You are on page 1of 13

TIME SIMULATION

Load Flow

NEPLAN AG
User´s Manual
Load Flow Time Simulation

Load Flow Time Simulation


This section describes in details the module Load Flow Time Simulation

Getting started

Start calculation

Open the standard NEPLAN example LoadProfiles in NEPLAN Examples – Pow-


er Systems – AC Steady State – Load Profile and Measurements

Click on the parameters menu option where you can choose whether to run a cal-
culation for a specific moment (One Load Flow) or over a specified period of time
with a given time increment (Time Simulation).

Fig. 1-Time Simulation Parameters

Attention: To run a time simulation the user needs to assign time depending scal-
ing types or measurements.
User can assign scaling types individually for each elements or set a global scal-
ing type in the calculation parameters in the pane “Options”.

NEPLAN User's Guide V5 1


Load Flow Time Simulation

Fig. 2-Time Simulation Parameters

NEPLAN will perform a Load Flow for each time step in the network (See theory
section of Time Simulation). In the pane “Selected Result for Time Simulation” the
user can select the elements for which results should be generated.

Results

There are two result sets to consider.


1. Results in the tables (Summary and Element)
2. Chart results

Fig. 3-Time Simulation Results

NEPLAN User's Guide V5 2


Load Flow Time Simulation

The explanation of the result variables, shown in the summary can be found in
the section “Load Flow Time Simulation – Results”
In the chart manager user can define the curves needed to be viewed.

NEPLAN User's Guide V5 3


Load Flow Time Simulation

Load Flow Time Simulation - Parameters

Parameters

Method There are two options: Calculation of one load flow at a cer-
tain date/time or time simulation, where a date/time range
has to be defined.
One Load flow The date/time for a single load flow calculation has to be de-
calculation fined.
Time simulation The date/time range (From date/time and To date/time) for
the time simulation has to be specified.
Time increment Increment for time simulation in minutes.
Get date and in- If measurements available this will set the From, To and In-
crement from crement of the time simulation calculation based on the
measurements measurements file

Options

Scaling types Selected scaling types library. The selected library should
contain the scaling types referenced in the load elements.
Day characteris- Selected day characteristic library. This library should contain
tics the day characteristics referenced in the scaling types library.
Long term char- Selected long term characteristic library. This library should
acteristics contain the long term types that are referenced in the select-
ed scaling types library.
Default scaling The default scaling type will be used for all loads with an
type empty scaling type entry. If no default scaling type should be
used, this field must remain empty.
Use measured If checked, measured data will be used.
data
Use scaling If checked, scaling types will be used. If option Use meas-
types ured data is also checked, measured data will be used for
those load elements with measured data available.
Save weak load If checked, the calculation detects the network low and high
/ maximum load load case and stores these two states as operational states.
as operational
state

NEPLAN User's Guide V5 4


Load Flow Time Simulation

Ignore meas- If checked, measurement devices without time dependent da-


urement devices ta assigned are ignored.
without time de-
pendent data
Enable parallel If checked, the calculation will be distributed to several logical
computing processors.
Number of pro- Number of processors the parallel computing can use.
cessors
Load measured If checked, the measured data is loaded gradually during the
data gradually calculation. If not checked, the complete set of measured da-
ta is loaded at the beginning of the calculation. Check this op-
tion if your computer may run into memory problems.
Interval length Interval length in days for the gradual loading of measured
data
Write XML result If checked, the xml result file is automatically created after
file the calculation.
Save all element If checked, the variables of all nodes and elements are
results stored; if unchecked, only the variables of the selected nodes
and elements are stored.
Save time-value Indicates, if the time courses of marked nodes/elements
curves of ele- should be saved, otherwise only the summary result are
ment variables saved.
Save min/max Indicates if the minimum and maximum values of variables of
values of ele- marked nodes/elements should be saved.
ment variables
Load flow Pa- Opens the load flow parameters dialog.
rameters

Selected Result for Time Simulation

The elements for which results will be saved can be selected here. If the option
"Save all Element Results" is selected, these settings will be ignored and results
will be available for all network elements.

