Professional Documents
Culture Documents
Bertoli s.r.l.
Via Tomasicchio 3/5
43013 Langhirano - Parma
Tel. 0521-861386 Fax: 0521-858265
Web: www.bertolisrl.it - E-Mail: info@bertolisrl.it
1
TABLE OF CONTENTS
2. SAFETY REGULATIONS.......................................................................................................... 8
2.1 General precautions ........................................................................................................ 8
2.2 Safety provisions: installation and start-up ...................................................................... 9
2.3 Residual risks .................................................................................................................. 9
2.4 Safety symbols and labels ............................................................................................... 9
2.5 Personal protection equipment ...................................................................................... 11
2.6 Workstation ................................................................................................................... 11
5. PROTECTIONS ....................................................................................................................... 21
5.1 Low oil pressure protection............................................................................................ 21
5.2 Engine high temperature protection............................................................................... 22
5.3 Fuel reserve protection.................................................................................................. 22
5.4 Short circuit and overload protection ............................................................................. 22
6. MAINTENANCE ...................................................................................................................... 22
6.1 Introduction.................................................................................................................... 22
2
6.2 Periodic engine maintenance ........................................................................................ 23
6.3 Engine oil and filter change ........................................................................................... 23
6.4 Cleaning the air filter...................................................................................................... 24
6.5 Replacing the fuel filter .................................................................................................. 24
6.6 Checking the coolant ..................................................................................................... 25
6.7 Checking the tension of the v-belts................................................................................ 25
6.8 Alternator maintenance ................................................................................................. 25
6.9 Battery maintenance...................................................................................................... 25
6.10 Storage.......................................................................................................................... 26
6.11 Inactive periods ............................................................................................................. 26
6.12 Table of scheduled operations....................................................................................... 26
6.13 Troubleshooting............................................................................................................. 27
10. MANUALS FOR THE USE AND MAINTENANCE OF THE COMPONENTS ....................... 29
3
1. GENERAL INFORMATION
Read this manual carefully before servicing the machine.
IF THE INDICATIONS PROVIDED IN THIS “USE AND MAINTENANCE MANUAL” ARE NOT DULY
APPLIED, THE PRODUCT WARRANTY IS TO BE CONSIDERED NULL AND VOID
The information contained herein is intended for all persons involved in the operating life cycle and who have access to
the generating set, as well as to its actual installation; this implies all those individuals who will actually carry out
specific activities and those who will supervise them.
The manual defines the purpose for which the machine was constructed and contains all the information necessary to
guarantee its safe and correct use. Constant observance of the indications contained herein guarantees operator
safety, operating cost efficiency, and an increased life span of the machinery itself.
It is strongly advised that you read the contents of this manual and the reference documents carefully; this is the only
way to ensure the proper long-term functioning of the generating set, its reliability, and to prevent possible property
damage and personal injury. The drawings are supplied as way of example. Even if the equipment you possess differs
noticeably from the illustrations contained in this manual, the safety and information about it are still valid.
In order to facilitate the consultation of the manual, it has been subdivided into sections that identify the main concepts;
for quick reference of a specific topic, use the index provided.
Note: the information contained in this publication was correct at the time of printing. The Manufacturer, in keeping with
the product development and updating policy, reserves the right to make modifications without prior notice.
1.2 Symbols
Important sections of text that must not be neglected are highlighted in bold print and preceded by the
symbols illustrated and defined below.
(DANGER) Indicates that it is necessary to pay attention in order to prevent serious
consequences that may cause personal injury or death.
(CAUTION) A situation that may occur during the life span of the product, system, or
installation considered at risk with regards to personal injury, property or environmental damage, or
economic loss.
(WARNING) Indicates that it is necessary to pay attention in order to prevent serious
consequences that may cause damage to material goods, resources, or the product itself.
(NOTICE) Particularly important information.
