GENERAL NOTES AND SYMBOLS (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)

FIRE SPRINKLER SYMBOLS FIRE SPRINKLER NOTES


PIPING SYMBOLS A. PROVIDE COMPLETE WET PIPE FIRE SPRINKLER SYSTEMS FOR
THE ENTIRE BUILDING DESIGNED AND INSTALLED IN
ACCORDANCE WITH IBC 2012 EDITION, UFC 3-600-01, WITH
SYSTEM RISER CHANGE 3, FM DATA SHEET (FMDS) 3-26, AND NFPA 13, 2013
EDITION.
ELBOW UP
B. VERIFY ALL LOCATIONS AND MEASUREMENTS AS CONDITIONS
ELBOW DOWN MAY VARY THROUGHOUT CONSTRUCTION. ALL CHANGES FROM
THE ORIGINAL DESIGN MUST BE APPROVED BY THE FPDOR.
VALVE IN DROP
C. SPRINKLER CONTRACTOR SHALL INSTALL TAMPER AND FLOW
VALVE IN CENTER DROP SWITCHES. CONNECTIONS TO THE FIRE ALARM SYSTEM'S
SIGNALING LINE CIRCUIT SHALL BE MADE UNDER SPECIFICATION
VALVE IN RISE DIVISION 28.

D. SPRINKLER CONTRACTOR SHALL UTILIZE FLOW DATA PROVIDED


DIRECTION OF FLOW
TO BASE HYDRAULIC CALCULATIONS AND SIZE PIPING. IF THE
TEST RESULTS ARE OVER ONE YEAR OLD, SPRINKLER
DIRECTION OF SLOPE DOWN CONTRACTOR TO PERFORM A NEW HYDRANT FLOW TEST.
CONCENTRIC REDUCER E. CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND
APPROVALS FROM THE AHJ PRIOR TO COMMENCING WORK.
ECCENTRIC REDUCER
F. HYDRAULICALLY CALCULATE THE WET PIPE SPRINKLER SYSTEMS
TEE OUTLET UP PER NFPA 13, AND UFC 3-600-01 DENSITY AND SPACING LISTED IN
THE SPRINKLER DESIGN CRITERIA TABLE BELOW. FIELD VERIFY
TEE OUTLET DOWN SYSTEM DESIGN AND LAYOUT PRIOR TO FABRICATION OR
INSTALLATION.
UNION
G. PROVIDE PIPE HANGERS AND SWAY BRACING ON ALL FIRE
STRAINER WITH SPRINKLER SYSTEM PIPING AND EQUIPMENT PER NFPA 13 AS
BLOWDOWN VALVE REQUIRED BY UFC 3-600-01.

GATE VALVE H. SEE ARCHITECTURAL DRAWINGS FOR ROOM FINISH SCHEDULE


AND ROOM USE. SEE ARCHITECTURAL, ELECTRICAL,
MECHANICAL, AND TELECOMMUNICATIONS PLANS FOR THE
CHECK VALVE LOCATION OF ALL CEILING-MOUNTED DEVICES. FIELD VERIFY AND
COORDINATE THE LOCATIONS OF ALL SYSTEM COMPONENTS
PRESSURE CONTROL VALVE INCLUDING PIPING, ALARMS, DRAINS, TEST POINTS, ETC. WITH
ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
EQUIPMENT WITHIN THE BUILDING.
RELIEF VALVE
I. PROVIDE AUXILIARY DRAINAGE WITH A DRAIN VALVE AND PLUG
FOR ALL TRAPPED SECTION OF PIPE, AS REQUIRED BY NFPA 13.
PRESSURE
GAUGE WITH
J. THESE DOCUMENTS DEPICT PERFORMANCE LEVEL ENGINEERING
GAUGE COCK
DESIGN CRITERIA TO BE UTILIZED AS GUIDANCE FOR THE
TEST PORT PLANNING OF THE FIRE SPRINKLER SYSTEM BY THE
CONTRACTOR. PROVIDE COMPLETE DOCUMENTS FOR REVIEW
AND APPROVAL FROM THE ENGINEER OF RECORD AND AHJ
FLOW SWITCH PRIOR TO INSTALLATION. INCLUDE IN THE SHOP DRAWINGS AND
CALCULATIONS ANY ADDITIONAL EQUIPMENT NECESSARY TO
PROVIDE A COMPLETE INSTALLATION.

SPRINKLER SYMBOLS K. PIPE MAIN DRAIN TO OUTSIDE OF BUILDING.

