Test Report issued under the responsibility of:

TEST REPORT
IEC 62040-1
Uninterruptible power systems (UPS) –
Part 1: General and safety requirements for UPS

Report Number. .............................. : 218478-CI3-1 CB / DE1-54209/M2


Date of issue................................... : 2015-12-14
Total number of pages ................... 53

Applicant’s name ........................... : APC by Schneider Electric


Address ........................................... : Boston ONE Campus; 800 Federal Street; ANDOVER MA
01810-1067; USA
Test specification:
Standard ......................................... : DIN EN 62040-1 (VDE 0558-510):2013-11
EN 62040-1:2008 + A1:2013-05
IEC 62040-1:2008 (First Edition) + Am 1:2013
Test procedure ............................... : VDE-GS, CB Scheme
Non-standard test method ............ : N/A
Test Report Form No. .................... : IEC62040_1C
Test Report Form(s) Originator .... : TÜV Rheinland Japan Ltd.
Master TRF ..................................... : Dated 2014-01
Copyright © 2014 Worldwide System for Conformity Testing and Certification of Electrotechnical
Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB
Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.

VDE File No 1924400-3335-0067/218478


Page 2 of 53 Report No. 218478-CI3-1

Test item description ..................... : Uninterruptible power supply (UPS)


Trade Mark ...................................... :

Manufacturer .................................. : APC by Schneider Electric; Boston ONE Campus; 800 Federal
Street; ANDOVER MA 01810-1067; USA
Model/Type reference .................... : SRT3000RMXLI; SRT3000RMXLW; SRT3000XLI; SRT3000XLW;
SRT2200RMXLI; SRT2200RMXLW; SRT2200XLI; SRT2200XLW;
(see model matrix)
Ratings ............................................ : See below 2 tables for UPS and External battery pack
Ambient: 40 °C

Rating of UPS:
Input 208-240Vac, 50/60Hz; Output 3000VA, 2700W

Model matrix:
SRT 3000 RM XL I xxxxxxxxxx
A B C D E F

A: SRT, means series name


B: 3000, 2200, means maximum VA output
C: RM (means Rack Mounted) or none (means Tower Stand)
D: XL, means Extended Run
E: I = International (220-230-240V), W = Worldwide (208-220-230-240V)
F: xxxxxxxxxx (x=0-9, a-z, A-Z, +, *, #, _, - or blank) for marketing purpose

UPS: Rating difference:


SRT3000RMXLI; SRT3000RMXLW; Input 220-240Vac or 208-240Vac, Max. 16A, 50-60Hz;
SRT3000XLI; SRT3000XLW;
Output 3000VA, 2700W
SRT2200RMXLI; SRT2200RMXLW; Input 220-240Vac or 208-240Vac, 50-60Hz, Max. 13A
SRT2200XLI; SRT2200XLW;
Output 2200VA, 1980W

Rating of external battery pack:


External battery pack: Rating:
SRT72BP, SRT72RMBP 72Vdc (for 2200VA models)
SRT96BP, SRT96RMBP 96Vdc (for 3000VA models)

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 4 of 53 Report No. 218478-CI3-1

List of Attachments (including a total number of pages in each attachment):


Appendix Description Page(s)
No.
1 Critical Component list 46-52
2 Modifications covered by this report 53

Summary of testing:

Tests performed (name of test and test Testing location:


clause):
American Power Conversion Holding Inc. Taiwan Branch
Under this procedure no tests have been 3F., No. 205, Sec. 3, Beixin Rd., Xindian Dist., New
performed, only Identity Check performed. Taipei City 23143, Taiwan (TDAP File No. 5003241-
See previous test reports for test results 9501-0001)

Summary of compliance with National Differences


List of countries addressed:

Note: EN Group Differences together with National Differences and Special National Conditions, see
previous test reports

The product fulfils the requirements of


DIN EN 62040-1 (VDE 0558-510):2013-11
EN 62040-1:2008 + A1:2013-05
IEC 62040-1:2008 (First Edition) + Am 1:2013

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 5 of 53 Report No. 218478-CI3-1

Copy of marking plate


The artwork below may be only a draft. The use of certification marks on a product must be
authorized by the respective NCBs that own these marks.

See previous test reports

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 6 of 53 Report No. 218478-CI3-1

Test item particulars...................................................:


Equipment mobility ....................................................: [] movable [] transportable
[X] stationary [X] Rack Mount
Connection to the mains ...........................................: [X] pluggable equipment [X] type A [] type B
[] permanent connection
[X] detachable power supply cord
[] non-detachable power supply cord
Operating condition ...................................................: [X] continuous
[] rated operating / resting time:
Access location .........................................................: [] operator accessible
[X] restricted access location
Over voltage category (OVC) ...................................: [] OVC I [X] OVC II [] OVC III [] OVC IV
[] other:
Mains supply tolerance (%) or absolute mains
supply values .............................................................: - 10 % / +6%
Tested for IT power systems ....................................: [] Yes [X] No
IT testing, phase-phase voltage (V) .........................: N/A
Class of equipment ...................................................: [X] Class I [] Class II
[] Not classified
Considered current rating of protective device as
part of the building installation (A) ..........................: 16 A Wall Breaker
Pollution degree (PD) ................................................: [] PD 1 [X] PD 2 [] PD 3
IP protection class .....................................................: IP --
Elevation during operation (m) ................................: ≤ 2000 m
Elevation of test laboratory (m) ...............................: 76 m
Mass of equipment (kg) ............................................: >18 kg
Possible test case verdicts:
- test case does not apply to the test object ........... : N/A
- test object does meet the requirement.................. : P (Pass)
- test object does not meet the requirement ........... : F (Fail)
Testing.......................................................................... :
Date of receipt of test item ........................................ : 2015-Dec
Date (s) of performance of tests ............................... : 2015-Dec
see also see previous Test Reports

General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing
laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.

Throughout this report a comma / point is used as the decimal separator.

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 7 of 53 Report No. 218478-CI3-1

Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:


APC by Schneider Electric; Boston ONE Campus; Yes
800 Federal Street; ANDOVER MA 01810-1067; Not applicable
USAThe application for obtaining a CB Test
Certificate includes more than one factory location
and a declaration from the Manufacturer stating that
the sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided ............................................................... :

When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) .......................... : 1. American Power Conversion Corporation
(A.P.C.) B.V.
LOT 3 BLK 14, PHASE III, PEZA, 4106
ROSARIO, CAVITE, PHILIPPINES
2. American Power Conversion Corporation
(A.P.C.) B.V.
LOT 10, BLK 16, PHASE IV, PEZA, 4106
ROSARIO, CAVITE, PHILIPPINES
3. American Power Conversion Corporation
(A.P.C.) B.V.
2ND ST, PEZA, Cavite Economic Zone, 4106
ROSARIO, CAVITE, PHILIPPINES

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 8 of 53 Report No. 218478-CI3-1

General product information:


Complete details of construction and testing as well as supporting documentation such as photographs
and schematics are done by previous Test Reports.
The UPS provides reinforced insulation between primary and secondary circuits.

Conditions of Installation:
The units are suitable for a maximum manufacturer’s recommended ambient operating temperature (Tma)
of 40 °C.
Unit is designed and approved for use in installation category II.
Unit intended for continuous operation while charging.
UPS are Class 1 and designed for Pollution Degree 2.
Unit could be used as stand-alone (tower) or rack mounted version.
VDE approved appliance inlets and outlets are used.
– Alternative construction for AC power input and/or output power outlet to be terminal block structure.
See installation manual for detail.
Secondary circuits are designed in 3 areas, (MB + DCLPS board and Communication Boards) other
boards are defined as Primary circuit area.

Model differences:
All models are identical except:
 UPS, Main differences:
1. Electric Ratings
2. Transformers: Charger transformer, DC/DC transformer, and Logic Power Supply
transformer
3. Chokes: Input choke (for EMI), PFC choke L1203, Inverter choke L1207
4. TRIAC (for improving relay transfer time), Hall Sensor (for current sense)
5. Size of PCB (2.2KVA is 2 inch shorter than 3KVA). Layout in the area of PFC choke, Inverter
choke

 External Battery Pack: (for example: SRT96BP/72BP)


1. Electric rating;
2. Quantity of batteries inside
3. Metal chassis is same as 2.2KVA of UPS.

In accordance with "§ 6 of the German Product Pass


Safety Act (ProdSG)", the manufacturers have to Fail
indicate their name and contact address on the
Not applicable
consumer product or, where that is not possible, on
its packaging.
If the manufacturer is not domiciled in the European
Economic Area (EEA), the name and the contact
address of the authorised person(s) within the EEA
or importer must be indicated.