4
a – Manufacturer’s EC Declaration of Conformity
b – Instruction manual for the use and maintenance of the generating sets (this manual).
c – Generating set installation manual.
d – Electrical wiring diagram of the command, control, and power panel.
e – Manual for the Use and Maintenance of the Motor.
f – Manual for Use and Maintenance issued by the Alternator Manufacturer.
g – Any other manuals for optional accessories issued by respective Manufacturers.
h – List of Bertoli Customer Assistance Centres.
i – Warranty Certificate
j – Warranty card
5
1.6 Identification of the machine
See Picture 2 ref. 1
1 – Manufacturer
2 – Machine model
3 – Year of construction
4 – Continuous power
5 – Rated voltage
6 – Serial number
7 – Declared frequency
8 – Rated current
9 – Machine operating speed
10 – Phases
The data that identifies the machine model, the serial number, and the year of construction must always be
communicated to the Manufacturer when requesting information, spare parts, etc.
Picture 2
6
1.7 Instrument panel
7
1.9 Test, Warranty, and Liability
Test
The equipment is shipped to the client after having passed the tests requested by the manufacturer according to
current legislation.
Warranty
The manufacturer agrees to guarantee the equipment described in this manual for a period of 12 months from the date
of delivery and agrees to repair or replace parts that are defective or malfunctioning within this time period provided that
the machine has been used correctly and according to the indications found in this "Use and maintenance manual".
The warranty becomes null and void if:
Personnel not authorized by BERTOLI have tampered with the equipment.
Non-original spare parts have been used.
The machine has not been maintained properly or has been used improperly.
The defective parts replaced under warranty were not returned to BERTOLI.
The warranty excludes parts of the equipment that are subject to wear.
Liability
BERTOLI is in no way liable for incorrect functioning or generic breakdowns caused by the inappropriate use of the
equipment or by servicing and/or tampering carried out by persons other than those authorized by BERTOLI.
Machine model;
Serial number;
Code of the piece to be ordered;
Quantity required;
Shipping method;
Contact person.
2. SAFETY REGULATIONS
8
- When maintenance operations are carried out on the generating set, disconnect the negative terminal of the
start-up battery to avoid accidental starting.
-In case of fuel or oil leaks, carry out an accurate cleaning to prevent fire hazard.
- Access is not allowed to persons with pace-makers, due to possible electromagnetic interference on
cardiovascular devices.
-In case of fire, use an approved extinguisher. Never use water.
If a problem should arise or you need clarification, contact the BERTOLI SERVICE office.
- The personnel responsible for the installation and start-up of the generating set must always use protective
helmets; wear safety shoes, and overalls.
-Use safety gloves.
-Never leave unassembled parts, equipment, or other objects that are not part of the system on or near the
engine.
-Never leave flammable liquids or clothes containing flammable liquid near the generating set, near electrical
equipment (including lamps), or near parts of the electrical system.
-Take precautions to avoid the danger of electrocution.
The machine was designed and constructed with a view to guaranteeing operator safety. There are, however, some
residual risks linked to an inappropriate use of the machine by the operator; to this view, danger signs and symbols
are placed near and on some parts of the machine.
ELECTRICAL HAZARD
9
DANGER OF MOVING PARTS
GENERAL DANGER
OIL CAP
10
OIL DIPSTICK
The operator, before beginning work, must know the location and function of the commands and the characteristics of
the machine and must have read this entire manual as well as the manuals and documentation attached.
The employer must train personnel concerning their correct use and maintenance.
The operator must always observe the precautions indicated on the labels found on the
machine.
The P.P.E. that the operator must use includes work clothes, shoes with non-skid soles, and gloves during operation,
service and maintenance, and cleaning operations.
2.6 Workstation
The machine was designed to be used by only one operator. During the start-up, adjustment, and stopping of the
machine, the operator should remain next to the control panel. During normal functioning, the generating set does
not require the constant presence of the operator.
11
Picture 3 – Key start panels
12
3.2 Control Panel
A control panel (Picture 3) for the commands and for starting and stopping operations is positioned on the generating
set. A motor protection module (Picture 4) controls the protection of the generating set by stopping the motor in case of
breakdown and signaling it by means of special warning lights.
