Professional Documents
Culture Documents
The main reason for doing earthing in electrical network is for the safety. When all
metallic parts in electrical equipment are grounded then if the insulation inside the
equipment fails there are no dangerous voltages present in the equipment case.
The process of electrically connecting to the earth itself is often called “earthing”,
particularly in Europe where the term “grounding” is used to describe the above ground
wiring.
If the live wire touches the grounded case then the circuit is effectively shorted and fuse
will immediately blow. When the fuse is blown then the dangerous voltages are away.
Purpose of Earthing
1. Safety for Human life / Building /Equipment
To save human life from danger of electrical shock or death by blowing a fuse i.e.
To provide an alternative path for the fault current to flow so that it will not
endanger the user
To protect buildings, machinery & appliances under fault conditions.
To ensure that all exposed conductive parts do not reach a dangerous potential.
To provide safe path to dissipate lightning and short circuit currents.
To provide stable platform for operation of sensitive electronic equipment i.e. To
maintain the voltage at any part of an electrical system at a known value so as to
prevent over current or excessive voltage on the appliances or equipment .
3. Voltage stabilization
There are many sources of electricity. Every transformer can be considered a separate
source. If there were not a common reference point for all these voltage sources it
would be extremely difficult to calculate their relationships to each other.
The earth is the most omnipresent conductive surface, and so it was adopted in the
very beginnings of electrical distribution systems as a nearly universal standard for all
electric systems.
These types of earth pit are generally filled with alternate layer of charcoal & salt or
earth reactivation compound.
It varies from soil to soil. It depends on the physical composition of the soil, moisture,
dissolved salts, grain size and distribution, seasonal variation, current magnitude etc. In
depends on the composition of soil, Moisture content, Dissolved salts, grain size and its
distribution, seasonal variation, current magnitude.
2. Soil Condition
Different soil conditions give different soil resistivity. Most of the soils are very poor
conductors of electricity when they are completely dry. Soil resistivity is measured in
ohm-meters or ohm-cm.
Soil plays a significant role in determining the performance of electrode. Soil with
low resistivity is highly corrosive. If soil is dry then soil resistivity value will be very
high. If soil resistivity is high, earth resistance of electrode will also be high.
3. Moisture
Moisture has a great influence on resistivity value of soil. The resistivity of a soil
can be determined by the quantity of water held by the soil and resistivity of the water
itself. Conduction of electricity in soil is through water.
The resistance drops quickly to a more or less steady minimum value of about 15%
moisture. And further increase of moisture level in soil will have little effect on soil
resistivity. In many locations water table goes down in dry weather conditions.
Therefore, it is essential to pour water in and around the earth pit to maintain moisture
in dry weather conditions. Moisture significantly influences soil resistivity.
4. Dissolved salts
Pure water is poor conductor of electricity. Resistivity of soil depends on resistivity of
water which in turn depends on the amount and nature of salts dissolved in it.
Small quantity of salts in water reduces soil resistivity by 80%. Common salt is most
effective in improving conductivity of soil. But it corrodes metal and hence
discouraged.
5. Climate Condition
Increase or decrease of moisture content determines the increase or decrease of soil
resistivity. Thus in dry whether resistivity will be very high and in monsoon months the
resistivity will be low.
6. Physical Composition
Different soil composition gives different average resistivity. Based on the type of soil,
the resistivity of clay soil may be in the range of 4 – 150 ohm-meter, whereas for
rocky or gravel soils, the same may be well above 1000 ohm-meter.
The earth pits located in such areas must be watered at frequent intervals,
particularly during dry weather conditions.
Though back fill compound retains moisture under normal conditions, it gives off
moisture during dry weather to the dry soil around the electrode, and in the process
loses moisture over a period of time. Therefore, choose a site that is naturally not well
drained.
11. Obstructions
The soil may look good on the surface, but there may be obstructions below a few feet
like virgin rock. In that event resistivity will be affected. Obstructions like concrete
structure near about the pits will affect resistivity.
If the earth pits are close by, the resistance value will be high.
In this method earth tester terminal C1 and P1 are shorted to each other and connected
to the earth electrode (pipe) under test. Terminals P2 and C2 are connected to the two
separate spikes driven in earth. These two spikes are kept in same line at the distance
of 25 meters and 50 meters due to which there will not be mutual interference in the
field of individual spikes.
If we rotate generator handle with specific speed we get directly earth resistance on
scale. Spike length in the earth should not be more than 1/20th distance between two
spikes. Resistance must be verified by increasing or decreasing the distance between the
tester electrode and the spikes by 5 meter.
Normally, the length of wires should be 10 and 15 meters or in proportion of 62% of
‘D’.
Suppose, the distance of Current Spike from Earth Electrode D = 60 ft, Then, distance
of Potential Spike would be 62 % of D = 0.62D i.e. 0.62 x 60 ft = 37 ft.
In this method error due to polarization effect is eliminated and earth tester can be
operated directly on A.C.
