You are on page 1of 2

FLAME DETECTION SYSTEM

600-IFD-140-SRS
FLAME RELAY

Safety Integrity Level

600-IFD-140-SRS

COMBUSTION AND ENERGY - info@ce2k.com - www.ce2k.com - Ph. +39.0341.260926 rev_02


FLAME DETECTION SYSTEM
600-IFD-140-SRS
FLAME RELAY
KEY FEATURES MECHANICAL FEATURES

• Flame ionization detection module • Electronic circuits


• Small dimensions • Operating temp. range: -40°C to +85°C
• Power supply: 115VAC or 230VAC • Dimensions: 45x75x110mm
50Hz/60Hz selected by an internal • Unit weight: 250g
voltage selector switch • Enclosure: PVC
• Degree of protection: IP20 • Connections: screw terminals
• Input: from any ionization rod
• Installation type: for DIN bar INSTALLATION
• Coloured LED bar graph 10 segment for
flame straight indication • Inside control local panel
• SIL 2
APPLY TO
OPTIONS
• Flares
• Ionization probe • Boilers
600-IFD-140-SRS

• Ionization cable • Burners


• Ex d version
INTERNATIONAL REGULATION
ELECTRICAL FEATURES
• CE marking
• Very low power consumption: approx.
15VA MANUFACTURER
• 115VAC or 230VAC power supply on the
same model Combustion and Energy Srl
• 2 NO contacts for flame status (flame on/ Part number: 600-IFD-140-SRS
off)
• Flame Failure Response Time (FFRT)
EN 298:2012
▪ 0 second (suggested for gas burners)
▪ 3 seconds (suggested for oil burners)
45

MAX
45

www.ce2k.com
600-IFD-140-SRS
FLAME RELAY
75

75

RELAY ON

POWER
FFRT 0 or 3 s Internal Jumper
115-230Vac Internal selector 50/60Hz
FIXING
BAR DIN 110
NEUTRAL
GND

ROD

LINE

N.O. N.O.

122
FRONT VIEW SIDE VIEW
BOTTOM VIEW

COMBUSTION AND ENERGY - info@ce2k.com - www.ce2k.com - Ph. +39.0341.260926


rev_02
Document is subject to change without any notice

You might also like