1 – “OIL” warning light [ref. 1] if the red light is on, the engine oil pressure is insufficient.
2 – “BATT” warning light [ref. 2] if the red light is on, the alternator battery charger is not working.
3 – “HIGH TEMPERATURE” warning light [ref. 3] if the red light is on, the engine temperature is too high.
4 – “FUEL RESERVE” warning light (ref. 4) if the red light is on, the fuel tank is empty.
5 – “GENERAL ALARM” warning light (ref. 5) the red light stands as an alarm.
6 – STOP button [ref. 6] this red button can be used to turn the machine off.
7 – Start/stop key [ref. 6].
Picture n. 4
Bertoli generating set may be equipped with 2 kind of Panels: Key Start [Picture 3] or automatic [Picture 5].
The key start version is equipped with an overload cut-out device to start, stop, and control the machine itself.
See [Picture 3] the various models of panels used depending on the power of the generating set.
The automatic version is equipped with an electronic controller managing the automatically switching between mains
and generator. See [Picture 5] for the various models of Automatic control panels.
For further information, please see the manual of the Automatic Panel, which is attached to
the panel.
When service is carried out on the generating set, disconnect the negative terminal of the
start-up battery to avoid accidental starting.
13
When service is carried out on the automatic generating set, disconnect the network to
avoid any accidental start-ups and damages to the electronic card.
Figure n. 5
14
4. USE OF THE GENERATOR
4.1 Installation
Below are the provisions established by the Circ.M.Interno (Ministry of the Interior Circular) of August 31, 1978 n.31
(Text coordinated with Circular n° 12 of July 8, 2003) Safety standards for the installation of internal combustion
engines coupled with electric generators or processing equipment.
4.1.1 Location
The sets may be installed outdoors or in closed spaces that are either isolated or part of buildings.
If installed indoors, they may be installed in floors above ground.
Sets running on diesel fuel, fuel oil, or natural gas (with density less than 0.8 compared to air) may be installed on the
first underground floor.
LPG sets may be installed only on ground floor levels.
It is prohibited to install systems with power greater than 50 kW inside high buildings with the exception of systems
fuelled by the natural gas or methane installed on the highest terrace of the building.
When the building is used, entirely or partially, as a cinema, theatre, meeting room, school, church, hospital or similar
venues, it is prohibited to install natural gas or gasoline systems in adjacent rooms or underneath rooms used as public
meeting places or passages for groups of people.
a) Certification.
At least one wall or part of a wall (no less than 50%) must be face an open, outdoor space (road, courtyard, garden, or
cavity wall that is either open or covered with a grate facing an open-air space, embankments).
According to these regulations, an open-air space may also be an area in front of a wall with overhangs of a ratio
greater than 2 between the height of the station from ground level and the overhang.
If the open-air space consists of a courtyard closed on all sides, the walls of the courtyard must be at least 3.50 m from
each other and the surface area must not be less than the product of the height of the lowest wall (expressed in metres)
multiplied by 3.
If the wall faces a cavity wall, it must be used only as the boiler room; it must be at least 0.60 m wide and the grated
surface must have a net cross-section at least one and a half times the aeration surface of the room itself. When the
cavity wall faces the courtyard, the courtyard must comply with the conditions described in the previous paragraph.
If the wall borders an embankment, the rise between ground level and the ceiling must be at least 0.60 m, in order to
allow for an aeration opening.
This opening must face an open-air space and be at least 50 cm high.
b) Structure.
The horizontal and vertical structures must be fire resistant to at least 120'.
c) Dimensions.
The clear interior height of the ceiling from the floor must not be less than 2.50 m.
The distance, on at least three sides, between the walls and the generator overall dimension perimeter must not be
less than 0.60 m.
15
room must occur directly from open-air spaces or from standard cavity walls covered with grates to be used exclusively
for this purpose.
The room must not have communication openings towards rooms destined for other uses.
