Professional Documents
Culture Documents
10000836407-PDC-000
This document contains Aker Subsea legal entity proprietary and confidential information that is legally privileged and is intended only
for the person or entity to which it is addressed and any unauthorised use is strictly prohibited. It is provided for limited purpose and
shall not be reproduced, stored electronically, transferred to other documents, disseminated or disclosed to any third parties without
the prior written consent of the relevant Aker Subsea legal entity. Any attachments are subject to the specific restrictions and
confidentiality regulations stated therein and shall be treated accordingly. The document is to be returned upon request and in all
events upon completion of use for which it was provided.
Document: 10000836407-PDC-000
FAT PROCEDURE XMT ASSEMBLY Version: 00 - Issued for IDC
GAS TEST & HYDROSTATICAL TEST Issue date: 2009.10.01
Page: 2 of 17
TABLE OF CONTENTS
1. INTRODUCTION ............................................................................................................................. 3
1.1. Purpose ........................................................................................................................................... 3
1.2. Health, Safety and Environment (HSE) ........................................................................................... 4
1.3. Required documentation.................................................................................................................. 5
1.4. Abbreviations ................................................................................................................................... 5
2. PRE-TEST PREPARATION............................................................................................................ 6
2.1. General Acceptance criteria for pressure testing ............................................................................ 6
2.1.1. Pressure test documentation........................................................................................................... 6
2.2. Project Requirement ........................................................................................................................ 6
2.3. Test equipment list........................................................................................................................... 7
2.4. Test fluid .......................................................................................................................................... 7
2.5. Identification..................................................................................... Error! Bookmark not defined.
5. RE-TEST ....................................................................................................................................... 15
6. APPROVAL................................................................................................................................... 16
7. DISCREPANCY LOG.................................................................................................................... 17
Document: 10000836407-PDC-000
FAT PROCEDURE XMT ASSEMBLY Version: 00 - Issued for IDC
GAS TEST & HYDROSTATICAL TEST Issue date: 2009.10.01
Page: 3 of 17
1. INTRODUCTION
Each XMT has a unique build number. Fill in the serial number for the XMT in question.
1.1. Purpose
The purpose of this document is to ensure correct performance factory acceptance test (FAT) of
the XMT assembly.
The purpose of the FAT is to ensure pressure integrity of the fully assembled XMT. We will
perform two tests.
This FAT, when referenced in combination with other FAT’s, is intended to satisfy, as a
minimum, the performance requirements of ISO 13628-4 and ISO 10423.
Document: 10000836407-PDC-000
FAT PROCEDURE XMT ASSEMBLY Version: 00 - Issued for IDC
GAS TEST & HYDROSTATICAL TEST Issue date: 2009.10.01
Page: 4 of 17
Authorities prior
study
to test or work
prior to test or
Toolbox meeting
work operation
work operation
prior to test or
procedure
personnel
Example of Test or work operation
operation
Category
Consider
Consider
notifying
moving
SAFOP
SJA on
Liquid test. High pressure.
1. Production- and Annulus bore X X X
( ≥ 5000 psi / 345 Bar)
For all safety matters, reference is made to the procedure HSE Requirements for High Risk
Operations (see table below).
Prior to testing both a SAFOP and a Safe Job Analysis (SJA) shall be performed. The SJA
worksheet shall be available to all personnel and located in the test area during the testing.
When a SAFOP is required, the completed Work Sheet shall be included with the test/operating
procedure. Comments and findings from the SAFOP shall be included as applicable.
The following procedures are applicable to safety during testing and high risk work operations:
Document SAP doc. number
Code of practice for pressure testing global procedure 10000517129
Pressure testing checklist 10000517230
Test procedure guideline 10000106196
Safe operations analysis (SAFOP) 10000106061
Safop work sheet 10000106061
Risk assessment and Job safety analysis (SJA) 10000192087
Table: HSE documents references
Document: 10000836407-PDC-000
FAT PROCEDURE XMT ASSEMBLY Version: 00 - Issued for IDC
GAS TEST & HYDROSTATICAL TEST Issue date: 2009.10.01
Page: 5 of 17
1.4. Abbreviations
To be found in the HSE folder. Or refer to 10000008969 “Subsea Standard Abbreviations Global
Procedure”.
Document: 10000836407-PDC-000
FAT PROCEDURE XMT ASSEMBLY Version: 00 - Issued for IDC
GAS TEST & HYDROSTATICAL TEST Issue date: 2009.10.01
Page: 6 of 17
2. PRE-TEST PREPARATION
Before conducting the tests, perform a Safety Job Analysis (SJA) of the tests that are to be
carried out. Thoroughly go through the steps of the test to identify any events that have to be
carried out with greater caution.
At the end of all tests, ensure that there is no trapped pressure anywhere.
That means that the following pressure drop is allowed for other holding periods:
BB11-HS0002-39
XMT Test Skid 1
(or similar)
10014224
X-mas Tree Handling Tool 1
(or similar)
HEX4078-A
H4 Blind Cap 1
(or similar)
BB40-HS0009-76
Volume Displacer 1
(or Similar)
3.1. Preparations
Make sure the following steps are done before and during testing:
Steps Initials
Install XMT on test stump using VGX seal. Isolate pressure in XT Connector
1
Lock (ventilate XT Connector Unlock).
Connect water pressure hose to production line on XT test skid, SCSSV (1)
9
on SCMMB and AVV (7) on RIMS plate.
10 Fill XMT bore, Meth/Service Lines and CI1 & CI2 with tap water.
Vent High Pressure Test Cap Unlock function and apply pressure to lock
function.
13
_________________
Record stroke length:
mm
Steps Initials
Slowly start to apply hydro pressure in steps through AVV line 7 on RIMS test
2 & flush plate up to test pressure 690 bar (10 000 psi). Production line on test
skid to be isolated. Allow pressure to stabilise.
Slowly start to apply hydro pressure in steps through AVV line 7 on RIMS test
5 & flushing plate up to test pressure 690 bar (10 000 psi). Production line on
test skid to be isolated. Allow pressure to stabilise.
8 Completely drain all water from XMT. Use compressed air if necessary.
4.2. Preparations
Make sure the following steps are done before and during testing:
Steps Initials
Verify that the hydrostatic test is successfully completed. Purge water out of
1
lines before gas test is started.
2 The test setup shall be set up accordance to chapter 3.1, step 1-7
Connect Gas pressure hose to production line on XT test skid, SCSSV (1) on
3
SCMMB and AVV (7) on RIMS plate.
IMPORTANT: All valves that are stated to be in open position shall only be partially open.
1 Verify that XMT is fully submerged in water (above the H4 test connector)
2 Slowly start to apply gas pressure in steps up to test pressure 690 bar (10 000 psi).
4 Hold 690 bar pressure for 60 minutes. Fill in table in Section 4.4.1
12 Verify that valve stems do not have leakage after being cycled.
15 Slowly start to apply gas pressure in steps up to test pressure 20 bar (290 psi).
Carefully open one of the following lines on RIMS Test & Flushing Plate: VXT (line 2),
20
AVV (line 7) or ACV (line 14).
5. RE-TEST
If any leak occurs during hydrostatic testing, please contact support engineer, perform
necessary corrective actions and restart procedure (new copy).
If any leak occurs during gas testing, please contact support engineer, perform necessary
corrective actions and use this re-test plan (copy this page if additional re-tests need to be
performed):
6. APPROVAL
Acceptance of FAT
Name Technician
7. DISCREPANCY LOG