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 9 of 53 Report No. 218478-CI3-1

Information to test report reference No. : 218478-CI3-1


VDE Test- and Certification Institute DIN EN 62040-1 (VDE 0558-510):2013-11
GmbH Merianstrasse 28 EN 62040-1:2008 + A1:2013-05
IEC 62040-1:2008 (First Edition) + Am 1:2013
D - 63069 Offenbach
Test item description: Uninterruptible power supply
Made by : APC by Schneider Electric; Boston ONE Campus; 800 Federal Street;
ANDOVER MA 01810-1067; USA
Trade mark :

Model/type ref. : Refer to page 2


Rated : Refer to page 2

Commission received from -- Date: --

Modification on the appliance:


1. Upgrade to:
DIN EN 62040-1 (VDE 0558-510):2013-11
EN 62040-1:2008 + A1:2013-05
IEC 62040-1:2008 (First Edition) + Am 1:2013
2. Revise the definition of model name.
SRT 3000 RM XL I xxxxxxxxxx
A B C D E F

A: SRT, means series name


B: 3000, 2200, means maximum VA output
C: RM (means Rack Mounted) or none (means Tower Stand)
D: XL, means Extended Run
E: I = International (220-230-240V), W = Worldwide (208-220-230-240V)
F: xxxxxxxxxx (x=0-9, a-z, A-Z, +, *, #, _, - or blank) for marketing purpose
3. Add an alternate source for relay RY1204.
Relay RY1204 Omron Corp G2RG-2A4 8A, 250Vac, Coil
24Vdc

4. Add an alternate source for MOV MV1204A, MV1205A.

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 10 of 53 Report No. 218478-CI3-1

Test Report History:

This report may consist of more than one report and is valid only with additional or previous issued reports:

Date: VDE-Certificate: VDE File No.: Modifications:


(jjjj-mm-dd) CB-Ref. No.: Test Report Number
2015-12-14 CB / DE1-54209/M2 218478-CI3-1 Additional test report (This report):
--Upgrade to
DIN EN 62040-1 (VDE 0558-510):2013-11
EN 62040-1:2008 + A1:2013-05
IEC 62040-1:2008 (First Edition) + Am 1:2013
--Revise definition of model name
--Alternative components (RY1204, MV1204A,
MV1205A)
2014-11-10 CB / DE1-54209/M1 1924400-3335-0067/203983 Additional test report:
Addition of alternate model SRT3000RMXLI-IEC with
alternate components
2013-10-31 CB / DE1-54209 1924400-3335-0067/203209 Main test report approved to
DIN EN 62040-1 (VDE 0558-510):2009-06
EN 62040-1:2008
IEC 62040-1 : 2008 (1st Edition)

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 11 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4 GENERAL CONDITIONS FOR TESTS P


4.5 Components P
Comply with IEC 62040-1 or relevant component (see appended table 4.5) P
standard
1.5.2/RD Evaluation and testing of components Certified components are P
used in accordance with their
ratings and certifications, and
they comply with applicable
parts of this standard.
Components not certified are
used in accordance with their
ratings and they comply with
applicable parts of IEC 60950-
1 2nd and the relevant
component standard.
Components, for which no
relevant IEC-Standard exists,
have been tested under the
conditions occurring in the
equipment, using applicable
parts of IEC 60950-1 2nd
1.5.3/RD Thermal controls No thermal controls N/A
1.5.4/RD Transformers See annex C for details P
1.5.5/RD Interconnecting cables Interconnecting cables are not N/A
used in this application
1.5.6/RD Capacitors bridging insulation Certified to IEC60384-14 2nd P
Edition. See Components List
for details.
Y2 capacitors used between
Lines and Ground and one Y1
between SELV and Primary
circuits
X2 capacitors used between
Line and Neutral.
See clause 2.4 RD for details
of requirements and
compliance of limited current
circuits.
1.5.7/RD Resistors bridging insulation Bridging resistor between Line P
and ground
1.5.7.1/RD Resistors bridging functional, basic or Functional insulation only N/A
supplementary insulation
1.5.7.2/RD Resistors bridging double or reinforced insulation N/A
between a.c. mains and other circuits
1.5.7.3/RD Resistors bridging double or reinforced insulation N/A
between a.c. mains and antenna or coaxial cable
1.5.8/RD Components in equipment for IT power systems N/A
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 12 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.6 Power interface P


1.6.1/RD AC power distribution systems TN-System P
1.6.2/RD Input current (see appended table 4.6) P
4.6 Neutral conductor Neutral is insulated from earth P
1.6.4/RD with basic insulation.
Components connected
between phases and earth are
rated and certified for a
minimum working voltage of
250 V. See Components List

4.7 Marking and instructions P


4.7.1 General P
4.7.2 Power rating Refer to copy of rating label P
1.7.1/RD
Input rated voltage/range (V) ........................... : See page 2 P
Input rated current/range (A) ............................ : See page 2 P
Input symbol for nature of supply (d.c.) ........... : AC Unit P
Input rated frequency/range (Hz) ..................... : See page 2 P
Number of Input phases and neutral ................ : one phase P
Output rated voltage/range (V) ........................ : See page 2 P
Output rated current/range (A) ........................ : See page 2 P
Output rated power factor, if less than unity, or See page 2 P
active power and apparent power or active power
and rated current ............................................. :
Number of output phases and neutral ............. : One phase P
Output rated active power (W or kW) .............. : See page 2 P
Output rated apparent power (VA or kVA) ...... : See page 2 P
Output symbol for nature of supply (d.c.) ........ : N/A
Output rated frequency/range (Hz) .................. : See page 2 P
Ambient operating temperature range (C) ..... : 40 °C P
Rated short-time withstand current (Icw) or rated N/A
conditional short-circuit current (Icc)
Manufacturer’s name or trademark or identification P
mark ................................................................. :
Type/model or type reference .......................... : See page 2 P
Symbol for Class II equipment only ................. : Class I equipment N/A
Other symbols ................................................. : P
Certification marks ........................................... : VDE GS P
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 13 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Instructions for units with automatic See Safety Instructions P


bypass/maintenance bypass, additional input a.c.
supply, or external batteries, having text "See
installation instructions before connecting to the
supply" ............................................................. :
4.7.3 Safety instructions See Safety Instructions P
4.7.3.1 General See Safety Instructions P
4.7.3.2 Installation ........................................................ : Unit is an auto-ranging type N/A
Location in a restricted access location only ... : N/A
Permanent connector UPS............................... : P
Pluggable type A or Pluggable type B UPS .... : P
4.7.3.3 Operation .......................................................... : P
4.7.3.4 Maintenance ..................................................... : P
4.7.3.5 Distribution related backfeed ............................ : P
4.7.4 Main voltage adjustment ................................. : N/A
1.7.4/RD
Methods and means of adjustment; reference to Unit is an auto-ranging type N/A
installation instructions .................................... :
4.7.5 Power outlets .................................................... : N/A
1.7.5/RD
4.7.6 Fuse identification (marking, special fusing Fuses are marked with ratings P
1.7.6/RD characteristics, cross-reference) ..................... : or symbols like F1, fuses are
not customer replaceable.
4.7.7 Wiring terminals See previous reports P
1.7.7/RD
1.7.7.1/RD Protective earthing and bonding terminals ...... : See previous reports P
1.7.7.2/RD Terminals for a.c. mains supply conductors ..... : See previous reports P
1.7.7.3/RD Terminals for d.c. mains supply conductors ..... : See previous reports P
4.7.8 Battery terminals ............................................. : P
4.7.9 Controls and indicators P
1.7.8/RD
1.7.8.1/RD Identification, location and marking ................. : P
1.7.8.2/RD Colours ........................................................... : No indicators with colours N/A
1.7.8.3/RD Symbols ........................................................... : P
1.7.8.4/RD Markings using figures ................................... : P
4.7.10 Isolation of multiple power sources ................. : No multiple power sources N/A
1.7.9/RD
4.7.11 IT power systems Not evaluated for IT power N/A
1.7.2.4/RD systems
4.7.12 Protection in building installation P

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 14 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Rated short-time withstand current (Icw) ........ : Over shoot and under shoot P
max. 4% of rated Voltage for
duration of 40 ms.
Rated conditional short circuit current (Icc) ..... : Over shoot and under shoot P
max. 4% of rated Voltage for
duration of 40 ms.
a) If higher Icp stated ≤ 10 kA N/A
a) If higher Icp stated > 10 kA N/A
4.7.13 High leakage current (mA) .............................. : Statement in the instructions P
5.1/RD that the unit is connected to a
separate ground connector in
the back of the unit near the
appliance inlet , screw is
marked with the ground
symbol
4.7.14 Thermostats and other regulating devices No adjustable thermal devices N/A
1.7.10/RD employed
4.7.15 Language(s) .................................................... : 
1.7.2.1/RD
and
1.7.8.1/RD
4.7.16 Durability of markings P
1.7.11/RD
4.7.17 Removable parts No marking on removable P
1.7.12/RD parts
4.7.18 Replaceable batteries Replaceable Lead Acid P
1.7.13/RD Batteries
Language(s) .................................................... : 
4.7.19 Operator access with a tool .............................. : Cannot access hazardous P
1.7.2.5/RD part.
4.7.20 Battery See component list P
Clearly legible information ............................... : P
Battery type (lead-acid, NiCd, etc.) and number of Sealed Lead Acid P
blocks or cells .................................................. :
Nominal voltage of total battery (V) ................. : P
Nominal capacity of total battery (optional) ..... : P
Warning label .................................................. : P
Instructions ...................................................... : P
2.1.1.5/RD Protection against energy hazards Battery terminals are N/A
protected
4.7.21 Installation instructions See previous reports P
1.7.2.4/RD

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 15 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

5 FUNDAMENTAL DESIGN REQUIREMENTS P


5.1 Protection against electric shock and energy P
hazards
5.1.1 Protection for UPS intended to be used in operator No operator access to P
2.1.1/RD access areas hazardous parts.
All user accessible outputs
fulfill SELV Requirements.
2.1.1.1/RD Access to energized parts See clause 2.1.1 P
Test by inspection ........................................... : all wires in the front and back P
of the unit which are
accessible with the test pin
are double insulated or have
an thickness of insulation >
0.4 mm
Test with test finger (Figure 2A) ...................... : P
Test with test pin (Figure 2B) .......................... : P
Test with test probe (Figure 2C) ...................... : P
2.1.1.2/RD Battery compartments P
2.1.1.3/RD Access to ELV wiring No ELV circuits N/A
Working voltage (Vpeak or Vrms); minimum See previous reports 
distance through insulation (mm)
2.1.1.4/RD Access to hazardous voltage circuit wiring No access to hazardous N/A
voltage circuit wiring
2.1.1.5/RD Energy hazards ............................................... : Battery terminal are provided P
2.1.1.6/RD Manual controls P
2.1.1.7/RD Discharge of capacitors in equipment P
Measured voltage (V); time-constant (s) .......... : 
2.1.1.8/RD Energy hazards – d.c. mains supply AC unit N/A
a) Capacitor connected to the d.c. mains supply .. : N/A
b) Internal battery connected to the d.c. mains N/A
supply .............................................................. :
2.1.1.9/RD Audio amplifiers in information technology No audio Amplifiers N/A
equipment ........................................................ :
5.1.2 Protection for UPS intended to be used in service P
2.1.1.5 c) access areas
/RD
Hazardous energy level ................................... : N/A
5.1.3 Protection for UPS intended to be used in N/A
2.1.1.5 c) restricted access areas
/RD
Hazardous energy level ................................... : N/A
5.1.4 Backfeed protection (see appended table 5.7) 