For rooms where sets that run on liquid fuels are installed, the access opening must have a threshold at least 20 cm
high.
e) Doors. The doors of the room and of the access room must open outwards, be fireproof, and be equipped with
self-closing devices. Those that open onto indoor rooms must also be smoke-proof.
f) Ventilation. The aeration openings must have a surface area of at least 1/30 of the floor surface area of the room for
systems with power up to 400 kW and at least 1/20 of the floor surface area of the room for systems with power greater
than 400 kW with a minimum of:
a) 0.50 m² for systems with power up to 400 kW;
b) 0.75 m² for systems with power up to 800 kW;
c) 1.00 m² for systems with power up to 1,200 kW;
Indicative dimensions of the rooms for generating sets with water-cooled diesel fuel engines.
16
Examples of installation rooms for generating sets
17
Aeration opening Metal door Footing Walls and ceiling REI 120 GE Panel
Emergency control GE/network switching Distances in meters Example of generating set
footing
Isolated rooms.
The rooms may have structures in non-combustible materials or in a Class 1 fire resistance class. In the latter case, the
room must not be less than 3 m from the nearest building. If the isolation is limited to three walls, the common wall must
have the characteristics of a firewall and a resistance of 120'.
The ventilation openings must not be less than those established in section 2.2.1 letter f).
Open-air installation.
Open-air installations must be located at a distance of no less than 3 m from combustible material storage.
The installations can be protected from atmospheric agents by a roof.
Two or more sets may be installed either next to each other or on top of each other for a maximum of two layers
provided that the total maximum power is no higher than 1,200 KW.
The sets can be fuelled by different fuels.
The sets can be installed within an airtight enclosure or not. In this case, the distance from the walls and the ceiling are
to be measured from the surface of the enclosure.
The supply to the built-in fuel tank must take place only by forced circulation.
18
a) Each engine must not have more than one built-in fuel tank, which must be firmly anchored to the frame and
protected against vibrations, impact, engine heat, and the exhaust pipe.
b) The fuel tanks must be in steel with welded joints or in other materials that guarantee the same performance
characteristics regarding fire prevention regulations (Circular 12/2003).
c) The fuel tank capacity must be proportionate to the engine power and in any case no greater than 50 litres for powers
up to 100 kW and 120 litres for higher powers. Sets located on ground floor level locations or outside on the ground
level that are fuelled by Category C fuels are allowed to use built-in fuel tanks with capacities no greater than 2,000
litres. In this case, a bund wall or basin with a volume at least equal to the tank capacity must be provided. (Circular
12/2003)
d) According to regulations, the supply of the built-in fuel tank must occur by means of a fixed piping system.
e) When the system is fuelled only by built-in tanks, the tank supply is allowed only with portable recipients if the engine
is not running and while taking maximum precautions.
Each set is equipped with an automatic safety system and/or control with a view to the following objectives:
a) shut down of the engine/turbine for either exceeding operating temperature or for a drop in oil pressure or level;
b) interception of fuel flow due to the stopping of the motor/turbine or to a lack of electrical energy generated (Circular
12/2003).
Stopping of the engine causes the exclusion of the electrical power of the engine power supply circuits, except for
safety lighting where the set is installed, which must always be guaranteed. (Circular 12/2003)
The free space around the enclosure must be ventilated by means of a forced ventilation system with continuous
functioning or discontinuous functioning if activated by the signal of an EC-approved gas or fume detector installed
inside the enclosure itself.
As an alternative to the forced ventilation system, an EC-approved gas or fume detector may be installed inside the
enclosure. This detector will block the power supply and the electrical system and will signal the audio and optical
alarms in the presence of gas or fumes in concentrations greater than 50% of the lower flammability limit. (Circular
12/2003)
Any insulating material installed inside the metal enclosure must have characteristics no lower than those for Class 1
fire resistant materials.
Materials.
Engine exhaust systems must be made of sufficiently strong and airtight steel, while connection fittings may be made in
cast iron.
Installation lay-out.
The gas piping must be installed in such a way as to discharge directly, or through a chimney, outside. In order to
guarantee that hot gases and sparks will not cause damage, the ends of the exhaust tubes must be installed at least
1.50 m from windows, doors, or practicable openings or air intakes and at a height of no less than 3 m from the floor
level.
