Modeling and Simulation of Static Var


Compensator to Enhance the Power System Security
VenkataPadmavathiS SaratKumarSahu AJayalaxmi
Ph.D Scholar, JNTUH. EEE Dept. EEE Dept.
& Asst. Prof., EEE Dept. M.V.G.R Engg. Col. Vizianagaram, JNTUH University
GITAM University A.P., India Hyderabad, A.P., India
Hyderabad, A.P., India

Abstract— Today’s Power system is more complex and operation in terms of power flow, stability limits with
consequently it would lead to less security. To meet the demand advanced control technologies in the existing power systems.
and better security levels with existing transmission lines, the FACTS devices can be categorized into three types, such as
Flexible AC Transmission System (FACTS) devices are one of the series compensators for controlling line flows, shunt
alternates. In this paper a Newton Raphson(NR) algorithm was
compensators for controlling bus voltages and combined
developed to find out the best operating point of a Static Var
Compensator(SVC) for the enhancement of system security. The series-shunt compensators [11].
proposed algorithm minimizes the security index iteratively. Static Var Compensator (SVC) is one among the different
Security index indicates the overload level of transmission lines. FACTS controllers introduced to improve the bus voltage with
The proposed algorithm is verified by IEEE 5 bus system. Line system security. SVC can be placed in order to control the bus
power flows and bus voltages and bus angles are obtained by the voltage based on variable susceptance. Here, the Security
Newton Raphson algorithm and the security index is calculated index is related to bus voltage and is minimized by an iterative
for both the cases with and without SVC. The results show that algorithm. The index would increase as the bus voltages
the voltage profile can be enhanced and the security margin reduces or increases w.r.t to nominal voltage. Therefore it can
increased by applying the proposed algorithm.
Key words— Flexible AC Transmission System (FACTS),
be said that if the index increases, the system security margin
Newton Raphson Algorithm(NR), Security Index(SI), Static Var will decrease. So by minimizing the security index we can
Compensator (SVC). improve the security [1]

I.INTRODUCTION
II.POWER SYSTEM SECURITY
In the present scenario, most of the power systems in the
Power system security is the ability to maintain the flow of
developing countries with large interconnected networks share
electricity from the generators to the customers, under sudden
the generation reserves to increase the reliability of the power
disturbed conditions such as electric short circuits or
system. However, the increasing complexities of large
unanticipated loss of system elements. The measures of power
interconnected networks had fluctuations in reliability of power
system security are amounts, duration and frequency of
supply, which resulted in system instability, difficult to control
customer outages [10]. Maintaining power system security is
the power flows, bus voltages and security problems that
one of the major challenges facing transmission system
resulted large number of blackouts in different parts of the
operators today. Reliable and secure operation of power
world. The reasons behind the above fault sequences may be
systems is a key to the success of deregulation.
due to the systematical errors in planning and operation, weak
interconnection of the power system, lack of maintenance or III.BUS VOLTAGE CONTROL IN POWER SYSTEMS
due to overload of the network. [8] AND SECURITY INDEX
To overcome these problems and to provide the desired Most of the electrical power systems in the world are
power flow and bus voltages along the transmission line with widely interconnected due to economic reasons to reduce the
better system security and reliability, new transmission lines cost of electricity and to improve system stability and
installation is required. However, the installation of new reliability. Because of the increasing complexity of power
transmission lines with the large interconnected power system
system, the challenge to meet the high quality power supply in
are limited to some of the factors like economic cost, a power system is highly desirable.
environment related issues. These complexities in installing
To overcome the power system limitations like Thermal,
new transmission lines in a power system challenges the
Voltage and Transient Stability limits, advanced controller
power engineers to research on the ways to increase the power
devices provide techniques to maintain system stability and to
flow with the existing transmission line without reduction in
reduce losses [11].
system security.The application of FACTS devices becomes
Different types of power controlling devices are:
an alternative.[8]
1. Phase Shifting Transformer (PST)
FACTS provides[3][5] the ability to increase the
2. High Voltage Direct Current (HVDC) Transmission
controllability and to improve the transmission system