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 16 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Shock hazard after de-energization of a.c. input for Output is not grounded, P
UPS Relays with 1.4 mm contact
gap are provided.
The measured voltage in
previous Test Reports is
voltage from the filter
capacitors (leakage current is
very low) refer to test results.
Measured voltage (V); time-constant (s) .......... : 
Description of the construction ........................ : Considered. P
Air gap is employed for backfeed protection See also previous test P
reports.
5.1.5 Emergency switching (disconnect) device N/A

5.2 Requirements for auxiliary circuits P


5.2.1 Safety extra low voltage circuit - SELV 2.2.3.1 – 2.2.3.3/RD P
2.2/RD
2.2.1/RD General requirements Data Circuits fulfil SELV P
requirements. SELV circuits
considered as safe touchable
under normal operating
condition and after a single
fault.
2.2.2/RD Voltages under normal conditions (V) ............. : Less than or equal to 42.4Vpk P
or 60Vdc
2.2.3/RD Voltages under fault conditions (V) ................. : Less than or equal to 42.4Vpk P
or Vdc
Maximum voltage under fault
condition less than 71Vpk or
12Vdc for not longer than 0.2
sec.
There are no single faults
which can cause voltage
levels on the outputs to
exceed the SELV limits.
2.2.4/RD Connection of SELV circuits to other circuits .. : SELV circuit are considered to P
be connected only to SELV or
earth.
5.2.2 Telephone network voltage circuits - TNV No TNV circuit N/A
2.3/RD
2.3.1/RD Limits N/A
Type of TNV circuits ......................................... : 
2.3.2/RD Separation of TNV circuits from other circuits and N/A
from accessible parts
2.3.2.1/RD General requirements N/A
2.3.2.2/RD Protection by basic insulation N/A
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 17 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.3.2.3/RD Protection by earthing N/A


2.3.2.4/RD Protection by other constructions .................... : N/A
2.3.3/RD Separation from hazardous voltages N/A
Insulation employed ......................................... : 
2.3.4/RD Connection of TNV circuits to other circuits N/A
Insulation employed ......................................... : 
2.3.5/RD Test for operating voltages generated externally N/A
5.2.3 Limited current circuits N/A
2.4/RD
2.4.1/RD General requirements N/A
2.4.2/RD Limit values 
Frequency (Hz) ................................................. : 
Measured current (mA) .................................... : 
Measured voltage (V) ....................................... : 
Measured circuit capacitance (nF or µF).......... : 
2.4.3/RD Connection of limited current circuits to other N/A
circuits
5.2.4 External signaling circuits P
3.5/RD
3.5.1/RD General requirements Interconnection of P/S outputs P
(SELV) with other circuits is to
be evaluated in end-use
product
3.5.2/RD Types of interconnection circuits ..................... : SELV circuits P
3.5.3/RD ELV circuits as interconnection circuits No ELV interconnection N/A
3.5.4/RD Data ports for additional equipment P
5.2.5 Limited power source See previous test reports P
2.5/RD
a) Inherently limited output N/A
b) Impedance limited output P
c) Regulating network limited output under normal P
operating and single fault condition
d) Overcurrent protective device limited output P
Max. output voltage (V), max. output current (A), 
max. apparent power (VA) ............................... :
Current rating of overcurrent protective device (A) .: 
Use of integrated circuit (IC) current limiters 

5.3 Protective earthing and bonding P


5.3.1 General P
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 18 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.6/RD Provisions for earthing and bonding P


2.6.1/RD Protective earthing Accessible metal parts are P
reliably earthed, refer to
installation instructions
2.6.2/RD Functional earthing Functional earthing not N/A
provided
2.6.3/RD Protective earthing conductors and protective VDE approved appliance inlet P
bonding conductors
2.6.3.1/RD General P
2.6.3.2/RD Size of protective earthing conductors Construction is designed for P
the expected current.
Rated current (A), cross-sectional area (mm2), 
AWG ................................................................. :
2.6.3.3/RD Size of protective bonding conductors See 2.6.3.2 P
2
Rated current (A), cross-sectional area (mm ), 
AWG ................................................................. :
Protective current rating (A), cross-sectional area 
(mm2), AWG ..................................................... :
2.6.3.4/RD Resistance of earthing conductors and their Considered. P
terminations; resistance (), voltage drop (V), test
current (A), duration (min) ................................ :
2.6.3.5/RD Colour of insulation........................................... : Green/Yellow used only for P
protective earthing
2.6.4/RD Terminals Unit is provided with two N/A
appliance inlet’s for input
2.6.4.1/RD General N/A
2.6.4.2/RD Protective earthing and bonding terminals Unit is provided with two N/A
appliance inlet’s for input
Rated current (A), type, nominal thread diameter 
(mm) ................................................................. :
2.6.4.3/RD Separation of the protective earthing conductor N/A
from protective bonding conductors
2.6.5/RD Integrity of protective earthing P
2.6.5.1/RD Interconnection of equipment N/A
2.6.5.2/RD Components in protective earthing conductors and None N/A
protective bonding conductors
2.6.5.3/RD Disconnection of protective earth P
2.6.5.4/RD Parts that can be removed by an operator N/A
2.6.5.5/RD Parts removed during servicing N/A
2.6.5.6/RD Corrosion resistance P
2.6.5.7/RD Screws for protective bonding P

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 19 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.6.5.8/RD Reliance on telecommunication network or cable N/A


distribution system
5.3.2 Protective earthing Accessible metal parts are P
2.6.1/RD reliable earthed.
Unit is provided with
appliance inlet’s for input
2.10/RD Clearances, creepage distances and distances Installation Category II is P
through insulation assumed for this unit.
4.2/RD Mechanical strength P
5.2/RD Electric strength P
5.3.3 Protective bonding P

5.4 AC and d.c. power isolation P


5.4.1 General P
3.4/RD Disconnection from the mains supply P
3.4.1/RD General requirement P
3.4.2/RD Disconnect devices Unit is provided with P
Appliance Inlet for input
3.4.3/RD Permanently connected equipment See 3.4.1 P
3.4.4/RD Parts which remain energized P
3.4.5/RD Switches in flexible cords N/A
3.4.6/RD Number of poles - single-phase and d.c. equipment See 3.4.1 P
3.4.7/RD Number of poles - three-phase equipment See 3.4.1 P
3.4.8/RD Switches as disconnect devices N/A
3.4.9/RD Plugs as disconnect devices N/A
3.4.10/RD Interconnected equipment N/A
3.4.11/RD Multiple power sources N/A
5.4.2 Disconnect devices P

5.5 Overcurrent and earth fault protection P


5.5.1 General P
2.7.3/RD Short-circuit backup protection Protective devices have P
adequate breaking (rupturing)
capacity to interrupt the max.
fault current (including short
circuit), see 2.7.1
2.7.4/RD Number and location of protective devices ..... : See schematics and P
component list for details.
Schematics available on
request.
2.7.5/RD Protection by several devices N/A
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 20 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.7.6/RD Warning to service personnel .......................... : N/A


5.5.2 Basic requirements P
5.5.3 Battery circuit protection P
5.5.3.1 Overcurrent and earth fault protection P
5.5.3.2 Location of protective device P
5.5.3.3 Rating of protective device P
5.3.1/RD Protection against overload and abnormal (see table 5.3 on RD Test P
operation Report according to IEC
60950-1 2nd )

5.5.4 Short-time withstand current Exemption from testing: N/A


UPS with declared Icw or Icc
not exceeding 10 kA
5.5.4.1 General N/A
5.5.4.2 Modes of operation N/A
5.5.4.3 Test procedure Exemption from testing: N/A
UPS with declared Icw or Icc
not exceeding 10 kA
5.5.4.3.1 General application N/A
Rated UPS output current/(r.m.s) (A) .............. : --- 
Prospective test current/(r.m.s) (A) ................. : --- 
Typical power factor ........................................ : --- 
Initial asymmetric peak current ration (Ipk / Icw) . : --- 
Minimum durating of prospective test current 
(cycles 50/60 Hz) ............................................. : ---
5.5.4.3.2 Exemption from testing Exemption from testing: P
UPS with declared Icw or Icc
not exceeding 10 kA

5.6 Protection of personnel – Safety interlocks N/A


5.6.1 Operator protection N/A
2.8/RD General principles N/A
2.8.1/RD Protection requirements N/A
2.8.2/RD Inadvertent reactivation N/A
2.8.3/RD Fail-safe operation N/A
2.8.4/RD Protection against extreme hazard N/A
2.8.5/RD Moving parts N/A
2.8.6/RD Overriding N/A
2.8.7/RD Switches, relays and their related circuits N/A

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 21 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.8.7.1/RD Separation distances for contact gaps and their N/A


related circuits ................................................. :
2.8.7.2/RD Overload test N/A
2.8.7.3/RD Endurance test N/A
2.8.7.4/RD Electric strength test N/A
2.8.8/RD Mechanical actuators N/A
5.6.2 Service person protection P
5.6.2.1 Introduction P
5.6.2.2 Covers P
5.6.2.3 Location and guarding of parts P
5.6.2.4 Parts on doors N/A
5.6.2.5 Component access P
2.8.3/RD Fail-safe operation N/A
5.6.2.6 Moving parts P
5.6.2.7 Capacitor banks N/A
5.6.2.8 Internal batteries P

