Professional Documents
Culture Documents
Abstract—Voltage regulation is an important issue for Low Several solutions have been meant dealing with voltage
Voltage (LV) distribution networks. The voltage in the point of problems in LV networks. The easiest and traditional way to
delivery to the end users should be kept within standard limits. compensate long term voltage drops was transformer tap
The paper deals with a single-phase Dynamic Voltage changer at substations. Some more advanced solution are
Conditioner (DVC) able to keep the output voltage at a set value series connected asynchronous Uninterruptible Power Supply
under load variations. A double loop control method, with outer (UPS) [5] and parallel connected STATCOM for the reactive
voltage and inner current controller, has been used in order to power support and so for power system voltage stability [6],
have a better control on current transient. Proposed control [7]. Other alternatives are the Unified Power Quality
method has been designed with MATLAB and several
Conditioner (UPQC) [8] and Open UPQC [9] those can be
simulations are presented to verify its performance. The device
can be interesting for Distribution System Operators (DSOs)
considered as an effective and reliable custom device to
and also within smart grid and micro-grid applications. manage the voltage variations [10].
Beside these devices, Dynamic Voltage Restorer (DVR) is
Index Terms-- Power Quality, Voltage Regulation, Dynamic a well-known series connected power electronics device, able
Voltage Conditioner, Distribution Network, Open UPQC. to compensate voltage sags/swells, flickers and other voltage
disturbances. It can be considered as a cost effective series
I. INTRODUCTION connected device that can support an area. Several
Power Quality (PQ) is an important topic from several compensation methods have been introduced [11] and
point of views. Improving the PQ in an electrical grid can different topologies have been practiced and tested in field
decrease the system losses and increase transmission and [12]. Among those, active power injection can be considered
distribution systems capacity. On the other hand, end users the easiest way to compensate voltage disturbances, however
need a reliable and continuous power supply [1]. New it needs a large storage system. To be able to manage long
technologies, such as renewable energy power plants and term voltage compensation and regulation, reactive power
power electronics devices included in different equipment, can injection is required to decrease the storage system size and
cause PQ and voltage problems at different levels, even if they system losses [13].
are installed respecting connection rules [2]. At the same time, Since DVR is a series connected device, so the whole load
modern systems, like smart grids and micro-grids, are also current passes through it and it has to be a voltage generator
requiring autonomous voltage and current PQ conditioners. that should pass the load current with minimum distortion.
In the case of LV networks, Distribution System Operators This makes its control more complex and difficult. The basic
(DSOs) are responsible to provide power to costumers device operation is to stay offline most of the time (equipped
respecting the PQ standards. In particular European standards with a detection algorithm) and once any disturbance is
impose to DSOs to provide the users a voltage in the point of detected, to react and to compensate it as fast as possible [14].
delivery within a given range [3]. In Italy, the Italian Since this offline functionality may cause transient current
Authority AEEGSI (Autorità per l’Energia Elettrica e il Gas e problems, different control methods have been analyzed in
il Sistema Idrico) has released a new standard upgrading the literature [15]. Additionally, series connected devices are
target for the continuity of service (progressively reducing the usually coupled to the system by means of a transformer. The
number and the length of disconnections per customer) in power electronics converter is connected at primary side and
2011. It mandates to monitor the PQ on the distribution grids the secondary is connected in series to the power line. This
starting from MV bus-bars in primary substations, before 2015 configuration with converter, LC filter at inverter output and
[4]. Hence, PQ improvement, especially in terms of voltage transformer is highly vulnerable to instability and resonant
regulation, became more important for DSOs in LV systems. problems.
564
OB ≡ Vs ,min_ b = VPCC _ ref cos(γ ) (5)
2 2
Where ωI t is the line current angular frequency and in
OD ≡ Vs ,min_ a = Vx ,max − VPCC _ ref sin(γ ) + VPCC _ ref cos(γ ) (4)
L
565
The second part of controller (Fig. 4) is meant to force the or over voltages under load variations, either by adding or
inverter to generate the requested reference voltage. Since the removing considerable portions of the load.
