You are on page 1of 3

SOHAR:

TEKLA STRUCTURE (TS) Connection Library

CHEVRON VERTICAL BRACE TO BEAM (EU-VTBCHb-*)

nothing to do

COLUMN 1 COLUMN 2 COLUMN 3 COLUMN 4 COLUMN 5 COLUMN 6 COLUMN 7 COLUMN 8 COLUMN 9 COLUMN 10 COLUMN 12 COLUMN 13
MAX
NUMBER OF GUSSET PL CONNECTION BUCKLING
XSTEEL ANGLE IN TEE LEG THICKNESS BRACE WELD SIZE
CONNECTION NAME BOLTS IN BOLTS THICKNESS CAPACITY LENGTH (L0)
JOINT DEGREES WIDTH (mm) mm GAUGE g (mm) W (mm)
BRACE (mm) (kN)

EU-VTBCHb-01a 60, Page 4 35 to 55 140-150 8-10 70 4 M20 A325M 10 6 300 250


EU-VTBCHb-02a 60, Page 4 35 to 55 151-175 9-11 90 4 M20 A325M 10 6 350 250
EU-VTBCHb-03a 60, Page 4 35 to 55 176-200 11-17 120 6 M20 A325M 12 6 560 250
EU-VTBCHb-04a 60, Page 4 35 to 55 201-250 12-14 140 6 M20 A325M 12 6 560 250
EU-VTBCHb-05a 60, Page 4 35 to 55 251-350 15-20 140 8 M20 A325M 14 8 750 250
EU-VTBCHb-06a 60, Page 4 35 to 55 351-400 20-24 140 10 M20 A325M 14 8 940 250

Important Notes: 1) These Connections are applicable to bracing members subjected to only Axial Load.
2) Grouping of the members is done on the basis of a fixed range of width of the connecting side for a similar shape of the sections.
3) The Connection Capacity tabulated above is for the section (among the group of members) for a profile with minimum leg size and thickness. It would definitely be higher
for other members in the same group.
4) The connection capacity is the factored axial member load as per ENV 1993-1-1:1992
5) For a member with end connection detail other than as specified and/or member force higher than the specified value in the table, the connection has to be designed
and developed as a special one.

Sohar Smelter Project Sheet 1 of 3


SOHAR:
TEKLA STRUCTURE (TS) Connection Library

VERTICAL BRACE CONNECTION @ BEAM-COLUMN FLANGE INTERFACE (EU-VTBbc-*)

nothing to do

CONNECTION
BRACE NUMBER OF NUMBER BOLTSPACE GUSSET PL WELD WELD CONNECTION Max. Buckling
XSTEEL ANGLE/ ANGLE LEG THICKNESS PL
CONNECTION NAME GAUGE BOLTS BOLTS OF BOLTS ON WSP THICKNESS SIZE SIZE CAPACITY Length Lo
JOINT SLOPE WIDTH mm THICKNESS
'g' (mm) "Nvb" "Nc" "BoltSpac" "tg"(mm) "W1" (mm) "W2" (mm) (kN) (mm)
"tc"(mm)

EU-VTBbc-01a 60, Page 4 35 to 55 140-150 8-10 70 4 M20 A325M 3 VARIES 10 10 6 6 300 250
EU-VTBbc-02a 60, Page 4 35 to 55 151-175 9-11 90 4 M20 A325M 3 VARIES 10 10 6 6 350 250
EU-VTBbc-03a 60, Page 4 35 to 55 176-200 11-17 120 6 M20 A325M 5 VARIES 12 12 6 6 560 250
EU-VTBbc-04a 60, Page 4 35 to 55 201-250 12-14 140 6 M20 A325M 5 VARIES 12 12 6 6 560 250
EU-VTBbc-05a 60, Page 4 35 to 55 251-350 15-20 140 8 M20 A325M 7 VARIES 14 14 8 8 750 250
EU-VTBbc-06a 60, Page 4 35 to 55 351-400 20-24 140 10 M20 A325M 8 VARIES 14 14 2 8 940 250

Important Notes: 1) These Connections are applicable to bracing members subjected to only Axial Load.
2) Grouping of the members is done on the basis of a fixed range of width of the connecting side for a similar shape of the sections.
3) The Connection Capacity tabulated above is for the section (among the group of members) for a profile with minimum leg size and thickness. It
would definitely be higher for other members in the same group.
4) The connection capacity is the factored axial member load as per ENV 1993-1-1:1992
5) For a member with end connection detail other than as specified and/or member force higher than the specified value in the table, the
connection has to be designed and developed as a special one.

Sohar Smelter Project Sheet 2 of 3


Connection Library

VERTICAL CHS BRACE WITH TONGUE PLATE (*CHSVTP-*)


17b

GUSSET/ MAX
MIN NUMBER OF WELD CONNECTION BUCKLING
DIA OF CHS GAUGE g NUMBER OF TONGUE PL WELD SIZE WELD SIZE W1
CONNECTION NAME THICKNESS BOLTS BOLT PITCH p (mm) LENGTH ' L' CAPACITY LENGTH (L0)
(mm) (mm) BOLT ROWS THICKNESS W (mm) (mm)
(mm) COLUMNS mm (kN) (mm)
(mm)

*CHSVTP-01a 100-124 5 M20 Grade 8.8 70 2 70 2 10 5 150 6 225 250

*CHSVTP-02a 125-149 5 M20 Grade 8.8 70 2 70 2 10 5 150 6 270 250

*CHSVTP-03a 150-169 5 M20 Grade 8.8 70 2 70 2 12 5 150 6 370 250

*CHSVTP-03b 150-169 5 M20 Grade 8.8 70 2 70 2 10 5 150 6 310 250

*CHSVTP-04a 170-199 5 M20 Grade 8.8 70 2 70 3 12 5 200 6 500 250

*CHSVTP-04b 170-199 5 M20 Grade 8.8 100 2 70 2 10 5 150 6 340 250

*CHSVTP-05a 200-239 6 M20 Grade 8.8 70 2 70 3 14 6 200 8 560 250

*CHSVTP-05b 200-239 6 M20 Grade 8.8 100 2 70 2 12 5 150 6 370 250

*CHSVTP-06a 240-299 6 M20 Grade 8.8 70 2 70 4 14 6 200 8 750 250

*CHSVTP-06b 240-299 6 M20 Grade 8.8 120 2 70 2 12 5 150 6 370 250

Important Notes: 1) These Connections are applicable to bracing members subjected to only Axial Load.
2) Grouping of the members is done on the basis of a fixed range of width of the connecting side for a similar shape of the sections.
3) The Connection Capacity tabulated above is for the section (among the group of members) for a profile with minimum dia and thickness. It would
definitely be higher for other members in the same group.
4) The connection capacity is the factored axial member load as per ENV 1993-1-1:1992
5) For a member with end connection detail other than as specified and/or member force higher than the specified value in the table, the connection has
to be designed and developed as a special one.
6) The capacities calculated are valid for S355JR ( British) and Q345B ( Chinese) grade of steel.

Sheet 3 of 3