5.7 Clearances, creepage distances and distances through insulation P


2.10/RD
2.10.1/RD General Over voltage Category II is P
assumed for this unit.
2.10.1.1/R Frequency ....................................................... : Considered P
D
2.10.1.2/R Pollution degrees ............................................. : Pollution Degree 2 P
D considered.
2.10.1.3/R Reduced values for functional insulation Functional insulation P
D provided, unit meets criteria
for functional insulation as per
5.3.4 a) or c).
2.10.1.4/R Intervening unconnected conductive parts Considered P
D
2.10.1.5/R Insulation with varying dimensions Considered P
D
2.10.1.6/R Special separation requirements Considered P
D
2.10.1.7/R Insulation in circuits generating starting pulses No starting pulses N/A
D
2.10.2/RD Determination of working voltage P
2.10.2.1/R General P
D
2.10.2.2/R RMS working voltage P
D
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 22 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.10.2.3/R Peak working voltage P


D
2.10.3/RD Clearances P
2.10.3.1/R General P
D
2.10.3.2/R Mains transient voltages Overvoltage Category II P
D
a) AC mains supply ......................................... : Between the phases AC250V P
2500 V transient
b) Earthed d.c. mains supplies ........................ : N/A
c) Unearthed d.c. mains supplies .................... : N/A
d) Battery operation ......................................... : N/A
2.10.3.3/R Clearances in primary circuits P
D
2.10.3.4/R Clearances in secondary circuits P
D
2.10.3.5/R Clearances in circuits having starting pulses N/A
D
2.10.3.6/R Transients from a.c. mains supply .................. : P
D
2.10.3.7/R Transients from d.c. mains supply .................. : N/A
D
2.10.3.8/R Transients from telecommunication networks and N/A
D cable distribution systems ............................... :
2.10.3.9/R Measurement of transient voltage levels Transient levels not N/A
D measured.
a) Transients from a mains supply N/A
For an a.c. mains supply ................................. : N/A
For a d.c. mains supply ................................... : N/A
b) Transients from a telecommunication network : N/A
2.10.4/RD Creepage distances P
2.10.4.1/R General P
D
2.10.4.2/R Material group and comparative tracking index P
D
CTI tests .......................................................... : Material group IIIb is assumed 
to be used
2.10.4.3/R Minimum creepage distances P
D
2.10.5 /RD Solid insulation P
2.10.5.1/R General P
D
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 23 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.10.5.2/R Distances through insulation P


D
2.10.5.3/R Insulating compound as solid insulation See clause 2.10.5.4 P
D
2.10.5.4/R Semiconductor devices All Opto-isolators have either a P
D distance through insulation of
0.4 mm, which has been
tested for 5000 VAC Electric
Strength and for compliance of
clause 2.10.5.5, or an internal
creepage distance of > 4 mm
and a Thermal Cycling Test to
clause 2.10.10 has been
performed to fulfil the
requirements for Pollution
Degree 1. All Opto-isolators
are also certified to VDE 0884
and/or IEC 60747-5-5
See critical component list for
details on Opto-isolators
2.10.5.5/R Cemented joints See 2.10.5.4 and 2.10.6.3 P
D
2.10.5.6/R Thin sheet material – General P
D
2.10.5.7/R Separable thin sheet material 3 layers, see annex C P
D
Number of layers (pcs) .................................... : 
2.10.5.8/R Non-separable thin sheet material Not used N/A
D
2.10.5.9/R Thin sheet material – standard test procedure See 2.10.5.10 N/A
D
Electric strength test 
2.10.5.10 Thin sheet material – alternative test procedure Alternative test procedure N/A
/RD used
Electric strength test (see appended table 8.2) 
2.10.5.11 Insulation in wound components N/A
/RD
2.10.5.12 Wire in wound components N/A
/RD
Working voltage ............................................... : 
a) Basic insulation not under stress ................ : N/A
b) Basic, supplementary, reinforced insulation : N/A
c) Compliance with Annex U ........................... : N/A
Two wires in contact inside wound component; N/A
angle between 45 and 90 ............................. :

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 24 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.10.5.13 Wire with solvent-based enamel in wound Not used N/A


/RD components
Electric strength test 
Routine test N/A
2.10.5.14 Additional insulation in wound components N/A
/RD
Working voltage ............................................... : 
- Basic insulation not under stress .................. : N/A
- Supplementary, reinforced insulation ............ : N/A
2.10.6/RD Construction of printed boards P
2.10.6.1/R Uncoated printed boards P
D
2.10.6.2/R Coated printed boards N/A
D
2.10.6.3/R Insulation between conductors on the same inner Compliance with clause N/A
D surface of a printed board 2.10.5.5 “c)”,
2.10.6.4/R Insulation between conductors on different layers N/A
D of a printed board
Distance through insulation (see appended table 2.10.5) N/A
Number of insulation layers (pcs) .................... : N/A
2.10.7/RD Component external terminations (see appended table 2.10.3 N/A
and 2.10.4)
2.10.8/RD Tests on coated printed boards and coated Coating not applied. N/A
components
2.10.8.1/R Sample preparation and preliminary inspection N/A
D
2.10.8.2/R Thermal conditioning N/A
D
2.10.8.3/R Electric strength test (see appended table 5.2) N/A
D
2.10.8.4/R Abrasion resistance test N/A
D
2.10.9/RD Thermal cycling See clause 2.10.5.4, 2.10.5.5, N/A
2.10.6.3
2.10.10/RD Test for Pollution Degree 1 environment and See clause 2.10.5.4 N/A
insulating compound
2.10.11/RD Tests for semiconductor devices and cemented See clause 2.10.5.4, 2.10.6.3 N/A
joints
2.10.12/RD Enclosed and sealed parts N/A

6 Wiring, connections and supply P


6.1 General P
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 25 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

6.1.1 Introduction P
3.1/RD General P
3.1.1/RD Current rating and overcurrent protection Internal wiring is adequate for P
the current. Protection is
adequate for the application
3.1.2/RD Protection against mechanical damage Wires do not touch sharp P
edges and heat sinks that
could damage the insulation
and cause hazard.
3.1.3/RD Securing of internal wiring Wires are adequately fixed to P
prevent excessive strain or
damage of the conductors'
insulation.
3.1.4/RD Insulation of conductors The insulation of the individual P
conductors is suitable for the
application and the working
voltage.
(see appended table 5.2)
3.1.5/RD Beads and ceramic insulators Beads or ceramic insulators N/A
are not used
3.1.6/RD Screws for electrical contact pressure Electrical and earthing P
connections engage at least
two complete threads into
metal.
No screws of insulating
material are used for electrical
and earthing connections.
3.1.7/RD Insulating materials in electrical connections Current carrying and P
protective earthing
connections are metal to
metal.
Screws with star/spring
washer are used for the
connection between ground
trace (PWB) and chassis
3.1.8/RD Self-tapping and spaced thread screws Thread cutting or space P
thread screw not used for
current carrying electrical
connections.
3.1.9/RD Termination of conductors Conductors are suitable P
terminated, creepage and
clearances maintained,
second securing for soldered
terminations provided.
10 N pull test 10 N applied to relevant P
conductors.
3.1.10/RD Sleeving on wiring Sleeving if safety related P
reliably kept in position.
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 26 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

6.1.2 Dimensions and rating of busbars and insulated P


conductors

6.2 Connection to power P


6.2.1 General provisions for connection to power P
3.2.2/RD Multiple supply connections Only one supply connection N/A
3.2.3/RD Permanently connected equipment UPS. N/A
Unit is provided with an
appliance inlet.
Number of conductors, diameter of cable and 
conduits (mm) .................................................. :
3.2.4/RD Appliance inlets see component list for details P
on appliance inlet
3.2.5/RD Power supply cords AC Power Cord was not part N/A
of this investigation
3.2.5.1/RD AC power supply cords See 3.2.5 N/A
Type ................................................................. : 
Rated current (A), cross-sectional area (mm²), 
AWG ................................................................ :
3.2.5.2/RD DC power supply cords Power cord for external N/A
batteries are not part of this
investigation
3.2.6/RD Cord anchorages and strain relief N/A
Mass of equipment (kg), pull (N) .................... : 
Longitudinal displacement (mm) ..................... : 
3.2.7/RD Protection against mechanical damage P
3.2.8/RD Cord guards N/A
Diameter or minor dimension D (mm); test mass 
(g) .................................................................... :
Radius of curvature of cord (mm) ..................... : 
6.2.2 Means of connection ....................................... : P
More than one supply connection ................... : N/A

6.3 Wiring terminals for external power conductors P


3.3/RD Wiring terminals for connection of external P
conductors
3.3.1/RD Wiring terminals N/A
3.3.2/RD Connection of non-detachable power supply cords N/A
3.3.3/RD Screw terminals N/A
3.3.4/RD Conductor sizes to be connected N/A
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 27 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Rated current (A), cord/cable type, cross-sectional 


area (mm2)........................................................ :
3.3.5/RD Wiring terminal sizes N/A
Rated current (A), type, nominal thread diameter 
(mm) ................................................................ :
3.3.6/RD Wiring terminal design N/A
3.3.7/RD Grouping of wiring terminals N/A
3.3.8/RD Stranded wire N/A

