Professional Documents
Culture Documents
2, MARCH/APRIL 2010
Abstract—Step voltage regulators are the workhorse of distri- the location of the needed regulators and the control settings.
bution feeders for maintaining the voltage at every customer’s The power flow program must be capable of modeling both the
meter to be within the ANSI standards. A step voltage regulator shunt capacitors and the step voltage regulators. The modeling
can be viewed as a tap-changing autotransformer. This paper will
apply a model of the step voltage regulator. The IEEE 13 Node of step voltage regulators can be complex. It is critical that the
Test Feeders will be used to demonstrate how the regulator is con- program is able to model the compensator circuit because this
trolled in order to maintain the desired voltage for full-, light-, and is the control that determines when a tap change is necessary.
future-load conditions. The coordination of step voltage regulators The compensator model will include the desired voltage to be
with shunt capacitors will be included. held within a specified bandwidth at the “regulation point” and
Index Terms—ANSI voltage standards, compensator settings, the R and X settings. The R and X settings model that line
IEEE Test Feeders, shunt capacitors, step voltage regulators. impedance from the location of the regulator to the regulation
point. This paper will utilize a distribution power flow program
(Windmil [2]) to demonstrate how the locations of regulators
I. I NTRODUCTION can be determined and then how the compensator settings are
determined.
E VERY CUSTOMER on a distribution feeder must be
supplied a voltage that is within the ANSI standards [1].
The ANSI standards give the distribution engineer a range
II. ANSI VOLTAGE S TANDARD
of “normal steady-state” voltages (Range A) and a range of
“emergency” steady-state voltages (Range B) to be supplied to The two critical voltages in the ANSI standard are the “max-
all customers. The two ranges are as follows: imum utilization voltage” and the “minimum service voltage.”
1) Range A Both of these voltages are measured at the customer’s meter.
a) nominal utilization voltage = 115 V; The “maximum utilization voltage” will be the metered voltage
b) maximum utilization voltage = 126 V; at the customer that is closest to the substation. Typically, this
c) minimum service voltage = 114 V; voltage is measured at the meter under a no-load condition. This
d) minimum utilization voltage = 110 V; implies that there is no voltage drop through the transformer,
2) Range B secondary, and service drop. The “minimum service voltage”
a) nominal utilization voltage = 115 V; will occur when the customer has the maximum load on and
b) maximum utilization voltage = 127 V; will include the transformer, secondary, and service-drop volt-
c) minimum service voltage = 110 V; age drops.
d) minimum utilization voltage = 107 V. In addition to the Range A and B requirements, the ANSI
standard recommends that the feeder should be operated so that
As the load on the feeder changes, every customer’s voltage the voltage imbalance at three-phase loads will not exceed 3%.
will vary so that the ANSI standard may not be satisfied. The Voltage imbalance is defined as
regulation of the voltages requires some method to regulate the
voltages as the load changes. The two most common methods voltageimbalance
are the application of switched shunt capacitors and step voltage
regulators. The step voltage regulators may be located in the max. deviation from average voltage
= · 100%. (1)
distribution substation or downstream from the substation. The average voltage
distribution planning engineer must have a means of analyzing
the feeder voltages in the present and into the future. A distri- The task for the distribution engineer is to design and operate
bution system power flow program can be used to determine the distribution feeder so that, under normal steady-state condi-
tions, the voltages at the meters will lie within Range A and the
voltage unbalance will not exceed 3%.
Paper 2009-REPC-005, presented at the 2009 IEEE Rural Electric Power
Conference, Fort Collins, CO, April 26–29, and approved for publication The ANSI voltage standards provide the basis for estab-
in the IEEE T RANSACTIONS ON I NDUSTRY A PPLICATIONS by the Rural lishing guidelines for an acceptable voltage profile from the
Electric Power Committee of the IEEE Industry Applications Society. Man- substation to the most remote customer. An example of a typical
uscript submitted for review January 28, 2009 and released for publication
July 24, 2009. First published January 15, 2010; current version published voltage profile is shown in Fig. 1.
March 19, 2010. Fig. 1 shows a typical voltage profile from the substation to
The author is with Milsoft Utility Solutions, Las Cruces, NM 88011-0909 the most remote customer for both maximum- and minimum-
USA, and also with WH Power Consultants, Las Cruces, NM 88003 USA
(e-mail: bjkersting@zianet.com). load conditions. Under maximum-load conditions, it is usually
Digital Object Identifier 10.1109/TIA.2010.2040060 assumed, on a 120-V base, that there will be a 1-V drop through
the service drop, a 2-V drop through the secondary, and a 3-V
drop through the transformer. With an acceptable low voltage
of 114 V at the customer’s meter, this requires that the input
voltage to the transformer should not be lower than 120 V
under the maximum-load condition. When running a power
flow study that models down to the primary of the distribution
transformers, all voltages must lie between 126 and 120 V.