PENDENT SPRINKLER, STANDARD


TEMPERATURE
UPRIGHT SPRINKLER, STANDARD
TEMPERATURE
SIDEWALL SPRINKLER, STANDARD
TEMPERATURE

ABBREVIATIONS WATERFLOW TEST DATA


AFF ABOVE FINISHED FLOOR TEST DATE: APRIL 5, 2016
AHJ AUTHORITY HAVING JURISDICTION
AVG AVERAGE STATIC PRESSURE: 54 PSIG
BFP DOUBLE CHECK BACKFLOW PREVENTER RESIDUAL PRESSURE: 41 PSIG
CFM CUBIC FEET PER MINUTE
CO CONTRACTING OFFICER DISCHARGE FLOW: 1,021 GPM
COTR CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE
ELEV ELEVATION GAUGE HYDRANT # AND LOCATION: 28 - ELEV. 736.0 FT.
FD FLOOR DRAIN FLOW HYDRANT # AND LOCATION: 5 - ELEV. 732.5 FT.
FDC FIRE DEPARTMENT CONNECTION LOWER LEVEL FLOOR: ELEV. 724 FT.
FHV FIRE HOSE VALVE
FP FIRE PUMP
FPC FIRE PUMP CONTROLLER
FPDOR FIRE PROTECTION DESIGNER OF RECORD
MISCELLANEOUS FVC
GALS
FIRE VALVE CABINET
GALLONS
GPH GALLONS PER HOUR
POINT OF NEW CONNECTION TO EXISTING PIPING
GPM
GV
GALLONS PER MINUTE
GATE VALVE
SPRINKLER DESIGN CRITERIA
JP JOCKEY PUMP
MIN MINIMUM DURATION MAXIMUM
CALCULATION NODE POINT (2 NODES) HAZARD SPRINKLER HOSE
GENERAL ROOM/AREA DENSITY OF SPRINKLER
NC NONCOMBUSTIBLE CLASSIFICATION TEMPERATURE ALLOWANCE
CLASSIFICATION REQUIREMENTS SUPPLY PROTECTION AREA
NIC NOT IN CONTRACT
CALCULATION NODE POINT (1 NODE)
NP NOT PERMITTED
OS&Y OUTSIDE SCREW & YOKE OFFICES, HC-1 0.10 GPM/SQFT OVER 60 MIN. 225 SQFT ORDINARY 250 GPM
PSIG POUNDS PER SQUARE INCH GAUGE CONTROL MOST REMOTE 1500 SQFT
SOV SOLENOID VALVE AREA
SQFT SQUARE FEET
UH UNIT HEATER STORAGE, BUILDING HC-2 0.20 GPM/SQFT OVER 60 MIN. 130 SQFT ORDINARY 250 GPM
VLV VALVE SERVICES MOST REMOTE 2500 SQFT

AE PROJ. NO. PROJECT NO.

REVISIONS FDZD7000 FIRE SUPPRESSION GENERAL NOTES, FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
SYMBOLS, AND ABBREVIATIONS
UA
R
AI

RD

DESIGNED BY

J.McLAUGHLIN
REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

I
V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
SCALE DATE 145TH AIRLIFT WING FX-001
10 / 21 / 16 CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
FLOW HYDRANT #5

12" WATER LINE


IP
"D
12 FH

12
SQUADRON
"D 12"
2-1/2" OPERATIONS
FACILITY
IP
NEW 12" DIP

Hercules Blvd
12" DIP
FH

3" CU
GAUGE HYDRANT #28

8" DIP

NE
LI
ER
AT rwall
" W
12

Enlisted Drive
W
12
"D
IP

FH

2-1/2 " WATER LINE

FH

6"

8" CIP

Payne Blvd
12"CIP
N
FH

AE PROJ. NO. PROJECT NO.

GENERAL NOTES REVISIONS FDZD7000 OVERALL SITE FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
FIRE SUPPRESSION PLAN
A. SHEET ILLUSTRATES EXISTING AND PROPOSED WATER MAINS AND FIRE
UA
R
AI

RD

HYDRANTS LOCATIONS, FOR REFERENCE ONLY. THE HYDRANT DESIGNED BY


IDENTIFICATION NUMBERS ARE SHOWN. REFER TO CIVIL PLANS FOR
ADDITIONAL INFORMATION.
J.McLAUGHLIN
REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

I
V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
SCALE DATE 145TH AIRLIFT WING FX-100
10 / 21 / 16 CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
GENERAL NOTES
A B C D
A. REFER TO SHEET FX-001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.

B. ALL AREAS SHALL BE DESIGNED FOR HC-1, UNLESS OTHERWISE NOTED.

C. SYSTEM DESIGN SHALL BE BASED ON DESIGN CRITERIA INDICATED ON


DRAWING FX-001.

Key Notes
Key Value Keynote Text

201 UNDERGROUND COMBINATION DOMESTIC/FIRE SERVICE. REFER TO


7 CIVIL PLANS FOR CONTINUATION.
203 PROVIDE VERTICAL BACKFLOW PREVENTER.
204 PROVIDE FLOOR CONTROL VALVE ASSEMBLY FOR LOWER LEVEL
STORAGE SPRINKLER ZONE.
205 PROVIDE FLOOR CONTROL VALVE ASSEMBLY FOR UPPER LEVEL
WEAPONS & 123
EOC VAULT SPRINKLER ZONE

4"
TACTICS
120 121 206 ASSEMBLY SHALL INCLUDE: CONTROL VALVE (WITH TAMPER
122 SWITCH), CHECK VALVE, WATER FLOW SWITCH, TEST/DRAIN. DRAIN
SHALL RUN TO A COMMON DRAINAGE POINT AND DISCHARGE
DIRECTLY TO EXTERIOR.
209 VERTICAL CHECK VALVE WITH AUTOMATIC BALL-DRAIN.
210 VERTICAL CONTROL VALVE WITH TAMPER SWITCH (NORMALLY
CLOSED).

4"
6 211 PROVIDE FIRE DEPARTMENT CONNECTION AND APPROPRIATE
SIGNAGE. MOUNT SIGNAGE ABOVE CONNECTION.
212 PROVIDE BACKFLOW PREVENTER TEST HEADER AND APPROPRIATE
SIGNAGE. MOUNT SIGNAGE ABOVE HEADER.
SECURITY 213 PIPE UP TO UPPER LEVEL SPRINKLER ZONE.
CHECKPOINT 214 PROVIDE CONTROL VALVE (WITH TAMPER SWITCH) TO ELEVATOR PIT
2 SPRINKLER.
CAT 112

4"
CORRIDORINTEL OFFICER STORAGE TACTICS CHIEF FX-102 215 ELEVATOR PIT SPRINKLER SHALL BE MOUNTED NO HIGHER THAN 24"
119 AFF AND EQUIPPED WITH PROTECTIVE GUARD.
TRAINING
111 126 125 124 216 PROVIDE VALVE ASSEMBLY FOR ELEVATOR MACHINE ROOM
118 F SPRINKLER ZONE.
217 PROVIDE SPRINKLER PROTECTION WITHIN ELEVATOR SPACE AND
EQUIP WITH PROTECTIVE GUARD.
5 220 PROVIDE WEATHER-PROOF TAMPER SWITCH AT POST INDICATOR
FRAME ROOM CORRIDOR 1 VALVE ALONG UNDERGROUND MAIN. REFER TO CIVIL PLANS FOR
FINAL LOCATION OF VALVE.

