𝐾𝑔
• Resistencia a la compresión del concreto del pilote 𝑓 ′ 𝑐 = 350 𝑐𝑚2
𝐾𝑔
• Resistencia a la compresión del concreto del cabezal 𝑓 ′ 𝑐 = 280 𝑐𝑚2
• El pilote tendrá un diámetro de 40cm
• 𝑃𝐶𝑃 = 8 𝑡𝑜𝑛
• 𝑃𝐶𝑉 = 6 𝑡𝑜𝑛
• 𝑀𝐶𝑃 = 2 𝑡𝑜𝑛 𝑚
• 𝑀𝐶𝑉 = 3 𝑡𝑜𝑛 𝑚
• El momento será absorbido por los pilotes.
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
ESTRATIGRAFIA
1. Corrección de 𝑵𝒔𝒑𝒕
𝑁60 (1𝑚) ≅ 0.7 (12) = 8.4 ≅ 8 𝑁60 (6𝑚) ≅ 0.7 (15) = 10.5 ≅ 11
𝑁60 (2𝑚) ≅ 0.7 (12) = 8.4 ≅ 8 𝑁60 (7𝑚) ≅ 0.7 (22) = 15.4 ≅ 15
𝑁60 (3𝑚) ≅ 0.7 (13) = 9.1 = 9 𝑁60 (8𝑚) ≅ 0.7 (24) = 16.8 ≅ 17
𝑁60 (4𝑚) ≅ 0.7 (13) = 9.1 = 9 𝑁60 (9𝑚) ≅ 0.7 (25) = 17.5 ≅ 18
𝑁60 (5𝑚) ≅ 0.7 (14) = 9.8 ≅ 10 𝑁60 (10𝑚) ≅ 0.7 (27) = 18.9 ≅ 19
0.5
1
𝐶𝑁 = � �
𝜎′
� 0�
𝑝𝑎
Factores de corrección
0.5 0.5
1 1
𝐶𝑁 (1𝑚) = � 𝜎 ′
� =� 1 � = 3.16
� 0 � � �
10
𝑝𝑎
(𝑁1 )60 (1𝑚) = 8 × 3.16 = 25.28 ≅ 25 (𝑁1 )60 (6𝑚) = 11 × 1.29 = 14.19 ≅ 14
(𝑁1 )60 (2𝑚) = 8 × 2.24 = 17.92 ≅ 18 (𝑁1 )60 (7𝑚) = 15 × 1.19 = 17.85 ≅ 18
(𝑁1 )60 (3𝑚) = 9 × 1.83 = 16.47 ≅ 16 (𝑁1 )60 (8𝑚) = 17 × 1.11 = 18.87 ≅ 19
(𝑁1 )60 (4𝑚) = 9 × 1.58 = 14.22 ≅ 14 (𝑁1 )60 (9𝑚) = 18 × 1.04 = 18.72 ≅ 19
(𝑁1 )60 (5𝑚) = 10 × 1.41 = 13.29 ≅ 14 (𝑁1 )60 (10𝑚) = 19 × 0.99 = 18.81 ≅ 19
CARGAS
𝑘𝑔
Con una resistencia cilíndrica del concreto para el pilote de 𝑓′𝑐 = 350 𝑐𝑚2 , y
Carga axial
Utilizando la combinación 1 y 2
Momento
Utilizando la combinación 1 y 2
Como el momento será absorbido por los pilotes, se debe tomar en cuenta
la transmisión del mismo, al colocar dos o más pilotes el momento se
descomponen en pares de fuerzas, las cuales actuaran sobre los pilotes como
cargas axiales equivalentes.
Cabezal de 2 pilotes
2.2.2 Separación
𝑃𝑠𝑒𝑟𝑣 𝑀𝑠𝑒𝑟𝑣
𝑄𝑎𝑐𝑡 (1𝑝𝑖𝑙𝑜𝑡𝑒) = +
2 𝑆𝑒𝑝𝑎𝑟𝑎𝑐𝑖𝑜𝑛
𝑝𝑖𝑙𝑜𝑡𝑒𝑠
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
14 𝑡𝑜𝑛 5 𝑡𝑜𝑛
𝑄𝑎𝑐𝑡 (1𝑝𝑖𝑙𝑜𝑡𝑒) = + = 12 𝑡𝑜𝑛
2 1
3. Chequeo
DISEÑO GEOTECNICO
𝐿 = 6𝑚 + 𝑑𝑐
∅
𝑑𝑐 = 4𝐷 + tan(45° + )
2
33°
𝑑𝑐 = 4(0.4 𝑚) tan �45° + � = 2.95 ≅ 3 𝑚
2
𝑄𝑝 = 𝐴𝑝 𝑞𝑝 = 𝐴𝑝 𝑞′𝑁𝑞∗
Dónde:
𝑸𝒑 = 𝟑𝟗. 𝟏𝟕 𝒕𝒐𝒏
𝑄𝑠 = � 𝑝𝛥𝐿𝑓
Al ser arena el suelo que esta alrededor del fuste del pilote, la capacidad
por fricción se calcula de la siguiente forma:
Dónde:
𝑡𝑜𝑛 𝑡𝑜𝑛
[0]+�2 3 (6 𝑚)−1 3 (6 𝑚)� 𝑡𝑜𝑛
����0 =
𝜎′ 𝑚 𝑚
= 3 𝑚2
2
𝛿 ′ = 0.8𝜙 ′
𝛿 ′ = 0.8(32°) = 25.6°
𝑝 = 𝜋𝐷
𝑝 = 𝜋(0.4) = 1.26 𝑚
𝑡𝑜𝑛
𝑄𝑠 = �(0.85) �3 𝑚2 � tan 25.6°� (1.26 )(6 𝑚) = 9.17 𝑡𝑜𝑛
𝑸𝒔 = 𝟗. 𝟏𝟕 𝒕𝒐𝒏
3. Capacidad ultima