After about 4 meter depth, there is no appreciable change in resistance to earth of the
electrode. Except a number of rods in parallel are to be preferred to a single long rod.
The salt content is expressed in percent by weight of the moisture content in the soil.
Considering 1M3 of Soil, the moisture content at 10 percent will be about 144 kg. (10
percent of 1440 kg). The salt content shall be 5% of this (i.e.) 5% of 144kg, that
is, about 7.2kg.
If the moisture content is already above 20% there is no point in adding quantity of
water into the earth pit, except perhaps wasting an important and scarce national
resource like water.
The usual practice is to select a diameter of earth electrode, which will have enough
strength to enable it to be driven into the particular soil conditions without bending or
splitting. Large diameter electrode may be more difficult to drive than smaller diameter
electrode.
The depth to which an earth electrode is driven has much more influence on its
electrical resistance characteristics than has its diameter.
Maximum allowable Earth resistance
Major power station = 0.5 Ohm
Major Sub-stations = 1.0 Ohm
Minor Sub-station = 2 Ohm
Neutral Bushing = 2 Ohm
Service connection = 4 Ohm
Medium Voltage Network = 2 Ohm
L.T.Lightening Arrestor = 4 Ohm
L.T.Pole = 5 Ohm
H.T.Pole = 10 Ohm
Tower = 20-30 Ohm
49 Comments
1.
Sandeep
NOV 13, 2018
Sir ,my question is that,can a industry or a building contains tow or more COPPER
PLATE FOR EARTHING,PLZ ANSWER,PLZ PLZ PLZ PLZ, PLEASE SIR
ANSWER
PAGE-2
What does a good grounding of the power substation and switching station
really mean?
The importance of an effective, durable and a dependable earth for ensuring
safety from electrical hazards does not require to be elaborated upon more.
Contents:
1. Requirements Of a Good Substation Earthing
2. Maximum Permissible Resistance Of Earthing System
3. Touch Voltage (E-TOUCH)
4. Step Voltage (E STEP)
5. Earthing System In a Substation
Earth Mat or Grid
Construction of Earth Mat
Earth Mat in a Substation
6. Location Of Earth Electrode
Pipe Electrode
7. Earthing Of Various Equipment In The Substation
Isolators and Switches
Lightning Arresters
Circuit Breakers
Transformers
Current Transformers and Potential Transformers
Other Equipment
Fences
Ground Wire
Cables and Supports
Panels and Cubicles
8. Distribution Transformer Structure Earthing
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 280px; width: 336px; display: block;">
The provision of such a surface of uniform potential under and around the
substation ensure that no human being in the substation subject in shock of
injury on the occurrence of a short circuit or development of other abnormal
conditions in the equipment installed in the yard.
The primary requirements of a good earthing system in a substation are:
1. It stabilizes circuit potentials with respect to ground and limits the overall
potential rise.
2. It protects life and property from over voltage.
3. It provides low impedance path to fault currents to ensure prompt and
consistent operation of protective devices during ground faults.
4. It keeps the maximum voltage gradient along the surface inside and around
the substation within safe limits during ground fault.
Go back to contents ↑
Go back to contents ↑
Go back to contents ↑
But if these individual electrodes area inter linked inside the soil, it increases
the area in constant with soil and creates a number or paralleled paths and
hence the value of earth resistance in the interlink state, which is
called combined earth resistance, will be much lower than the individual
resistance.
The spreading of such a mat in the soil also ensures the object of earthing
that and surface under and around the sub-station is kept at as nearly
absolute earth potential as possible.
Go back to contents ↑
The trenches are then filled up with soil of uniform fine mass of earth mixed with
required chemicals depending upon the soil resistivity. If location of equipment
is fixed, the intervals are also arranged that the earth mat passes nearby the
equipment location to facilitate for easy interlinking.
It is preferable to extend the mat beyond the fence for about one meter that
fence can also be suitably earthed and made safe for touching.
Normally the earth mat is buried horizontally at a depth of about half a meter
below the surface of the ground and ground rods at suitable points.
Figure 3 – Substation grounding
Go back to contents ↑
5.3 Earth Mat in a Sub-Station
Earth Mat is connected to the Following in a Substation:
The neutral point of such system through its own independent earth.
Equipment frame work and other non-current carrying parts of the
electrical equipments in the sub-station.
All extraneous metallic frame work not associated with equipment.
Handle of the operating pipe.
Fence if it is within 2 m from earth mat.
Go back to contents ↑
Go back to contents ↑
Go back to contents ↑
One connection is made with the nearest longitudinal conductor, while the
other is made to the nearest transverse conductor of the mat.
Figure 6 – HV switch
grounding (photo credit: Brink Constructions, Inc.)
Go back to contents ↑
7.2 Lightning Arresters
Conductors as short and straight as practicable to ensure minimum
impedance shall directly connect the bases of the lightning arresters to the
earth grid. In addition, there shall be as direct a connection as practicable from
the earth side of lightning arresters to the frame of the equipment being
protected.
