You are on page 1of 4

POWER

AN OVERVIEW OF CURRENT FEEDWATER AND BOILER WATER


TREATMENT PROGRAMS
up. Since these waters contained calci- 10Ca-2 + 6PO4-3 + 2OH- →

A
um and magnesium, the formation of 3Ca3(PO4)2·Ca(OH)2 Eq. 3
mineral scales was a serious problem.
Internal “softening” treatments were As boiler pressures increased, the
used to prevent the formation of the hydroxide levels led to problems such
least desirable scales such as calcium as caustic gouging. This is caused by
successful cy- sulfate and silica scales. Caustic soda the dissolution of iron oxide by high
cle chemistry and soda ash (sodium carbonate) were levels of caustic, particularly underneath
program re- commonly used. The so-called “car- deposits. In conjunction with an im-
quires both the selection of the appro- bonate cycle” caused calcium carbon- provement in makeup treatment tech-
priate program and the proper and con- ate to precipitate preferentially over niques, the phosphate control regimen
sistent application of that treatment ap- calcium sulfate (a more adherent scale). changed to protect against caustic at-
proach. The cycle chemistry program The high boiler water pH also protected tack. This regimen was coordinated
has to minimize or prevent the following boiler surfaces from corrosion. Equa- phosphate treatment. This program was
concerns: tions 1 and 2 represent the carbonate designed to eliminate the free hydrox-
cycle reactions. ide formed by the reaction of phosphate
● The transport of corrosion products and water. It is illustrated in Equation 4.
from the condensate/feedwater cy- Ca+2 + SO4-2 + Na2CO3 →
cle to the boiler. CaCO3 + Na2SO4 Eq. 1 PO4-3 + H2O → HPO4-2 + OH- Eq. 4
● Corrosion of boiler tube metal.
CaCO3 + H2O + Heat → Mixtures of trisodium phosphate and
● Transport of detrimental anions (e.g., Ca(OH)2 + H2CO3 Eq. 2 disodium phosphate or monosodium
chloride & sulfate) or metals (e.g.,
phosphate were fed to maintain phos-
copper) to the turbine. Later, it was found that phosphate phate in the range of approximately 5 to
chemistry could completely prevent the 15 parts per million (ppm) as phosphate
Where We’ve Been formation of calcium sulfate scale and (PO4) and a pH range equivalent to a
In the history of feedwater and boiler would form a sludge (calcium hydroxy- sodium to phosphate ratio of 2.85:1 to
water treatment, the two traditional bug- apetite) that was more “free flowing” 3.0:1. This was no longer a precipitating
aboos have been oxygen and caustic. than calcium carbonate. The calcium program. This program required a high
Oxygen has been a concern because of hydroxyapetite sludge could be re- purity and consistent feedwater. The
oxygen pitting attack, while caustic is moved by blowdown. Equation 3 repre- primary purpose was to control pH but
associated with caustic gouging. sents the calcium hydroxyapetite reac- some protection against the ingress of
tion.
Drum boilers. Phosphate treatment
has long been the staple for treating
drum boilers. Before the advent of ion-
exchange (IX) makeup water treatment,
phosphate provided both pH control
and protection against the ingress of
scale forming ions.
Before the development of IX technol-
ogy, there were no “high-pressure” boil-
ers (by today’s standards) and untreat-
ed or “raw” waters were used for make-

By K. Anthony Selby
Water Technology Consultants Inc.

ISSN:0747-8291. COPYRIGHT (C) Tall Oaks Pub-


lishing, Inc. Reproduction in whole, or in part,
including by electronic means, without permission
of publisher is prohibited. Those registered with the
Copyright Clearance Center (CCC) may photocopy Figure 1. Typical CPT control chart.
this article for a flat fee per copy.

ULTRAPURE WATER® OCTOBER 2004--UP210749 49


systems and 8.8 to 9.2 for mixed metal-
lurgy systems. Hydrazine was often in
the range of 20 to 50 parts per billion
(ppb) at the economizer inlet, but con-
trol of the upper part of the range was
not considered to be important. The use
of hydrazine and other reducing agents
was found to be a significant factor in
flow accelerated corrosion (FAC) in feed-
water systems.

