Professional Documents
Culture Documents
Temperature
Temperature scales are a way of describing how hot a substance is. A lump of matter contains energy. There are many
forms of energy, one of them is Kinetic energy and measuring temperature is a way of measuring how furiously the
molecules contained in a lump of substance are moving about. This molecular activity causes what we perceive as the
temperature of an object. A refrigeration mechanic must be able to deal with temperatures in various scales.
Traditionally the English system has been used (Fahrenheit degrees) and a whole series of familiar capacity
measurements like Horse Power, BTU's, Tons, and PSI have been the norm. However the metric system which is
supposed to be easier to work with is encroaching in many locations. In both systems there are standard and absolute
temperature scales. Try playing with the above temperature converter. Type a value in any one of the input boxes and
click on the Convert Button. Here are several interesting values to try: -40 튔, 0 튣, 40 튔, 373 튚, 21 튏
Fahrenheit
The Fahrenheit temperature scale was developed by no less than Fahrenheit himself back in the early 1700's. It was
based on scientifically observable occurrences such as human body temperature and melting ice. Those points were
assigned arbitrary values which made sense at the time. The newly created number scale was widened for easier
reading and when boiling water was measured at 212 degrees, Fahrenheit changed the value of freezing water from 30
to 32 degrees to achieve the more attractive scale of 180 degrees between water's freezing and boiling points. There are
180 degrees in 1/2 of a circle and this was a temptation too great to resist.
Celsius
In theory the Celsius scale should be much easier to work with. It is based on calling the freezing point of water zero
and the boiling point of water 100. There are therefore 100 degrees between those 2 points. The Celsius temperature
scale is also referred to as the "Centigrade" scale. Centigrade means "consisting of or divided into 100 degrees. I
wonder what a comfortable room of 70?F would be in Celsius? If you don't happen to have a conversion calculator at
your disposal you can always rely on the following 2 formulae:
Kelvin
Scientists use the Kelvin scale, which is based on the Celsius scale, but has no negative numbers. Instead of basing it's
zero point on the freezing point of water, it bases it's zero point on Absolute Zero. which is the theoretical temperature
where all heat has been removed from a substance. Hence any amount of heat added creates a positive temperature.
Negative numbers can mess up a scientist's mathematical calculations. You will find that in refrigeration, we too must
use absolute temperature scales for some things. At Absolute Zero scientists believe that molecular motion would stop.
Rankine
Rankine is the English version of an absolute temperature scale. Add 460 degrees to Fahrenheit temperatures to obtain
the Rankine temperature. Input 0?in the Rankine box on the calculator above and you will see why.
Heat
Specific Heat
Different substances have different heat holding capabilities and thermal properties. Just
because 1 Lb. of water will change precisely through 1?F when 1 BTU is applied to it does not
necessarily mean that the same thing will happen with 1 Lb. of copper or 1 Lb. of steel or 1 Lb.
of ice cream. There is a need to be able to specify those differences and the method utilized is
to compare all substances to water. Water is given a specific heat value of 1. This means that
it that 1 BTU is required to change the temperature of 1 Lb. of water through 1?F. The specific
heat of water can also be described in the metric system. The metric specific heat of water is 1
calorie per gram per degree Celsius. This value also works out to 1. In other words it would
take 1 calorie of heat to raise the temperature of 1 gram of water through 1 degree Celsius.
Specific heat is a dimensionless quantity. It is purely a number having no unit of measurement
associated with it. In Refrigeration specific heat values are used to calculate capacity
requirements for refrigerating known quantities of product. For example one might need to be
able to select refrigeration equipment capable of cooling 5000 Lb. of beef from 55?F to -20?F.
A calculation like that must take into consideration the fact that the specific heat of a
substance usually is different above and below it's freezing point.
Latent Heat
Latent Heat is the heat given up or absorbed by a substance as it changes state. It is called
latent because it is not associated with a change in temperature. Each substance has a
characteristic latent heat of fusion, latent heat of vapourization, latent heat of condensation
and latent heat of sublimation.
Sensible Heat
Sensible Heat is associated with a temperature change, as opposed to latent heat. This is so-
called because it can be sensed by humans. If the air in a building was to be heated from 60 튔
to 70 튔 only sensible heat would be involved. However, if the air in a building was to be cooled
from 80 튔 to 70 튔 and humidity was to be removed from the air at the same time, then both
sensible and latent heats would be involved.