Notice in Fig. 1 that a “regulation point” has been defined. The Fig. 3. Three-phase voltage regulator model.
idea here is that as load varies, the regulation point becomes
the pivot point for the profile. In other words, the voltage at IV. S TEP VOLTAGE R EGULATOR M ODEL
the regulation point will remain constant as the load varies. In The model for a step regulator is developed in [4]. For a
Fig. 1, it is shown that during minimum-load conditions, the single-phase type-B regulator, the relationships between the
output of the regulator has been reduced, and the voltage at the source voltage and current to the output voltage and current are
last customer is greater. This is the desired operating condition given by
that is the basis for determining the settings for the control
circuit (compensator) of the substation voltage regulator. Note 1
VL = · VS
also in Fig. 1 that there are laterals tapped off the main feeder aR
so that the current leaving the regulator will not be the same as IL = aR · IS (2)
the current arriving at the regulation point.
where
III. S TEP VOLTAGE R EGULATOR N2
aR = 1 ∓ .
A step voltage regulator consists of an autotransformer and a N1
load tap-changing mechanism. The voltage change is obtained In (2), the minus sign is when the regulator is in the raise
by changing taps on the series winding of the autotransformer. position, while the plus sign is when the regulator is in the lower
The position of the tap is controlled by the compensator position.
circuit. Standard step regulators contain a reversing switch The actual number of turns on the series and shunt windings
enabling a ±10% regulator range, usually in 16 steps up and is not known; however, each change in tap changes the voltage
16 steps down. This amounts to a 5/8% change/step or 0.75-V by 5/8% or 0.00626 per unit. Therefore, the effective regulator
change/step on a 120-V base. Step regulators can be connected ratio can be given by
in a type-A or type-B connection according to the ANSI/IEEE
C57.15-1986 standard [3]. The more common type-B connec- aR = 1 ∓ 0.00625 · Tap. (3)
tion is shown in Fig. 2.
Note that the input to the type-B step voltage regulator is In (2) and (3), the minus sign is when the regulator is in the
across the series and shunt windings. The type-A step voltage raise position, while the plus sign is when the regulator is in the
regulator would have the load side connected across the series lower position.
and shunt windings. In Fig. 2, when a change in taps is required, Single-phase regulators can be connected in wye, delta, and
the preventive autotransformer changes the number of turns on open delta for three-phase lines. For all of the connections, the
the series winding (N2 ). general three-phase model is shown in Fig. 3 [4].
622 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 46, NO. 2, MARCH/APRIL 2010
With the regulation point identified, the R and X settings are Fig. 7. Phase-C voltage profile.
computed by
There is also a slight voltage rise on the line from 4 to 5.
For i = a, b, c Because the load at node 5 is just a phase-B load, the voltage
Vregi − Vreg_pti rise is caused by the imbalanced currents flowing on the line.
Zlinei = ohms (8) With node 4 selected as the regulation point, the equivalent
Iregi
line impedances per phase were computed using the source
where voltages, regulation point voltages, and source line currents
Vreg actual line-to-neutral voltage at the regulator; from the power flow run.
Vreg_pt actual line-to-neutral voltage at the regulation point; Define CT rating and PT ratio
Ireg actual line current leaving the regulator. 2400
With the potential transformer ratio and current transformer CTp := 700 Npt := Npt = 20.
120
ratings determined and the equivalent line impedance computed
for each phase, (8) is used to determine the R and X settings Define voltages and currents at 1.05 PU and no reg
in volts. ⎛ ⎞
2521.87 · ej·0
Vreg := ⎝ 2521.87 · e−j·120·deg ⎠
VI. IEEE 13 N ODE T EST F EEDER 2521.87 · ej·120·deg
⎛ ⎞
The IEEE 13 node test feeder [8] is modified to demonstrate 2347 · e−j·3.1·deg
how the compensator settings are determined. The one-line Vreg_pt := ⎝ 2361.2 · e−j·124.2·deg ⎠
diagram is shown in Fig. 6. 2261.6 · ej·115.2·deg
The IEEE 13 node test feeder was originally developed to ⎛ ⎞
test the convergence capabilities of different software programs. 537.5 · e−j·34.4·deg
The feeder is highly imbalanced and is a good test for conver- Ireg := ⎝ 633.9 · e−j·150.4·deg ⎠ .
gence. For this paper, the feeder is modified to balance the sys- 703.1 · ej·81.5·deg
tem better so that a straightforward application of the substation Compute equivalent line impedance per phase
voltage regulators can be demonstrated. The modifications are
as follows: i := 1, . . . , 3
1) line 4–12 changed to phases B–C; ⎛ ⎞
Vregi − Vreg_pti 0.1403 + 0.3823j
2) Transformer 6–7 changed to ungrounded wye–delta with Zlinei := Zline = ⎝ 0.0892 + 0.3686j ⎠ .
the same voltages, kilovoltampere rating, and impedance; Iregi
0.131 + 0.4481j
3) load at 7 converted to a delta–PQ;
4) load at 8 changed to delta–PQ; Compute average line impedance
5) load at 14 changed to phase-B wye–PQ;
6) load added to 5 of wye–PQ of 300 + j145.3 kVA. Zavg := mean(Zline ) Zavg = 0.1202 + 0.3997j.
