Resistance of a given conductor refer to Tables 1 & 2, and apply
the following formula
Since the resistance of the conductor changes with temperature, for operational temperatures of
other than 20° C, allowable variations have to be incorporated. The minimal cross sectional area (in
copper) can be determined by:
A = 3 0 0 x I x [1 + .075(N-1)]
A more accurate method of determining conductor size is by the voltage drop method. Allowable
voltage drop is the governing factor in conductor selection and is directly dependant on the cross
sectional area and the length of the bus bar. Voltage drop can be determined by use of the following
formula.
V= R x I
To find bus bar resistance at temperatures others than 20° C, the following formula can be used.
R2 = R1[1+ a (T2-T1)
Page 6
Production
Considerations
It is desirable to build prototype and/or limited
production bus bars with a minimum tooling investment.
Tolerance Production
Guidelines
Mounting hole location ± .020”
Formed angles ± 2°
Page 7
Equipment
Other Products Manufactured by
Circuit Components, Inc.
BOARD STIFFENERS
VIA/PLANE® Substrates *
Page 8