7 Physical requirements P
7.1 Enclosure P

7.2 Stability P
4.1/RD
Angle of 10 P
Test force (N) .................................................. : P

7.3 Mechanical strength P


4.2/RD
4.2.1/RD General P
4.2.2/RD Steady force test, 10 N Applied to relevant parts. P
No hazard.
4.2.3/RD Steady force test, 30 N Applied to relevant parts. P
No hazard.
4.2.4/RD Steady force test, 250 N Applied to relevant parts. P
No hazard.
4.2.5/RD Impact test Test performed on the top, P
bottom and on the side of the
unit. No hazard.
Fall test P
Swing test P
4.2.6/RD Drop test; height (mm) ..................................... : N/A
4.2.7/RD Stress relief test N/A
4.2.8/RD Cathode ray tubes No CRT’s N/A
Picture tube separately certified ...................... : N/A
4.2.9/RD High pressure lamps No High Pressure Lamps N/A
4.2.10/RD Wall or ceiling mounted equipment; force (N) . : Unit is not intended for wall or N/A
ceiling mounting

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 28 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

7.4 Construction details P


7.4.1 Introduction P
4.3.1/RD Edges and corners All edges and corners were P
judged to be sufficiently well
rounded as to not constitute a
hazard.
4.3.2/RD Handles and manual controls; force (N)........... : No handles and manual N/A
controls.
4.3.3/RD Adjustable controls No adjustable controls. N/A
4.3.4/RD Securing of parts No loosening of parts impairing P
creepage distances or
clearances is likely to occur.
4.3.5/RD Connection by plugs and sockets P
4.3.7/RD Heating elements in earthed equipment Not heating elements N/A
4.3.11/RD Containers for liquids or gases No such a container N/A
4.4/RD Protection against hazardous moving parts P
4.4.1/RD General Unit is provided with a DC fan P
4.4.2/RD Protection in operator access areas ................ : UPS. Fan guards provided P
4.4.3/RD Protection in restricted access locations ......... : N/A
4.4.4/RD Protection in service access areas P
4.4.5/RD Protection against moving fan blades P
4.4.5.1/RD General P
Not considered to cause pain or injury. a) ....... : P
Is considered to cause pain, not injury. b) ....... : N/A
Considered to cause injury. c) ....... : N/A
4.4.5.2 Protection for users UPS. Fan guards provided P
Use of symbol or warning ................................ : N/A
4.4.5.3 Protection for service persons UPS. Fan guards provided P
Use of symbol or warning ................................ : N/A
4.5/RD Thermal requirements P
4.5.1/RD General P
4.5.2/RD Temperature tests See previous test reports P
Normal load condition per Annex L ................. : P
4.5.3/RD Temperature limits for materials P
4.5.4/RD Touch temperature limits P
4.5.5/RD Resistance to abnormal heat .......................... : P
7.4.2 Openings P

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 29 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

7.4.3 Gas Concentration P


7.4.4 Equipment movement P

7.5 Resistance to fire P


4.7/RD
4.7.1/RD Reducing the risk of ignition and spread of flame Risk of ignition due to high P
temperatures minimized by
design and components.
Materials with the required
flammability classes are used.
Safety relevant components
used within their specified
rating.
Electrical parts are not likely
to ignite nearby materials.
Temperatures see 4.5.1
Method 1, selection and application of components (see appended table 7.5) P
wiring and materials
Method 2, application of all of simulated fault (see appended table 7.5) N/A
condition tests
4.7.2/RD Conditions for a fire enclosure Enclosure is entirely made of P
metal
4.7.2.1/RD Parts requiring a fire enclosure P
4.7.2.2/RD Parts not requiring a fire enclosure P
4.7.3/RD Materials P
4.7.3.1/RD General P
4.7.3.2/RD Materials for fire enclosures P
4.7.3.3/RD Materials for components and other parts outside Front Bezel rated HB (for P
fire enclosures decorative only); Bezel for
Display (UI interface) is rated
HB (LPS circuits are
complied.)
4.7.3.4/RD Materials for components and other parts inside All internal materials are rated P
fire enclosures V-2 or better, or are mounted
on printed wiring boards rated
V-1 or better
4.7.3.5/RD Materials for air filter assemblies No air filter assemblies N/A
4.7.3.6/RD Materials used in high-voltage components No high-voltage components N/A

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 30 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

7.6 Battery location P


7.6.1 Battery location and installation See manual, additional P
battery data available on
request
7.6.2 Accessibility and maintainability P
7.6.3 Distance P
7.6.4 Case insulation P
7.6.5 Wiring P
7.6.6 Electrolyte spillage P
7.6.7 Ventilation N/A
7.6.8 Charging voltage P

7.7 Temperature rise P


4.5/RD Thermal requirements P
4.5.1/RD General P
4.5.2/RD Temperature tests P
Normal load condition per Annex L ................. : (see appended table 7.7) P
4.5.3/RD Temperature limits for materials (see appended table 7.7) P
4.5.4/RD Touch temperature limits P
4.5.5/RD Resistance to abnormal heat .......................... : (see appended table 4.5.5) P
Based on the physical
characteristic of the
thermoplastic materials
employed in the power
supply, this test was not
considered necessary

8 Electrical requirements and simulated abnormal conditions P


8.1 General provisions for earth leakage P
5.1.1/RD General P
5.1.7/RD Equipment with touch current exceeding 3,5 mA N/A

8.2 Electric strength P


5.2/RD
5.2.1/RD General (see appended table 8.2) P
5.2.2/RD Test procedure (see appended table 8.2) P

8.3 Abnormal operating and fault conditions P


8.3.1 General P
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 31 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

5.3.1/RD Protection against overload and abnormal (see appended table 8.3) P
operation
5.3.2/RD Motors (see appended Annex B) P
5.3.3/RD Transformers (see appended Annex C) P
5.3.4/RD Functional insulation......................................... : P
5.3.5/RD Electromechanical components N/A
5.3.9/RD Compliance criteria for abnormal operating and P
fault conditions
5.3.9.1/RD During the tests P
5.3.9.2/RD After the tests P
8.3.2 Simulation of faults P
8.3.3 Conditions for tests P

9 Connection to telecommunication networks N/A


6/RD
6.1/RD Protection of telecommunication network service persons, and users of other N/A
equipment connected to the network, from hazards in the equipment
6.1.1/RD Protection from hazardous voltages N/A
6.1.2/RD Separation of the telecommunication network from N/A
earth
6.1.2.1/RD Requirements N/A
Supply voltage (V) ........................................... : --- 
Current in the test circuit (mA) ...................... : --- 
6.1.2.2/RD Exclusions ....................................................... : N/A
6.2/RD Protection of equipment users from overvoltages on telecommunication networks N/A
6.2.1/RD Separation requirements N/A
6.2.2/RD Electric strength test procedure N/A
6.2.2.1/RD Impulse test N/A
6.2.2.2/RD Steady-state test N/A
6.2.2.3/RD Compliance criteria N/A
6.3/RD Protection of the telecommunication wiring system N/A
from overheating
Max. output current (A) .................................... : --- 
3.5/RD Interconnection of equipment N/A
3.5.1/RD General requirements N/A
3.5.2/RD Types of interconnection circuits ..................... : N/A
3.5.3/RD ELV circuits as interconnection circuits N/A
3.5.4/RD Data ports for additional equipment N/A
2.1.3/RD Protection in restricted access locations N/A

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 32 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.3.1/RD Limits N/A


Type of TNV circuits ......................................... : --- 
2.3.2/RD Separation from other circuits and from accessible N/A
parts
2.3.2.1/RD General requirements N/A
2.3.2.2/RD Protection by basic insulation N/A
2.3.2.3/RD Protection by earthing N/A
2.3.2.4/RD Protection by other constructions .................... : N/A
2.3.3/RD Separation from hazardous voltages N/A
Insulation employed ......................................... : --- 
2.3.4/RD Connection of TNV circuits to other circuits N/A
Insulation employed ......................................... : --- 
2.3.5/RD Test for operating voltages generated externally N/A
2.6.5.8/RD Reliance on telecommunication network or cable N/A
distribution system
2.10.3.3/R Clearances in primary circuits N/A
D
2.10.3.4/R Clearances in secondary circuits N/A
D
2.10.4/RD Creepage distances N/A
2.10.4.1/R General N/A
D
2.10.4.2/R Material group and comparative tracking index N/A
D
CTI tests ........................................................... : --- 
2.10.4.3/R Minimum creepage distances N/A
D
M/RD Annex M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1/RD) N/A
M.1/RD Introduction N/A
M.2 /RD Method A N/A
M.3/RD Method B N/A
M.3.1/RD Ringing signal N/A
M.3.1.1/RD Frequency (Hz) ................................................ : --- 
M.3.1.2/RD Voltage (V) ...................................................... : --- 
M.3.1.3/RD Cadence; time (s), voltage (V) ........................ : --- 
M.3.1.4/RD Single fault current (mA) .................................. : --- 
M.3.2/RD Tripping device and monitoring voltage .......... : N/A
M.3.2.1/RD Conditions for use of a tripping device or a 
monitoring voltage ---
M.3.2.2/RD Tripping device N/A
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 33 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