𝑄𝑢 = 𝑄𝑝 + 𝑄𝑠
𝑸𝒖 = 𝟒𝟖. 𝟑𝟒 𝒕𝒐𝒏
𝑄𝑢
𝑄𝑝𝑒𝑟𝑚 =
𝐹𝑆
48.34
𝑄𝑝𝑒𝑟𝑚 = = 16.11 𝑡𝑜𝑛
3
GRUPO DE PILOTES
1. Chequeo de eficiencia
• Converse-Labarre
Dónde:
Por lo tanto:
𝑛1 = 2
𝑛2 = 1
𝐷 = 0.4 m
𝑑=1m
𝐷 0.4
𝜃 = 𝑡𝑎𝑛−1 �𝑑 � = 𝑡𝑎𝑛−1 � 1 � = 21.8° = 0.38
(2 − 1)1 + 0
𝜂 =1−� � 0.38 = 0.9979 ≈ 1
90 × 1 × 2
𝐷
𝜂 =1− �𝑛 (𝑛 − 1) + 𝑛2 (𝑛1 − 1) + √2(𝑛1 − 1)(𝑛2 − 1)�
𝜋𝑑𝑛1 𝑛2 1 2
0.4
𝜂 =1− [0 + 1(2 − 1) + 0] = 0.9363 ≈ 1
𝜋×1×2×1
𝑄𝑢 = 48.34 𝑡𝑜𝑛
�𝑄𝑤𝑝 + 𝜉𝑄𝑤𝑠 �𝐿
𝑆𝑒 (1) =
𝐴𝑝 𝐸𝑝
𝑘𝑔
𝐸𝑝 = 15100�𝑓′𝑐 = 15100√350 = 282495.13 = 2824951.33 𝑡𝑜𝑛/𝑚²
𝑐𝑚2
𝑺𝒆 (𝟏) = 𝟎. 𝟎𝟐𝟖 𝒄𝒎
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
2.3 Asentamiento del pilote causado por la carga en la punta del pilote
𝑺𝒆(𝟐)
𝑞𝑤𝑝 𝐷
𝑆𝑒 (2) = (1 − 𝜇𝑠 2 )𝐼𝑤𝑝
𝐸𝑠
𝑡𝑜𝑛 𝑡𝑜𝑛
𝐸𝑠 =∝ 𝑁60 𝑝𝑟𝑜𝑚 𝑃𝑎 = 10 × 19 × 10 2
= 1900 2
𝑚 𝑚
Dónde:
𝑁60 𝑝𝑟𝑜𝑚 = 19
𝑡𝑜𝑛
𝑃𝑎 = 10 𝑚2
𝜙 ′ − 25 33 − 25
𝜇𝑠 = 0.1 + 0.3 � � = 0.1 + 0.3 � � = 0.22
20 20
𝐼𝑤𝑝 = 0.85
77.349 × 0.4
𝑆𝑒 (2) = (1 − 0.222 )0.85 = 0.0137 𝑚 = 1.317 𝑐𝑚
1900
𝑺𝒆 (𝟐) = 𝟏. 𝟑𝟏𝟕 𝒄𝒎
2.4 Asentamiento del pilote causado por la carga transmitida a lo largo del
fuste del pilote 𝑺𝒆(𝟑)
𝑄𝑤𝑠 𝐷
𝑆𝑒 (3) = � � (1 − 𝜇𝑠 2 )𝐼𝑤𝑠
𝑝𝐿 𝐸𝑠
𝑝 = 𝜋(0.4) = 1.26 𝑚
𝑡𝑜𝑛 𝑡𝑜𝑛
𝐸𝑠 =∝ 𝑁60 𝑝𝑟𝑜𝑚 𝑃𝑎 = 10 × 18 × 10 = 1700
𝑚2 𝑚2
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
Dónde:
𝑁60 𝑝𝑟𝑜𝑚 = 17
𝑡𝑜𝑛
𝑃𝑎 = 10 𝑚2
𝜙 ′ − 25 32 − 25
𝜇𝑠 = 0.1 + 0.3 � � = 0.1 + 0.3 � � = 0.205
20 20
𝐿 9
𝐼𝑤𝑠 = 2 + 0.35� = 2 + 0.35� = 3.66
𝐷 0.4
2.28 0.4
𝑆𝑒 (3) = � � (1 − 0.2052 )3.66 = 0.00017 ≅ 0.017 𝑐𝑚
1.26 × 9 1700
𝑺𝒆 (𝟑) = 𝟎. 𝟎𝟏𝟕 𝒄𝒎
𝐵𝑔
𝑆𝑔 = � 𝑆𝑒
(𝑒) 𝐷
Dónde:
1.6
𝑆𝑔 =� × 1.362 = 2.72 𝑐𝑚
(𝑒) 0.4
𝑺𝒈 = 𝟐. 𝟕𝟐 𝒄𝒎
(𝒆)
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
DISEÑO ESTRUCTURAL
1. Acero de refuerzo longitudinal
1.1 Obtención de la cuantía geométrica
1.1.1 Pilotes que trabajan a comprensión pura
Como sobre los pilotes solo actúan cargas axiales el acero requerido se
obtiene a partir de la cuantía mínima (Criterio FEMA 450, 750 y ACI:543):
𝜌 = 0.005
𝐴𝑆𝐿 = 0.005𝐴𝑔
𝜋(40)2
𝐴𝑠𝐿 = 0.005 × = 6.28 𝑐𝑚2
4
𝐴𝑆𝐿
𝑁° 𝐵𝑎𝑟𝑟𝑎𝑠 =
Á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑏𝑎𝑟𝑟𝑎
𝐴𝑆𝐿 6.28
𝑁° 𝐵𝑎𝑟𝑟𝑎𝑠 = = = 2.20 ≅ 3 𝑏𝑎𝑟𝑟𝑎𝑠
Á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑏𝑎𝑟𝑟𝑎 2.85
• 4 𝑐𝑚
• 2.54 𝑐𝑚
𝑅𝑒𝑐𝑢𝑏 = 7.5 𝑐𝑚
Ahora las barras serán colocadas a una separación centro a centro de:
La zona de confinamiento será de 3D = 3 × 0.4 = 1.2 m por debajo del fondo del
cabezal.