NEPLAN User's Guide V5 5


Load Flow Time Simulation

Load Flow Time Simulation - Results

For each node and element the normal load flow results (current, voltage, power,
etc.) will be calculated (see chapter Load Flow). The user has the possibility to
display the results in tables (Summary or Element) or a chart.

Summary Table
LoadFactor Load scaling factor
LoadEnergy Total energy consumption
kWh
MaximumLoad Highest recorded power demand in calculation period
kW
MinimumLoad Lowest recorded power demand in calculation period
kW
EnergyLosses Total energy losses in calculation period
kWh
CoreLosses Energy loses of cables in calculation period in kWh
kWh
CoreLossesPerc Energy loses of cables in calculation period in %
%
LTLosses kWh Energy loses of low voltage network in calculation period in
kWh
LTLossesPerc Energy loses of low voltage network in calculation period in
% %
HTNMLosses Energy loses of high voltage network in calculation period in
kWh kWh
HTNWLoss- Energy loses of high voltage network in calculation period in
esPerc % kWh
MaximumLoss- Highest recorded network losses in calculation period
es kW
MinimumLoad- The moment when the lowest power demand was measured
DateTime
MaximumLoad- The moment when the highest power demand was measured
DateTime
FromDate- Start of time simulation
AndTime
ToDateAndTime End of time simulation
NumLFNotFea- Number of converged load flows with limit violations in calcu-
sible lation period

NEPLAN User's Guide V5 6


Load Flow Time Simulation

NumLFNotConv Number of not converged load flows in calculation period


NumLFTotal Number of converged load flows in calculation period
OperationalDat- Selected operational data
aName
ProjectName Name of current project
FileNameOfIm- File name of imported measurements
portedMeas-
urements
HasErrors Whether there were any errors recorded during the calcula-
tion

Element Table
Name Name of the element
Alias Name 1&2 Total energy consumption
Library Type Library type of the element
Type Element type of the element (Line, transformer, …)
EnergyLosses Total energy losses in calculation
kW
MaximumLoss- Highest recorded losses of the element in calculation period
es kWh
Area Area of the element
Zone Zone of the element
Feeder Feeder the element is assigned to
Calculation Time Indicates, when the calculation was done

Charts
To open the graphical result window choose "Time simulation” from the analysis
menu and click on “Chart” button.

Theory of Load Flow Time Simulation

The module Time Simulation (Load Flow) makes a single Load Flow calculation
(forecast) or a sequence of Load Flow calculations (Time Simulation). The active
and reactive power of consumers and generators with measurement data are de-
termined before each Load Flow calculation.

NEPLAN User's Guide V5 7


Load Flow Time Simulation

Measured load data will be automatically applied. If measured data for a load at a
certain date cannot be found in the database during a time simulation, the en-
tered constant values for active and reactive power will be used. Missing meas-
ured values of a day profile will be linearly interpolated. This means that meas-
ured load values for a certain date (day) must be defined at least by one meas-
ured point. Otherwise the constant values of active and reactive power will be ap-
plied.
In case Scaling Types are used, the scaling of loads is done based on the load
profiles defined in Day Characteristics and Long Term Characteristics, and the
weakly/seasonal definition (see Scaling Types section)

NEPLAN User's Guide V5 8


Load Flow Time Simulation

Measured Data

Measured data can be assigned to load elements and measurement devices.


Measured data for a network element consists of a series of data records. One
record has the following main data fields:
• DateAndTime
• M11, M12, M13, M21, M22, M23, M31, M32, M33
• InputDataDefinition: information about the meaning of the fields M11 to
M33

The following values for InputDataDefinition are allowed:


• 0: M11 = symmetrical current in A, M12 to M33 undefined
• 1: M11, M12, M13 = phase currents in A, M21 to M33 undefined
• 2: M11, M12 = total active and reactive power in kW and kVar, M13 to M33
undefined
• 3: M11, M12 = total active and reactive power in MW and MVar, M13 to
M33 undefined
• 4: M11, M12, M13 = active power per phase in kW; M21, M22, M23 = reac-
tive power per phase in kVar; M31 to M33 undefined
• 5: M11, M12, M13 = active power per phase in MW; M21, M22, M23 = re-
active power per phase in MVar; M31 to M33 undefined
• 6: M11 = symmetrical current in A, M12 = symmetrical line-to-line voltage in
V, M13 = power factor cos(phi); M21 to M33 undefined
• 7: M11, M12, M13 = phase currents in A; M21, M22, M23 = phase voltages
in V; M31, M32, M33 = power factor cos(phi) for each phase