Individual ground electrodes should be provided for each lighting arrester for
the reason that large grounding system in itself may be relatively of little
use for lightning protection. These ground electrodes should be connected to
the main earth system.
In the case of lighting arresters mounted near transformers, earthing conductor
shall be located clear off the tank and coolers in order to avoid possible oil
leakage caused by arcing.
Figure 7
– 144kV Lightning Arresters with grounded bottom terminals and with insulated
leads (photo credit: arresterworks.com)
Go back to contents ↑
Go back to contents ↑
7.4 Transformers
The tank of each transformer shall be directly connected to the main grid. In
addition there shall be as direct a connection as practicable from the tank to the
earth side of projecting lightning arresters.
Go back to contents ↑
One connection is made with the nearest longitudinal conductor, while the
other is made to the nearest transverse conductor of the mat.
Go back to contents ↑
Go back to contents ↑
7.7 Fences
The Sub-station fence should be generally too far outside the substation
equipment and grounded separately from the station ground. The station and
the fence ground should not be linked.
To avoid any risk to the person walking near the fence inside the station, no
metal parts connecting connected to the station ground, should be near to
the fence five feet and it is desirable to cover the strip about ten feet wide
inside the fence by a layer of crushed stone which keeps its high resistively
even under wet condition.
If the distance between the fence and station structures, cannot be increased at
least five feet and if the fence is too near the substation equipment structure
etc., the station fence should be connected to the fence ground.
Go back to contents ↑
In order that the station earth potentials during fault conditions are not applied
to transmission line ground wires and towers, all ground wires coming to the
station must be broken at and insulated on the station side of the first
tower or pole external to the station by means of 10” disc insulator.
Go back to contents ↑
Where cables which are connected to the station earth grid pass under a
metallic station perimeter fence, they shall be laid at a depth of not less than
762 mm (2’-6”) below the fence, or shall be enclosed in an insulating pipe for
a distance of not less than 1524 mm (5’) on each side of the fence.
Go back to contents ↑
The frame earth bar shall in turn be connected to the earth grid by an
earthing conductor.
Figure 13 –
Panel earthing
Go back to contents ↑
1. For earthing three earth pits in triangular formation at a distance of six meter
from each other are to be provided.
2. Earth pit should be digged for 45 cm x 45 cm size and 5 ft. depth.
3. 3 Nos. of 40 mm dia and 2.9 mm thickness and 3 mts. (10 ft) length of earth
pipe should be used for earthing.
This earth pipe is erected in 5 ft. depth earth pit and for the balance length of
earth pipe is driven by hammering into the ground.
4. When a pipe is driven into the earth, the earth surrounding the pipe can be
considered to be consisting of concentric cylinders of earth which will be
bigger in size and area, as they are away from the pipe. The current can
travel into the earth with large area having little resistance.
5. 3 m. length of electrode will have contact with the earth area of 3 m in
radius. Hence to have better effect 3 m pipe should be fixed at a distance of
6 m (i.e.) twice the distance of pipe length.
6. For better earth connection, one G I clamp should be welded to the earth
pipe and the other clamp bolted with 2 nos. 11/2 x 1⁄2 G I bolt nuts and 4
nos. G. I. washers to the earth pipe.
7. Two separate distinct connections through G I wire should be made from the
transformer neutral bushing to the earth pit No. 2.
8. Two separate distinct connections through GI wire should be made from the
transformer HT lightning Arrester to the earth pit No. 1.
As far as possible this earth wire should not have contact with other earth
wire connections. If needed PVC sleeves can be used for insulation.
9. Two separate distinct connections through GI wire from the following parts of
the structure should be made to the earth pit No. 3 as shown in figure 14
below.
Metal part of the disc and stay.
Top channel.
AB switch frame, metal part of the insulator, side Arms.
HG fuses frame and metal part of the insulator.
LT cross arm, metal part of the insulator, open type fuse frame.
AB switch guide and operating pipe ( At the top and bottom )
Transformer body.
Belting angle.
Seating channel
LT lightning arrester.
The above earth connections should be made as far as possible without
joints. Wherever joints are necessary, GI sleeves should be used by proper
crimping.
The earth pits No. 2 and 3 can be interlinked to serve as parallel path and lower
the earth resistance.
If the earth resistance of the earth pit No. 1 is high, then another earth pit No. 4
can be formed as a counter poise earth and linked with the HT lightning arrester
pit.
Figure 14 – Earthing of Distribution Transformer Structure
Go back to contents ↑
BS 7671 lists five types of earthing system: TN-S, TN-C-S, TT, TN-C, and IT. T = Earth (from
the French word Terre) N = Neutral S = Separate C = Combined I = Isolated (The source of an
IT system is either connected to earth through a deliberately introduced earthing impedance or
is isolated from Earth.