Parter A
Parter A 16/1/2019
Parter A
Quantity Luminaire (Luminous emittance)
48 ZUMTOBEL - 42182767 (STD - Standard) PERLUCE O
LED4600-840 L1520 LDE IP54 WH
Luminous emittance 1
Fitting: 1xLED-Z42182766 41W
Light output ratio: 100.03%
Lamp luminous flux: 4870 lm See our luminaire catalog for
Luminaire luminous flux: 4871 lm an image of the luminaire.
Power: 41.0 W
Luminous efficacy: 118.8 lm/W
Colorimetric data
1x: CCT 3000 K, CRI 80
Total lamp luminous flux: 233760 lm, Total luminaire luminous flux: 233808 lm, Total Load: 1968.0 W, Luminous efficacy: 118.8 lm/W
Page 2
Parter A 16/1/2019
Room 2
Clearance height: 7.000 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80
Workplane
Surface Result Average (Target) Min Max Min/average Min/max
1 Workplane 2 Perpendicular illuminance (adaptive) [lx] 187 (≥ 500) 121 227 0.65 0.53
Height: 0.000 m, Wall zone: 0.400 m
Lighting power density: 4.64 W/m² (Floor area of room 212.02 m²),
Lighting power density: 5.36 W/m² = 2.86 W/m²/100 lx (Area of working plane 183.67 m²)
The energy consumption quantities refer to the lights planned for the room without taking into account light scenes and their dimming levels.
Consumption: 1700 - 2700 kWh/a of maximum 7450 kWh/a
Page 3
Parter A 16/1/2019
Room 2
Page 4
Parter A 16/1/2019
Page 5
Parter A 16/1/2019
Page 6
Parter A 16/1/2019
Isolines [lx]
Scale: 1 : 200
Page 7
Parter A 16/1/2019
Scale: 1 : 200
Page 8
Parter A 16/1/2019
Scale: 1 : 200
Page 9
Parter A 16/1/2019
Room 3
Clearance height: 7.000 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80
Workplane
Surface Result Average (Target) Min Max Min/average Min/max
1 Workplane 3 Perpendicular illuminance (adaptive) [lx] 187 (≥ 500) 121 229 0.65 0.53
Height: 0.000 m, Wall zone: 0.400 m
Lighting power density: 4.63 W/m² (Floor area of room 212.64 m²),
Lighting power density: 5.34 W/m² = 2.85 W/m²/100 lx (Area of working plane 184.33 m²)
The energy consumption quantities refer to the lights planned for the room without taking into account light scenes and their dimming levels.
Consumption: 1700 - 2700 kWh/a of maximum 7450 kWh/a
Page 10
Parter A 16/1/2019
Room 3
Page 11
Parter A 16/1/2019
Isolines [lx]
Scale: 1 : 200
Scale: 1 : 200
Scale: 1 : 200
Page 12