The purpose of this document is lay to down the guidelines and design procedure for
performing the LV cable size and voltage drop calculation.
Relevant IS standards:-
Procedure
1. Cable Derating Amp should be higher than Full Load Current of Load.
4. Cable Short Circuit Capacity should be higher than System S.C Capacity.
IL = KW / (∛ * V * pf )
Where ,
KW = Output KW nameplate Rating of the load .In case of a battery charger
maximum load considering normal load + boost charging to be
considered.
V = Line to line voltage in case of 3 ph ac line to phase in case of 1 ph AC /
DC voltage in case of Dc ( in KV and name plate voltage rating of the
consumer, not the switchgear bus voltage) in KV.
Compare the cable size as per short circuit and according to load current select the
higher cable size.
The current carrying capacity of a cable corresponds t the maximum current that it can
carry under speci ed conditions without the conductors exceeding the permissible limit
of steady state temperature for the type of insulation concerned. Derating factor or
correction factor(C) shall be applied every where the installation condition di er from
those for which values of current carrying capacity are de ned derating factors generally
considered are as follows:
C =Cs * Cg * Cd *Ct
Where,
Cs = Rating factor for variation in ground temperature
C = Ca * Cg
Where,
C) Values of di erent derating factors for calculating ‘C’ shall be taken as per
manufacture catalogs. The value of C thus calculated is multiplied by the cables
continuous current obtained from the standard tables and gives the derated
current capacity of cables.
D) In case cables laid partially in air and large size in ground, take the derating
factor from ground calculation.
Total load current after derating Factor (Purpose for select the cable from manufacture
data sheet for voltage drop calculation)
I = I˪/C
Step-3 Veri cation of cable size according to permissible voltage drop during steady state
operating conditions and motor start up.
Where,
Indian Electricity Rules specify maximum voltage variation from the declared voltage
at consumer’s supply point as +65 for LV and MV +6%, -9% for HV and + 10%, 12.5% for
EHV systems.
Rating factor:-
Rating factor for variation in ambient temperature for cable laid in air
Air in Temp in C 25 30 35 40 45 50 55 60
MV cable XLPE
1.16 1.11 1.06 1.00 0.094 0.88 0.81 0.74
insulated
Rating factor for variation in ground temperature for cable laid in direct ground
Ground Temp in C 15 20 25 30 35 40 45 50
MV cable XLPE
1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82
insulated
Rating factor for Depth of laying for cable lay in direct in ground
MV cable XLPE
1.00 0.99 0.97 0.95 0.94 0.93 0.87 0.90
insulated
Group rating factors for circuits of three core cables lay direct in ground
Spacing
No of between
cables in cable 1 2 3 4 5 6 7 8 9 10 11 12
Group centre in
mm
Touching 1 0.8 0.68 0.62 0.58 0.55 0.52 0.50 0.48 0.46 0.45 0.44
MV cable
XLPE
150 1 0.84 0.74 0.69 0.65 0.62 0.59 0.57 0.55 0.54 0.53 0.52
insulated
300 1 0.87 0.79 0.75 0.72 0.69 0.67 0.66 0.65 0.64 0.63 0.62
Source:
OMAN 450 1 0.90 0.83 0.80 0.77 0.75 0.73 0.72 0.71 0.70 0.70 0.69
Cables
600 1 0.91 0.86 0.83 0.80 0.78 0.77 0.75 0.75 0.74 0.74 0.73
Soil Correction Factor of Soil (When Thermal Resistance of Soil is not known)
Nature of Soil Ct
Dry Soil 1
let’s take Quick Example
Q- Which cable size use for 3 phase motor for buried / underground cable?
Temperature is approximate 45 C,
Calculations :-
I˪= 122.5 A
C = 0.91
Select the cable size (Cable Manufacture data sheet : Havells )) for voltage drop.
Voltage drop of cable = (1.732 * 122.5 * 100 (0.532 *0.8 + 0.076 * 0.6) *100) / (1 *415* 1000) = 2.24%
To decide 70 Sq.mm cable, cable selection condition should be checked.
1. Cable derating Amp (122.85 Amp) is higher than full load current of load (122.5
Amp)= O.K
2. Cable voltage drop (2.24%) is lower than de ned voltage drop (5%) = O.K
4. Cable short circuit capacity (5.32KA) is higher than system short circuit capacity at
that point (6.0KA) = Not OK
“70 Sq.mm cable not satis ed all four condition and so it is advisable not to use.”
1. Cable derating Amp (150.15 Amp) is higher than full load current of load (122.5
Amp)= O.K
2. Cable voltage drop (1.8%) is less than de ned voltage drop (5%) = O.K
4. Cable short circuit capacity (7.22KA) is higher than system short circuit capacity at
that point (6.0KA) = O.K
“95 Sq.mm cable satis ed all four condition and so it is advisable to use.”