FAC concerns. FAC has been a prob-


lem in feedwater systems and heat re-
covery steam generator (HRSG) evapo-
rators. Single-phase FAC typically oc-
curs within a specific temperature range
(approximately 300oF) and is accelerat-
Figure 2. Schematic of PT, CPT, and EPT. ed by a pH below 9. A strongly reducing
environment destabilizes the magnetite
film protecting the feedwater piping and
hardness salts was maintained. gen damage. allows a gradual thinning of the pipe
So-called “caustic attack” (some of EPRI also had a phosphate treatment wall. FAC failures are serious and have
this could have been acid phosphate (PT) regimen with phosphate in the 2.5 resulted in loss of life in several cases.
corrosion) was still experienced, espe- to 10 ppm (as PO4) range and a pH Figure 3 shows a feedwater line with an
cially as boiler pressures increased generated by TSP +1 ppm of OH. FAC failure. Figure 4 shows the scal-
above 1,500 pounds per square inch Figure 2 is a chart that summarizes the loped surface in the area of the failure,
gauge (psig). As a result, congruent control ranges that were used for PT, which is characteristic of single-phase
phosphate treatment (CPT) was devel- CPT and EPT. It should be noted that FAC.
oped to further reduce boiler water pH CPT and EPT are no longer part of
and ensure against caustic attack. C PT EPRI’s recommended programs. Where We Are Today
operated with a phosphate concentra- The choice of a treatment program for a
tion of approximately 2 to 5 ppm of PO4. Once-through/supercritical boilers. particular plant is a function of several
It could go up to 10 ppm. The sodium- Once-through boilers came into play in factors, including system metallurgy and
to-phosphate ratio was often in the range the 1960s. Many, but not all, once- feedwater purity. There are several pro-
of 2.3:1 to 2.6:1, although this varies through boilers operate in the supercrit- grams to choose from, depending on
from a low of 2.1:1, and a high of 2.8:1. ical pressure range. Since there is no cycle design and water chemistry con-
In many, but not all cases, CPT was steam drum in a once-through boiler, all siderations. Available programs con-
linked to severe “phosphate hideout” feedwater is converted to steam and sist of oxygenated treatment (OT), AVT
and boiler tube failures due to acid enters the turbine. Therefore, there are (reducing and oxidizing), phosphate
phosphate corrosion. no separate “feedwater” and “boiler programs, and treatment with caustic.
A chart showing a typical CPT control water” treatment programs. The feed-
range is shown in Figure 1. This chart water must protect the feedwater cycle Oxygenated treatment. Over the years,
shows the CPT control “box” with a and the boiler and be compatible with there have been a number of “sacred
phosphate concentration of 2.0 to 4.5 the turbine. cows” associated with boiler water treat-
ppm of PO4 and a Na:PO4 ratio of 2.3 to The original all-volatile treatment (AVT) ment. Chief among these was the role of
2.6:1. programs used only volatile chemicals dissolved oxygen. OT was developed
The equilibrium phosphate treatment to control pH and dissolved oxygen. in Germany in the early 1970s and used
(EPT), using low levels of phosphate, The development of IX condensate pol- successfully there until it was finally
and allowing a small amount of free ishers made the concept possible by used in the United States in 1991. At the
caustic, was designed to minimize phos- producing feedwater of sufficient purity present time, more than 100 supercriti-
phate hideout and prevent acid phos- to protect the turbine. In many cases, cal once-through units in the United
phate corrosion. EPT was typically op- however, control of anionic impurities States use OT. OT is also applicable to
erated using trisodium phosphate. The was not sufficient to prevent turbine drum units, but is not yet widely used in
phosphate control range was less than corrosion. There were numerous in- this country.
2 ppm of PO4 with up to 1 ppm of free stances of turbine corrosion in the 1980s. Feedwater purity requirements are
hydroxide (OH). EPT does minimize As a result, control of AVT programs has stringent with OT. Cation conductivity
phosphate hideout but provides little been tightened considerably. must be less than 0.15 microsiemens
protection from corrosion resulting from The AVT regimen consisted of adding per centimeter (µS/cm). Oxygen is con-
anionic species such as chloride and ammonia to control pH and hydrazine trolled 30 to 150 ppb at the economizer
sulfate. According to the Electric Power as an oxygen scavenger/reducing inlet. The result is significantly reduced
Research Institute (EPRI), EPT has been agent. The targeted pH range was iron transport from the feedwater train to
associated with incidences of hydro- typically greater than 9.4 for all-ferrous the boiler.

50 ULTRAPURE WATER® OCTOBER 2004--UP210749


Figure 3. Feedwater line FAC failure. Figure 4. Scalloped appearance characteristics of FAC.

