Professional Documents
Culture Documents
RECORD OF REVISION
The revisions listed below have been incorporated in this copy of the document.
REV. PAGE
SECTION DESCRIPTION OF CHANGES
NO. NO.
Add some abbreviation” AC, PO, UPS, GMS, MCC, and
B 1.3 5
MOV”
7.1.1,
B 12, 14 Deleted Limit Switch
7.2..2.2
TABLE OF CONTENT
1.0 INTRODUCTION
1.1 General
Husky-CNOOC Madura Ltd. (HCML) plans to develop the Madura Strait Block BD gas reserves for
sales gas to buyers in Java Island. This field is located offshore in the Madura Strait East Java,
about 65 km east of Surabaya and about 16km south of Madura Island. The project envisages
development of a wellhead platform; an offshore spread moored Floating, Production, Storage, and
Offloading (FPSO) barge with gas processing facilities; Gas metering Station (GMS); flexible risers
from wellhead platform to FPSO and Export gas pipeline from WHP to GMS.
The facility is designed for 110 MMSCFD sales gas. An unmanned wellhead platform with four well
slots and two slots for future expansion would be set in 182 feet of water.
The onshore gas reception and metering facility is installed prior to tie-in to the gas buyer‟s pipeline
The Gas Metering Station facility will include the provision of a 4 (four) metering skid with orifice
meter type (Two (2) metering skid are designed for 40 / 30 MMscfd, one (1) metering skid is
designed for 30 MMscfd, and one (1) standby metering skid designed for 40 MMscfd) including
piping, valves and fittings and other accessories : Gas Inlet KO Drum, Filters; automatic shutdown
valves to fully isolate the facilities; control valve; control building with flow computers, power
distribution, UPS system, Emergency Diesel Generator including diesel day tank, and other
equipment/accessories to support the operation of the facility.
1.2 Scope
This specification covers the minimum requirements for the design, procurement, material,
fabrication, inspection & testing, protective coating, preparation for shipment, and delivery of
Pneumatic ON-OFF Valve and Motor Operated Valve valves complete with their actuator assemblies
to be installed for Gas Metering Station (GMS) in Madura Strait Block BD Development Project.
The Vendor shall clearly identify any deviation to this specification, and the references codes,
standard and Company specifications, and list them, with references to the document clause, in the
quotation. In absence of any specific mentioning of the deviations, it shall be assumed that the
vendor shall fully comply with all the specifications and codes referenced herein.
It shall be the responsibility of the Vendor to provide a complete, tested, individual valve assembly
including, but not limited to the valve, actuator, instrument pneumatic and hydraulic system
assemblies, and limit proximity switches.
The Vendor‟s scope of supply shall include but not be limited to the following as a minimum:
a. Design, fabrication, and supply of the following :
- Pneumatic ON-OFF Valves
- Motor Operated Valves
b. Inspection, testing, and precommissioning at Vendor‟s works
c. Vendor documentation
d. Vendor assistance for Installation & precommissioning at Contractor‟s fabrication yard
e. Vendor assistance for start-up onshore
f. Commissioning spares
g. Special tools for Installation, operation, and maintenance
Definitions
COMPANY : This shall mean Husky CNOOC Madura Ltd
CONTRACTOR : This shall mean EPC CONTRACTOR
VENDOR : This vendor of the equipment defined in the specification
PURCHASER : COMPANY / CONTRACTOR WHO ISSUES A Purchase Order
on Vendor.
Abbreviations
AC : Alternating Current
PO : Purchase Order
PCS : Process Control System
SIS : Safety Instrumented System
UPS : Uninterruptible Power Supply
GMS : General Metering Station
RTJ : Ring Type Joint
MDR : Manufacturer Data Report
MOV : Motor Operated Valve
MCC : Motor Control Center
MTBF : Mean Time between Failures
MTTR : Mean Time to Repair
MAAT : Maximum Allowable Actuator Torque
MAST : Maximum Allowable (valve) Stem Torque
2.0 REFERENCES
The pneumatic On-Off valves and motor operated valves shall be designed and fabricated in
accordance with accepted design practices and applicable sections of the latest edition of the listed
specification, codes, and standards, including any and all modification and interpretation.
Government Regulation of Republic of Indonesia No. 19, 1973 (LN of 1973 No. 25, TLN No.
3003 concerning Mining Work Safety Regulation and Control).
Government Regulation of Republic of Indonesia No. 11, 1979 (LN of 1979 No. 18, TLN No.
3135 concerning Work Safety in Oil and Gas Refining and Processing).
Decision of Director General for Oil and Natural Gas no. 36/KTPS/DJ/MIGAS/1977.