4"
117 110 222 SPRINKLERS LOCATED UNDER STAIRCASE. PROVIDE PROTECTIVE
WIRE GUARDS.
224 PIPE UP TO CEILING SPRINKLERS. SEE SHEET F-102 FOR
HC-2 CONTINUATION.
EA CELL 226 WHERE AREA IS OPEN TO ABOVE, PROVIDE SPRINKLERS WITH
CONSOLE AREA 216 206 WATER SHIELD.
113

CORRIDOR
ELEVATOR TO UPPER LEVEL

4"
BRIEFING
EQUIPMENT SPRINKLERS

109
104
103
CP MANAGER
116 HC-2

4 TOILET 217
WOMEN MEN LOBBY ELEVATOR TO DINGHY ROOM
115

4"
SPRINKLERS

4"
106 108 102 HC-2 E01

215 UPPER LEVEL


TO LOWER LEVEL 114' - 0"
214 SPRINKLERS

STORAGE 222
HC-2 UP
114

4"
222
205

4"
JANITOR CORRIDOR
STAIR 01
107 105 4" 4"
S101

2.8 203
3 NVG HELMET

4"
211
132 LOCKERS
TER SUPT.
134
130 131
HELMET REPAIR 222
CORRIDOR 135 LOWER LEVEL
133 100' - 0"

HC-2 VESTIBULE
EQUP.
INSPECTION FLIGHT EQUIP. 101 TO UNDERGROUND
4"

OFFICE INSPECTION MAIN

139 137
FIRE SUPPRESSION - RISER SECTION
TRAINING 3 1/4" = 1'-0"
226 138 HC-2
4"

FX-101
2 C
6"
E
EQUIPMENT
STORAGE
HC-2 LAUNDRY
226 142
141
226
PARACHUTE

6"
206 205 213
DINGHY ROOM SHOP
HC-2 MECHANICAL 140 136
4"
226 143
6"

HC-2 HC-2 203

4"
6"

6"
224
6" 6"
6"
206 204
1
210
HC-2 209

8"
212
ELECTRICAL 211
144 220 201
2
A.5 FX-101
N
ENLARGED FIRE SUPPRESSION RISER ROOM
3
2 1/4" = 1'-0"
FX-101 FX-101

AE PROJ. NO. PROJECT NO.

REVISIONS FDZD7000 LOWER LEVEL FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
FIRE SUPPRESSION PLAN
UA
R
AI

RD

0 2' 4' 8' 12' DESIGNED BY

1/4" = 1'-0" J.McLAUGHLIN


REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

0 4' 8' 16' 24' I


V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
LOWER LEVEL FIRE SUPPRESSION PLAN 1/8" = 1'-0" SCALE DATE 145TH AIRLIFT WING FX-101
1 1/8" = 1'-0" CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
10 / 21 / 16
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
GENERAL NOTES
A B C D
A. REFER TO SHEET FX-001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.

B. ALL AREAS SHALL BE DESIGNED FOR HC-1, UNLESS OTHERWISE NOTED.

C. SYSTEM DESIGN SHALL BE BASED ON DESIGN CRITERIA INDICATED ON


DRAWING FX-001.

Key Notes
Key Value Keynote Text

202 DUE TO AESTHETICS, PROVIDE SIDEWALL SPRINKLER PROTECTION


7 VESTIBULE
FLIGHT
SUPERINTENDENT WITHIN CORRIDOR. MINIMIZE PIPING WITHIN THIS CORRIDOR.
EXPOSED PIPING SHALL BE PAINTED TO MATCH ADJACENT
207 SCHEDULING 221 SURFACES. PROVIDE ADDITIONAL SPRINKLER PROTECTION UNDER
DUCTWORK, AS REQUIRED BY NFPA 13.
220
GROUP DEPUTY GROUP 206 ASSEMBLY SHALL INCLUDE: CONTROL VALVE (WITH TAMPER
COMMANDER CMNDR.

4"
SWITCH), CHECK VALVE, WATER FLOW SWITCH, TEST/DRAIN. DRAIN
217 218 SHALL RUN TO A COMMON DRAINAGE POINT AND DISCHARGE
DIRECTLY TO EXTERIOR.
AIRLIFT SQ 223 219 PROVIDE VALVE ASSEMBLY FOR TOP OF ELEVATOR SHAFT
COMNDR. (TYP) RADIO DISPATCH SPRINKLER ZONE.
222 221 WITHIN BOUNDARY, PROVIDE SPRINKLER PROTECTION ABOVE FALSE
216
CEILING AND ALONG ACOUSTIC TILE CEILING. TWO LEVELS OF
OPERATIONS DIR. PROTECTION IS REQUIRED. EXPOSED PIPING SHALL BE PAINTED TO
ADMIN SUPPORT 219 MATCH ADJACENT SURFACES.
6 208 FLIGHT DATA 223 PROVIDE INTERMEDIATE-TEMPERATURE SPRINKLERS WHERE
OPS SUPPORT MGMNT. LOCATED WITHIN SKYLIGHTS.
CMNDR. 225 PIPE DOWN TO LOWER LEVEL SPRINKLER ZONE.
223
215 227 PROVIDE AN AUXILIARY DRAIN FOR UPPER LEVEL SPRINKLERS AND
WEATHER DISCHARGE TO LOCATION SHOWN. DISCHARGE OUTLET SHALL BE NO
HIGHER THAN 6" FROM GRADE.

