You are on page 1of 1

0RWRU67$786

3DJHRI
&DVH1XPEHU%

&DVH+LVWRU\
The plant opened the motor
referred to in case history
9712012A for inspection. The
outboard bearing was found to be
“wiped” and replaced.

• Average 1x vibration was


reduced by the repair, but it is
still high.
Outboard bearing replaced
• Maximum 1x vibration still
peaks very high.

Electrical 120 Hz peak is still a


concern. Average 120 Hz trend is
continuing to slowly increase.

&RQFOXVLRQV 5HFRPPHQGDWLRQV

A problem still exists in this motor.

$XWKRUSean McGrady 'DWHDecember 22, 1997


&RPSDQ\CSI 3ODQWPower Plant (anonymity requested)