Directorate General Oil and Natural Gas (MIGAS) Regulation No. 43P/382/DDJM/1992 for
Terms and Conditions for Appointment of third party MIGAS Guidelines under Regulation no.
06P/0746/M.PE/91.
Any omission in the requirements detailed herein shall not relieve the VENDOR of his responsibility
to deliver equipment in accordance with the specified performance.
If VENDOR finds conflict between documents or has any doubts on specified requirements, these
shall be communicated immediately to COMPANY in writing. Work related aspects should not
proceed until VENDOR receives clarification from COMPANY in writing. Verbal communications
shall not be considered official.
In the event of a conflict between this specification and any requirements of statutory and safety
regulations, codes and standards and other documents, the most stringent shall prevail. The order
of priority of project documents shall be as follows:
Indonesian Codes and Regulations
This specification
All apparent conflicts shall be reported to the CONTRACTOR in writing for resolution. The
CONTRACTOR / COMPANY decision shall be final.
Hazardous area classification for the GMS shall be in accordance with API RP 505.
The gasses likely to be present in areas designated as hazardous will be a combination of heavier
and lighter-than-air gasses.
All equipment intended for use in hazardous areas shall be tested and certified for operation in the
required zone by an international, recognized testing authority in accordance with API RP 505
requirements.
All equipment shall be rated for the location installed. All equipment in Gas Metering Station shall be
rated for Class I, Zone 2, Gas Group IIA, temperature class T3. All instrument analyzers in the field
shall be explosion proof suitable for the area classification. In addition, all equipment shall be
designed for an outdoor, salt-laden, tropical, marine environment.
Refer to area classification drawing for further details: Drawing No. GMS-16005, GMS Hazardous
Area Classification Drawing
6.1 General
All valves shall be suitable for installation in outdoor, unprotected locations, and shall be adequately
protected from corrosion likely to occur due to exposure to marine environment and adverse weather
conditions. Valve and accessories shall be able to withstand exposure to wind driven dust, saline
damp air, and high ambient temperatures.
The valves shall be supplied fully assembled and tested and capable of operating in automatic mode
and shall require minimum maintenance.
All valves shall be dust proof, fungus proof, and vermin proof using accessories such as bug screens
and protective coatings.
All materials shall be suitable for service in the process temperature, pressure range, and fluid
properties stated in data sheet.
Valves shall be of a proven design and shall have demonstrated leak-tight shut off. The
opening/closing times shall be as per data sheet / specifications.
Vendor shall provide the data regarding Probability of Failure on Demand (PFD) values for the
Actuated ON-OFF Valve and Motor Operated Valve.
The Vendor shall provide information, where indicated, on the Purchasers data sheets.
The vendor shall select valves and actuators from his standard range that is in accordance with data
sheets, data sheets notes, and this specification.
The required stroking times for each valve shall be detailed on the data sheet. The vendor shall state
if ancillaries such as flow controls or quick exhaust are included to achieve the specified valve
opening and closing times.
Sufficient descriptive information shall be furnished with the Vendor's Tender Document to enable
equipment size, weight, performance, quality, capacity, and specification adherence to be
determined.
7.2 Design Criteria
7.2.1 General
Flow direction shall be clearly indicated by an arrow on the body as part of valve casting for uni-
directional valves or those with a preferred flow direction. Alternatively, the valve shall be clearly
marked with the manufacturer's recommended high-pressure side.
Valves shall be no smaller than the line size.
The following guidelines shall be used in the selection of valve body types. Other specific
requirements shall take precedence over these guidelines.
Ball valves may be resilient seated, provided the temperature is below 400 F and the service is
clean. Otherwise a metal seated design is required. Metal seated ball valves shall have electroless-
nickel plating or chrome plating on the ball.
Pneumatic On-Off Valve and Motor Operated Valve (MOV) shall be ANSI 150 RF as minimum.
Valves in hydrocarbon service shall be fire-safe in accordance with API 607 or API 6FA.
Valve body construction shall be as per piping specification GMS-SPM-001 and shall be in
accordance with API 6D.
7.2.2 Operators (Actuators)
7.2.2.1 Pneumatic On – Off Actuator
The valve operator shall be a self-contained unit designed for top mounting on the valve stem,
except for butterfly valves which may have the operator mounted on the end of the horizontal shaft.
The preferred operator orientation is with the valve in horizontal pipe and the operator oriented
parallel to the process line. The Vendor shall submit an assembly drawing for Buyer review and
approval.
The Vendor shall submit calculations that confirm that the operator will open and close the valve
with the differential pressure and temperature as noted on the individual data sheets. As a
minimum, the operator shall be sized with a safety factor of one hundred and thirty percent (1.3
times the maximum valve torque requirement) for butterfly valves and one hundred and fifty
percent (1.5 times the maximum valve torque requirement) for ball valves.
