You are on page 1of 1

3/29/2017 45366 ­ 1791DS: Module replacement Guidelines

(/app/answers/detail/a_id/45366#)

1791DS: Module replacement Guidelines


45366 | Date Created: 10/25/2007 | Last Updated: 12/01/2015
Support
Access Center (/app/home)
Level: TechConnect
 Email this page   Subscribe to Updates
Menu 

Question
Can a 1791DS module be preconfigured for use on a safety network of a specific SmartGuard 600, so that the module can be used as a spare without the need for
RSNetWorx at the time of replacement? 

Environment
1791DS module
1752­L24BBB
1752­L24BBBE

Answer
Yes.

To allow for a replacement of a 1791DS module without having to reset ownership of the module, i.e. a plug and play replacement, the Safety Serial Number and the
Configuration Signature can be downloaded to a spare 1791DS module.  This spare module can then be swapped with the module presently on the SmartGuard
safety netwok.  It will not be necessary to perform any operation within RSNetWorx for DeviceNet.

To configure the spare module:

1. Configure the 1791DS module that will be used with the SmartGuard600 and upload from device using RSNetWorx.  Note the Safety Network Number and the
Configuration Signature.
2. Swap with an identical 1791DS module and download to device using RSNetWorx.
3. Upload from device using RSNetWorx and verify that the Safety Network Number and the Configuration Signature are the same for both modules.
4. Replace the original module.  The spare module is now preconfigured for use with that SmartGuard600 controller.

NOTE: If the 1791DS module is to be used with a different SmartGuard600, it will be necessary to reset the safety device using RSNetWorx for DeviceNet by
following the standard procedure.

DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such
subjects. Accordingly, the information in this web site is not intended to constitute application, design, software or other professional engineering advice or services.
Before making any decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor.

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE
AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS
PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL,
CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE)
PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON­INFRINGEMENT.
Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.

This page is best viewed in Internet Explorer 10, Firefox 31, Chrome 37, Safari 6 or newer.

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/45366 1/1

You might also like