M.3.2.3/RD Monitoring voltage (V) ..................................... : N/A

A/RD Annex A, Tests for resistance to heat and fire N/A


A.1/RD Flammability test for fire enclosures of movable equipment having a total mass N/A
exceeding 18 kg, and of stationary equipment (see 4.7.3.2/RD)
A.1.1/RD Samples............................................................ : --- 
Wall thickness (mm) ......................................... : --- 
A.1.2/RD Conditioning of samples; temperature (C) ..... : N/A
A.1.3/RD Mounting of samples ....................................... : N/A
A.1.4/RD Test flame (see IEC 60695-11-3) N/A
Flame A, B, C or D .......................................... : --- 
A.1.5/RD Test procedure N/A
A.1.6/RD Compliance criteria N/A
Sample 1 burning time (s) ................................ : --- 
Sample 2 burning time (s) ................................ : --- 
Sample 3 burning time (s) ................................ : --- 
A.2/RD Flammability test for fire enclosures of movable equipment having a total mass not N/A
exceeding 18 kg, and for material and components located inside fire enclosures
(see 4.7.3.2/RD and 4.7.3.4/RD)
A.2.1/RD Samples, material............................................. : --- 
Wall thickness (mm) ......................................... : --- 
A.2.2/RD Conditioning of samples; temperature (°C) ..... : N/A
A.2.3/RD Mounting of samples ....................................... : N/A
A.2.4/RD Test flame (see IEC 60695-11-4) N/A
Flame A, B or C ............................................... : --- 
A.2.5/RD Test procedure N/A
A.2.6/RD Compliance criteria N/A
Sample 1 burning time (s) ................................ : --- 
Sample 2 burning time (s) ................................ : --- 
Sample 3 burning time (s) ................................ : --- 
A.2.7/RD Alternative test acc. to IEC 60695-11-5, cl. 5 and 9 N/A
Sample 1 burning time (s) ................................ : --- 
Sample 2 burning time (s) ................................ : --- 
Sample 3 burning time (s) ................................ : --- 
A.3/RD Hot flaming oil test (see 4.6.2/RD) N/A
A.3.1/RD Mounting of samples N/A
A.3.2/RD Test procedure N/A
A.3.3/RD Compliance criterion N/A
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 34 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

B/RD Annex B, Motor tests under abnormal conditions (see 4.7.2.2/RD and 5.3.2/RD)
B.1/RD General requirements DC Fans are used P
Position ............................................................ : See Components List 
Manufacturer ................................................... : 
Type ................................................................. : 
Rated values .................................................. : 
B.2/RD Test conditions P
B.3/RD Maximum temperatures P
B.4/RD Running overload test N/A
B.5/RD Locked-rotor overload test N/A
Test duration (days) ........................................ : 
Electric strength test: test voltage (V) ............. : 
B.6/RD Running overload test for d.c. motors in secondary Fans are VDE or TÜV P
circuits certified to IEC/EN 60950-1
B.6.1/RD General See B.6 P
B.6.2/RD Test procedure See B.6 P
B.6.3/RD Alternative test procedure See B.6 P
B.6.4/RD Electric strength test; test voltage (V) ............. : See B.6 P
B.7/RD Locked-rotor overload test for d.c. motors in Fans are VDE or TÜV P
secondary circuits certified to IEC/EN 60950-1
2nd Edition
B.7.1/RD General See B.7 P
B.7.2/RD Test procedure See B.7 P
B.7.3/RD Alternative test procedure See B.7 P
B.7.4/RD Electric strength test; test voltage (V) ............. : See B.7 N/A
B.8/RD Test for motors with capacitors N/A
B.9/RD Test for three-phase motors N/A
B.10/RD Test for series motors N/A
Operating voltage (V) ...................................... : --- 

C/RD Annex C, Transformers (see 1.5.4/RD and 5.3.3/RD) P


Position ............................................................ : See previous Test Reports 
Manufacturer ................................................... : 
Type ................................................................. : 
Rated values .................................................. : 
Method of protection......................................... : 

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 35 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

C.1/RD Overload test P


C.2/RD Insulation P
Protection from displacement of windings........ : P

D/RD Annex D, Measuring instruments for touch current tests (see 5.1.4/RD) P
D.1/RD Measuring instrument N/A
D.2/RD Alternative measuring instrument P

E/RD Annex E, Temperature rise of a winding (see Annex E/RD) N/A

F/RD Annex F, Measurements of clearances and creepage distance (see 2.10/RD and P
Annex G/RD)

G/RD Annex G, Alternative method for determining minimum clearances N/A


G.1/RD Clearances N/A
G.1.1/RD General N/A
G.1.2/RD Summary of the procedure for determining minimum clearances N/A
G.2/RD Determination of mains transient voltage (V) N/A
G.2.1/RD AC mains supply ............................................. : N/A
G.2.2/RD Earthed d.c. mains supplies ............................ : N/A
G.2.3/RD Unearthed d.c. mains supplies ........................ : N/A
G.2.4/RD Battery operation ............................................. : N/A
G.3/RD Determination of telecommunication network N/A
transient voltage (V) ........................................ :
G.4/RD Determination of required withstand voltage (V) N/A
G.4.1/RD Mains transients and internal repetitive peaks : N/A
G.4.2/RD Transients from telecommunication networks . : N/A
G.4.3/RD Combination of transients N/A
G.4.4/RD Transients from cable distribution systems N/A
G.5/RD Measurement of transient voltages (V) N/A
a) Transients from a mains supply N/A
For an a.c. mains supply N/A
For a d.c. mains supply N/A
b) Transients from a telecommunication network N/A
G.6/RD Determination of minimum clearances ............ : N/A

H Annex H, Guidance on protection against ingress of water and foreign objects N/A
(see IEC 60529)

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 36 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

I Annex I, Backfeed protection test P


I.1 General See previous test reports P
I.2 Test for pluggable UPS P
I.3 Test for permanently connected UPS N/A
I.4 Load-induced change of reference potential See previous test reports P
I.5 Solid-state backfeed protection P
(see clause 7.1-7.5 of IEC 62040-2 and clause 7.1-
7.2 of IEC 62040-3)

J/RD Annex J, Table of electrochemical potentials (see 2.6.5.6/RD) P


Metal(s) used ................................................... : 

K/RD Annex K, Thermal controls (see 1.5.3/RD and 5.3.8/RD) N/A


K.1/RD Making and breaking capacity N/A
K.2 /RD Thermostat reliability; operating voltage (V) .... : N/A
K.3/RD Thermostat endurance test; operating voltage (V) N/A
.......................................................................... :
K.4/RD Temperature limiter endurance; operating voltage N/A
(V) .................................................................... :
K.5/RD Thermal cut-out reliability N/A
K.6/RD Stability of operation N/A

L Annex L, Reference loads P


L.1 General P
L.2 Reference resistive load P
L.3 Reference inductive-resistive load 
L.4 Reference capacitive-resistive loads N/A
L.5 Reference non-linear load N/A
L.5.1 General N/A
L.5.2 Test method N/A
L.5.3 Connection of the non-linear reference load 

M Annex M, Ventilation of battery compartments P


M.1 General Refer to test data, none P
ventilation batteries
M.2 Normal conditions P
M.3 Blocked conditions P
M.4 Overcharge conditions P
VDE File No 1924400-3335-0067/218478
TRF No. IEC62040_1C
Page 37 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

N Annex N, Minimum and maximum cross-sections of copper conductors suitable for N/A
connection (see 6.3)

U/RD Annex U, Insulated winding wires for use without interleaved insulation P
(see 2.10.5.4/RD)

V/RD Annex V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1/RD) P


V.1/RD Introduction P
V.2/RD TN power distribution systems P
V.3/RD TT power distribution systems P
V.4/RD IT power distribution systems N/A

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 38 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.6, TABLE: Electrical Data (in normal conditions) P


1.6.2/RD
fuse # I rated (A) U (V) P (W) I (mA) I fuse condition/status
(mA)

Supplementary information: refer to previous Test Reports

5.1.1 TABLE: Max. V, A, VA Test P


2.1.1.5/RD
Voltage (rated) Current (rated) Voltage (max.) Current (max.) VA (max.)
(V) (A) (V) (A) (VA)

Supplementary information: refer to previous Test Reports

5.1.1 TABLE: Stored Energy P


2.1.1.5/RD
Capacitance C (µF) Voltage U (V) Energy E (J)

Supplementary information: refer to previous Test Reports

5.1.1 TABLE: discharge of capacitors in the primary circuit P


2.1.1.7/
RD
Condition  calculated  measured t u 0V Comments
(s) (s) (s)

Supplementary information: refer to previous Test Reports

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 39 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

5.2.1 TABLE: Evaluation Of Voltage Limiting Components In SELV Circuits P


2.2/RD
Component (measured between) max. voltage (V) Voltage Limiting Components
(normal operation)
V peak V d.c.

Fault test performed on voltage limiting Voltage measured (V) in SELV circuits
components (V peak or V d.c.)

Supplementary information: refer to previous Test Reports ; Opto-isolator between mains and SELV
output

5.2.5 TABLE: Limited Power Sources P


2.5/RD
Circuit output tested:
Note: Measured Uoc (V) with all load circuits disconnected:
Components Sample No. Uoc (V) Isc (A) VA
Meas. Limit Meas. Limit

Supplementary information: refer to previous Test Reports

5.7 Table: Working Voltage Measurement P


2.10.2/RD
Location RMS voltage (V) Peak voltage (V) Comments

supplementary information: refer to previous Test Reports

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 40 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

5.7 TABLE: Clearance And Creepage Distance Measurements P


2.10.3/RD
clearance cl and creepage Up U r.m.s. Required cl required dcr dcr
distance dcr at/of: (V) (V) cl (mm) (mm) (mm) (mm)

Supplementary information: refer to previous Test Reports

5.7 TABLE: Distance Through Insulation Measurements P


2.10.5.2/
RD
Distance through insulation di at/of: U r.m.s. Test voltage Required di di
(V) (V) (mm) (mm)

Supplementary information: refer to previous Test Reports

5.7 and TABLE: Clearance and creepage distance measurements P


2.10.4/RD
Clearance (cl) and creepage U peak U r.m.s. Required cl Required cr
distance (cr) at/of/between: (V) (V) cl (mm) (mm) cr (mm) (mm)
Basic / supplementary:

Reinforced:
Supplementary information: refer to previous Test Reports;

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 41 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

7.7 TABLE: Heating Test P


4.5/RD
Test voltage (V) ...................................................... : 
Ambient (oC) ........................................................... : 
Thermocouple Locations max. temperature max. temperature limit,
measured, (oC)
(oC)