Generally, operators shall be pneumatic spring-return (rack and pinion, vane, or scotch yoke),
pneumatic double-acting cylinder types.
Pneumatic valve operators shall be quarter turn type valves, spring opposed rack and pinion type,
vane type or scotch-yoke type cylinder actuators totally enclosed design with no external moving
linkages.
The actuator shall be capable of 100 rotation and shall include open and closed position stops
with a minimum of 20 total travel adjustment.
The actuator shall be rated for continuous operation using dry instrument air and suitable for
mounting in any position.
Actuators shall be non-breathable and not to draw sulphurous air into cylinders when operated.
To meet the fail-safe requirement, actuator shall be spring return type.
When a volume tank is required, it shall be sized to stroke the valve a minimum of three full
strokes, assuming an initial bottle pressure of 80 psig.
Local position indicators shall be shaft mounted and visible from 3 meters (10 feet).
Actuator motor and other accessories shall be certified to the hazardous area specified in the
project documents. In addition to this the actuator shall be weather-proof to IP 66. Minimum
certification shall be Class 1 Zone 2, Gas Group IIA, T3.
7.2.3 Valve Body
Valve body shall generally be butt well or flanged end. Flange facing for sizes up to and including
24” shall be to match ASME B16.5; for those above 24” they shall match ASME B16.47 series
„A‟. Flange Rating shall be in accordance with the valve data sheet and line class.
Flange Finish shall be RF smooth serrated spiral finish (125-250 μinch) for class 150 to 600.
Flange facing finish shall be RTJ for class 900 and above.
Preferably all ball valves shall be trunnion mounted for sizes equal to or greater than the
following: Supplier shall clearly mention trunion selection criterion in the offer.
150# - 300# size ≤ 2” is floating ball
150# - 300# size > 2” is trunnion ball
Rating greater than 300# and size greater than 2” is trunnion mounted ball valve
7.2.4 Material Selection
The Vendor shall ensure that all materials offered for valve bodies, flanges, trim and soft goods
are in complete compliance with the individual valve specifications stated in GMS-SPM-001,
"Piping Material Specification Line Class -Process and Utility Piping". The required valve
specification number is stated on the individual instrument data sheets. Where any conflict exists
for material selection between GMS-SPM-001, this specification and the datasheets, then the
data sheets shall take precedence.
The Vendor shall provide a compliance statement with the tender stating that all valve materials
are offered in compliance with data sheets. Where alternatives are offered these shall be
detailed as non-conformances in the tender.
7.2.5 Leakage Class
The shut-off valve leakage shall be accordance with API 598 with shut-off class shall be Class as
per datasheet.
7.2.6 Sizing Criteria for Pneumatic Operator
Actuator shall be sized for a minimum air supply pressure of 80 psig and 130 % of the required
valve reseat / break torque when the valve is closed against maximum differential pressure. The
vendor shall guarantee that the equipment shall not be damaged with an air supply pressure of
160 psig or make suitable provisions to withstand that pressure.
The instrument air supply for the actuator is 80 psig minimum, 100 psig normal, and 150 psig
1 maximum. Actuator shall be designed to withstand maximum pressure. Valve closing time shall
be based on a speed of 1 second per inch of nominal pipe diameter for pneumatic On Off Valves
and Motor Operated valves, as a minimum.
Actuator shall be sized without the necessity for pressure relieving devices. Actuator orientation
shall be as per as per datasheet details.
The Vendor shall provide Valve / Actuator orientation sketches post award to enable the
purchaser to select the required valve and actuator orientation prior to valve actuator assembly.
The Vendor shall offer standard interchangeable position mounting for the instrument air and
solenoid assemblies.
7.2.7 Ancillary Equipment for Pneumatic On-Off Valve
All ancillary equipment, except for proximity switches shall be mounted on a rigid 316 stainless
steel plate which shall be securely bolted on the actuator. Devices such as restrictors and quick
exhausts may be mounted in line. The Vendor shall ensure dissimilar metals are adequately
segregated to prevent galvanic corrosion.
When applicable, proximity switches shall be contained in a single housing and shall be arranged
to operate directly off the Centre shaft. Electric type proximity switches shall have the following:
Anti-corrosion sealed fully proven construction
Contact: 0.5A @ 24 VDC (two SPDT), proximity type
Electrical entry shall be 3/4" NPTF
Certification Ex'd' Proximity switch contacts will be as per the following table :
Table 1.1 – Proximity switch contacts
Valve Open Limit Proximitor Valve Closed Proximitor
Valve Closed Open Closed
Valve Open Closed Open
Valve in Travel Open Open
Actuator deterioration due to corrosion from ingress of wet salt laden air is of specific concern.