4𝑎𝑠 (𝐷𝑐 − 𝑑𝑏 )
𝜌𝑠 =
𝑠𝐷𝑐2
4 × 0.712(25 − 0.95)
𝜌𝑠 = = 0.01
10(25)2
Dónde:
𝐷𝑐 = 𝐷 − 2 × 𝑟𝑒𝑐𝑢𝑏 = 40 − 2 × 7.5 = 25 𝑐𝑚
f′c Ag 1.4P
ρs = 0.25 � �� − 1� �0.5 + �
fyh Ach f′c Ag
π × 40²
350 4 1.4 × 16.8 × 1000
= 0.25 � �� − 1� �0.5 + � = 0.01
4200 π × (25)² π × 40²
350 ×
4 4
Dónde:
𝑃𝑢 𝑀𝑢 19.2 7.2
𝑃= + = + = 16.8 𝑡𝑜𝑛
2 𝑆𝑒𝑝𝑎𝑟𝑎𝑐𝑖𝑜𝑛 2 1
𝑝𝑖𝑙𝑜𝑡𝑒𝑠
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝐿𝑦 = 𝐷 + 0.20
𝐿𝑥 = 𝑆 + 𝐷 + 0.20
0.24 + 0.6
𝑑= = 0.42 ≅ 0.45 𝑚
2
𝑳𝒚 = 𝟔𝟎 𝒄𝒎
𝑳𝒙 = 𝟏𝟔𝟎 𝒄𝒎
𝒅= 𝟒𝟓 𝒄𝒎
𝒉= 𝟓𝟓 𝒄𝒎
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝑃𝑢 𝑀𝑢
𝑃𝑢𝑒 = 2 � + �
2 𝑆
19.2 7.2
𝑃𝑢𝑒 = 2 � + � = 33.6 𝑡𝑜𝑛
2 1
𝑃𝑢𝑒 𝑆
𝑇𝑥 =
4𝑑
33.6(1)
𝑇𝑥 = = 18.67 𝑡𝑜𝑛
4(0.45)
4. Diseño estructural
𝑇𝑥
𝐴𝑠 =
𝜑 𝑓𝑦
18.67 × 1000
𝐴𝑠 = = 5.93 𝑐𝑚2
0.75(4200)
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
Se debe comprobar que esta sea mayor que el acero mínimo requerido
para el cabezal
𝐴𝑆 𝑚𝑖𝑛 = 𝜌𝑏ℎ
• Dirección en x
• Dirección en y
• Dirección en x
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎
𝐴𝑠 𝑥
60 − 2 × 7.5
𝑆𝑒𝑝 = × 1.27 = 9.62 𝑐𝑚 ≅ 9 𝑐𝑚
5.94
• 𝑑𝑏 = 1.27 𝑐𝑚
• 2.5 𝑐𝑚
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑁𝑐𝑎𝑏 =
𝑆𝑒𝑝
60 − 2 × 7.5
𝑁𝑐𝑎𝑏 = = 5 𝑏𝑎𝑟𝑟𝑎𝑠
9
• Dirección en y
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎
𝐴𝑠 𝑦
160 − 2 × 7.5
𝑆𝑒𝑝 = × 1.27 = 11.63 𝑐𝑚 ≅ 11 𝑐𝑚
15.84
• 𝑑𝑏 = 1.27 𝑐𝑚
• 2.5 𝑐𝑚
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑁𝑐𝑎𝑏 =
𝑆𝑒𝑝
160 − 2 × 7.5
𝑁𝑐𝑎𝑏 = = 13.18 ≅ 14 𝑏𝑎𝑟𝑟𝑎𝑠
11
• Dirección en x
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎
𝐴𝑠 𝑥
60 − 2 × 7.5
𝑆𝑒𝑝 = × 1.27 = 9.62 𝑐𝑚 ≅ 9 𝑐𝑚
5.94
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑁𝑐𝑎𝑏 =
𝑆𝑒𝑝
60 − 2 × 7.5
𝑁𝑐𝑎𝑏 = = 5 𝑏𝑎𝑟𝑟𝑎𝑠
9
• Dirección en y
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎
𝐴𝑠 𝑦
160 − 2 × 7.5
𝑆𝑒𝑝 = × 1.27 = 11.63 𝑐𝑚 ≅ 11 𝑐𝑚
15.84
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑁𝑐𝑎𝑏 =
𝑆𝑒𝑝
160 − 2 × 7.5
𝑁𝑐𝑎𝑏 = = 13.18 ≅ 14 𝑏𝑎𝑟𝑟𝑎𝑠
11
6. Punzonado
6.1.1 Resistencia
αs = 40
0.5
𝛽𝑐 = =1
0.5
2 2
a. 𝑉c = 0.53 �1 + 𝛽𝑐
� 𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.53 × �1 + 1� × 1 × √280 × 380 × 45
αs d 40×45
b. 𝑉c = 0.27 �2+ bo
� 𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.27 �2 + 380
� × 1 × √280 × 380 × 45
𝑉𝑐 𝑐 = 314.75 𝑡𝑜𝑛
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
6.1.3 Chequeo
6.2.1 Resistencia
𝑑 0.4 0.45
𝑏𝑜 = 2𝜋 �𝑟 + � = 2𝜋 × � + � = 2.67 𝑚
2 2 2
2 2
a. 𝑉c = 0.53 �1 + 𝛽𝑐
� 𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.53 × �1 + 1� × 1 × √280 × 267 × 45
αs d 40×45
b. 𝑉c = 0.27 �2+ bo
� 𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.27 �2 + 267
� × 1 × √280 × 267 × 45
𝑉𝑐 𝑝 = 221.18 𝑡𝑜𝑛
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝑃𝑢𝑒 33.6
𝑉𝑢 𝑝 = = = 16.8 𝑡𝑜𝑛
𝑛 2
Dónde:
6.2.3 Chequeo
𝑉𝑢 𝑝 < 𝜑𝑉𝑐 𝑝
7. Aplastamiento
𝐴2 = (𝐷 + 0.20)2
𝐹𝐴 𝑐𝑜𝑙𝑢𝑚𝑛𝑎 = 𝜑(0.85𝑓 ′ 𝑐 𝐴1 )
𝐴2
𝐹𝐴 𝑐𝑎𝑏𝑒𝑧𝑎𝑙 = 𝜑�0.85𝑓 ′ 𝑐 𝐴1 �� ≤ 2𝜑�0.85𝑓 ′ 𝑐 𝐴1 �
𝐴1
3600
𝐹𝐴 𝑐𝑎𝑏𝑒𝑧𝑎𝑙 = 0.65 × 0.85 × 280 × 2500 × � ≤ 2 × 0.65 × 0.85 × 280 × 2500
2500
= 464100 𝐾𝑔 ≤ 773500 𝐾𝑔
7.5 Chequeo
𝑃𝑢𝑒 = 33600 𝐾𝑔
𝑃𝑢 ≤ 386750 𝐾𝑔
𝑃𝑢 ≤ 464100 𝐾𝑔
Zona No Confinada.
Espirales 3/8” cada 20 cm.
𝐾𝑔
• Resistencia a la compresión del concreto del pilote 𝑓 ′ 𝑐 = 350 𝑐𝑚2
𝐾𝑔
• Resistencia a la compresión del concreto del cabezal 𝑓 ′ 𝑐 = 280 𝑐𝑚2
• Diámetro del pilote 40 cm
• 𝑃𝐶𝑃 = 15 𝑡𝑜𝑛
• 𝑃𝐶𝑉 = 20 𝑡𝑜𝑛
• 𝑀𝐶𝑃 = 5 𝑡𝑜𝑛 − 𝑚
• 𝑀𝐶𝑉 = 2.5 𝑡𝑜𝑛 − 𝑚
• El momento será absorbido por las vigas de riostra.