The nominal voltage rating of the feeder is 4160 line-to-line V.
The regulation point was determined by setting the source line- Compute compensator R and X settings
to-neutral voltage at node 1 to 1.05 per unit (2401.8 V). The CTp
power flow program was run for a full load. All three-phase Zset := Zavg · Zset = 4.2 + 14j.
Npt
voltages dropped below 120 V at node 4. A profile for phase C
(the lowest) is shown in Fig. 7. Because of the load imbalance, the phase equivalent im-
The voltage profile shows that the phase-C voltages at nodes pedances are not the same. Because the regulator compensator
3, 4, and 5 are below the minimum primary transformer voltage. circuits are set with the same R and X values for each phase,
624 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 46, NO. 2, MARCH/APRIL 2010
This paper indicates that 100 kvar per phase of shunt capaci-
tors can be added to the feeder. The node-4 capacitor bank will
be increased by 100 kvar per phase.
With the additional capacitors, all node voltages are within
Fig. 12. 10% load growth. the ANSI limits.
Even though the plots are busy, it is interesting to display
each of the profiles on one graph. Fig. 14 shows how well the
voltage regulation has held the desired voltage level at node 4
for all of the cases studied. Because all of these have only
plotted the phase-C voltages, it is seen that the pivot point lies
between nodes 3 and 4. This is a result of using an average
value of the equivalent impedance between the regulator and
the regulation point.
VII. S UMMARY
This paper has demonstrated how wye-connected step volt-
age regulators located in the substation can be set to hold a
desired voltage at the regulation point. The application of shunt
capacitors is included to demonstrate that the regulators and
capacitors work together to hold the desired voltage at the reg-
Fig. 13. Growth of 10% with additional caps.
ulation point for full-, minimum-, and future-load conditions.
The methods demonstrated in this paper are used to regulate
The voltage rise shown in Fig. 10 is a result of the leading the voltages on the IEEE 34-node test feeder [9].
power factor operating condition for the feeder.
The final study is to look into the future. A 10% load growth R EFERENCES
is assumed with the resulting voltage profile shown in Fig. 12 [1] American National Standard for Electric Power—Systems and Equipment
(see also Fig. 13). Voltage Ratings (60) Hertz, ANSI C84.1-1995, 1996.
It is noted that the output voltage of the regulator exceeds the [2] Milsoft Utility Solutions, Inc., Product Documents. [Online]. Available:
http://www.milsoft.com/
maximum allowed voltage of 126 V. Once again, this problem [3] IEEE Standard Requirements, Terminology and Test Code for Step-Voltage
can be corrected by installing additional shunt capacitors. and Induction Regulators, ANSI/IEEE C57.15-1996, 1988.
626 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 46, NO. 2, MARCH/APRIL 2010
[4] W. H. Kersting, Distribution System Modeling and Analysis. Boca Raton, W. H. Kersting (SM’64–F’89–LF’03) was born in
FL: CRC Press, 2007. Santa Fe, NM. He received the B.S.E.E. degree from
[5] Voltage Regulators 225-10. [Online]. Available: http://www.cooperpower. New Mexico State University, Las Cruces, and the
com/Library/Literature/section-asp?ProductLineID=17 M.S.E.E. degree from Illinois Institute of Technol-
[6] Setting the Control. [Online]. Available: http://beckwithelectric.com/ ogy, Chicago.
Instruction-Books/M-6200-IB-01MC2%20(7-08)%20Screen.pdf In 1962, he became a Faculty Member at New
[7] SEL-2431 Voltage Regulator Control. [Online]. Available: https://customer. Mexico State University, where he was a Professor of
selinc.com/metadot/index.pl?id=5799&isa=Category&op=show electrical engineering and the Director of the Electric
[8] IEEE Radial Test Feeders. [Online]. Available: http://ewh.ieee.org/ Utility Management Program until his retirement in
soc/pes/dsacom/testfeeders.html 2002. He is currently a Consultant for Milsoft Utility
[9] W. H. Kersting, “The modeling and analysis of step voltage regulators,” in Solutions, Las Cruces, NM, and also a Partner in WH
Proc. IEEE Power Syst. Conf. Expo., Seattle, WA, Mar. 2009, pp. 1–8. Power Consultants, Las Cruces.