Professional Documents
Culture Documents
Connection procedure
Cabling examples are presented below. Frame size E: Cable lug installation (16 to 70 mm2
[AWG6 to AWG2/0] cables)
Tightening torques are presented on page 5
and at appropriate points in the text.
Remove the plastic shroud covering the main
terminals. Lift up with a screw driver from the Insulate the ends of the 30
44 N·m
cable lugs with tape or (22
32 lbf·ft)
corner.
shrink tube
Connect the twisted shields of the power
cables and separate grounding conductors to UDC+
U1 V1 W1 R- R+ UDC- U2 V2 W2
the grounding terminals of the drive module.
Connect the phase conductors of the supply
cable to the U1, V1 and W1 terminals, and
the phase conductors of the motor cable to
the U2, V2 and W2 terminals. The
recommended stripping length is 16 mm
(0.63) for frame size E0 and 28 mm (1.1)
for frame size E.
Secure the cables mechanically outside the
drive module. PE
Cut holes for the installed cables into the 8 N·m (5.9 lbf·ft)
clear plastic shroud to accommodate the
power cables. Press the shroud onto the
terminals.
Connect the other ends of the power cables.
To ensure safety, pay special attention to
connection of the grounding conductors. Input power cable Motor cable
Cabling examples
UDC+
PE U1 V1 W1 R- R+ UDC- U2 V2 W2 PE
b
UDC+
U1 V1 W1 R- R+ UDC- U2 V2 W2
Tightening torques
Drive type Power terminals PE
ACS850-04
N·m (lbf·ft) N·m (lbf·ft)
-103A-5, -144A-5 15 (11) 15 (11)
Cable lug installation
8 (5.9)
30
44 (22
32)
-166A-5
-290A-5 Allen screw
20
40 (15
30)
8 (5.9)
Screw terminal installation
30
44 (22
32)
XD24
XD24
2 2 0.7 N·m
3 3 (6.2 lbf·in)
4 4
1 1
2 2
AI1 Determines whether Analog input AI1 is
used as a current or voltage input.
Current Voltage
7 7
Routing the control cables
AI1 AI1
AI2 AI2
1 1 Use shrink tubing or tape
AI2 Determines whether Analog input AI2 is to contain strands
used as a current or voltage input.
Current Voltage
Remove outer jacket of cable
7 7 at clamp to expose cable
shield. Tighten to 1.5 N·m
AI1 AI1
(13 lbf·in).
AI2 AI2
1 1
T Drive-to-drive link termination. Must be set
to the ON position when the drive is the last unit
on the link.
Termination ON Termination OFF
T T
Technical data
UL checklist
The ACS850-04 is an IP20 (UL open type)
drive to be used in a heated, indoor
controlled environment. The drive must be
installed in clean air according to enclosure
classification. Cooling air must be clean, free
from corrosive materials and electrically
conductive dust. See the Hardware Manual
for detailed specifications.
The maximum ambient air temperature is
40 °C (104 °F) at rated current. The current
is derated for 40 to 55 °C (104 to 131 °F).
The drive is suitable for use in a circuit
capable of delivering not more than 100,000
rms symmetrical amperes, 500 V maximum.
The cables located within the motor circuit
must be rated for at least 75 °C (167 °F) in
UL-compliant installations.
The input cable must be protected with fuses
or circuit breakers. Suitable IEC (class gG)
and UL (class T) fuses are listed in the
Technical data section of the Hardware
Manual. For suitable circuit breakers, contact
your local ABB representative.
For installation in the United States, branch
circuit protection must be provided in
accordance with the National Electrical Code
(NEC) and any applicable local codes. To
fulfill this requirement, use the UL classified
fuses.
For installation in Canada, branch circuit
protection must be provided in accordance
with Canadian Electrical Code and any
applicable provincial codes. To fulfill this
requirement, use the UL classified fuses.
The drive provides overload protection in
accordance with the National Electrical Code
(NEC). See the appropriate Firmware
Manual for overload protection settings.