‹,(((


,((($VLD3DFLILF&RQIHUHQFHRQ3RVWJUDGXDWH5HVHDUFKLQ0LFURHOHFWURQLFVDQG(OHFWURQLFV 3ULPH$VLD 

3. Flexible AC Transmission Systems (FACTS)


Among these FACTS are used in this work.
Line
A.Securityindex:
When the bus voltage value near to the desired value, the
index Jv would be a small. Minimization of Jv means the
maximization of security margins. Therefore it can be said that
if the security index [2] [7] increases, the system security
margin will decrease. The index Jcan be used to indicate the
severity of each contingency and security level of the
operating system.

n 2

Security index = JV = ¦ Wi Vi − Vref ,i TCR TSC C R


i Fig. 1: Model of SVC

Where 
i: Bus number B.ShuntVaribleSuseptanceModelofSVC:
Wi : weighing factor 
 V k
JV : Security index which means how much the bus voltage
Isvc
nearer to the ref voltage
Vref ,i : Nominal voltage
Bsvc

IV.FLEXIBLE ALTERNATING CURRENT


TRANSMISSION SYSTEMS (FACTS)
FACTS are highly engineered power electronics based
devices. These controllers are introduced depending on the
type of power system problems. Some of these controllers are
capable of addressing multiple problems in a power system but Fig. 2: SVC Equivalent [14] variable Susceptance model
some are limited to solve for a particular problem. They have
the ability to control the bus voltage, the power flow and The mathematical modeling [14] equations of SVC can be
improve the performance of the power system without written as
changing the topology. SVC is one among the different The current drawn by the SVC
FACTS controllers introduced to improve the voltage profile at I SVC = JBSVC *VK
the buses. [11]
Reactive power drawn or injected into the bus
A.StaticVarCompensator(SVC): QSVC = QK = −VK 2 * BSVC
SVC [14] is a shunt connected FACTS controller and is
a Static Var generator or absorber whose output is adjusted to The linearized equations of SVC, where the Bsvc is taken as
exchange inductive or capacitive current to maintain the bus the state variable.
voltage. SVC is modeled as variable susceptance model.SVC
is having two main components.
1. Thyristor Controlled Reactor(TCR) or Thyristor ª ΔPK º ª0 0 º ª Δθ K º
Switched Reactor(TSR) « ΔQ » = «0 Q » « ΔB / B »
2. Thyristor Switched Capacitor(TSC)
¬ K¼ ¬ K¼¬ SVC SVC ¼

TCR or TSR is composed of a shunt connected reactor and At the end of kth iteration the susceptance value can be
controlled by two parallel connected thyristors.In the same updated as follows.
K
way TSC is composed of a shunt connected capacitor K K −1 § ΔB · K −1
controlled by two parallel connected thyristors.So SVC can BSVC = B SVC + ¨ SVC ¸ BSVC
absorb or generate the reactive power to control the bus © BSVC ¹
voltage to within the limits. The Susceptance value is varied in the Newton Raphson Load
flow problem as a state variable until to get the voltage
magnitude to the specified value.


,((($VLD3DFLILF&RQIHUHQFHRQ3RVWJUDGXDWH5HVHDUFKLQ0LFURHOHFWURQLFVDQG(OHFWURQLFV 3ULPH$VLD 

V. MODELLING OF SVC IN NEWTON RAPHSON


METHOD
The SVC power equations are combined with the system System Data
equations and linearized with respect to the state variables
[12]. The linearized power flow equations can be represented
as [F(X)] = [J] [įX].
Where [F(X)] is power flow mismatch vector, [J] is the Bus Voltage
Jacobian matrix; [įX] is the state variable correction vector. Calculation
For the SVC, the variable Susceptance is taken as state
variable. The inclusion of this variables to form conventional
Jacobian matrix, which increases the dimension of the Calculation of Security INDEX
jacobian.The SVC shunt variable susceptance is adjusted in (Jref)
the Newton Raphson algorithm in each iteration to achieve the
specified voltage and SVC shunt variable susceptance is
operated in either capacitive or inductive modes. SVC Placement
VI. RESULTS AND DISCUSSION
The proposed method has been tested for standard 5-bus
system as shown in figure. Bus Voltage Calculation
Change
G Location
3 4
1
of SVC Calculation of Security Index (Jnew)

