You are on page 1of 12

Company: Project: Engineering Contractor:

OFFSITES ENGINEERING WORKS


FOR THE ERBIL REFINERY
40,000 B/D EXPANSION PROJECT

Contract no.: 10J01762-01


Company doc. no.: Job no.: 10J01762 Engineering doc. no.:
N/A Sheet 1 of 12 10J01762-ICT-DS-000-015

OFFSITES ENGINEERING WORKS FOR THE


ERBIL REFINERY 40,000 B/D EXPANSION PROJECT

DATA SHEET FOR INSTRUMENT CABLES

D2 30/12/2011 Re-Approved for Design Lucarelli Pagliardini Cilia


D1 09/09/2011 Re-Approved for Design Lucarelli Pagliardini Cilia
D0 08/08/2011 Approved for Design Lucarelli Pagliardini Cilia
C0 29/04/2011 Issued for Company approval Mariotti Pagliardini Cilia
REV. DATE REVISION TITLE PREPARED CHECKED APPROVED

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 2 of 12 10J01762-ICT-DS-000-015

INDICE

1 INDEX SHEET ..............................................................................................................................3


2 DATA SHEETS .............................................................................................................................4

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 3 of 12 10J01762-ICT-DS-000-015

1 INDEX SHEET
Index sheet
Page
Cable type Cable description Applications / Notes
No.
1x2x1.5mm²
Analogue
Single Pair 1.5 mm²
D1-1 4 N.I.S. Instrumentation
Outdoor cable (above/below ground), Overall
DCS
shield, Twisted Pair, Flame Retardant, Black
Outer Sheath.
12x2x1.0mm²
Digital/Analogue
D1-12 5 Outdoor cable (above/below ground), Individual N.I.S. Instrumentation
shield, Overall shield, Twisted Pair, Flame DCS
Retardant, Black Outer Sheath.
20x2x1.0mm²
Digital/Analogue
D1-20 6 Outdoor cable (above/below ground), Individual N.I.S. Instrumentation
shield, Overall shield, Twisted Pair, Flame DCS
Retardant, Black Outer Sheath.
30x2x1.0mm²
Digital/Analogue
D1-30 7 Outdoor cable (above/below ground), Individual N.I.S. Instrumentation
shield, Overall shield, Twisted Pair, Flame DCS
Retardant, Black Outer Sheath.
1x2x1.5mm²
Digital
D2-1 8 Single Pair 1.5 mm² N.I.S. Instrumentation
Outdoor cable (above/below ground), Twisted DCS
Pair, Flame Retardant, Black Outer Sheath.
5x2x1.0mm²
Digital
D2-5 9 Outdoor cable (above/below ground), Overall N.I.S. Instrumentation
shield, Twisted Pair, Flame Retardant, Black DCS
Outer Sheath.
10x2x1.0mm²
Digital
D2-10 10 Outdoor cable (above/below ground), Overall N.I.S. Instrumentation
shield, Twisted Pair, Flame Retardant, Black DCS
Outer Sheath.
20x2x1.0mm²
Digital
D2-20 11 Outdoor cable (above/below ground), Overall N.I.S. Instrumentation
shield, Twisted Pair, Flame Retardant, Black DCS
Outer Sheath.
1x2x2.5mm² SOV @24VDC
LSHL @230VAC (MCC system)
D3-1 12 Outdoor cable (above/below ground), Overall N.I.S. Instrumentation
shield, Twisted Pair, Flame Retardant, Black DCS
Outer Sheath.

Legend: I.S. = Intrinsically safe


N.I.S. = Not Intrinsically Safe

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 4 of 12 10J01762-ICT-DS-000-015

2 DATA SHEETS

INSTRUMENT CABLE TYPE: D1-1


Application: Not Intrinsically Safe - Analogue - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other: ______________
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 1x2 Additional telecomm. pair
5 Nominal cross section area of cores: 1.5 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 5 of 12 10J01762-ICT-DS-000-015

INSTRUMENT CABLE TYPE: D1-12


Application: Not Intrinsically Safe – Digital/Analogue - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other:______________
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 12x2 Additional telecomm. pair
5 Nominal cross section area of cores: 1.0 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 6 of 12 10J01762-ICT-DS-000-015

INSTRUMENT CABLE TYPE: D1-20


Application: Not Intrinsically Safe – Digital/Analogue - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other:______________
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 20x2 Additional telecomm. pair
5 Nominal cross section area of cores: 1.0 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 7 of 12 10J01762-ICT-DS-000-015