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
ESTRATIGRAFÍA
𝑁𝑝𝑟𝑜𝑚 (𝐶𝐿) = 11
CARGAS
𝑄𝑛𝑜𝑚 = 𝛼 𝑓 ′ 𝑐 𝐴𝑝
Tomando a 𝛼 = 0.65
Carga axial
Utilizando la combinación 1 y 2
3. Chequeo
DISEÑO GEOTECNICO
𝐿 = 6𝑚 + 𝑑𝑐
∅
𝑑𝑐 = 4𝐷 + tan(45° + )
2
0°
𝑑𝑐 = 4(0.4 𝑚) tan �45° + � = 1.50 𝑚
2
Por lo tanto, el pilote tendrá una longitud total igual a 7.50 metros.
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝑄𝑝 ≈ 𝑁𝑐∗ 𝑐𝑢 𝐴𝑝 = 9𝑐𝑢 𝐴𝑝
𝑸𝒑 = 𝟓. 𝟒𝟕 𝒕𝒐𝒏
𝑄𝑎𝑑ℎ = 𝑝𝛥𝐿𝑓
En este caso como al rededor del fuste hay arcilla, se aplica el método 𝛼,
que indica lo siguiente:
𝑓 = 𝛼𝐶𝑢
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
Dónde:
𝜎′ 0.45
�����
𝛼 = 𝐶 � 𝐶 0�
𝑢
𝐶 = 0.5
𝑡𝑜𝑛
[0]+�1.70 3 (6 𝑚)−(6 𝑚)� 𝑡𝑜𝑛
����0 =
𝜎′ 𝑚
= 2.1 𝑚2
2
𝑡𝑜𝑛 0.45
2.1
𝛼 = 0.5 � 𝑚2 � = 0.45
𝑡𝑜𝑛
2.64 2
𝑚
Por lo tanto:
𝑡𝑜𝑛
𝑄𝑎𝑑ℎ = [𝜋(0.4 𝑚)](6 𝑚) �0.45 �2.64 �� = 8.96 𝑡𝑜𝑛
𝑚2
𝑸𝒂𝒅𝒉 = 𝟖. 𝟗𝟔 𝒕𝒐𝒏
3. Capacidad última, 𝑸𝒖
𝑄𝑢 = 𝑄𝑝 + 𝑄𝑎𝑑ℎ
𝑸𝒖 = 𝟏𝟒. 𝟒𝟑 𝒕𝒐𝒏
𝑄𝑢
𝑄𝑝𝑒𝑟𝑚 =
𝐹𝑆
14.43 𝑡𝑜𝑛
𝑄𝑝𝑒𝑟𝑚 = = 4.81 𝑡𝑜𝑛
3
1.1𝑄𝑠𝑒𝑟𝑣 1.1 × 25
𝑛 𝑝𝑖𝑙𝑜𝑡𝑒𝑠 = = = 5.72 → 6 𝑝𝑖𝑙𝑜𝑡𝑒𝑠
𝑄𝑝𝑒𝑟𝑚 4.81
DISEÑO ESTRUCTURAL
Como sobre los pilotes solo actúan cargas axiales el acero requerido se
obtiene a partir de la cuantía mínima (Criterio FEMA 450, 750 y ACI:543):
𝜌 = 0.005
𝐴𝑆𝐿 = 0.005𝐴𝑔
𝜋(40)2
𝐴𝑆𝐿 = 0.005 � � = 6.28 𝑐𝑚2
4
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝐴𝑆𝐿
𝑁° 𝐵𝑎𝑟𝑟𝑎𝑠 =
Á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑏𝑎𝑟𝑟𝑎
𝐴𝑆𝐿 6.28
𝑁° 𝐵𝑎𝑟𝑟𝑎𝑠 = = = 3.18 ≅ 4 𝑏𝑎𝑟𝑟𝑎𝑠
Á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑏𝑎𝑟𝑟𝑎 1.98
• 4 𝑐𝑚
• 2.54 𝑐𝑚
𝑅𝑒𝑐𝑢𝑏 = 7.5 𝑐𝑚
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
Ahora las barras serán colocadas a una separación centro a centro de:
La zona de confinamiento será de: 7𝐷 = 7 × 0.4 = 2.8 m por debajo del fondo
del cabezal, por tratarse de un suelo cohesivo blando (Criterio FEMA 450).
4𝑎𝑠 (𝐷𝑐 − 𝑑𝑏 )
𝜌𝑠 =
𝑠𝐷𝑐2
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
4𝑎𝑠 (𝐷𝑐 − 𝑑𝑏 )
𝜌𝑠 =
𝑠𝐷𝑐2
4 × 0.712(25 − 0.712)
𝜌𝑠 = = 0.01
10(25)2
𝑓′𝑐 𝐴𝑔 1.4𝑃
𝜌𝑠 = 0.25 � �� − 1� �0.5 + �
𝑓𝑦ℎ 𝐴𝑐ℎ 𝑓′𝑐 𝐴𝑔
π × 40²
350 4 1.4 × 6 × 1000
= 0.25 � �� − 1� �0.5 + � = 0.016
4200 π × (25)² π × 40²
350 ×
4 4
Dónde:
𝑃𝑢 36
𝑃= = = 6 𝑡𝑜𝑛
𝑛 6
𝐿𝑦 = 𝑆 + 𝐷 + 0.20
𝐿𝑥 = 2𝑆 + 𝐷 + 0.20
𝑑 ≥ 0.52 𝑆
𝑑 ≥ 0.52(1) = 0.52 𝑚
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝑑 ≥ 1.33𝑆
𝑑 = 0.925 ≅ 0.95
𝑳𝒚 = 𝟏𝟔𝟎 𝒄𝒎
𝑳𝒙 = 𝟐𝟔𝟎 𝒄𝒎
𝒅= 𝟗𝟓 𝒄𝒎
𝒉= 𝟏𝟎𝟓 𝒄𝒎
𝑷𝒖𝒆 = 𝟑𝟔 𝒕𝒐𝒏
𝑃𝑢𝑒 𝑆
𝑇𝑥 =
3𝑑
36(1)
𝑇𝑥 = = 12. 63 𝑡𝑜𝑛
3(0.95)
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝑃𝑢𝑒 𝑆
𝑇𝑦 =
4𝑑
36(1)
𝑇𝑦 = = 9.47 𝑡𝑜𝑛
4(0.95)
4. Diseño estructural
𝑇𝑥
𝐴𝑠𝑥 =
𝜑 𝑓𝑦
12.63 × 1000
𝐴𝑠𝑥 = = 4.01 𝑐𝑚2
0.75(4200)
𝑇𝑦
𝐴𝑠𝑦 =
𝜑 𝑓𝑦
9.47 × 1000
𝐴𝑠𝑦 = = 3.01 𝑐𝑚2
0.75(4200)
Se debe comprobar que esta sea mayor que el acero mínimo requerido
para el cabezal
𝐴𝑆 𝑚𝑖𝑛 = 𝜌𝑏ℎ
• Dirección en x
• Dirección en y
• Dirección en x
𝐴𝑠 𝑥 < 𝐴𝑆 min 𝑥
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎
𝐴𝑠 𝑥
260 − 2 × 7.5
𝑆𝑒𝑝 = × 2.85 = 14.2 ≅ 14 𝑐𝑚
49.14
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑁𝑐𝑎𝑏 =
𝑆𝑒𝑝
260 − 2 × 7.5
𝑁𝑐𝑎𝑏 = = 17.5 ≅ 18 𝑏𝑎𝑟𝑟𝑎𝑠
14
• Dirección en y
𝐴𝑠 𝑥 < 𝐴𝑆 min 𝑦
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎
𝐴𝑠 𝑥
160 − 2 × 7.5
𝑆𝑒𝑝 = × 2.85 = 13.66 ≅ 13 𝑐𝑚
30.24
𝑏 − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑁𝑐𝑎𝑏 =
𝑆𝑒𝑝
160 − 2 × 7.5
𝑁𝑐𝑎𝑏 = = 11.16 ≅ 12 𝑏𝑎𝑟𝑟𝑎𝑠
13
Como ℎ > 60 𝑐𝑚, se debe colocar un 10% de 𝐴𝑠 𝑝𝑟𝑜𝑝 como acero lateral.