4"
224 2
GROUP CHIEF FX-102
214
CONFERENCE
AIRCREW F
221

4"
209 BRIEFING (TYP)
202
225
SIDEWALL SPRINKLER
3
5

MEDICAL SUITE
227
PLANNING PLANNING PLANNING

211
226 227 228
ORDERLY
210

4"
UPPER LEVEL MAIN
STAN. / EVAL TESTING

CORRIDOR
CURRENT
OPERATIONS 229 230

206
FIRST SERGEANT
219 206
213 212

TO UPPER LEVEL FLOOR


4 ELEVATOR

4"
CONTROL VALVE ASSEMBLY
WOMEN MEN E02
203 205 RECORDS LOBBY
TRAINING 3
232 201
231 FX-102 HC-2

4"
ARMS
233
HC-2
4" 4" DN

JANITOR CORRIDOR

4"
204 202 223
202 (TYP)
UPPER
UPPERLEVEL
LEVEL
3 STAIR 01 2.8 EL: 114'-- 0"
114' 0"
TELECOM
S201
235 CHIEF FLIGHT BREAK ROOM
CHIEF NAV. CHIEF PILOT CHIEF LDMSTR.
ENG
HC-2 237 239 244
243

4"
241

4" 4" 4" 4" 4" FIRE SUPPRESSION - CORRIDOR 202 SECTION
FLIGHT
3 1/4" = 1'-0"
NAVIGATORS PILOTS ENGINEERS LOADMASTERS FX-102
236 238 240 242

6" 5 4 3
2
E TYPICAL: UPRIGHT SPRINKLERS UNDER DECK

BRANCHLINE TO SPRINKLERS
6"

TYPICAL: PENDENT SPRINKLERS


UNDER ACOUSTIC TILE CEILING

UPPER LEVEL
114' - 0"

225 LOWER LEVEL


100' - 0"
A.5
N
FIRE SUPPRESSION - LOBBY 201 SECTION
3 2 1/8" = 1'-0"
FX-101
FX-101

AE PROJ. NO. PROJECT NO.

REVISIONS FDZD7000 UPPER LEVEL FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
FIRE SUPPRESSION PLAN
UA
R
AI

RD

0 2' 4' 8' 12' DESIGNED BY

1/4" = 1'-0" J.McLAUGHLIN


REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

0 4' 8' 16' 24' I


V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
UPPER LEVEL FIRE SUPPRESSION PLAN 1/8" = 1'-0" SCALE DATE 145TH AIRLIFT WING FX-102
1 1/8" = 1'-0" CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
10 / 21 / 16
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
GENERAL NOTES
A. REFER TO SHEET FX-001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.

ISOLATION CONTROL B. ALL AREAS SHALL BE DESIGNED FOR HC-1, UNLESS OTHERWISE NOTED.

TO UPPER LEVEL
VALVE WITH TAMPER
C SWITCH
C. SYSTEM DESIGN SHALL BE BASED ON DESIGN CRITERIA INDICATED ON

SPRINKLERS
CHECK VALVE DRAWING FX-001.

SUPPLY FROM
SPRINKLER RISER
FLOW
SWITCH PRESSURE GAUGE
TO LOWER LEVEL SPRINKLERS

WATER FLOW SWITCH (TYP) TO


SYSTEM

CHECK VALVE (TYP)

CONTROL VALVE (TYP)


SECTIONAL DRAIN
VALVE

DRAIN
TO
TEST VALVE OR TEST/DRAIN
ASSEMBLY
UNION

SIGHT GLASS

ZONE / FLOOR CONTROL ASSEMBLY DETAIL


TO FIRE DEPARTMENT
2 NOT TO SCALE
CONNECTION

TO BACKFLOW PREVENTER VERTICAL BACKFLOW


TEST HEADER PREVENTER

FLANGE PROVIDE 2-INCH ANNULAR SPACE


BOLLARD AND (TYP)
SPIGOT
PIECE ESCUTCHEON AT TO FIRE PROTECTION
EXPOSED LOCATIONS SYSTEMS
CONTROL VALVE BY FIRE PROTECTION
ARM OVER SHALL MEET CONTRACTOR
NFPA 13 CRITERIA BUILDING
CHECK VALVE SEALANT
LOWER LEVEL FLOOR
100' - 0"

BY SITE UTILITY
CONTRACTOR

RESTRAINED JOINT

SUPPLY (REF CIVIL) VERTICAL


SUSPENDED CEILING RESTRAINED JOINT
SPRINKLER MAIN
OR BRANCH LINE
DUCTILE IRON

TO UNDERGROUND PENDENT CONCEALED HORIZONTAL


WATER MAIN SPRINKLER SPRINKLER RESTRAINED JOINT

FIRE SUPPRESSION - RISER PLAN SPRINKLER ARM OVER DETAIL (TYPICAL) FIRE WATER SERVICE DETAIL
1 NOT TO SCALE 3 NOT TO SCALE 4 NOT TO SCALE

STRUCTURAL
MEMBER

SWIVEL SWAY 1/2" THRU BOLT


BRACING

BRACE PIPE

RETAINER
STRAP

BEAM CLAMP
WITH LOCKNUT

PIPE CLAMP STRUCTURAL SPAN

RETAINER
STRUCTURAL STRAP TOP BEAM
CLAMP WITH
MEMBER LOCKNUT
STRUCTURAL
ALL THREAD MEMBER
ROD PIPE, ANGLE
IRON, OR HEX NUT AND
STRUCTURAL CHANNEL PER FLAT WASHER
SURGE NFPA 13
MEMBER
RESTRAINER SWIVEL SWAY
BRACING 1/2" THRU BOLT

ALL THREAD
ROD BRACE PIPE
SURGE
SURGE
RESTRAINER
PIPE RING RESTRAINER ALL THREAD
ROD SIZED PER
NFPA 13
PIPE RING

NOTE: TO BE USED ONLY WITH BAND HANGERS TO RESTRAIN THE


UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD PIPE CLAMP
ACTIVATION OR SEISMIC ACTIVITY. INSTALL AT THE END OF EACH BRANCH
LINE AND AT 30' INTERVALS ALONG BRANCH LINES PER NFPA 13.