19
Piping protection.
a) The piping inside the room must be protected with insulating materials to ensure that their external surface does not
reach a temperature of at least 100° C lower than the self-ignition temperature of the fuels used.
b) The piping must be adequately protected or shielded to prevent people from accidentally coming into contact with
them.
c) The insulating and protective materials must be non-combustible or combustible with Class 1 of fire resistance.
The lubricating oil tanks must be airtight; oil fumes must be recycled in the engine or condensed in specific containers.
Any vent hole must be directly connected to the outdoors by means of a ventilation duct and the end of the duct must be
at least 1.50 meters from doors, windows, practicable openings, or air intakes.
The electrical systems and devices must be installed in the relative rooms according to current standards as
established in Law n. 186 or March 1, 1968.
The circuit commands, excluding those built-in in the system, must be centralized on a panel to be situated as far a
possible from the sets and in an easily accessible position.
All circuits must be connected to a master switch to be installed outside of the rooms and in an easily accessible
position.
For fire prevention, portable fire extinguishers approved for Class B and C fires containing no less than 6 kg of
extinguishing agent must be installed.
The number of extinguishers must be:
- One for installations of sets with power up to 400 kW;
- Two for powers up to 800 kW;
- Three for powers up to 1,200 kW.
20
For more detailed information, consult the manual provided by the engine manufacturer
and included with each generating set.
4.4 Start-up
Before starting the set, verify that the preliminary checks described in paragraph 4.1 have been carried out. Proceed
with the start-up by turning the key to the START position on the control panel [Picture 4, ref. 7] and release it only
when start-up has occurred, taking care not to exceed 15 seconds for each attempt and pausing for at least 30 seconds
between attempts. .
Repeated failed start-up attempts may cause the starter to overheat, causing potentially
serious engine problems. If start-up is difficult, do not insist, but call authorized personnel immediately.
Before stopping the generating set, it is advisable to let it run for a few minutes without
drawing power supply in order to allow a gradual cooling of the engine and alternator.
5. PROTECTIONS
Generating sets are equipped with a series of protection devices that prevent them from improper use or faults that
may compromise the functioning. When the generating set is shut down by a protection device, a warning light will
appear on the motor protection module of the control panel to indicate the reason for the intervention [Picture 4].
21
Picture 4
The low oil pressure protection does not indicate the level of motor oil in the pan. This level
must be checked daily.
If one of the abovementioned protection devices is activated and the cause of activation
has been found and eliminated, it is then necessary to position the key on "0" to reset the control panel
(otherwise the signal will stay lit and inhibit engine start-up).
6. MAINTENANCE
6.1 Introduction
Any maintenance operation to the generating set must be carried out when the equipment is
22
shut down, after it cooled sufficiently, and must be executed by duly trained, authorized personnel.
It is strongly advised to carefully follow the indication provided in the attached Engine Manufacturer's manual provided
with each generating set. It is important to inspect and carry out maintenance on the generating set regularly and
service must be scheduled according to the number of hours of operation.
Before accessing the generating set, remove a terminal of the start-up battery in order to
avoid accidental start-up.
- The first oil change must be carried out after 50 hours of operation of the generating set; the second and
following changes may be carried out after every 200 hours of operation.
-For more detailed information concerning engine lubrication, consult the engine use and maintenance
manual attached to the generating set.
-Do not pollute the environment by disposing of used oil or fuel inappropriately. Bring the used oil to
specialized Collection Centres for safe and proper disposal.
Do not bring the engine oil into contact with skin. During maintenance operations, use
protective gloves and glasses. In case of contact with the lubricating oil, wash the area immediately with soap
and water.
In order to replace the oil filter cartridge, unscrew it from its support by using the special tool that is normally available
for this purpose. Reposition the new cartridge, taking care to lubricate the rubber ring gasket. The first change should
be carried out after 50 hours of operation of the generating set, while the second and following changes should be
made after every 400 hours of operation. For further information, consult the engine use and maintenance manual.