8.55
𝐴𝑠 𝑙𝑎𝑡𝑒𝑟𝑎𝑙 1 𝑐𝑎𝑟𝑎 = = 4.275 𝑐𝑚2
2
ℎ − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎
𝐴𝑠 𝑙𝑎𝑡𝑒𝑟𝑎𝑙 1 𝑐𝑎𝑟𝑎
105 − (2 × 10)
𝑆𝑒𝑝 = × 1.98 = 39.36 ≅ 39 𝑐𝑚
4.275
ℎ − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑁𝑐𝑎𝑏 =
𝑆𝑒𝑝
105 − (2 × 10)
𝑁𝑐𝑎𝑏 = = 2.16 𝑏𝑎𝑟𝑟𝑎𝑠
39
6. Punzonado
6.1.1 Resistencia
αs = 40
0.7
𝛽𝑐 = =1
0.7
2 2
a. 𝑉c = 0.53 �1 + �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.53 × �1 + 1� × 1 × √280 × 660 × 95
𝛽𝑐
αs d 40×84.5
b. 𝑉c = 0.27 �2+ �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.27 �2 + �× 1 × √280 × 660 × 95
bo 618
𝑉𝑐 𝑐 = 1154.09 𝑡𝑜𝑛
𝑉𝑢𝑐 = 𝑃𝑢 = 36 𝑡𝑜𝑛
6.1.3 Chequeo
6.2.1 Resistencia
𝑑 0.40 0.95
𝑏𝑜 = 2𝜋 �𝑟 + � = 2𝜋 × � + � = 5.03 𝑚
2 2 2
2 2
a. 𝑉c = 0.53 �1 + �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.53 × �1 + 1� × 1 × √280 × 503 × 95
𝛽𝑐
αs d 40×84.5
b. 𝑉c = 0.27 �2+ �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.27 �2 + �× 1 × √280 × 503 × 95
bo 470
𝑉𝑐 𝑝 = 879.56 𝑡𝑜𝑛
𝑃𝑢 36
𝑉𝑢 𝑝 = = = 6 𝑡𝑜𝑛
𝑛 6
Dónde:
6.2.3 Chequeo
𝑉𝑢 𝑝 < 𝜑𝑉𝑐 𝑝
7. Aplastamiento
2
𝐴2 = �√3 𝑆�
2
𝐴2 = �√3 × 1� = 3 𝑚2
𝐹𝐴 𝑐𝑜𝑙𝑢𝑚𝑛𝑎 = 𝜑(0.85𝑓 ′ 𝑐 𝐴1 )
𝐴2
𝐹𝐴 𝑐𝑎𝑏𝑒𝑧𝑎𝑙 = 𝜑�0.85𝑓 ′ 𝑐 𝐴1 �� ≤ 2𝜑�0.85𝑓 ′ 𝑐 𝐴1 �
𝐴1
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
30000
𝐹𝐴 𝑐𝑎𝑏𝑒𝑧𝑎𝑙 = 0.65 × 0.85 × 280 × 4900 × � ≤ 2 × 0.65 × 0.85 × 280 × 4900
4900
7.5 Chequeo
𝑃𝑢𝑒 = 36000 𝐾𝑔
𝑃𝑢 ≤ 758030 𝐾𝑔
𝑃𝑢 ≤ 1516060 𝐾𝑔
Zona No Confinada.
Espirales 3/8” cada 20 cm.