BEAM CLAMP HANGER DETAIL SURGE RESTRAINER DETAIL SWAY BRACING DETAILS TRAPEZE HANGER DETAIL
5 NOT TO SCALE 6 NOT TO SCALE 7 NOT TO SCALE 8 NOT TO SCALE

AE PROJ. NO. PROJECT NO.

REVISIONS FDZD7000 FIRE SUPPRESSION FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
DETAILS
UA
R
AI

RD

DESIGNED BY

J.McLAUGHLIN
REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

I
V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
SCALE DATE 145TH AIRLIFT WING FX-201
10 / 21 / 16 CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
(ALL SYMBOLS AND ABBREVIATIONS SHOWN ARE
FIRE ALARM / MASS NOTIFICATION NOT NECESSARILY USED ON THE DRAWINGS)

GENERAL NOTES SYMBOLS - PANEL ABBREVIATIONS


GENERAL NOTES SYMBOL DESCRIPTION ACU AUTONOMOUS CONTROL UNIT
1. SYSTEM SHALL BE DESIGNED, INSTALLED, AND COMMISSIONED IN ACCORDANCE WITH THE FACP FIRE ALARM CONTROL PANEL AFF ABOVE FINISHED FLOOR
FOLLOWING: AHJ AUTHORITY HAVING JURISDICTION
- NORTH CAROLINA STATE BUILDING CODE (NCBC), (2012 EDITION); FMCP FIRE ALARM / MASS NOTIFICATION CONTROL PANEL AVG AVERAGE
- NFPA 72 (2016 EDITION);
- UFC 3-600-01 (CHANGE 3 MARCH 2013) ASSD AIR SAMPLING SMOKE DETECTOR PANEL CA CLEAN AGENT
- UFC 4-021-01 (CHANGE 1 JANUARY 2010) CO CONTRACTING OFFICER
- APPLICABLE LOCAL AND NATIONAL CODES/STANDARDS. RECP RELEASING CONTROL PANEL COR CONTRACTING OFFICER REPRESENTATIVE
COTR CONTRACTING OFFICERS TECHNICAL REPRESENTATIVE
2. THESE DOCUMENTS DEPICT A PERFORMANCE LEVEL ENGINEERING DESIGN LAYOUT TO BE UTILIZED ANN ANNUNCIATOR PANEL
AS GUIDANCE FOR THE PLANNING OF THE SYSTEM BY THE CONTRACTOR. PROVIDE COMPLETE ELEV ELEVATION
DOCUMENTS FOR REVIEW AND APPROVAL FROM THE ENGINEER OF RECORD AND THE AUTHORITY GAP GRAPHIC ANNUNCIATOR PANEL EOL END OF LINE RESISTOR
HAVING JURISDICTION PRIOR TO INSTALLATION. INCLUDE IN THE SHOP DRAWINGS AND CALCULATIONS
ANY ADDITIONAL EQUIPMENT NECESSARY, INCLUDING INITIATING DEVICES AND NOTIFICATION LOC LOCAL OPERATING CONSOLE FPC FIRE PUMP CONTROLLER
APPLIANCES, TO PROVIDE A COMPLETE INSTALLATION AND COMPLY WITH LOCAL CODES, FPDOR FIRE PROTECTION DESIGNER OF RECORD
AMENDMENTS AND BASE STANDARDS. NAC NOTIFICATION APPLIANCE CONTROL PANEL
IDC INITIATING DEVICE CIRCUIT
3. FOR COMPLETE SYSTEM CONTROL, REFER TO THE MATRIX OF OPERATIONS WITHIN THIS PACKAGE. ERS EMERGENCY RESPONSE SYSTEM CONTROL PANEL
MIN MINIMUM
4. PROVIDE AN ADDRESSABLE FIRE ALARM/MASS NOTIFICATION CONTROL PANEL WITH RADIO ALARM REMOTE ANTENNA
TRANSMITTER TO TRANSMIT ALARM, TROUBLE, AND SUPERVISORY SIGNALS TO THE MONACO BASE NAC NOTIFICATION APPLIANCE CIRCUIT
REPORTING SYSTEM. NC NONCOMBUSTIBLE
NIC NOT IN CONTRACT
5. FINAL ACCEPTANCE TESTING SHALL BE WITNESSED BY THE CONTRACTING OFFICER'S TECHNICAL
REPRESENTATIVE AND AUTHORITY HAVING JURISDICTION. FILE A "RECORD OF COMPLETION"
SYMBOLS - INITIATING NP NOT PERMITTED

