You are on page 1of 2

DC Power System DPS 600B-48-4 19IN

The Power behind.

Main features Description


• 19” / 2U shelf power system up to 2400 W The DPS 600B-48-4 19IN power supply system is
• High power density designed for various applications such as digital
access, wireless base stations, microwave links as
• Very short depth well as PABX. Numerous options provide solutions for
• Fits into 300 mm deep ETSI cabinets global applications in different environments.
• Fan cooled rectifiers DPR 600B-48 or DPR 300B-48 The integrated modular power system allows flexible
• Integrated power distribution adaptations. It contains up to 4 rectifiers DPR 600B-
48 or DPR 300B-48, AC- and DC-connections, battery
• Easy installation connection and power system controller. These
• Dimensions (h x w x d) 88.9 x 430 x 280 mm features together with the very short depth are the key
factors for the success of this power system, offering
Applications cost-effective and reliable solutions.
• Digital subscriber line (DSL) This compact and high density power supply system
• Fiber in the loop is the perfect choice for space-critical locations.
• Transmission
• PBX
• Network components

LF_DPS-600B-48-4-19IN_en.doc / rev. 1.1 / 22.07.2005 / HPG www.deltaenergysystems.com


DC Power System DPS 600B-48-4 19IN
Technical Specifications

General Mechanics
Efficiency > 92 % Construction Steel rack
Losses, max. EN 55 022, class B Cabinet standard 19 IN
Safety EN 60 950, class I Width, body 430 mm
Cooling Fan cooled Depth, overall 280 mm (including handles)
Protection IP 20 Height, overall 88.9 mm (2 U)
Weight, system 5 kg / 11 lb (excluding rectifier)
Input Weight, rectifiers 0.9 kg / 2.0 lb
AC connection 1 x L/N/PE
Nominal voltage 230 Vrms Environment
Voltage range 80 ... 300 Vrms Operation temperature -25 … +65 °C
Range, reduced power 80 … 130 V rms Relative humidity 95 % max, non condensing
Frequency range 50 / 60 Hz
Current nominal 11.6 Arms Control and monitoring
Current maximum 24 Arms Power system controller PSC 1
Line current Meets IEC 1000-3-2
Mains terminal common terminal Options
Transient OVP Option / external Number of rectifiers 1…3
LVD 60 A
Output AC selectivity fuse 4A (5x20mm) per module
Voltage, nominal 53.5 Vdc Transient OVP For external installation
Voltage range 42 …58 Vdc
Output current 44.8 Adc Accessories
Current limitation 56.0 Adc Rectifier front cover D0117507
Power, limitation 4 x 600 W
Power, nominal 2400 W All technical data is valid for a system with DPR 600B-48
Power, redundant 1800 W rectifier module.
Power, at 88Vrms 1600 W
*on request
Load distribution
Fuses (DIN 72581-3) 12 pcs / 1 … 30 A Subject to change due to technical progress.
PLD None

Battery connection
Fuses (DIN 72581-3) 2 pcs / 40 A
LVD Option

Delta Energy Systems (Switzerland) AG


Freiburgstrasse 251
CH-3018 Bern-Bümpliz
Phone: +41 31 998 53 11 Fax: +41 31 998 53 53 www.deltaenergysystems.com