ESTRATIGRAFÍA
1. Corrección de 𝑵𝒔𝒑𝒕
1.1. Corrección 𝑵𝟔𝟎
𝑁60 ≅ 0.7𝑁𝑠𝑝𝑡
′ ′
𝜎(1𝑚) = 1 × 1.9 − 1 × 1 = 0.9𝑡𝑜𝑛/𝑚² 𝜎(6𝑚) = 3.6 + 2 × 2 − 2 × 1 = 5.6𝑡𝑜𝑛/𝑚²
′ ′
𝜎(2𝑚) = 2 × 1.9 − 2 × 1 = 1.8𝑡𝑜𝑛/𝑚² 𝜎(7𝑚) = 3.6 + 3 × 2 − 3 × 1 = 6.6𝑡𝑜𝑛/𝑚²
′ ′
𝜎(3𝑚) = 3 × 1.9 − 3 × 1 = 2.7𝑡𝑜𝑛/𝑚² 𝜎(8𝑚) = 3.6 + 4 × 2 − 4 × 1 = 7.6𝑡𝑜𝑛/𝑚²
′ ′
𝜎(4𝑚) = 4 × 1.9 − 4 × 1 = 3.6𝑡𝑜𝑛/𝑚² 𝜎(9𝑚) = 3.6 + 5 × 2 − 5 × 1 = 8.6𝑡𝑜𝑛/𝑚²
′ ′
𝜎(5𝑚) = 3.6 + 1 × 2 − 1 × 1 = 4.6𝑡𝑜𝑛/𝑚² 𝜎(10𝑚) = 3.6 + 6 × 2 − 6 × 1 = 9.6𝑡𝑜𝑛/𝑚²
0.5
1
(𝑁1 )60 = 𝐶𝑁 × 𝑁60 ; 𝐶𝑁 = � 𝜎′
�
� 0�
𝑝𝑎
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
0.5 0.5
1 1
(𝑁1 )60 (1𝑚) =� � × 7 = 23.33 (𝑁1 )60 (6𝑚) =� � × 10 = 13.36
0.9 5.6
� 10 � � 10 �
≅ 23 ≅ 13
0.5 0.5
1 1
(𝑁1 )60 (2𝑚) = � � × 8 = 18.86 (𝑁1 )60 (7𝑚) = � � × 11 = 13.54
1.8 6.6
� 10 � � 10 �
≅ 19 ≅ 14
0.5 0.5
1 1
(𝑁1 )60 (3𝑚) = � � × 8 = 15.4 ≅ 15 (𝑁1 )60 (8𝑚) = � � × 11 = 12.62
2.7 7.6
� 10 � � 10 �
≅ 13
0.5 0.5
1 1
(𝑁1 )60 (4𝑚) = � � × 9 = 15 (𝑁1 )60 (9𝑚) = � � × 13 = 14.02
3.6 8.6
� 10 � � 10 �
≅ 14
0.5 0.5
1 1
(𝑁1 )60 (5𝑚) = � � × 9 = 13.27 (𝑁1 )60 (10𝑚) = � � × 14 = 14.29
4.6 9.6
� 10 � � 10 �
≅ 13 ≅ 14
𝑁𝑝𝑟𝑜𝑚 (𝑆𝑃) = 18
𝑁𝑝𝑟𝑜𝑚 (𝑆𝑊) = 14
CARGAS.
1. Capacidad nominal
𝑄𝑛𝑜𝑚 = 𝛼𝑓′𝑐 𝐴𝑝
𝑘𝑔
Tomando el criterio de la Sociedad Venezolana de Geotecnia, 𝛼𝑓′𝑐 = 35 𝑐𝑚2
𝜋(80)2 1
𝑄𝑛𝑜𝑚 = 35 × × = 175.93 𝑡𝑜𝑛
4 1000
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
2. Cargas actuantes.
Carga axial
Utilizando la combinación 1 y 2
Momento
Utilizando la combinación 1 y 2
1.1𝑃𝑠𝑒𝑟𝑣 1.1 × 80
𝑛 𝑝𝑖𝑙𝑜𝑡𝑒𝑠 = = = 0.5 → 1 𝑃𝑖𝑙𝑜𝑡𝑒
𝑄𝑛𝑜𝑚 175.93
Cabezal de 1 pilote
2.2.3. Separación
No aplica.
3. Chequeo
DISEÑO GEOTECNICO
𝐿 = 10 𝑚
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
2. Capacidad de pilotes
2.3. Pilotes rotados en arena
2.3.1. Capacidad por punta (SW)
′
𝑞 ′ = 𝜎(10𝑚) = 9.6 𝑡𝑜𝑛/𝑚²
𝐿 10 𝜋
𝐹𝑞𝑑 = 1 + 𝐶 tan−1 � � = 1 + 0.276 tan−1 � � � � = 1.412
𝐷𝑝 0.8 180°
Calculo de 𝐹𝑞𝑐
𝜙′ 32°
𝐼𝑐𝑟 = 0.5𝑒𝑥𝑝 �2.85 cot �45 − �� = 0.5𝑒𝑥𝑝 �2.85 cot �45 − �� = 85.489
2 2
𝑡𝑜𝑛
Tomando 𝛼 = 10, para arenas normalmente consolidadas; y 𝑝𝑎 = 10 𝑚2
𝑡𝑜𝑛
𝐸𝑠 = 𝛼(𝑁1 )60 𝑝𝑎 = 10 × 14 × 10 = 1400
𝑚2
𝜙 ′ − 25 32 − 25
𝜇𝑠 = 0.1 + 0.3 � � = 0.1 + 0.3 � � = 0.205
20 20
𝜙 ′ − 25 32 − 25
𝑛 = 0.005 �1 − � = 0.005 �1 − � = 0.00325
20 20
𝑞′ 9.6
Δ=𝑛 = 0.00325 � � = 0.00312
𝑝𝑎 10
𝐸𝑠 1400
𝐼𝑟 = = = 96.839
2(1 + 𝜇𝑠 )𝑞′ tan 𝜙′ 2(1 + 0.00325)9.6 tan 32°
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝐼𝑟 96.839
𝐼𝑟𝑟 = = = 74.369
1 + 𝐼𝑟 Δ 1 + (96.839)(0.00312)
𝜋(0.8)2
𝑄𝑝 = [9.6 × (23.18 − 1) × 1.625 × 1.412 × 0.939] = 230.193 𝑡𝑜𝑛
4
′ ′
𝜎(0𝑚) + 𝜎(4𝑚) 0 + 3.6 𝑡𝑜𝑛
���𝑜′ =
𝜎 = = 1.8 2
2 2 𝑚
2 ′ 2
𝛿′ = 𝜙 = (30°) = 20°
3 3
3. Capacidad última
4. Capacidad permisible
𝑄𝑢 233.49
𝑄𝑝𝑒𝑟𝑚 = = = 77.83 𝑡𝑜𝑛
𝐹𝑆 3
1.1𝑄𝑎𝑐𝑡 1.1 × 80
𝑛 𝑝𝑖𝑙𝑜𝑡𝑒𝑠 = = = 1.13 → 2 𝑃𝑖𝑙𝑜𝑡𝑒𝑠
𝑄𝑝𝑒𝑟𝑚 77.83
De esta forma la carga actuante que recibe cada pilote será menor que la
carga permisible estimada en el diseño geotécnico.