PREPARED IN ACCORDANCE WITH NFPA 72, AND THE FIRE ALARM TEST REPORT WITH THE FPDOR AND SLC SIGNALING LINE CIRCUIT
AHJ. SYMBOL DESCRIPTION SQFT SQUARE FEET
F MANUAL PULL STATION
6. THE FLASH RATE OF VISIBLE NOTIFICATION APPLIANCES SHALL NOT EXCEED 2 FLASHES PER WP WEATHER PROOF
SMOKE DETECTOR
SECOND, NOR BE LESS THAN 1 FLASH EVERY SECOND, IN ACCORDANCE WITH NFPA 72. A MAXIMUM P = PHOTOELECTRIC
PULSE DURATION SHALL BE 0.2 SECONDS WITH A MAXIMUM DUTY CYCLE OF 40%, IN ACCORDANCE P,I,ASD I = IONIZATION
WITH NFPA 72. VISIBLE NOTIFICATION APPLIANCES SHALL BE SPACED IN ACCORDANCE WITH NFPA 72. ASD = AIR SAMPLING DETECTOR
ALL STROBES SHALL BE SYNCHRONIZED.
DUCT DETECTOR
7. AUDIBLE FIRE ALARM SOUND LEVELS SHALL BE AT LEAST 15 dBA ABOVE THE AVERAGE AMBIENT ID ID = FAN UNIT DESIGNATION
SOUND LEVEL OR 5 dBA ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 S,R S = SUPPLY
SECONDS, WHICHEVER IS GREATER, MEASURED 5 FEET ABOVE THE FLOOR IN THE OCCUPIABLE AREA,
R = RETURN
BUT NOT GREATER THAN 120 dBA AT THE MINIMUM HEARING DISTANCE FROM THE AUDILE
APPLIANCE. PROVIDE ADEQUATE NOTIFICATION APPLIANCES THROUGHOUT THE FACILITY TO MEET
THE NFPA 72 REQUIREMENTS. CARBON MONOXIDE DETECTOR
CO

8. SPRINKLER SYSTEM TAMPER AND FLOW SWITCHES SHALL BE INSTALLED UNDER SPECIFICATION
DIVISION 21. CONNECT DEVICES TO THE FIRE ALARM SIGNALING LINE CIRCUITS.

9. OBTAIN APPROVALS FROM THE FPDOR AND AHJ PRIOR TO COMMENCING WORK.

10. MOUNT THE OPERABLE PART OF MANUAL PULL STATIONS AT 48" AFF.

11. DO NOT LOCATE DETECTORS IN DIRECT AIR OR CLOSER THAN 3 FEET FROM AN AIR SUPPLY OR
RETURN DIFFUSER. SYMBOLS - NOTIFICATION
12. MOUNT ALL WALL-MOUNTED VISUAL AND VISUAL/AUDIBLE NOTIFICATION APPLIANCES WITH THE
ENTIRE STROBE LENS BETWEEN 80" TO 96" ABOVE THE FINISHED FLOOR. SYMBOL DESCRIPTION
COMBINATION FIRE ALARM / MASS NOTIFICATION
SPEAKER/STROBE (WALL-MOUNTED, UNLESS OTHERWISE NOTED)
CD,C
CD = CANDELA RATING
C = CEILING-MOUNTED

SPEAKER (WALL-MOUNTED, UNLESS OTHERWISE NOTED)


C C = CEILING-MOUNTED

SYMBOLS - MISCELLANEOUS
SYMBOL DESCRIPTION
MM MONITOR MODULE

CM CONTROL MODULE

C TAMPER SWITCH
TS
C WATER FLOW SWITCH
WF
KB KNOX BOX (WITH TAMPER SWITCH)

AE PROJ. NO. PROJECT NO.

REVISIONS FDZD7000 FIRE ALARM GENERAL NOTES, FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
SYMBOLS, AND ABBREVIATIONS
UA
R
AI

RD

DESIGNED BY

J.McLAUGHLIN
REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

I
V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
SCALE DATE 145TH AIRLIFT WING FA-001
10 / 21 / 16 CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
GENERAL NOTES
A B C D
A. REFER TO SHEET FA-001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.