Insulator
Electrical wires are coated with an insulating material so electricity stays in the conductor
(wire). Thermal insulation on the other hand tries to keep heat from transferring. Thermal
insulation does not stop heat transfer, it only slows down the rate of transfer. The greater the
amount and quality of insulation, the greater the insulating effect and the slower is the
thermal transfer. There is insulation inside cooler and freezer walls and in the perimeter walls
of conditioned spaces. If fiberglass batting is being used it should be noted that the glass
fibers are actually a poor insulator. It is the tiny pockets of trapped air in-between the fibers
that actually are responsible for the insulating effect.
Conductor
The chart below shows the specific heat values of several materials. Notice the very small
specific heat value that copper has. This means it would take a mere .093 BTU to raise 1 Lb. of
copper through 1 degree. Copper has a bigger temperature change for the same heat input
compared to many other materials. Copper transfers heat readily and would not make a very
good insulator, it conducts heat too well. The smaller the specific heat number, the better of a
conductor a material is. You can see why heat transfer devices like evaporators and
condensers are made from materials like aluminum and copper.
Pressure
Pressure is what occurs when a force is applied over an area. More specifically, pressure is the
ratio of the force acting on a surface to the area of the surface. The equation for pressure
represents this rather straightforwardly; P=F/A This equation means that Pressure equals
Force divided by Area. Let's look at a couple of very simple examples. As is demonstrated in
the sketch below, the same weight can exert completely different pressures depending on how
much surface area it is spread out over. Note that when you multiply FT by Lb.s you get a unit
called FT Lb.. (pronounced Foot Pounds) This is a legitimate unit of pressure however in
refrigeration we use pounds per square inch not pounds per square foot. This is abbreviated to
PSI. Just as with temperature, pressure has many different scales that can be used and can be
described with the English system or the Metric system. The remainder of this book will be
referring to the English system of measurements. We seldom deal with gravitational forces as
shown in the diagram although it is an important concept to be aware of. Rather, we deal with
the pressures and temperatures of gases and that is what the next section is all about.
Controls
Part 1
Refrigeration systems require operating controls so they can cycle on and off to maintain a certain temperature. They
also require safety controls to stop operation if unsafe conditions occur. There are many varieties of controls.
Different types respond to temperature, pressure, humidity, liquid levels, other controls, manual intervention and
other things.
Thermostatic Control
Lets add a basic control system to a refrigeration system. First we
need to know what loads there are to be controlled. The image on
the left shows a small split system for a walk in cooler with 3
electrical devices; a compressor, condenser fan motor and
evaporator fan motor. Those 3 electrical devices are represented on
the ladder schematic shown below. This type of wiring diagram has
branch runs all shown as parallel circuits going from the left line
(L1) to the neutral line (N). They look like the rungs in a ladder
hence the name ladder schematic. The EFM (Evaporator Fan Motor)
must run all the time so that the box temperature stays uniform and
the thermostat senses the average box temperature not some pocket
of stratified air. Press the Off Cycle Button to see the circuit through
the EFM. Now Press the On Cycle Button to close the T-Stat and
call for refrigeration. The T-Stat "makes" on a rise of temperature.
Notice that the COMPR (compressor) and the CFM (Condenser Fan
Motor) both come on. A T-Stat that "makes on a rise" is a cooling T-
Stat. A T-Stat that "makes on a fall" is a heating T-Stat.
Also note that just because the wiring on the left side of the T-Stat is not coloured red when the T-Stat is open, that
does not mean there is no electricity there. There is a full electrical potential on that line and if you were to come
along an stick your finger at that point you would be shocked. The red coloured wiring indicates the logical flow
routes. Non red wires are not necessarily without voltage potential.
The graph below shows how an operating control cycles. The control is set to start
refrigeration if the box warms up to 40 튔. That's called the Cut In point. The system keeps
running until it reaches the Cut Out point which is 37 튔 where it shuts off and awaits the
next call for cooling. In this example there is a 3 degree differential between the 2 points.
The differential must be wide enough that the equipment does not short cycle. Short cycling
means to turn on and off too rapidly. Starting is hard on the equipment, so you want to keep
the number of starts per hour to a reasonable amount, not an excessive amount. The 40 튔
point is a very special temperature. It is the standard cut in point for most refrigeration
systems. Above 40 튔, bacteria growth rates in stored food increase dramatically. Below 40
튔, bacteria growth rate is subdued.