The Vendor shall submit with tender a proposed method of preventing the ingress of wet salt
laden air into the actuator internal chambers or clarify how the actuator is protected against
corrosion. Closed and lor lubricated systems shall be considered.
Tube shall be 316 stainless steel minimum 3/8" OD x 0.049" WT. All instrument tube fittings shall
be Swagelok double ferrule 316 SS compression type. All tubing shall be adequately supported.
Solenoid valve bodies shall be AISI 316 Stainless steel. Valve trim shall be stainless steel with
Viton or similar resilient seat to provide tight shut off, 24 VDC electrical power, 5 Watts max rating
unless otherwise specified, complete with suppression diode and shall be suitable for Hazardous
area classification Ex‟d‟ Solenoid valve vent ports shall be fitted with stainless sintered metal bug
screens.
Screwed terminals shall be provided for all electrical connections to the solenoid valves and
position switches. All cable entries shall be 1/2” NPT preferable on Ex‟d‟ casing. Others shall
provide cable glands.
All pneumatic ancillary equipment shall suitable for 3/8" NPT(F) air supply connections.
All valve actuators shall be fitted with local mechanically driven position indication (beacon) flags
painted red in color for the closed position and indicating green for the open position. Where
specified in P&ID the solenoid valve shall be provided with manual reset or/and manual over ride.
Pilot valve and quick exhaust valve shall be Versa make and material shall be 316 SS. Wherever
required.
Material of construction for ancillaries such as fittings, flow restrictors, etc. shall be 316 SS
7.2.8 Torque / Thrust Characteristics.
The torque / thrust characteristics of the actuator in its line application including static and
dynamic pressure effects shall be determined to be compatible with the valve VENDOR‟s quoted
torque / thrust curves, taking into account the size of valve, valve stem size and type, rating, and
construction.
Torque definition for quarter turn valves
BTO - Break to open torque / break away torque (highest torque required by quarter turn valve) -
start opening from fully closed position
ETO - End to open torque - fully open
RT - Running torque
BTC - Break to close torque - start closing from fully opened position
ETC - End of close torque - fully closed
VENDOR shall provide, at the time of quotation, the following torque data in tabular form along
with the quotation:
Minimum requirement for pneumatic torque performance table
Valve size, rating ,and type
Shutoff DP used for actuator sizing Torque required by valve (BTO, ETO, RT, BTC, ETC)
Actuator type
Instrument air pressure used for actuator sizing
Torque delivered by actuator (BTO, ETO, RT, BTC, ETC)
Safety factor for all the position (opening, running, and closing)
Valve MAST (Maximum Allowable Stem Torque)
Maximum torque developed by actuator
Opening / closing time
All items in the load path between valve seat and actuator shall be capable of withstanding the
maximum torque / thrust produced by the actuator without exceeding allowable stresses or being
subjected to unacceptable deflections. Maximum torque shall be determined at maximum air
supply. Actuator must never be able to apply torque above MAST of valve / stem. There shall be
generous degree of safety between MAST and Maximum Allowable Actuator Torque (MAAT).
7.2.9 Material Certification
All materials shall be provided with certificates proving that the material furnished meets the
requirements of the specification and the grade to which it is to be supplied.
The material certification types and traceability levels shall be as per EN 10204, edition 2004.
Certification for pressure containing parts shall be as per EN 10204 type 3.1 and all other wetted
parts to type 2.2.
7.2.10 Approved Manufactures
The approved project valve manufacturers are detailed in the Approved Manufacturer List. The
Vendor shall ensure the actuator / Valve coupling bolting material is of non-corroding steel.
7.2.11 Inspection and Testing
7.2.11.1 QA/QC Certification
Vendor shall provide the QA/QC Test and Inspection Certificates / Reports for the complete
supply:
a) QA/QC Certification for Visual controls:
Type and model
Material
ANSI Rating
Labeling
Painting
Dimensions (flanges, threading, piping)
and clearly marked as “Spare Part" and shipped with the equipment in accordance with the
instruction from purchaser. Packing list shall be furnished complete and in detail so that part
can be handled without uncrating, if desired.
Recommended spares should take into account related factors of equipment reliability, effect of
equipment downtime upon production and safety, cost of parts and availability of equipment
service facilities.
8.0 DOCUMENTATION
COMPANY and CONTRACTOR shall review Vendor's drawings and documentation and make any
corrections before "Approved for Construction" drawings are issued. All modifications and changes
to any drawing, software or hardware configuration made during construction, installation, and start-
up shall be reflected on Vendor's final "As-Built" sets of documentation.