2 5 Jref
G >Jnew

Fig. 3: A Standard 5-Bus Network [13]

Best Fit of SVC


The best fit of SVC Controller was obtained by using
the algorithm shown in figure 4 [1].
The standard 5-bus test system was tested by SVC to Fig. 4: Flow chart representation of Best fit of SVC
know the behavior of the system. Here bus 1 is taken as
Slack bus, bus 2 is taken as generator bus and buses 3, 4, TABLE 1: BUS VOLTAGES WITH AND WITHOUT SVC
5 are taken as load buses. Here the SVC is connected at Bus No. Nodal Voltage
bus 3 to maintain the nodal voltage to 1 p.u. The SVC is Nodal Voltage
Magnitude without
Magnitude with SVC
modeled as variable susceptance model in the power SVC in Per
in Per Unit(p.u)
flows study and its value is adjusted in each iteration to Unit(p.u)
meet the specified value. Initially the susceptance value is 1 1.060 1.060
taken as 0.02 p.u. and converges at 6 iterations. After 2 1.000 1.000
connecting SVC at bus 3, the voltage increased from 3 0.987 1.000
0.987 to 1.0 p.u. the power flows slightly changed as 4 0.984 0.994
shown in Table 3.
5 0.972 0.975

It is observed from Table 1, that the voltage at bus 3


is improved from 0.987 to 1.0 p.u.


,((($VLD3DFLILF&RQIHUHQFHRQ3RVWJUDGXDWH5HVHDUFKLQ0LFURHOHFWURQLFVDQG(OHFWURQLFV 3ULPH$VLD 

determined by the proposed algorithm to decrease the


TABLE II: BUS POWERS WITH AND WITHOUT SVC security index related to the voltages at the buses.
Bus Bus powers without SVC Bus powers with
No. in Per Unit(p.u) SVC in Per Unit(p.u)

P(MW) Q(MVAR) P(MW) Q(MVAR) REFERENCES


    [1].A. Kazemi, H. A. Shayanfar, A. Rabiee, and J. Aghaie “Power System
1 1.311 0.908 1.311 0.853 Security Improvement Using the Unified Power Flow Controller (UPFC)”
Power India Conference IEEE 2006
2 0.400 -0.616 0.400 -0.770
[2].H. R. Baghaee, Student Member, IEEE, B. Vahidi, Senior Member, IEEE,
3 -0.450 -0.150 -0.450 0.054 S. Jazebi,G. B. Gharehpetian, Member, IEEE, and A. Kashefi “Power
4 -0.400 -0.050 -0.400 -0.050 System Security Improvement by Using Differential Evolution Algorithm
Based FACTS Allocation” Power System Technology and IEEE Power
5 -0.600 -0.100 -0.600 -0.100
India Conference, 2008. POWERCON 2008. Joint International
Conference on pp 1-6
It is observed from Table II, that the active power at the [3].A.K.Chakraborty S. Majumdar , “Active Line Flow Control of Power
buses is maintained constant and the reactive power at the System Network with FACTS Devices of choice using Soft Computing
buses is slightly changed. Technique” International Journal of Computer Applications (0975 – 8887),
TABLE III: ACTIVE AND REACTIVE POWER FLOWS IN THE Volume 25– No.9, July 2011
LINES WITH AND WITHOUT SVC [4].Ghamgeen I. Rashed, Yuanzhang Sun, H. I. Shaheen “Optimal TCSC
Line Power flow without Power flow with SVC Placement in a Power System by Means of Differential Evolution
Bus-Bus SVC in Per Unit(p.u) in Per Unit(p.u) Algorithm Considering Loss Minimization”  6th IEEE Conference on
Industrial Electronics and Applications 2011,pp 2209-2215
P(MW) Q(MVAR) P(MW) Q(MVAR) [5].D.J.Gotham, G.T.Heydt, "Power flow control and power flow studies for
   