Use only original spare parts in order to guarantee the long-life and proper running of the
engine.
When operations are completed, carefully clean all the parts of the generating set that have
been dirtied with oil or fuel.
23
6.4 Cleaning the air filter
Generating sets are equipped with an air filter that prevents foreign bodies from entering the combustion chamber. In
order to maintain it, clean the filtering material with diesel fuel once a year to free it from impurities.
Do not dispose of the liquids used to wash the air filter in the environment. Bring them to the
specialized Collection Centres for safe and proper disposal.
Do not bring the fuel into contact with skin. During maintenance operations, use protective
gloves and glasses. In case of contact with the fuel, wash the area immediately with soap and water.
When the operation has been completed, carefully clean all the traces of fuel and bring the
clothes used to the specialized Collection Centre for safe and proper disposal.
24
6.6 Checking the coolant
It is necessary to periodically check the level of coolant in the closed cooling circuit. If the level is insufficient, add
coolant inside the radiator chamber, taking care not to exceed the maximum level index.
Never open the radiator cap when the engine is hot to avoid dangerous coolant leaking.
Do not pollute the environment by disposing of used coolant inappropriately. Bring the
used coolant to specialized Collection Centres for safe and proper disposal.
In order to avoid slipping, keep the belt clean from oil. Clean the belt with gasoline if it
seems dirty with oil.
Never put your hands near the v-belt or pulleys with the engine running.
If the battery is left completely dead for long periods, it may be irreparably damaged.
25
The positive terminal of the battery must be protected with vaseline grease to prevent corrosion or oxidation from
building up.
Protective rubber gloves and glasses must be worn to prevent accidental contact of
sulphuric acid with the skin while topping up the battery, either with distilled water and/or with acid. In case of
accidental contact, wash the part involved with water and soap and contact a physician.
Before charging the battery, check the electrolyte level and top it up with distilled water if
necessary. This operation must be repeated following completion of the recharging cycle.
6.10 Storage
In case of extended storage, leave the machine sheltered from rain and wind and possibly in a dry place.
Take particular care to protect electrical components from rain and atmospheric agents.
The machine may suffer serious damage if, while awaiting installation, it is kept in an environment with critical
temperatures.
Do not expose the machine to temperatures lower than -10° C or higher than +60° C.
It is prohibited to place tools or other objects on the machine that have not been
specifically designed for this purpose.
26
* Replace oil filter 400
Control battery electrolyte level Monthly
Clean and deoxidate metal parts Annually
Clean air filter Annually
* First service after 50 hours, then follow maintenance intervals according to the
table.
6.13 Troubleshooting
The starter turns but the engine does not start up.
- Check if there is fuel in the tank. (Refuel)
- Check if the stop switch is activated. (Consult the Technical Assistance Centre)
- Carry out de-aeration inside the supply circuit. (See par. 4.2)
The engine protection module does not turn on when the START button is pushed
-Check if the thermal protection switch [Picture 3, ref.5] is open. (Reset the contact by pushing the red button [Picture 4,
ref. 3]).
- Check the connection cables and terminals to the battery and the electrical connections. (Reconnect)
- Check the condition of the battery. (Recharge or replace)
- To prevent personal injury if the machine should fall, ensure that there are no people in the range of action of
lifting machines during their operation.
-Lifting, transport, and positioning activities and electrical connections must be carried out by technically
qualified persons who have been specifically trained in these fields.
-Before any movement, always check that the lifting equipment and relative tools (cables, hooks, etc…) are
appropriate to the load to be moved and check that the load itself is firmly secured.
Picture n. 6
9. WIRING DIAGRAM
The wiring diagram is in the set documentation. Please consult this documentation before
modifying the panel itself.
The Manuals for the Use and Maintenance of the components are attached to the machine
documentation. Please consult these manuals for any problems that may arise.
Each component has a declaration of conformity included in the documentation supplied with the
set.
The spare parts list and code can be found in the relevant component manual. Before ordering a
spare part, please consult the component manual.
29
13. MAINTENANCE OPERATION REPORT
30