You are on page 1of 1

DOCUMENT NO.

BA4-MTB-E-CS-ECLPB-005
PT. BUKIT ASAM (PERSERO) Tbk. ELECTRICAL LOAD LIST
SWITCHGEAR/MCC : SUBSTATION 6
REV. DATE DESCRIPTION BY CHK. APR. PROJECT NO.
0 11/02/2015 Issued for Review OKT FRD FRD

At Load Factor Consumed Load

Utility Factor
Circuit Type
Load Type
Motor or
Absorbed
Equipment Tag Voltage Rating Data Validity Load Factor Full Load

Bus
Rev. No P&ID Number Description Load Eff. Power Factor Continuous Intermittent Standby Remarks
No. (Volt) Equipment Current (FLC)

kW kW Rev. Type Dec Dec A Cos α kW kVAR kVA A kW kVAR kVA A kW kVAR kVA A
SWITCHGEAR / MCC : SUBSTATION 6

MOTOR CONTROL CENTER (MCC)


1 OLC 2 M DOL C 380 315.00 315.00 ME 1.00 0.90 625.61 0.85 350.00 216.91 411.76 625.61
2 MOTOR BRAKE OLC 2 M DOL C 380 9.00 9.00 ME 1.00 0.90 17.87 0.85 10.00 6.20 11.76 17.87
3 SPARE F - S 380 315.00 315.00 ES 1.00 1.00 563.05 0.85 315.00 195.22 370.59 563.05

TOTAL 360.00 223.11 423.53 643.49 0.00 0.00 0.00 0.00 315.00 195.22 370.59 563.05

NOTE Description Continuous Intermittent Standby


Load Type = M (Motor), F (Feeder), and O (Other / Package) Total (kW/kVAR/kVA/A) 360.00 223.11 423.53 643.49 0.00 0.00 0.00 0.00 315.00 195.22 370.59 563.05
Circuit Type = DOL (Direct Online), FR (Forward Reverse), YD (Wye-Delta), SS (Soft Starter), and VSD (Variable Speed Drive) Power Factor 0.85 0.00 0.85
Utility Factor = C (Continuous), I (Intermittent), and S (Standby) Total Rated kW 324.00 0.00 315.00

Normal Load / Average Load = (1.00 x Total Continuous Load) + (0.50 x Total Intermittent Load) LOAD SUMMARY
Peak Load = Normal Load + (0.10 x Total Standby Load) Normal/Average Load = 360.00 kW 223.11 kVAR 423.53 kVA 643.49 A
Demand Load = Peak Load + (Peak Load * 0.20) Peak Load = 391.50 kW 242.63 kVAR 460.59 kVA 699.79 A
Demand Load = 469.80 kW 291.16 kVAR 552.71 kVA 839.75 A