The cut out point is more of a compromise than anything else. Some products may store
better at colder temperatures but colder temperatures might adversely affect other products
in the same box. There is also a concern about keeping the evaporator from icing up. There
is no active defrost system in a standard refrigeration system. (defrost systems are only a
standard item with freezers) If you forced a refrigeration system to CI at 36 튔 and CO at 33
튔, the evaporator would be operating about 10 튔 colder than each of those points and you
would have forced the evaporator to operate in the temperature range of 26 튔 to 23 튔.
Since the freezing point of water is 32 튔, you can see that moisture in the air is going to
sublimate onto the evaporator surface and grow into thicker and thicker layers of ice. Not
only does ice act like an insulator and reduce thermal transfer, it can totally block airflow
through the evaporator fins and virtually stop thermal transfer. Some people try to push this
wall a little and it is possible to squeak out a degree or 2 colder than a 40 튔 cut in point.
However, anything more than a couple of degrees will risk icing the evaporator.
A countering force is the "off cycle defrost" effect. Since a refrigerator is designed to have a
temperature of 40 튔, the recirculating air will tend to melt ice build up on the evaporator
during the times it has it has cycled off. There are of course refrigeration systems that are
designed to operate in the 35 튔 (and colder) range. However these typically have some
form of defrost system. Systems that are designed to operate below 32 튔 are freezers and
they typically operate in temperature ranges like 0 튔, -10 튔, -15 튔 as well as much colder.
The adjustment knob on a commercial T-Stat sets the cut in point.
The differential is adjustable by setting a slider inside the enclosure.
Thermostatic controls are manufactured with an wide range of
variations. They have fixed differentials, adjustable differentials,
different operating ranges and various accuracy 뭩 , various
electrical load ratings, different types of sensors, electro-mechanical,
electronic etc.
The sensing bulb of the control should be mounted so that it senses the evaporator inlet air. During the off cycle the
constant fan recirculates the air in the box. The temperature of the air becomes an average of the product
temperature, the wall temperature, any infiltrated air and any other loads such as caused by a person entering the
box. When the air temperature reaches the cut in point of the control it brings on refrigeration.
When refrigeration is operating, 40 튔 air passes through the evaporator and drops in
temperature several degrees. That's why the sensor can not be placed in or near the
discharge air stream. If it was placed there, the control would think that the whole box was
cold and shut off the system as soon as it started. It is the average box temperature that
should be monitored, not the discharge air temperature.
Some thermostatic controls are designed with a capillary line temperature sensor which is
intended to be inserted between the evaporator fins on units that have a tendency to ice up.
An example might be a commercial cooler in a hot environment which is constantly being
accessed. That type of control forces an off cycle defrost at the end of each run cycle. The
control will remain open until the evaporator has reached a temperature which indicates
that any frost accumulated during the previous run cycle has been melted. This type of
control is used in appliances like beverage coolers. Adjusting the knob on this type of control
changes only the Cut Out setting, the Cut In setting remains fixed. They are known as a
Constant Cut In Control and also as a beverage cooler control.
Controls
Part 2
Cut In and Cut Out set points can be adjusted by screws on the top
of an LPC. Some LPC's provide Cut In and Differential adjustment
screws instead. The sensing line of the control must sense constant
low side pressure and the evap fan must be left running
continuously. The recirculating air imposes a load on the evaporator
which is sensed by the LPC.
Operating and Safety Controls
A Pressure control can also be used as a safety control. The electrical circuitry shown below has two controls in
series. Therefore, if the LPC trips, the compressor will not run even if the T-Stat is calling. The LPC in this example
is set to protect the system from a loss of refrigerant charge and is set to cut out at a pressure that is lower than
anticipated operating low side pressure. The compressor should not be allowed to operate with an undercharge as the
windings can overheat and other types of damage can occur as well. Unless there is a loss of charge the LPC will
therefore remain permanently closed during all off cycles and run cycles. The LPC's contacts are therefore said to be
normally closed (NC). Small leaks cause a gradual loss of refrigerant and a LPC might only trip once in a while
during the initial stages of a refrigerant leak. As time passes the safety will trip more and more often and can
eventually get to the point where the system will only run for a few seconds before cutting out. After a short time the
high and low side pressures will equalize and the system will try starting once again. This is called short cycling. It's
not good for the system but is certainly better than letting the compressor destroy itself by operating indefinitely
with an undercharge or no refrigerant.