GRUPO DE PILOLTES
1. Chequeo de eficiencia
𝑄𝑢 = 233.49 𝑡𝑜𝑛
�𝑄𝑤𝑝 + 𝜉𝑄𝑤𝑠 �𝐿
𝑆𝑒 (1) =
𝐴𝑝 𝐸𝑝
𝑘𝑔 𝑡𝑜𝑛
𝐸𝑝 = 15100�𝑓′𝑐 = 15100√280 = 252671.328 2
= 2526713.28 2
𝑐𝑚 𝑚
Tomando 𝜉 = 0,67
𝜋(0.8)²
𝐴𝑝 = = 0.503 𝑚²
4
𝑞𝑤𝑝 𝐷
𝑆𝑒 (2) = (1 − 𝜇𝑠 2 )𝐼𝑤𝑝
𝐸𝑠
𝐸𝑠 = 1400 𝑡𝑜𝑛/𝑚²
𝜇𝑠 = 0.205
𝐼𝑤𝑝 = 0.85
𝑄𝑤𝑝 43.38
𝑞𝑤𝑝 = = = 86.3 𝑡𝑜𝑛/𝑚²
𝐴𝑝 0.503
86.3 × 0.8
𝑆𝑒 (2) = × (1 − 0.2052 ) × 0.85 = 0.04 𝑚 = 4.016 𝑐𝑚
1400
2.4. Asentamiento causado por la carga transmitida a lo largo del fuste del
pilote
𝑄𝑤𝑠 𝐷
𝑆𝑒 (3) = � � (1 − 𝜇𝑠 2 )𝐼𝑤𝑠
𝑝𝐿 𝐸𝑠
𝑡𝑜𝑛
Tomando ∝= 10, para arenas normalmente consolidadas; y 𝑝𝑎 = 10 𝑚2
𝑡𝑜𝑛
𝐸𝑠 =∝ (𝑁1 )60 𝑝𝑎 = 10 × 18 × 10 = 1800
𝑚2
𝜙 ′ − 25 30 − 25
𝜇𝑠 = 0.1 + 0.3 � � = 0.1 + 0.3 � � = 0.175
20 20
𝑝 = 𝜋𝐷 = 𝜋 × 0.8 = 2.513 𝑚
10
𝐼𝑤𝑠 = 2 + 0.35� = 3.237
0.8
0.62 0.8
𝑆𝑒 (3) = � �× × (1 − 0.1752 ) × 3.237 = 3.441 × 10−5 𝑚 = 0.003 𝑐𝑚
2.513 × 10 1800
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝐵𝑔
𝑆𝑔 = � 𝑆𝑒
(𝑒) 𝐷
2.8
𝑆𝑔 =� × 4.054 = 7.58 𝑐𝑚
(𝑒) 0.8
DISEÑO ESTRUCTURAL
Como sobre los pilotes solo actúan cargas axiales el acero requerido se
obtiene a partir de la cuantía mínima (Criterio FEMA 450, 750 y ACI-543).
𝜌 = 0.005
𝜋(80)2
𝐴𝑆𝐿 = 𝜌𝐴𝑔 = 0.005 × = 25.13 𝑐𝑚²
4
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝐴𝑆𝐿 25.13
𝑁𝑐𝑎𝑏 = = = 4.96 ≅ 5 𝑏𝑎𝑟𝑟𝑎𝑠
Á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑏𝑎𝑟𝑟𝑎 5.07
• 4 𝑐𝑚
𝑅𝑒𝑐𝑢𝑏 = 7.5 𝑐𝑚
𝐷𝑐 = 𝐷 − 2 × 𝑟𝑒𝑐𝑢𝑏 = 80 − 2 × 7.5 = 65 𝑐𝑚
𝜋𝐷² 𝜋(80)2
𝐴= = = 5026.548 𝑐𝑚²
4 4
𝜋𝐷𝑐 ² 𝜋(65)2
𝐴𝑐ℎ = = = 3318.307 𝑐𝑚²
4 4
f′c Ag 1.4P
ρs = 0.25 � �� − 1� �0.5 + �
fyh Ach f′c Ag
Dónde:
𝑃𝑢 106
𝑃= = = 53 𝑡𝑜𝑛
2 2
f′c 1.4P 280 1.4 × 53 × 1000
ρs = 0.12 � � �0.5 + � = 0.12 � � �0.5 + � = 0.004
fyh f′c Ag 4200 280 × 5026.548
CABEZALES
La altura útil del cabezal para cumplir con el ángulo recomendado por
Landa B:
1.2 + 0.48
𝑑= = 0.84 ≅ 0.9 𝑚
2
ℎ = 0.9 + 0.1 = 1 𝑚
𝑃𝑢 𝑆 106 × 2
𝑇𝑥 = = = 58.89 𝑡𝑜𝑛
4𝑑 4 × 0.9
4. Diseño estructural
𝑇𝑥 58.89 × 1000
𝐴𝑠 = = = 18.69 𝑐𝑚2
𝜑 𝑓𝑦 0.75 × 4200
Se comprueba que esta sea mayor que el acero mínimo requerido; donde
para barras con 𝑓𝑦 = 4200 𝑘𝑔/𝑐𝑚², 𝜌 ≥ 0.0018
• Dirección X
• Dirección Y
• 𝑑𝑏 = 2.54 𝑐𝑚
• 2.5 𝑐𝑚
• Dirección Y
𝐴𝑆 𝑚𝑖𝑛 = 54 𝑐𝑚²
• 𝑑𝑏 = 2.54 𝑐𝑚
• 2.5 𝑐𝑚
• Dirección X
𝐴𝑆 𝑚𝑖𝑛 = 18 𝑐𝑚²
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
• 𝑑𝑏 = 2.54 𝑐𝑚
• 2.5 𝑐𝑚
• Dirección Y
𝐴𝑆 𝑚𝑖𝑛 = 54 𝑐𝑚²
• 𝑑𝑏 = 2.54 𝑐𝑚
• 2.5 𝑐𝑚
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝐴𝐿 7.7
𝐴𝑠 𝑙𝑎𝑡𝑒𝑟𝑎𝑙 1 𝑐𝑎𝑟𝑎 = = = 3.85 𝑐𝑚²
2 2
ℎ − 2 × 𝑟𝑒𝑐𝑢𝑏 100 − 2 × 10
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎 = × 1.27 = 26.38 𝑐𝑚
𝐴𝐿 3.85
≅ 26 𝑐𝑚
ℎ − 2 × 𝑟𝑒𝑐𝑢𝑏 100 − 2 × 10
𝑁𝑐𝑎𝑏 = = = 3.08 ≅ 4 𝑏𝑎𝑟𝑟𝑎𝑠
𝑆𝑒𝑝 26
5. Corte
5.1. Fuerza cortante actuante
𝑆 𝑏𝑐 2 0.5
𝑥= − −𝑑 = − − 0.9 = −0.15 𝑚
2 2 2 2
𝐷 0.8
= = 0.4 𝑚
2 2
𝐷
Debido a que 𝑥 es menor que 2 , la fuerza cortante actuante debe interpolarse
𝑃𝑢 106
𝑉𝑚𝑎𝑥 = = = 53 𝑡𝑜𝑛
2 2
𝑉𝑚𝑖𝑛 = 0 𝑡𝑜𝑛