systems with FACTS devices", IEEE Trans on power systems, Vol. 13,
1-2 0.8933 0.7400 0.8911 0.7406
No. 1, Feb 1998, pp. 60-65.
1-3 0.4179 0.1682 0.4195 0.1128
2-3 0.2447 -0.0252 0.2449 -0.095 [6].R. Jahani, H.A. Shayanfar, N.M. Tabatabaei “Optimal Placement of
2-4 0.2771 -0.0172 0.2766 -0.073 Unified Power Flow Controller in power system by a new advanced
2-5 0.5466 0.0556 0.5448 0.0275 heuristic method” IJTPE, Issue 5 Volume 2.
3-4 0.1939 0.0286 0.1965 0.111 [7]. Omid Ghanaati, Vahid Reza Seirafian, Iman Naderpour, Jalal Teymouri
4-5 0.0660 0.0052 0.0678 0.033 “Power System Security Improvement with Optimal Placement of
FACTS Devices Using Genetic Algorithms”ICCAIE2011.
It is observed from Table III, that the overall active power [8].Salah Kamel, Mamdouh Abdel-Akher, and Mohamed K. El-nemr “Direct
Modeling of UPFC in Newton Raphson Power flow Analysis Based on
flow in the lines was slightly increased and the SVC injected
Current Injections” International Middle East Power Systems 2010, Paper
reactive power to the bus to maintain the bus voltage to 1p.u. ID 281,pp 770-774
[9].Bhanu Chennapragada Venkata Krishna, Kotamarti S. B. Sankar,
TABLE IV: SECURITY INDEX WITH AND WITHOUT SVC
Pindiprolu. V. Haranath, “Power System Operation and Control Using
Security Index Security Index
FACT Devices”, 17th International Conference on Electricity Distribution,
without SVC with SVC
Jv Jv 12-15 May 2003.
[10].Rajiv K. Varma, “Introduction to FACTS Controllers”, Power Systems
Conference and Exposition, 2009. PSCE '09. IEEE/PES pp.1-6.
0.0048 0.0042
[11].N.G.Hingorani &L.Gyugyi New York: IEEE, 2000.Understanding
FACTS, Concepts & Technology of Flexible AC Transmission Systems.
[12].Samina E. Mubeen, R. K. Nema, and Gayatri Agnihotri “Comparison of
It is observed from the Table IV that the security index of Power flow control TCSC versus UPFC”, Power System Technology
the system without and with SVC is 0.0048 and 0.0042, and and IEEE Power India Conference, 2008. POWERCON 2008. Pp 1-5.
the former is considered as reference index when SVC is [13].G.W. Stagg & A.H. El-Abiad, Computer Methods in Power System
placed. By incorporating SVC at bus 3 the security index Analysis.
value is reduced and it can be said that if the security index [14].H. Amhriz-PBrez, E. Acha, and C. R. Fuerte-Esquivel “Advanced SVC
reduces, the system security margin will increase. Models for Newton-Raphson Load Flow and Newton Optimal Power
Flow Studies” IEEE transactions on power systems. VOL. 15. NO. 1,
Consequently, the severity will be reduced and the power
February 2000
system security will be enhanced.

VII.CONCLUSION
In this paper, a standard 5-bus network is considered and
power flow program with SVC is simulated in MATLAB.
From the satisfactory results it has been observed that the
voltage profile is improved to a pre-specified value. The
power flows are slightly increased. So, it can be concluded
that after the incorporation of SVC the voltage profile
improves and also the performance of SVC operating point