reference voltage (6) is an AC signal, instead of normal PI
controller, P-Resonant (P-R) controller is used inside inverter The simulation has been carried out with discrete, fixed
controller loop [16]. This P-R controller due to its AC intrinsic step solver, so the implemented control method easily can be
can easily ignore any DC offset at inverter output because of adopted for digital microprocessor implementation. System
transformer or any error at inverter control. performance dealing with voltage drops and over voltages
under considerable load variations has been tested. The
It is worth to note that instead of ideal P-R controller a simulation is done for both 10% under and over voltage at grid
practical one is implemented with a cut-off frequency to side cases, by adding a certain load and removing the same
increase the bandwidth of controller [16]. The transfer load. At both cases system at starting condition works with
function is reported in (7). 10kW + 12kVAr load to compensate grid voltage drops or
over voltages. Then at t =3s, 10kW is added to the load. Power
Factor (PF) is changed from 0.65 to 0.85 and current is
kiωcut s (7) increased from 66A to 100A rms. Transient behavior of the
H P−R ( s) = k p + 2
s + 2ωcut s + ω0
2
device is shown. Then at t =5s the 10kW is removed from the
load and system transient starts. So the system comes back to
P-R output is considered as control current Ic and it is the starting condition with 10kW + 12kVAr load, but with
added to measured line current IL to produce the reference 10% voltage drop or over voltage at grid side.
current for inverter current controller. So, as it can be noticed
the P-R controller is responsible to produce just the small A. Under Voltage Compensation
control current which is added to line current. The grid voltage is simulated to get 10% voltage drop. The
DVC is working under constant load to compensate this
The last controller in loop is a Model based Predictive
voltage drop and set PCC voltage to nominal value. Fig. 5
current Controller (MPC) as described in [17], [18] and shown
shows DVC response to load increment during voltage drop
in Fig. 4. It generates control voltage, vc for constant switching
compensation.
frequency PWM strategy module. With this configuration the
inverter switching frequency will be kept constant and it can As it can be noticed in Fig. 5, the device is able to deal
avoid problems due to variable switching frequency. with this critical change. Voltage drop at grid voltage is shown
at Fig. 5(a). The disturbance in PCC voltage is negligible in
IV. RESULTS AND DISCUSSIONS Fig. 5(b) and thanks to MPC current controller there is no any
The configuration shown in Fig. 1 has been tested by inrush current through the load. There is a fast change in
MATLAB simulations. The parameters of the system are injected voltage in Fig. 5(c) due to the critical change in line
reported in TABLE I. current phase. As it is shown in (6) any change in line current
angular frequency ω I t affects Vx reference magnitude and
L
566
Fig. 6 shows the DVC response to removing the same load Fig. 8 shows the system response to remove 10kW load. At
(10kW) at t =5s under the same 10% voltage drop. So, the t=5s, the load is removed and system comes back to the
DVC is working with 20kW + 12kVAr before t =5s and, starting condition. As it can be seen in Fig. 8(b), PCC voltage
removing 10kW, the system comes back to starting condition. is not affected with this critical load change. Fig. 8(c) shows
Fig. 6(a) shows the grid voltage, Fig. 6(b) depicts the PCC that, by changing the load current, the injected voltage
voltage that is not affected with this load change, injected magnitude and phase have been changed accordingly. And
voltage experiences a phase and magnitude change because of current waveform is shown at Fig. 8(d) and smoothly changes.
the quite critical change of load phase, as shown in Fig. 6(c).
The line current is smoothly changes and there is no over or
under shoot on it Fig. 6(d).
By changing the injected voltage phase, there is a small
change in VPCC phase too. Although this change is not visible
in Fig. 6(b), because the injected voltage comparing to the
VPCC has a small magnitude, Fig. 6(b) and Fig. 6(c) have
different voltage scales.
Figure 7. Load increment under 10% over voltage compensation (a) grid
voltage, (b) PCC voltage, (c) injected voltage, (d) line current
Figure 6. Load decrement under 10% voltage drop compensation (a) grid
voltage, (b) PCC voltage, (c) injected voltage, (d) line current
567
as it is shown in Fig. 9, and it is consistent with Fig. 5(c) and [4] AEEG, “ARG/elt 198/11 – Testo integrato della regolazione della
Fig. 7(c) simulation results. qualità dei servizi di distribuzione, misura e vendita dell'energia
elettrica per il periodo di regolazione 2012-2015” [Online]. Available:
www.autorita.energia.it/it/docs/11/198-11arg.htm
[5] P. Mattavelli, "An improved deadbeat control for UPS using
disturbance observers." Industrial Electronics, IEEE Transactions on
vol. 52, no. 1 pp. 206-212. Feb. 2005:
[6] Y. Xu, and F. Li, “Adaptive PI Control of STATCOM for Voltage
Regulation,” Power Delivery, IEEE Transactions on vol. 29, no. 3, pp.
1002 - 1011, June 2014.
[7] H. Hafezi, E. Akpinar, and A. Balikci, "Assessment of two different
reactive power estimation methods on single phase loads," in 16th
International Power Electronics and Motion Control Conference and
Exposition (PEMC), 2014, pp. 82- 87.