Current AVT concepts. Because of rather than mixtures containing disodi- concept is shown in Figure 6.
concerns for FAC, EPRI has taken a um or monosodium phosphate and that OT is the regimen of choice in all
close look at AVT concepts. They are polymers not be used (2). . ferrous systems with very high feedwa-
currently recommending two separate The phosphate continuum establish- ter purity, as represented by a tight
AVT regimens, depending on system es a minimum phosphate concentration condenser or a well-operated conden-
metallurgy (1). Oxidizing all volatile of 0.2 ppm of PO4. The treatment range sate polisher, in conjunction with good
treatment [AVT(O)] applies to plants with is bounded by the sodium (Na) to PO4 air in-leakage control. In the United
all-ferrous metallurgy, which is defined molar ratio line of 3.0 and the TSP+1 States, OT is used in once-through units
as having no copper in the cycle except ppm NaOH line. The phosphate contin- but, in reality, is applicable to drum-type
for possibly the condenser. Reducing uum provides for a range of phosphate units with appropriate feedwater quali-
all volatile treatment [AVT(R)] applies to levels depending on feedwater purity. ty. Very few HRSG plants in the United
plants with copper alloys in the conden- At low phosphate levels, feedwater pu- States operate with the level of feedwa-
sate/feedwater cycle. With AVT(O), no rity requirements are the same as the ter purity needed for successful appli-
reducing agent is added and the oxida- AVT programs. High phosphate levels cation of OT.
tion-reduction potential (ORP) is approx- are used in response to poorer feedwa- AVT(O) is applicable to those all fer-
imately 0 millivolts (mV). AVT(R) pro- ter quality (e.g., 0.3 µS/cm cation con- rous systems where feedwater quality is
vides the reducing atmosphere needed ductivity). not quite good enough for OT. AVT(R) is
to limit copper corrosion but minimizes This phosphate continuum is shown in applicable to systems containing cop-
the risk of FAC. A reducing agent is Figure 5 (2). . per alloys in the feedwater heater train.
used, but ORP is maintained in the range AVT programs are applicable to
of –300 to –350 mV. Both regimens use Caustic Treatment HRSGs, as well as conventional boilers
ammonia for pH control. In the United States, the fear of caustic if feedwater purity is adequate. AVT
Current EPRI recommendations for gouging led to the abandonment of the chemistry is required in HRSG low-pres-
operation of an AVT program (either use of caustic and the development of sure units that provide feedwater to boil-
AVT(O) or AVT(R) regimens) are to main- “caustic-free” programs such as CPT. er sections operating at a higher pres-
tain a feedwater and steam cation con- The whole basis of CPT was to keep the sure.
ductivity limit of less than 0.2 µS/cm. sodium to phosphate ratio in a range The phosphate continuum, or caustic
The sodium, chloride and sulfate limit in where there could be no free caustic. In treatment regimens are also applicable
steam is 2 ppb. other parts of the world, particularly in to both HRSGs and conventional fossil
the United Kingdom, caustic treatment units. Lower levels of phosphate treat-
Phosphate treatment concepts. Once for high-pressure boilers is the stan- ment are applicable to plants with better
acid phosphate corrosion was identi- dard. Caustic treatment (CT) uses less feedwater quality. Higher levels are
fied, the use of CPT was greatly re- than 2 ppm of sodium hydroxide (NaOH) needed in cases where feedwater qual-
duced. EPT replaced CPT in many in the boiler water. EPRI guidelines ity is not quite so good.
cases. However, EPT has been associ- currently include caustic treatment.
ated with the occurrence of hydrogen Summary
damage. EPRI has now developed the Continuum of treatments. EPRI has The cycle chemistry program in an elec-
concept of a “phosphate continuum” tied these treatment choices into a “con- tric utility plant must simultaneously pro-
where the phosphate concentration is a tinuum of treatments” that is applied, tect the boiler and the turbine. Over the
function of feedwater and steam purity. depending on condenser “tightness” years, it had been necessary to develop
EPT as such no longer exists in the EPRI and/or presence of a condensate pol- new treatment programs as increasing
phosphate continuum. An important isher with additional consideration giv- boiler pressures generated new chal-
aspect of the EPRI recommendations is en to air in-leakage control (1). This lenges. There is a range of choices
that only trisodium phosphate is used available today that take advantage of
ULTRAPURE WATER® OCTOBER 2004--UP210749 51
the ability to produce high-quality make-
up water and feedwater. The treatment
regimens are applicable to both con-
ventional boilers and HRSGs, depend-
ing on feedwater quality.■

References
1. Dooley, B.; Shields, K. “Cycle Chemistry
for Conventional Fossil Plants and Com-
bined Cycle/HRSGs”, Seventh Interna-
tional Conference on Cycle Chemistry in
Fossil Plants, Houston, Texas (June 2003).
2. Dooley, B.R.; Paterson, S.R.; Pearson,
J.M. “HRSG Dependability”, Power Plant
Chemistry 5(12) (December 2003). .

Author K. Anthony Selby is president of


Water Technology Consultants Inc.,
based in Evergreen, Colorado. Mr. Sel-
Figure 5. Phosphate continuum for HRSGs.
by has more than 35 years of experience
in the field of water and wastewater
technology. He has a background in
boiler water technology, cooling water
operations, makeup water pretreatment,
ion exchange, membrane systems, wa-
ter reuse, and overall plant water man-
agement.

Key words: ALL-VOLATILE TREAT-


MENT, BOILERS, CONDENSATE, COR-
ROSION, ION EXCHANGE, OXYGEN,
OXYGENATED TREATMENT, PHOS-
PHATE, POWER

This paper was originally given at the 24th annual


Electric Utility Chemistry Workshop, which was con-
ducted in Champaign, Ill., May 11-13, 2004.

Figure 6. EPRI continuum of treatments.

52 ULTRAPURE WATER® OCTOBER 2004--UP210749

You might also like