Supplementary information:
TABLE: Heating test, resistance method
Test voltage (V) ...................................................... : 
Ambient, t1 (C)....................................................... : 
Ambient, t2 (C)....................................................... : 
Temperature rise of winding R1 (Ω) R2 (Ω) ΔT (K) Max. dT (K) Insulation
class

Supplementary information: refer to previous Test Reports

7.4 TABLE: Ball Pressure Test of Thermoplastics P


4.5.5/RD
Allowed impression diameter (mm) ...................: 
Part Test temperature (C) Impression diameter (mm)

Supplementary information: refer to previous Test Reports

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 42 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

5.7 TABLE: Dielectric Strength P


2.10.5
Test voltage applied between: Test potential applied Breakdown / flashover
(V) (Yes/No)

Supplementary information: refer to previous Test Reports

7.5 TABLE: Resistance to fire P


4.7/RD
Part Manufacturer of Type of material Thickness Flammability Evidence
material (mm) class

Supplementary information: refer to previous Test Reports

8 TABLE: touch current measurement P


5.1/RD
Measured between: Measured Limit Comments/conditions
(mA) (mA)

Supplementary information: refer to previous Test Reports

8.3 TABLE: Fault condition tests P


5.3/RD
Ambient temperature (C) ................................ : 
Power source for EUT: Manufacturer, 
model/type, output rating ................................. :
Com- Fault Supply Test Fuse # Fuse Observation
ponent voltage time current
No. (V) (A)

Supplementary information: refer to previous Test Reports

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 43 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

C.2/RD TABLE: transformers P


Loc. Tested insulation Working Working Required Required Required Required
voltage voltage electric clearance / creepage distance thr.
peak / V rms / V strength mm distance / insul.
mm
(2.10.2) (2.10.2) (5.2) (2.10.3) (2.10.4) (2.10.5)

Loc. Tested insulation Test Measured Measured Measured


voltage/ clearance / creepage distance thr.
V mm dist./ mm insul. / mm;
number of
layers

Supplementary information: see Appendix or/and refer to previous Test Reports

C.2/RD TABLE: transformers P


Transformers
refer to previous Test Reports

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 44 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

M Ventilation of battery compartments N/A


The required dimension for the ventilation openings will be calculated with
the following formula:
A ≥ Q/360 [m²]
with Q = 0.054 * n * I * C
where:
Q : airflow in m³/h
n : number of battery cells
I : constant factor (0,2A/100Ah for valve regulated lead acid
batteries)
C : is the battery nominal capacity in Ah at the 10h discharge rate
With the specific data for the UPS the following dimension for the
ventilation openings is required:
n :?
C :?
A ≥ (0.054 * n * 0.2 A/100 Ah * C)/360
A ≥ ? m²
Verdict
The size of ventilation openings in battery cabinet exceeds the required
airflow by far (as well as the UPS).
Battery has no ventilation openings

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 45 of 53 Report No. 218478-CI3-1
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.5 TABLE: Critical components information P


Object / part Manufacturer/ Type / model Technical data Standard Mark(s) of
No. trademark conformity1)

See Appendix 1

Supplementary information:
1) Provided evidence ensures the agreed level of compliance. See OD-CB2039.

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 46 of 53 Report No. 218478-CI3-1
Critical Component list APPENDIX 1

4.5 TABLE: List of critical components


Object/part no. Manufacturer/ Type/model Technical data Standard Mark(s) of
trademark conformity 1.
Printed Circuit Board Various Various V-0 UL 796 UL
UPS
Fan (490-1059) Kaimei JF0825B2SRAR 24Vdc, 0.17A, max. IEC/EN 60950-1 50029788 (TUV)
48.53 CFM
Appliance Inlet Rong Feng SS-3B 16A, 250Vac IEC/EN 60320-1 40013645 (VDE)
(770-0339)
ELCOM EMI-18 16A, 250Vac 40014433 (VDE)
Alternate – Input WECO 327-HDS 3P 600V 1924400-3335- UL, CSA,
Terminal Block (740- Electrical 0065 / 180170 40039779 (VDE)
0076A) Connectors Inc.
AC Output Socket ELCOM EMO-14 10A, 250Vac IEC/EN 60320-1 40005067 (VDE)
(770-0006-Z-001)
Alternate -Output MOLEX 39910-0103 3P 600V, 65A 1924400-3335- UL
Terminal Block 0065 / 180170
(740-0067-Z)
Internal Battery Anderson SBS50 50A UL1977 E26226 (UL)
Connector
Connector for Anderson SBS75X 75A UL1977 E26226 (UL)
external battery
Case of display -- -- HB min. UL746C UL
module
Main Board (640-3700x for 3KVA, 640-3699x for 2.2KVA)
Choke (L1200) for APC 420- Class B IEC 60950-1 Tested within
model SRT3000XLI, 2213XXXXXXXX equipment
SRT3000RMXLI XX
(420-2213-Z) (X can be any
alphanumeric, +,
*, #, _, - or blank)
Choke (L1200) for APC 420- Class B IEC 60950-1 Tested within
model SRT2200XLI, 2209XXXXXXXX equipment
SRT2200RMXLI XX
(420-2209-Z) (X can be any
alphanumeric, +,
*, #, _, - or blank)
Choke (L1206) (420- APC 420- Class B IEC 60950-1 Tested within
0006-Z) 0006XXXXXXXX equipment
XX
(X can be any
alphanumeric, +,
*, #, _, - or blank)

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 47 of 53 Report No. 218478-CI3-1
Critical Component list APPENDIX 1

4.5 TABLE: List of critical components


Object/part no. Manufacturer/ Type/model Technical data Standard Mark(s) of
trademark conformity 1.
Choke (L1203) APC 420- Class B IEC 60950-1 Tested within
for model 2214XXXXXXXX equipment
SRT3000XLI, XX
SRT3000RMXLI (X can be any
(420-2214-Z) alphanumeric, +,
*, #, _, - or blank)
Choke (L1203) APC 420- Class B IEC 60950-1 Tested within
for model 2210XXXXXXXX equipment
SRT2200XLI, XX
SRT2200RMXLI (X can be any
alphanumeric, +,
*, #, _, - or blank)
Choke (L1207) APC 420- Class B IEC 60950-1 Tested within
for model 2215XXXXXXXX equipment
SRT3000XLI, XX
SRT3000RMXLI (X can be any
alphanumeric, +,
*, #, _, - or blank)
Choke (L1207) APC 420- Class B IEC 60950-1 Tested within
for model 2211XXXXXXXX equipment
SRT2200XLI, XX
SRT2200RMXLI (X can be any
alphanumeric, +,
*, #, _, - or blank)
Choke (L1208) APC 420- Class B IEC 60950-1 Tested within
(420-2202-Z) 2202XXXXXXXX equipment
XX
(X can be any
alphanumeric, +,
*, #, _, - or blank)
Choke (L1201, APC 422- Class B IEC 60950-1 Tested within
L1202) 0016XXXXXXXX equipment
XX
(X can be any
alphanumeric, +,
*, #, _, - or blank)
Charger Transformer APC 433- Class B IEC 60950-1 Tested within
(T1204) 0136XXXXXXXX equipment
for model XX
SRT3000XLI, (X can be any
SRT3000RMXLI alphanumeric, +,
*, #, _, - or blank)

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 48 of 53 Report No. 218478-CI3-1
Critical Component list APPENDIX 1

4.5 TABLE: List of critical components


Object/part no. Manufacturer/ Type/model Technical data Standard Mark(s) of
trademark conformity 1.
Charger Transformer APC 433- Class B IEC 60950-1 Tested within
(T1204) 0132XXXXXXXX equipment
for model XX
SRT2200XLI, (X can be any
SRT2200RMXLI I alphanumeric, +,
*, #, _, - or blank)
AUX Charger APC 433- Class B IEC 60950-1 Tested within
Transformer (T1201) 0133XXXXXXXX equipment
SRT3000XLI, XX
SRT3000RMXLI (X can be any
alphanumeric, +,
*, #, _, - or blank)
AUX Charger APC 433- Class B IEC 60950-1 Tested within
Transformer (T1201) 0123XXXXXXXX equipment
SRT2200XLI, XX
SRT2200RMXL (X can be any
alphanumeric, +,
*, #, _, - or blank)
DC to DC APC 433- Class B IEC 60950-1 Tested within
transformer (T1203) 0135XXXXXXXX equipment
SRT3000XLI, XX
SRT3000RMXLI (X can be any
alphanumeric, +,
*, #, _, - or blank)
DC to DC APC 433- Class B IEC 60950-1 Tested within
transformer (T1203) 0130XXXXXXXX equipment
SRT2200XLI, XX
SRT2200RMXL (X can be any
alphanumeric, +,
*, #, _, - or blank)
Current Sense APC 460-1003 Class B IEC 60950-1 Tested within
Transformer XXXXXXXXXX equipment
(CT1200) (X can be any
alphanumeric, +,
*, #, _, - or blank)
Current Sense APC 460-1032 Class B IEC 60950-1 Tested within
Transformer XXXXXXXXXX equipment
(CT1201) (X can be any
alphanumeric, +,
*, #, _, - or blank)
Current Sense APC 460-1006 Class B IEC 60950-1 Tested within
Transformer XXXXXXXXXX equipment
(CT1202) (X can be any
alphanumeric, +,
*, #, _, - or blank)

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 49 of 53 Report No. 218478-CI3-1
Critical Component list APPENDIX 1