INSTRUMENT CABLE TYPE: D1-30


Application: Not Intrinsically Safe – Digital/Analogue - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other:______________
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 30x2 Additional telecomm. pair
5 Nominal cross section area of cores: 1.0 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 8 of 12 10J01762-ICT-DS-000-015

INSTRUMENT CABLE TYPE: D2-1


Application: Not Intrinsically Safe - Digital - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other: ______________
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 1x2 Additional telecomm. pair
5 Nominal cross section area of cores: 1.5 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 9 of 12 10J01762-ICT-DS-000-015

INSTRUMENT CABLE TYPE: D2-5


Application: Not Intrinsically Safe - Digital - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other: ______________
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 5x2 Additional telecomm. pair
5 Nominal cross section area of cores: 1.0 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 10 of 12 10J01762-ICT-DS-000-015

INSTRUMENT CABLE TYPE: D2-10


Application: Not Intrinsically Safe - Digital - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other:______________
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 10x2 Additional telecomm. pair
5 Nominal cross section area of cores: 1.0 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 11 of 12 10J01762-ICT-DS-000-015

INSTRUMENT CABLE TYPE: D2-20


Application: Not Intrinsically Safe - Digital - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other:______________
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 20x2 Additional telecomm. pair
5 Nominal cross section area of cores: 1.0 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:

File name: 10J01762-ICT-DS-000-015-D2.doc


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR INSTRUMENT CABLES
Company doc. no.: Rev.: C0 D0 D1 D2 Engineering doc. no.:
N/A Sheet 12 of 12 10J01762-ICT-DS-000-015

INSTRUMENT CABLE TYPE: D3-1


Application: Not Intrinsically Safe - SOV - LSHL - Outdoor
Reference Std/Doc.: BS 5308-2 ; API RP 552 ; IEC 60332-3C; Purchaser requisition documents
1 Nominal Voltage: 300/500 V 450/750 V 600/1000 V
2 Type: DC Single phase a.c. Thermocouple Other: (Note 1)
3 Frequency: 50 Hz 60 Hz Not Applicable
4 Number of cores and Construction: 1x2 Additional telecomm. pair
5 Nominal cross section area of cores: 2.5 mm2 Required Length See doc. 10J01762-ICT-LS-000-003
6 Conductors: Copper Other:
7 Insulation: To Vendor's std. Other: PVC
8 Shield: No Overall Individual pair Individual triple
9 Drain wire: No Yes Dia: ≥ 0.5 mm
10 Heat Barrier: Waxed paper Non-hygroscopic Other ______________
11 Separation Sheath: To Vendor’s std Other: PVC Colour: BLACK
12 Lead Sheath: No Yes
13 Fibrous tape No Yes (Between sheath and armour)
14 Armour: Galvanized Wire Steel tape Aramide yarns Other ____________
15 Outer Sheath: To Vendor's std. Other: PVC Colour: BLACK
16 Fire Performance: Flame Retardant (IEC 60332-3C) Fire Resistant (IEC 60331) Standard
17 Other performance Hydrocarbon Resistant Rodent Resistant Other: UV/Ozone resistant
18 Core Identification Pair (Blue/Black, numbered) Triples (Blue/Black/Brown, numbered)
19 Installation: Outdoor Tray Buried Unfilled Trenches
Indoor False floor Tray Conduit
20 Certification: Yes, (BS, IEC)
21 Inspection Req’d: Yes
22 Quality Plan Req’d: Yes
23 Cable Marking : Yes
MANUFACTURER/SUPPLIER DATA (TO BE COMPLETED)
24 Cable Dimensions: Diameter under armour: mm
Diameter over armour: mm
Overall Diameter: mm
Weight per km: kg
Minimum bending radii: mm
25 Resistance: Max d.c. at 20°C: Ω/km
26 Inductance: mH/km
27 Capacitance: Core-core: µF/km Core-shield: µF/km Core-Armour: µF/km
28 Cable armour resistance per km: Ω/km
29 Cable Drain Wire resistance per km: Ω/km
30 Max L/R ratio: H/Ω
31 Max mutual capacitance: µF/km
32 Cable current carrying capacity: A Rating Factor:
33 Oxygen index :
34 Max allowed pulling force kN
35 Min/Max allowed temp. for installation °C
36 Materials Used: Insulation:
Shield:
Separation sheath:
Armour:
Outer Sheath:
37 Halogen Acid Evaluation:
Notes:
1) LSHL contacts rating: 4A @ 230VAC.

File name: 10J01762-ICT-DS-000-015-D2.doc

You might also like