You are on page 1of 8

UPGRADING OF AL AWABI, AL HAZIM AND WADI BANI GHAFIR PRIMARY SUBSTATIONS (33/11kV) TO 2X2

GOVERNORATE
TENDER NO.: 08/2016

Components details with country of origin

S. No. Components Part number


1. Transformer Differential Protection Relay 0787EX1D1D0X71810810
Directional & Non-directional Overcurrent & Earth Fault Protection
2. 751201D1D1D0X810810
Relay
3. Neutral Displacement Relay 751A51D1D0X73810810
4. Test Blocks 4M200-01
5. High Burden Hand/Electrical Reset Trip Relay TR12-DD-42
6. High Burden Hand/Electrical Reset Cross Trip Relay BJ-8RP HB 110VDC
7. Trip Circuit Supervision Relay XRD-6DB-TBD-R2
8. Protection DC supply supervision Relay XRD-4DB-TBD-R2
9. Interface panel DC supply supervision Relay XRD-4DB-TBD-R2
10. Indication circuit DC supply supervision Relay XRD-4DB-TBD-R2
11. Transformer Mechanical Protection Relays AR25-DN-12-L
12. Multi-function Meter Elite-443
13. Annunciator UC625
14. Remote/Supervisory Selector Switch R20
15. Cross Trip IN/OUT selector switch R20
16. Discrepancy selector switch DR20
17. Semaphore Indicator for Earth switch position indication SPSR-30S-DC110
18. Push Buttons P2AF
19. Indication Lamps 3PLBR
20. Fuse & Disconnecting Links RS20F
21. Contact Multiplication Relays 55.32, 55.34
22. VT supply supervision Relay XM-52M-M400LN
23. AC Miniature Circuit Breakers A9F
24. DC Miniature Circuit Breakers A9N
25. DC changeover contactor AF30-30-00-13
26. Thermostat 205-C
27. Panel Heater SH/006/145
28. Heater ON/OFF switch XB5AD21
29. Power Socket with Switch VX1300
30. Door Limit Switch 3SE3020
31. Cubicle Illumination Lamp FMS200/111
32. Hooter AUH-1122
33. OFF Delay Timer H3DK-M1
34. CT Terminals WTL 6/3
35. VT Terminals WTL 6/1
36. Control Terminals & AC/DC Terminals CTS4UN
37. SCADA Terminals CKT4U
38. Diode Terminals CDL4UED2
39. Earth Test Link CSTSN5U
HAFIR PRIMARY SUBSTATIONS (33/11kV) TO 2X20 MVA AT SOUTH AL BATINAH
GOVERNORATE
TENDER NO.: 08/2016

ents details with country of origin

Make Country of Origin


SEL USA

SEL USA

SEL USA
RMS Australia
RMS Australia
Arteche Spain
RMS Australia
RMS Australia
RMS Australia
RMS Australia
RMS Australia
CEWE Sweden
RTK UK
Comelectric Italy
Comelectric Italy
Comelectric Italy
Fuji Japan
TEKNIC India
TEKNIC India
Bussmann Hungary
Finder Italy
RMS Australia
Schneider India
Schneider India
ABB Germany
Grishego India
Grishego India
Schneider India
Volex UK
Siemens Germany
Philips India
Alan India
Omron Japan
Weidmuller Germany
Weidmuller Germany
Connectwell India
Connectwell India
Connectwell India
Connectwell India
UPGRADING OF AL AWABI, AL HAZIM AND WADI BANI GHAFIR PRIMARY SUBSTATIONS (33/11kV) TO 2X20 MVA AT SOUTH AL BATINAH GOVERNORA
TENDER NO.: 08/2016
Compliance statement against MZEC comments for Rev.D drawing of 33kV Incomer CRP (typical) drawing
Drawing No.: 08/2016/AWB/V/1120-33KV CRP
Schematic drawing
S. No. MZEC comments Jasubhai response

1. Sheet 06 of 37

Previously the trip reset command from SCADA was provided


Why revised? Changes without cloud shall not be acceptable. directly from SCADA panel. Received comment to provide the
a. reset command through interposing relay. Complied as per
comment. Missed to put cloud. Regret for the same.

2. Sheet 07 of 37

Previous comments not addressed. That is the ANSI code of The comment is retained by providing clarification regarding
a. 67/67N has not been provided elaborately as per the this and got confirmation mail to retain the same ANSI code
function of that relay. via mail dated 05/11/2017 from Mazoon.

3. Sheet 08 of 37

What is the change in Rev.D? Why the cloud has not been
a. Regret. Missed to remove.
removed?
4. Sheet 09 of 37

Kindly note that, as per the trailing mail dated 31/12/2017,


a. Provide OLTC Bucholz Alarm and Trip. these signals have not required, since, there is no provision of
the same in RTCC panel, SCADA signal list and approved PMD.

b. Check RTCC drawing whether WTI (LV) has provided? Complied. Provided the WTI (LV) signal as per RTCC drawing.
5. Sheet 10 & 11 of 37
It is retained since, the 11kV SBEF has been provided in the
a. Consultant please clarify why 11kV SBEF is to be deleted? switchgear panel to trip the 33kV trip coil.

Check the interface details of 33kV switchgear with Complied. Checked and modified the interface details of 33kV
b. respective drawing. switchgear details as per 33kV switchgear drawing.

6. Sheet 12 of 37

Checked. The close/open command of CB through IEC61850


Contractor to check whether the SCADA system drawings IEC is not available in SCADA drawing. Hence the text has been
a. 61850 through close and open of CB is available. removed now. However, contractor has to provide
confirmation to MZEC/consultant in this regard.

7. Sheet 15A of 37

a. Change the Earth switch reference of 33kV Line VT as '1H1'. Complied. Changed.

Why 11kV side Line VT earth switch (1T1) status has been As per the previous comment and as shown in 11kV SLD, the
b. provided in 33kV CRP? same has been provided in 33kV CRP.
) TO 2X20 MVA AT SOUTH AL BATINAH GOVERNORATE

ncomer CRP (typical) drawing


P

MZEC/Ritaj comments/response