WHICH SMOKE DETECTOR IS THE Ruskin considers the following when factory
RIGHT ONE TO USE? installing duct smoke detectors:
Selecting the correct type of detector (area or Location - Ruskin factory installs the detec-
duct) with the correct principle of operation is tor on the sleeve within 5 feet of the damper
very important. Area and duct smoke detec- with the sampling tube traversing the sleeve
tors are categorized according to the principle at its widest point. The detector is typically
of operation utilized to sense the smoke. The installed on the top or side of the sleeve
two most widely used duct detectors are the opposite from the actuator and other control
photoelectronic type and the ionization type. options (see illustration below).
Ionization smoke detection is based on the Space - The space "envelope" or overall size of
principle of ion flow within a chamber. An the damper assembly is increased. The
alarm condition occurs when the ion flow is
affected by smoke particles. This type of
Width
detector is most effective near the fire source. Inlet sampling
tube with
Photoelectronic smoke detection is based holes facing
airflow.
on the principle of optical detection. It is also
known as the "scattered" light principle. An
alarm condition occurs when smoke particles Actuator
and Control
enter a light path and some of the light is Height Options.
"scattered" by reflection and refraction onto a Refer to
sensor. This type of detector is best for areas Space
Envelope
where dense smoke may occur, such as in Specifica-
ductwork tion Sheet
for dimen-
sions.
Detector
Ruskin factory installs photoelec- DSDF
tronic duct detectors when the duct
SPACE ENVELOPE FOR RUSKIN
smoke detection option is ordered.
FACTORY MOUNTED SMOKE DETECTORS
Page 2 of 3
Ruskin DSD literature shows the additional use of smoke detectors. The authority
"space" needed for a factory installed duct having jurisdiction should be con-
detector. sulted prior to applying any type of
detector.
Air Flow - Ruskin factory installs duct smoke
detectors for use in systems with air velocities 2. Area detectors are the preferred means of
of 0 to 4,000 fpm. If air flow is present it must controlling smoke spread per NFPA72.
be uniform. A detector requiring airflow is
mounted on the damper sleeve so the holes in 3. Photoelectronic type detectors are recom-
the sensing tube face away from the damper mended for sensing smoke in ductwork.
(downstream of the damper and upstream of
the fan). The holes in the sensing tube must 4. Factory installed smoke detectors require
face in the direction of airflow. The air flows additional "envelope space." Refer to the
into the sensor through the tube, is sampled, damper manufacturer's literature for appli-
and is exhausted through the exhaust tube. If cation information.
airflow is opposite of that indicated above, the 5. Ruskin factory installs photoelectronic duct
damper installer must rotate the sensing tube smoke detectors per code requirements, in
so the holes face in the direction of airflow. accordance with the manufacturer's recom-
mendations and with UL approval.
Summary
6. Field installed duct smoke detectors must
The application of smoke detectors can be con- follow the detector manufacturer’s installa-
fusing. In order to make the process simpler, tion instructions.
remember the following items:
7. The damper/detector package is not UL
1. More codes and standards are requiring the listed as an assembly.
Page 3 of 3