More safety controls can be added such as a High Pressure Control. If high head pressure
occurs for any reason the switch will open protecting the compressor. Controls can be
automatic reset or manual reset. If the manual reset type trips, a little button pops out and
the unit will not restart until the button is manually reset. This is to force attention to the
fact that there has been a safety trip.
An LPC and a HPC are available in a single unit called a
dual pressure control. It's easy to recognize the low
pressure capillary at a glance because it ties into a larger
bellows assembly. The low pressure gas needs a larger
bellows area to activate the linkage whereas the high
pressure side exerts more force and can function
properly with a smaller
Note that the suction gauge decreases in pressure which is to be expected. However, do you know why the high side
pressure did not increase when the system is pumped down? The amount of refrigerant in the high side increased but
the pressure does not because of what you have learned about the PT relationship of refrigerants. When there are
saturated conditions the pressure will correspond to the pressure that the PT Chart predicts regardless of the quantity
of liquid refrigerant.
The schematic below depicts a simple pump down system. Press the "Off Cycle" Button and
note that the evap fans are running constantly. The T-Stat is the operating control but does
not directly control the compressor. Press "T-Stat On" and see that it allows a circuit to the
LLSV. When the LLSV is energized it allows refrigerant flow from the high side to the low
side. When the low side pressure builds to the cut in point of the LPC, the Compressor and
condenser fans come on. (Press LPC on) The system operates until the T-Stat is satisfied.
Press "T-Stat Off" and note that the LLSV is de-energized but the compressor is still
operating. It will run until the cut out point of the LPC is reached and that has been set at 1
PSI. In other words, the low side of the system will pump down to just a slight positive
pressure at the end of every run cycle. Press "Off Cycle" to simulate the end of the pump
down. The next time the T-Stat calls the sequence repeats.
Relays
It demonstrated how a relay can be held in by it's own contacts. It also demonstrated how
complex functionality can be accomplished with a small number of controls.
Contactors
A contactor is like a large relay. Relays are generally used for
switching light loads like control circuitry and relatively small
motors. Contactors are used for bringing larger loads online like
compressors and large motors. Contactors can have 1,2,3 or 4 sets of
contacts. Contactors have NO contacts but can also have auxillary
contacts which can be NO or NC.
Sometimes a manufacturer designs in a lock out circuit to protect the equipment. They group a particularly important
bunch of safety controls in series and surround the group with a lock out circuit. If any safety control within the group
opens, the compressor stops and will not restart even if the safety control resets. Press the Normal button. Note how ther
no electrical flow through the LO (Lock Out) coil even though it looks like there should be. That's because the LO coil i
high impedance coil (high resistance) and the electricity takes the route of least resistance through all the closed safety
controls. However if any of the controls in the group open the electricity has no choice than to flow through the LO coil
Press the Lock Out button and see this happen when the HPC opens. The LO coil becomes energized and it's NC contac
open. This forces the LO coil to remain energized which stops electrical flow to the group of safety controls permanentl
So even if the HPC was to reset the compressor would still be held off by the open LO contact which disallows a circuit
the compressor contactor (CC).
A lock out forces attention to a problem situation rather than allowing the equipment to cycle
indefinitely on a safety control and perhaps go unnoticed until damage occurs. Interrupting the
power will reset the lock out if the safeties are reset. However, if all the controls in a lock out
group have reset it is not possible to tell which one caused the lock out. An inspection of the
equipment may reveal the cause. For example a dirty condenser might indicate that the HPC ha
tripped and reset after the high pressure condition subsided (while the system was off).
If there are no visible indications there is a trick that can be used to determine which control is
opening. Wire a very small capacity fuse (1/100 AMP) in parallel with each of the safety controls
As long as nothing trips the electricity will once again take the route of least resistance through
the series of closed safety controls. However as soon as one of them opens, the electricity will
attempt to flow around the open control through the fuse which will blow instantly due to it's
extremely small rating. The next time the equipment is inspected it will not matter if all of the
safeties in the lock out group have reset. The fuses can be Ohmed out and the one that is blown
will indicate which safety opened.
[The CD-ROM controls section carries on with transformers, oil failure controls,
humidistats, defrost timers, fan delay stats, termination stats, bi-metal controls
and low voltage controls]