If current carrying capacity is not adequate
NA
arrangement proposed
44
Details of arrears if any pending in respect of
Nil
the applicant or its sister concern
TANGEDCO side:
1. Erection of 11 KV VCB for the newly proposed feeder
namely 11 KV HITEMP feeder
in the 110/33-11 KV Irunkattukottai SS .
2. Laying of HTUG 11 KV 3 x300 sq.mm XLPE cable to a
length of 70 mtrs ( including on pole & coiling ) from SS to
Loc 1 as per the sketch.
3. Provision of 2 Nos of 11 KV 3 x 300 sq.mm OD kit
Details of work involved 4. Erection of 11 KV OH line with ACSR 7/4.09 MM conductor
to a distance of 3.06 KM from SS to location 48 A, with
erection of 46 Nos of 36’ RSJ Poles as per the sketch.
5. Erection of check meter arrangements with 100-50/5 A
Metering set with TOD meter of 0.2 s class of accuracy.
CONSUMER side:
1. Replacement of existing of 40-20/5 A Outdoor Metering
set by 100-50/5 A with class 0.2s accuracy .
50 Remarks if any
CHIEF ENGINEER/DISTRIBUTION
CHENNAI SOUTH REGION
DETAILED ESTIMATE FOR EXTENSION OF 11 KV SUPPLY TO M/S. HIGHTEMP FURNANCES LTD , FOR A DEMAND OF
500KVA OVER AND ABOVE THE EXG DEMAND 700 KVA AT IRUNGATTUKOTTAI , SRIPERUMBUDUR TALUK,
KANCHIPURAM DISTRICT IN CHENGALPATTU/EDC
Contingencies 1 % 6558.10
Total 875981.81
Contingencies 1 % 954.06
Total 127436.29
410015643.xls
DATA III ERECTION OF 11 KV HT OH FEEDER TANGEDCO SIDE
Contingencies 1 % 14541.02
contingencies 1% 1,676.90
410015643.xls
Total 209,146.94
410015643.xls
DATA V ERECTION OF 11 KV METERING SET'
78,379.35
80,730.73
104,949.95
128,038.94
78,269.00
46,599.20
53,589.08
410015643.xls
ABSTRACT
TANGEDCO SIDE
CHIEF ENGINEER/DISTRIBUTION