Key Notes
Key Value Keynote Text

101 PROVIDE COMBINATION ADDRESSABLE FIRE ALARM/MASS


NOTIFICATION CONTROL PANEL. ALL SIGNALING LINE CIRCUITS AND
NOTIFICATION APPLIANCE CIRCUITS SHALL ORIGINATE FROM THIS
PANEL. PROVIDE BATTERY BACK-UP TO THE CONTROL PANEL.
7 103 PROVIDE MONITOR MODULES FOR THE FOLLOWING FIRE
SUPPRESSION SWITCHES: 2 MODULES FOR BACKFLOW PREVENTER
TAMPERS, 2 MODULES FOR FLOOR VALVE TAMPERS, 2 MODULES FOR
15,C FLOOR WATER FLOW SWITCHES, AND 1 MODULE FOR BACKFLOW
75,C 75,C STORAGE PREVENTER TEST HEADER TAMPER.
123 104 PROVIDE MODULES AND INTERFACE WITH ELEVATOR CONTROLLER.
MODULES SHALL INITIATE: PRIMARY RECALL, ALTERNATE RECALL,
WEAPONS & FIRE FIGHTER HAT (CONSTANT), FIRE FIGHTER HAT (FLASH). PROVIDE
115 MODULE TO MONITOR POWER TO SHUNT TRIP.
(TYP) EOC VAULT TACTICS
105 PROVIDE EMERGENCY RESPONSE SYSTEM CONTROL PANEL. SYSTEM
120 121 122 SHALL PROVIDE EMERGENCY RESPONDERS ADEQUATE RADIO
CM LC COVERAGE WITHIN THE FACILITY. PROVIDE MODULES TO MONITOR
MANUAL ACTIVATION OF THE SYSTEM AND A CONTROL MODULE TO
AUTOMATICALLY ACTIVATE THE SYSTEM.
6 106 PROVIDE MODULE TO MONITOR POST INDICATOR VALVE TAMPER
75,C 15,C SWITCH. PROVIDE SURGE SUPPRESSOR FROM MODULE TO TAMPER
75,C SWITCH.
107 PROVIDE MODULE TO DEACTIVATE PUBLIC ADDRESS SYSTEM.
SECURITY MOUNT MODULE WITHIN THREE FEET OF CONTROLLER.
CHECKPOINT CORRIDOR 108 PROVIDE A CONTROL MODULE TO SHUTDOWN FAN AND MOUNT
112 111 MODULE WITHIN THREE FEET OF THE UNIT CONTROLLER.
CAT
C 109 PROVIDE MONACO RADIO ALARM TRANSMITTER IN ORDER TO SEND
119 ALARM, SUPERVISORY, AND TROUBLE SIGNALS TO A CENTRAL
30,C INTEL OFFICER STORAGE TACTICS CHIEF MONITORING STATION. PANEL SHALL BE MOUNTED ABOVE FMCP.
CM LC 15 126 125 124
F
15,C 110 PROVIDE MASS NOTIFICATION REPORTING SYSTEM, MANUFACTURED
TRAINING BY WHELEN, IN ORDER TO CONNECT TO BASE-WIDE MASS
NOTIFICATION NETWORK. PANEL SHALL BE MOUNTED ABOVE FMCP.
118
5 111 COMPONENTS SHALL BE FLUSH MOUNTED TO WALL.
CORRIDOR 112 INSTALL DEVICE BELOW MEZZANINE GRATED FLOOR, ABOVE
110 BOILER/WATER HEATER AND ABOVE FMCP.
CM LC FRAME ROOM 15,C 113 PROVIDE REMOTE ANTENNA WITHIN BUILDING TO BOOST
EMERGENCY RESPONSE SIGNAL.
117
EA CELL 104 114 PROVIDE MODULE TO MONITOR KNOX BOX TAMPER SWITCH.
CONSOLE AREA 115 PROVIDE CONTROL MODULE FOR EACH EMERGENCY LIGHTING
113 C 30 INTERFACE CONTROLLER IN ORDER TO OVERRIDE THE OCCUPANCY
75,C SENSOR FUNCTION AND OPERATE ALL LIGHTS UPON ANY FIRE
75,C
CM (5) ALARM SIGNAL.
CM LC
MM
CP MANAGER CM LC
CORRIDOR C
116 WF MM
109 BRIEFING C
TS MM P
104 ELEVATOR
4 EQUIPMENT
LOBBY
TOILET
103
102
115
WOMEN
MEN 15,C
15,C 106 ELEVATOR
108 P
E01
STORAGE 113 75,C
C
114 JANITOR TS MM
107
15 15
F

CORRIDOR
15,C 105 15,C STAIR 01
S101
3 2.8

LOC A
CM HELMET

CORRIDOR
WP SUPT. NVG LOCKERS VESTIBULE

NN
101

133
P 131 132 15,C 134 15,C
107 TER

F
130

CM EF-1 HELMET REPAIR


135

KB
EQUP. 15,C
108 INSPECTION 111
OFFICE TRAINING
139 138 30,C 114
15,C 15,C WP
FLIGHT EQUIP.
CM LC INSPECTION
15,C
137

2
30 E
EQUIPMENT
STORAGE LAUNDRY

142 141

30
PARACHUTE
MECHANICAL DINGHY ROOM
30 SHOP
F

143 140
136
CM
CO 75
112

WP
F

ANN LOC

ELECTRICAL 112
106
144
TS MM

C
110 MM
P WF MM (2)
MNS 75 C 15
RAT TS MM (3)
RAT CM C
TS MM (2)
C

109 FMCP ERS F


1
WP
101
105 A.5 103
N

AE PROJ. NO. PROJECT NO.

REVISIONS FDZD7000 LOWER LEVEL FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
FIRE ALARM PLAN
UA
R
AI

RD

DESIGNED BY

J.McLAUGHLIN
REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

0 4' 8' 16' 24' I


V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
LOWER LEVEL FIRE ALARM PLAN 1/8" = 1'-0" SCALE DATE 145TH AIRLIFT WING FA-101
1 1/8" = 1'-0" CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
10 / 21 / 16
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
GENERAL NOTES
A B C D
A. REFER TO SHEET FA-001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.

Key Notes
Key Value Keynote Text
VESTIBULE
111 102 PROVIDE DUCT DETECTOR TO MONITOR AIR HANDLING FAN UNIT.
207
WP DETECTOR SHALL BE MOUNTED ALONG SUPPLY DUCTWORK.
PROVIDE A CONTROL MODULE TO SHUTDOWN UNIT AND MOUNT
MODULE WITHIN THREE FEET OF THE UNIT CONTROLLER.

ANN LOC F
7 FLIGHT 108 PROVIDE A CONTROL MODULE TO SHUTDOWN FAN AND MOUNT
SCHEDULING MODULE WITHIN THREE FEET OF THE UNIT CONTROLLER.
GROUP DEPUTY GROUP SUPERINTENDENT
COMMANDER CMNDR. 111 COMPONENTS SHALL BE FLUSH MOUNTED TO WALL.
220
221 113 PROVIDE REMOTE ANTENNA WITHIN BUILDING TO BOOST
217 218 15,C EMERGENCY RESPONSE SIGNAL.
115 PROVIDE CONTROL MODULE FOR EACH EMERGENCY LIGHTING
RADIO DISPATCH INTERFACE CONTROLLER IN ORDER TO OVERRIDE THE OCCUPANCY
15 SENSOR FUNCTION AND OPERATE ALL LIGHTS UPON ANY FIRE
222 ALARM SIGNAL.
AIRLIFT SQ
COMNDR. OPERATIONS DIR.
216 219
15,C 30,C
6
FLIGHT DATA
OPS SUPPORT ADMIN SUPPORT MGMNT.
CMNDR.
208 223
215 WEATHER
CONFERENCE 224
209
15,C
CM LC

