Building Services Engineering Consultants (Pvt) Ltd.

1, 33rd Lane, Bagatalle Road, Colombo 03.


DESIGN NOTE
Record No: 01
Tel : 94- 11-2501727 Issue No 1 Rev 0
Fax : 94- 71-8802859 Date of Issue: 21 Feb 2019
Email: contact@bsec.lk Page No: 01 of 01
Project Softlogic Supermarket at Kottawa
D/N No. BSEC-SLkOT-ELE-01/02/03

Employer Softlogic Supermarkets (Pvt) Ltd


Date 21.02.2019
Engineer Building Services Engineering Consultants (Pvt.) Ltd

To Attention:
Sintech Engineering Pvt Ltd,
Status For Information
Title

Reference to e-mail with subject “Glomark Kottawa - Query Sheet 01” sent by Eng. Tharindu M. Liyanage on
20.02.2019
Query Description Response
No.
As per the specification stated that Main Switch Not necessary
1.1 board should be Type Tested Design. Is it
compulsory.?
According to the Specification it is mentioned Form 3b segregation shall be recommended for
that Main Panel should main panel.
1.2 be Form 3B. But in the Electrical Notes in the
Drawings stated as Form
2B. Please confirm the required separation type?
Please confirm the installation type (Sunk All the Distribution Boards shall be surface mounted.
2.1 mounted or surface mounted) of the Distribution
Board.
Is there any technical specification for Generator Generator Spec already included in tender package
3.1
System.? issued on 09.01.2019
As per the BOQ stated that IP rating of Light Dust proof Light fittings (IP54) shall be
4.1 fittings are IP 54 (Including 2"X2" fitting). Is it recommended.
compulsory.?
Ceiling recessed type light fittings shall be used for all
Please advise the mounting method of light
the areas with ceiling and other areas without ceiling
4.2 fittings of each area. (Ground Floor, First floor &
shall use soffit mounted light fittings. Ceiling areas to
Second Floor)
be clarified with architectural drawings.
As per instruction received in the pre-bid It shall be recommended to use powder coated cable
5.1 meeting, inside building cable trays are powder trays inside the building and HDGI cable trays outside
coated and outdoor cable trays are HDGI. the building.
Feeder Cable of MDB to PFCP (3C x 70mm2
Feeder Cable of MDB to PFCP (3C 70mm2
Cu/XLPE/PVC + 1C x 35mm2 Cu/PVC Earth Cable) will
6.1 Cu/XLPE/PVC 1C 35mm2 Cu/PVC Earth Cable) is
be included in amendment – 01 of BSEC-SLK-ELE-
not included in the BOQ. Please clarify.
BOQ
There are some discrepancies of incoming 1. MDB to DB-GF-1:
cables sizes between received SLDs &  4C-25mm ² Cu/XLPE/SWA/PVC +1C-16mm²
Schematic drawing. Please advise the Cu/PVC(E)
drawing which should be followed us.  Reff - BSEC-SLK-ELE-11
2. MDB to DB-FF-1:
1. MDB to DB-GF-1
 4C-10mm ² Cu/PVC/PVC +1C-10mm²
6.2 2. MDB to DB-FF-1 Cu/PVC(E)
3. SDB to DB-SF  Reff - BSEC-SLK-ELE-13
4. SDB to DB-UPS 3. SDB to DB-SF:
 4C-16mm ² Cu/XLPE/PVC +1C-16mm²
Cu/PVC(E)
 Reff - BSEC-SLK-ELE-13
4. SDB to DB-UPS:
 2C-16mm ² Cu/XLPE/PVC +1C-16mm²
Cu/PVC(E)
 Reff - BSEC-SLK-ELE-12

Enclosures

Cc:

Responded By: BSEC

Signature Date