Scaling Types

The user can define constant scaling factors and time-dependent scaling factors
for day times, week days, months, and years. The factors may be defined in the
library.
Scaling Types and time-dependent characteristics can be defined in the library
(Library - Edit Library - Scaling Factors)

NEPLAN User's Guide V5 9


Load Flow Time Simulation

Scaling Types
A list of all existing scaling factor types appears after selecting the tab “Scaling
Types” in the Scaling Factor section of the library. For every type, the user can
define constant scaling factors and time-dependent characteristics. Scaling Types
may be added or removed.

Name Shows all existing scaling factor types. With “New,” a type
may be added; with “Delete,” a type may be removed.
Description Description of the scaling type.
Velander, Power Kvel1, Kvel2, Ginf, Gkey, Gexp, cos(phi). These parame-
factor and Low ters are explained in the relevant sections.
Voltage simulta-
neity factors
Long Term A predefined “Long Term Characteristic” can be assigned.
Characteristic
Edit Table After selecting and item (scaling type) user can see the ta-
ble of this type which includes the Day Characteristic, the
month and the weekday definition.

For each moment, a time-dependent scaling factor is determined and it is calcu-


lated as follows:

Pfactor_t(t) = fday(t) * flongTerm(t)


Qfactor_t(t) = fday(t) * flongTerm(t)

This factor is being then applied to the initial active and reactive power of the
Load which is assigned with this Scaling Type.
This is used only for the module "Time Simulation (Load Flow)".

Day Characteristics
A list of all existing "Day Characteristics” appears after selecting the respective
tab in the Scaling Factor Library Editor. By clicking on a characteristic type, the
corresponding curve will be displayed and its values may be modified (with Edit
Table). Characteristic types may be added or removed.

Types Shows all existing day characteristic types. With “New,” a


type may be added; with “Delete,” a type may be removed.
Description Description of the day characteristic type.
Edit behavior Definition table. The program interpolates linearly between

NEPLAN User's Guide V5 10


Load Flow Time Simulation

two points. A maximum of 1440 time values may be en-


tered; for every second a value.
Time Time (hour and minutes), editable directly in the table.
Factors A P-factor and a Q-factor between 0 and 1 may be entered
or edited directly in the table.
Insert 1 item Inserts one time value after the marked line. If no line is
selected, the additional value will be added at the end of
the table.
Insert items Inserts the indicated amount of time values after the
marked line. If no line is selected, the additional time val-
ues will be added at the end of the table.
Remove Removes the marked time values.
Same values for If this checkbox is checked, the Q-factors of the table will
P and Q scaling not be considered. Instead, the Q-factors will be the same
as the P-factors.

NEPLAN User's Guide V5 11


Load Flow Time Simulation

Long Term Characteristics


A list of all existing "Long Term by Year" characteristics appears after selecting
the respective tab in the Scaling Factor Editor. By clicking on a characteristic
type, the corresponding curve will be displayed and its values may be modified
(with Edit Table). Characteristic types may be added or removed.

Types Shows all existing year characteristic types. With “New,” a


type may be added; with “Delete,” a type may be removed.
Description Description of the year characteristic type.
Factors For every year, a P-factor and a Q-factor between 0 and 1
may be entered.
Year Year (4 digits: e.g. 2004) for which a P-factor and a Q-
factor should be defined.
P-factor P-factor for the respective year.
Q-factor Q-factor for the respective year.
Insert 1 item Inserts one year value after the marked line. If no line is
selected, the additional value will be added at the end of
the table.
Insert items Inserts the indicated amount of year values after the
marked line. If no line is selected, the additional year val-
ues will be added at the end of the table.
Remove Removes the marked year values.
Same values for If this checkbox is checked, the Q-factors of the table will
P and Q scaling not be considered. Instead, the Q-factors will be the same
as the P-factors.

NEPLAN User's Guide V5 12

You might also like