[8] V. Khadkikar, “Enhancing Electric Power Quality Using UPQC: A
Comprehensive Overview,” Power Electronics, IEEE Transactions on,
vol. 27, no. 5, pp. 2284 - 2297, May 2012.
[9] G. D'Antona, D. Della Giustina, R. Faranda, and H. Hafezi, “Open
UPQC Power Quality Manager within Distributed Generation
Systems,” in Diagnostics for Electrical Machines, Power Electronics
and Drives (SDEMPED), 2015 IEEE 10th International Symposium on,
Guarda, Portugal, pp. 501 - 507.
Figure 9. Vector representation of load change [10] M.C. Falvo, L. Martirano, D. Sbordone, M.G. Ippolito, E. Telaretti, G.
Zizzo, I. Bertini, B. Di Pietra, G. Graditi, B. Pelligra, F. Vellucci. “A
Another comment; changing active load doesn’t change comparison of Two Innovative Customer Power Devices for Smart
the Vx phase and magnitude and consequently the control Micro-Grids,” in IEEE EEEIC 2015. 15th International Conference on
limits so much. However, if the change on reactive power is Environment and Electrical Engineering. Rome, Italy.
[11] A. K. Sadigh, and K. M. Smedley, “Review of voltage compensation
applied, the voltage and phase change will be wider. Here the methods in dynamic voltage restorer (DVR),” in Power and Energy
system capability to deal with transients was in interest and Society General Meeting, 2012 IEEE, San Diego, CA, pp. 1 - 8.
the transient behavior is quite the same for either active or [12] J. G. Nielsen, and F. Blaabjerg, “A detailed comparison of system
reactive load variation. topologies for dynamic voltage restorers,” Industry Applications, IEEE
Transactions on, vol. 41, no. 5, pp. 1272 - 1280, Sept.-Oct. 2005.
V. CONCLUSIONS [13] T. Jimichi, H. Fujita, and H. Akagi, “Design and Experimentation of a
Dynamic Voltage Restorer Capable of Significantly Reducing an
The paper presents control method for single phase voltage Energy-Storage Element,” Industry Applications, IEEE Transactions on
regulator capable to keep PCC voltage regulated under grid vol. 44, no. 3, pp. 817 - 825, May-june 2008.
side over or under voltage. The transient behavior of the [14] J. G. Nielsen, M. Newman, H. Nielsen, and F. Blaabjerg, “Control and
testing of a dynamic voltage restorer (DVR) at medium voltage level,”
device under load variation has been investigated and shown Power Electronics, IEEE Transactions on vol. 19, no. 3, pp. 806 - 813,
by MATLAB simulations. The results show the proposed May 2004
control method for DVC guarantees a good response under [15] Y. W. Li, P. C. Loh, F. Blaabjerg, and D. M. Vilathgamuwa,
load variations and it can be used in different configurations “Investigation and Improvement of Transient Response of DVR at
within LV distribution networks. Medium Voltage Level,” Industry Applications, IEEE Transactions on
vol. 43, no. 5, pp. 1309 - 1319, Sept.-oct. 2007.
The described device will be realized as Open UPQC [16] H. Cha, T.-K. Vu, and J.-E. Kim, “Design and control of Proportional-
series unit with all the functionalities within smart grid. Resonant controller based Photovoltaic power conditioning system,” in
Energy Conversion Congress and Exposition, ECCE, San Jose, CA, pp.
2198 - 2205.
REFERENCES [17] G. D'Antona, R. Faranda, H. Hafezi, and M. Bugliesi, “Experiment on
bidirectional single phase converter applying simple model predictive
[1] M.C. Falvo, U. Grasselli, R. Lamedica, A. Prudenzi. “LV Harmonics control,” in Environment and Electrical Engineering (EEEIC), 2015
monitoring survey on office appliances,” in IEEE ICHQP Conference IEEE 15th International Conference on, Rome, pp. 1019 - 1024.
2010 - International Conference on Harmonics and Quality of Power. [18] G. D’Antona, R. Faranda, H. Hafezi, and M. Bugliesi, “Experiment on
Bergamo , Italy. Bidirectional Single Phase Converter Applying Model Predictive
[2] IEEE Standard for Interconnecting Distributed Resources with Electric Current Controller,” Energies, vol. 9, no. 9, pp. 13, 24 March, 2016.
Power Systems IEEE Std 1547- July 2003
[3] IEEE Recommended Practice for Monitoring Electric Power Quality
IEEE Std 1159 - June 2009
568