4.5 TABLE: List of critical components


Object/part no. Manufacturer/ Type/model Technical data Standard Mark(s) of
trademark conformity 1.
Transformer (T1200) APC 430-7205 Class B IEC 60950-1 Tested within
(430-7205-Z) XXXXXXXXXX equipment
(X can be any
alphanumeric, +,
*, #, _, - or blank)
Backfeed Relay Song Chuan 832A-1A-F-C-H- 20A, 250Vac EN 61810-1 6615 (VDE)
(RY1205) 24VDC Coil 24 Vdc UL60947-1 E88991 (UL)
(450-3005-Z)
Omron G8P-1A4P-BG 20A, 250Vac EN 61810-1 400004714
Coil 24 Vdc (VDE )
Backfeed Relay HASCO HAT901CSDC24- 30A, 240Vac EN 61810-1 R 50194653
(RY1206) 1-4K Coil 24 Vdc (TUV)
(450-0029-Z)
Relay (RY1204) SongChuan 894H-2AH1-F-S 8A, 240Vac EN 61810-1 40007827 (VDE)
(450-2151A-Z) Coil 24 Vdc
Alternative Omron Corp G2RG-2A4 8A, 250Vac, Coil EN 61810-1 VDE
24Vdc
Relay (RY1202, SongChuan 832A-1A-F-C U29 30A, 250Vac UL60947-1 E88991 (UL)
RY1203) Coil 24 Vdc
(450-3006-Z)
OMRON G8P-1A4P-A04 30A, 250Vac UL60947-1 E41643 (UL)
Coil 24 Vdc
Relay (RY1200) HASCO HATF905ASDC2 50A, 28Vdc UL60947-1 E75887 (UL)
(450-3004-Z) 4 Coil 24 Vdc
Capacitor X2 CAMEL MPX series 250Vac min., 2.2uF IEC/EN 60384-14 136014 (VDE)
(C1226, C1227, Technology
C1228)
(232-1225-Z-001) EPCOS B3292 Series 40005524,
Electronic 40005536,
40010694,
40019254,
40021331
(VDE)
ARCOTRONIC R.46 V4413 (ENEC03)
S
Capacitor Y2 Murata KH 250Vac, 4700pF IEC/EN 60384-14 40002796 (VDE)
(C1239, C1240,
C1241, C1242, Apex NU 40023096
C1243, C1244, (VDE)
C1245, C1246)
(221-1502-Z)
MOV (MV1200) Panasonic V14681U 680V, 190J max. IEC/EN 61051 5912 (VDE)
(380-4200-Z)
Epcos S14K420 420V, 90J IEC/EN 61051 40027582 (VDE)
Thinking TVR14681 680V, 130J IEC/EN 61051 5944 (VDE)

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 50 of 53 Report No. 218478-CI3-1
Critical Component list APPENDIX 1

4.5 TABLE: List of critical components


Object/part no. Manufacturer/ Type/model Technical data Standard Mark(s) of
trademark conformity 1.
MOV (MV1204A, MAIDA D65ZOV511RA19 510Vac, 470J IEC/EN 61051 40031393
MV1205A) 0 (VDE)
(380-0511-Z)
Alternative Panasonic ERZV20D471 300Vac IEC/EN 61051-1 VDE
Creamic
products
Alternative Ceramate GNR20D471 300Vac IEC/EN 61051-1 VDE
Technical Co.
Ltd
Alternative Maida D63 series 300Vac IEC/EN 61051-1 VDE
Alternative Wujin Thinking TVR20471 300Vac IEC/EN 61051-1 VDE
Electronic Co.
Ltd
Alternative Epcos S20K series 300Vac IEC/EN 61051-1 VDE
Electronic
Components
Fuse COOPER MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)
(F1202, F1203) BUSSMANN
(512-0030-Z)
Fuse LITTELFUSE TE5 808 250Vac, 3A UL 248-14 E67006 (UL)
(F1204, F1205)
(513-0020-Z) COOPER PCB-3-R 250Vac, 3A UL 248-14 E19180 (UL)
BUSSMANN
Fuse (F1200) (513- BEL FUSE MRT 4 250Vac, 4A EN 60127-3 139937 (VDE)
0022-Z) Schurter AG MST 250 250Vac, 4A EN 60127-3 40013529 (VDE)

LITTELFUSE 372 250Vac, 4A EN 60127-3 097187 (VDE)

Fuse (F1201) COOPER GBH-V030A6F 500V , 30A UL 248-1 E19180 (UL)


(515-1030A-Z) BUSSMANN

LITTELFUSE 505030 500V , 30A UL 248-1 E10480 (UL)

DC LPS board (640-3708x)


Isolated Transformer APC 433- Class B IEC 60950-1 Tested within
(T701) 0129XXXXXXXX See attached equipment
(433-0129-Z) XX datasheet
(X can be any
alphanumeric, +,
*, #, _, - or blank)
Diode (D709) -- -- 3A, 200V -- --
(330-3100-Z)
Diode (D710) -- -- 1A, 200V -- --
(339-0030-Z)

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 51 of 53 Report No. 218478-CI3-1
Critical Component list APPENDIX 1

4.5 TABLE: List of critical components


Object/part no. Manufacturer/ Type/model Technical data Standard Mark(s) of
trademark conformity 1.
Inverter Driver Board
Transformer (T801, APC 4300516XXXXXX Class B IEC 60950-1 Tested within
T802, T803) XXXX equipment
(X can be any
alphanumeric, +,
*, #, _, - or blank)
SOG Board
Output Relay SongChuan 832A-1A-F-C 30A, 250Vac UL60947-1 UL (E88991)
(RY881, RY882) Coil 24 Vdc
(450-3006-Z) OMRON G8P-1A4P 30A, 250Vac UL60947-1 UL (E41643)
Coil 24 Vdc
PFC Driver Board (640-3711x)
Transformer (T831) APC 430- Class B IEC 60950-1 Tested within
(430-5016-Z) 5016XXXXXXXX equipment
XX
(X can be any
alphanumeric, +,
*, #, _, - or blank)
Communication Board (640-6009x)
Optical Isolator Liteon LTV-817 Dti > 0.8 mm UL1577 40015248
(IC1715, IC1710, 5000V min. IEC/EN 60747-5- (VDE)
IC1718) isolation 5 E113898(UL)
(349-0100-Z) FAIRCHILD FOD817B Dti > 1 mm 40026857
5000V min. (VDE)
isolation E90700 (UL)
ISOCOM ISP817X Dti > 0.6 mm 40028086
5000V min. (VDE)
isolation E91231(UL)
VISHAY SFH6156 Dti > 0.5 mm 91888(VDE)
5000V min. E52744(UL)
Isolation
EVERLIGHT EL816 Dti > 0.4 mm 132249(VDE)
5000V min. E214129(UL)
isolation
AVAGO HCPL-817 Dti > 0.4 mm 5000V 40016429 (VDE)
Technologies min. isolation E55361(UL)

Optical Isolator AVAGO 6N137-360E (for Single channel, IEC/EN 60747-5- 40009430 (VDE)
( IC1707, IC1708, Technologies Tube) 1000V 5
IC1711, IC1712) 6N137-560E (for /us, 630V
(349-0137-Z-001) Tape and Reel)
Battery Pack
Fuse (F1, F2) COOPER MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)
(512-0030-Z) BUSSMANN

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 52 of 53 Report No. 218478-CI3-1
Critical Component list APPENDIX 1

4.5 TABLE: List of critical components


Object/part no. Manufacturer/ Type/model Technical data Standard Mark(s) of
trademark conformity 1.
Battery CSB HR1221W 12V, 21W UL 1989 MH14533(UL)
(910-6003-001) B&B BP5-12 12V, 5Ah MH19884(UL)
Case LG AF312A 5V, 2.1mm min. UL746C E67171 (UL)
(876-1046)
(876-1047)

Optional Battery Pack SRT72BP, SRT72RMBP, SRT96BP, SRT96RMBP


Front Bezel -- -- HB min. UL746C --
Shunt Board (640-9926x)
Fuse (F1, F2) COOPER MDA-V-R 125Vdc, 30A UL 248-14 E19180 (UL)
BUSSMANN
Fuse (F3) Conquer MET Series 250V, 2A UL 248-14 40017155 (VDE)
(513-0002-Z) COOPER SR-5-2A-AP 40020046 (VDE)
BUSSMANN
LITTELFUSE 372 097187 (VDE)
Transformer (T1) APC 430- Class B IEC 60950-1 Tested within
10056XXXXXXX equipment
(430-10056-Z)
XXX
(X can be any
alphanumeric, +,
*, #, _, - or blank)
Battery Pack
Fuse (F1, F2) COOPER MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)
(512-0030-Z) BUSSMANN
Battery KUNG LONG WP5-12 12V, 5Ah UL 1989 MH16982 (UL)
(910-6003-001)
B&B BP5-12 12V, 5Ah MH19884(UL)
6 or 8 used *)
Case LG AF312A 5V, 2.1mm min. UL746C E67171 (UL)
(876-1046)
(876-1047)
1
) an asterisk indicates a mark which assures the agreed level of surveillance
*) Number of batteries: 6 for battery pack SRT72BP, SRT72RMBP or 8 for SRT96BP, SRT96RMBP

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C
Page 53 of 53 Report No. 218478-CI3-1
Modifications covered by this report APPENDIX 2

1. Revise the definition of model name.


SRT 3000 RM XL I xxxxxxxxxx
A B C D E F

A: SRT, means series name


B: 3000, 2200, means maximum VA output
C: RM (means Rack Mounted) or none (means Tower Stand)
D: XL, means Extended Run
E: I = International (220-230-240V), W = Worldwide (208-220-230-240V)
F: xxxxxxxxxx (x=0-9, a-z, A-Z, +, *, #, _, - or blank) for marketing purpose

2. Add an alternate source for relay RY1204.


Relay RY1204 Omron Corp G2RG-2A4 8A, 250Vac, Coil 24Vdc

3. Add an alternate source for MOV MV1204A, MV1205A.

VDE File No 1924400-3335-0067/218478


TRF No. IEC62040_1C