CORRIDOR
GROUP CHIEF 15,C AIRCREW F

206
214 BRIEFING
225
15,C 15,C
5
PLANNING
ORDERLY PLANNING PLANNING
CM LC 226
210 15,C 15,C 227 228
MEDICAL SUITE
15,C
211
STAN. / EVAL TESTING
229 230
FIRST SERGEANT CM LC
213 30,C
30,C CM LC
CURRENT
15,C OPERATIONS 15,C

212
LOBBY
4
RECORDS 201
WOMEN MEN
113 232
203 205
P
15,C 15,C P ELEVATOR
15 15 TRAINING ARMS E02
C
JANITOR 231 233 WF MM
15,C CM LC C
204 TS MM
115 15
(TYP)
15 15
CORRIDOR
111
202
F CM LC
3 TELECOM 2.8
CHIEF FLIGHT BREAK ROOM
WP 235 CHIEF NAV. CHIEF PILOT ENG 244 CHIEF LDMSTR.
30,C
P 237 239 241 243

30,C 30,C 30,C 30,C

FLIGHT
NAVIGATORS PILOTS ENGINEERS LOADMASTERS
236 238 240 242

2
102 RTU-1 RTU-1 E
S R
CM

102 AHU-1 AHU-1


S R
CM

108

CM ERV-1

A.5
N

AE PROJ. NO. PROJECT NO.

REVISIONS FDZD7000 UPPER LEVEL FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
FIRE ALARM PLAN
UA
R
AI

RD

DESIGNED BY

J.McLAUGHLIN
REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

0 4' 8' 16' 24' I


V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
UPPER LEVEL FIRE ALARM PLAN 1/8" = 1'-0" SCALE DATE 145TH AIRLIFT WING FA-102
1 1/8" = 1'-0" CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
10 / 21 / 16
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA
GENERAL NOTES
JUNCTION BOX A. REFER TO SHEET FA-001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.
CONDUIT FROM CONDUIT TO
PREVIOUS DEVICES REMAINING DEVICES

FINISHED CEILING
SIGNALING LINE AND NOTIFICATION (WHERE PROVIDED)
APPLIANCE CIRCUIT CONDUIT
(SINGLE CONDUIT, WHEN
PERMITTED BY MANUFACTURER)

FIRE ALARM NOTIFICATION


APPLIANCE LOCATION ZONE
(AUDIBLE ONLY APPLIANCES
SHALL BE MOUNTED NOT LESS
THAN 90" AFF AND NOT LESSTHAN
6" BELOW THE FINISHED CEILING)

MAXIMUM HORIZONTAL
DISTANCE TO EXIT IS 5 FEET FIRE

96" AFF
80" AFF
MOUNTED PULL
STATION AND BACKBOX

42" - 48" AFF


FINISHED FLOOR

FIRE ALARM MOUNTING DETAIL


2 NOT TO SCALE

20 MM EMT CONDUIT
J-BOX ON FLOOR SLAB

100 MMx100 MMx58 MM J-BOX


15 MM FLEX WITH FIRE
DETECTION CIRCUITS

STRUCTURAL "T" BAR TYPE HANGER


MEMBER 20 MM EMT CONDUIT
SMOKE
DETECTOR BASE J-BOX ON
SMOKE
EXPOSED CEILING
DETECTOR BASE
DROP CEILING TILE
SMOKE
DETECTOR SMOKE DETECTOR

EXPOSED CEILING DETECTOR DETAIL SUSPENDED CEILING DETECTOR DETAIL


3 NOT TO SCALE 4 NOT TO SCALE

ANTENNA
(OMNI
DIRECTIONAL)
ROOF/PARAPET

MAST SIZE AS
REQUIRED
LIGHTNING ARRESTER

WALL
MOUNTED RAIN PROOF
ENCLOSURE

GROUND CLAMP

COAXIAL CABLE

DRIP
GROUND WIRE USE PROOF
NO. 10 AWG SERVICE BUILDING
COPPER WIRE OR LOOP WALL
LARGER FOR
GROUNDING WIRE.
SUPPORT THE WIRE
EVERY 4'-0" TO 6'-0".
WEATHER-HEAD
STANDOFF SUPPORT
COAXIAL CABLE
AS PER
COAXIAL CABLE MANUFACTURERS
RECOMMENDATIONS
GROUND CLAMP IN 3/4" CONDUIT TO
CONTRACTOR TO FIRE ALARM
GROUND ROD 3/4" X 8': PROVIDE SILICONE TRANSMITTER.
LOCATE GROUND ROD AWAY CAULKING AT THE
FROM TRAFFIC AREA. EXACT CONDUIT
LOCATION SHALL BE PENETRATION
APPROVED BY CONTRACTING
OFFICER PRIOR TO
INSTALLATION

FIRE ALARM MATRIX OF OPERATION NOTIFICATION ANTENNA DETAIL


1 NOT TO SCALE 5 NOT TO SCALE

AE PROJ. NO. PROJECT NO.

REVISIONS FDZD7000 FIRE ALARM FJRP


T I ON A L
089066
NA
DRAWN BY
G
REV DATE DESCRIPTION INITIAL M.CONNOLLY
DETAILS
UA
R
AI

RD

DESIGNED BY

J.McLAUGHLIN
REPLACE SQUADRON OPERATIONS FACILITY
NG
C I

GE O

REVIEWED BY
US

SHEET
AM
GR

TR

H
A

NE
P

IA
E CO NF IN IA PE
SCI ENT IAE QUE

I
V

J.BEALS NORTH CAROLINA AIR NATIONAL GUARD


I

L
R

E
EN GI N E
SCALE DATE 145TH AIRLIFT WING FA-201
10 / 21 / 16 CHARLOTTE-DOUGLAS IAP, NORTH CAROLINA
NCANG CIVIL ENGINEERING CHARLOTTE-DOUGLAS IAP CHARLOTTE, NORTH CAROLINA