Asumiendo que 𝑉𝑚𝑎𝑥 se da a 0.5𝐷 por fuera de la sección critica, y 𝑉𝑚𝑖𝑛 se da 0.5𝐷
dentro de la sección crítica, el corte interpolado al realizar una relación de
triángulos, será:
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
𝑉𝑚𝑎𝑥
𝑉𝑢 = (0.5𝐷 + 𝑥) ×
0.5𝐷 + 0.5𝐷
53
𝑉𝑢 = (0.5 × 0.8 − 0.15) × = 16.56 𝑡𝑜𝑛 = 16562.5 𝑘𝑔
0.5 × 0.8 + 0.5 × 0.8
Y este valor al compararlo con la resistencia la corte del concreto debe ser menor
𝑉𝑢 ≤ 𝜑0.53�𝑓 ′ 𝑐 × 𝑏 × 𝑑
Dónde:
𝜑 = 0.75, según FONDONORMA tabla 9.4 y el artículo 21.2 del ACI 318-14
16562.5 𝑘𝑔 ≤ 59863.02 𝐾𝑔
6. Punzonado
Columna central
6.1.1. Resistencia
αs = 40
0.5
𝛽𝑐 = =1
0.5
2 2
a. 𝑉c = 0.53 �1 + �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.53 × �1 + 1� × 1 × √280 × 560 × 90
𝛽𝑐
αs d 40×90
b. 𝑉c = 0.27 �2+ �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.27 �2 + �× 1 × √280 × 560 × 90
bo 560
𝑉𝑐 𝑐 = 927.69 𝑡𝑜𝑛
6.1.3. Chequeo
6.2.1. Resistencia
𝑑 0.8 0.9
𝑏𝑜 = 2𝜋 �𝑟 + � = 2𝜋 × � + � = 5.34 𝑚
2 2 2
2 2
a. 𝑉c = 0.53 �1 + �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.53 × �1 + 1� × 1 × √280 × 534 × 90
𝛽𝑐
αs d 40×90
b. 𝑉c = 0.27 �2+ �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.27 �2 + �× 1 × √280 × 534 × 90
bo 534
𝑉𝑐 𝑝 = 884.73 𝑡𝑜𝑛
𝑃𝑢 106
𝑉𝑢 𝑝 = = = 53 𝑡𝑜𝑛
𝑛 2
Dónde:
6.2.3. Chequeo
𝑉𝑢 𝑝 < 𝜙𝑉𝑐 𝑝
7. Aplastamiento
7.1. Determinación del área cargada
𝐴2 10000
� =� =2
𝐴1 2500
𝐴2
𝐹𝐴 𝑐𝑎𝑏𝑒𝑧𝑎𝑙 = 𝜙�0.85𝑓 ′ 𝑐 𝐴1 �� = 0.65(0.85 × 280 × 2500) × 2 = 773500 𝑘𝑔
𝐴1
= 773.5 𝑡𝑜𝑛
7.5. Chequeo
𝑃𝑢 = 106 𝑡𝑜𝑛
Zona No Confinada.
Espirales 3/8” cada 20 cm.
ESTRATIGRAFÍA
1. Corrección 𝑵𝑺𝑷𝑻
1.1. Corrección 𝑵𝟔𝟎
𝑁60 ≅ 0.7𝑁𝑠𝑝𝑡
𝑁𝑝𝑟𝑜𝑚 (𝐶𝐻) = 11
CARGAS
4. Capacidad nominal
𝑄𝑛𝑜𝑚 = 𝛼𝑓′𝑐 𝐴𝑝
𝑘𝑔
Tomando el criterio de la Sociedad Venezolana de Geotecnia, 𝛼𝑓′𝑐 = 35 𝑐𝑚2
𝜋(100)2 1
𝑄𝑛𝑜𝑚 = 35 × × = 274.889 𝑡𝑜𝑛
4 1000
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
5. Carga actuante
Carga axial
Utilizando la combinación 1 y 2
Momento
Utilizando la combinación 1 y 2
a. 𝑃𝑈 = 1.4𝑀𝐶𝑃 = 1.4 × 4 = 14 𝑡 − 𝑚
Número de pilotes
1.1𝑃𝑠𝑒𝑟𝑣 1.1 × 65
𝑛 𝑝𝑖𝑙𝑜𝑡𝑒𝑠 = = = 0.26 → 1 𝑃𝑖𝑙𝑜𝑡𝑒
𝑄𝑛𝑜𝑚 274.889
Cabezal de 1 pilote
5.1.3. Separación
No aplica.
6. Chequeo
DISEÑO GEOTECNICO
𝐿 = 10 𝑚
2. Capacidad de pilotes
2.4. Pilotes rotados en arcilla
2.4.1. Capacidad por punta en arcilla (CH)
𝑄𝑝 = 𝐴𝑝 𝑐𝑢 𝑁𝑐∗
Tomando 𝑁𝑐∗ = 9
𝜋 × (1)²
𝑄𝑝 = × 4.84 × 9 = 34.212 𝑡𝑜𝑛
4
𝑄𝑎𝑑ℎ = 𝑝𝐿𝑓
Cálculo de 𝑓:
𝑝𝑎 10
𝛼 = 0.21 + 0.25 � � = 0.21 + 0.25 � � = 0.92
𝑐𝑢 3.52
3. Capacidad última, 𝑸𝒖
𝑄𝑢 95.27
𝑄𝑝𝑒𝑟𝑚 = = = 31.76 𝑡𝑜𝑛
𝐹𝑆 3
1.1𝑄𝑎𝑐𝑡 1.1 × 65
𝑛 𝑝𝑖𝑙𝑜𝑡𝑒𝑠 = = = 2.25 → 3 𝑃𝑖𝑙𝑜𝑡𝑒𝑠
𝑄𝑝𝑒𝑟𝑚 31.76
De esta forma la carga actuante que recibe cada pilote será menor que la
carga permisible estimada en el diseño geotécnico.
DISEÑO ESTRUCTURAL
Como sobre los pilotes solo actúan cargas axiales el acero requerido se
obtiene a partir de la cuantía mínima (Criterio FEMA 450, 750 y ACI:543):
𝜌 = 0.005
𝜋(100)2
𝐴𝑆𝐿 = 𝜌𝐴𝑔 = 0.005 × = 39.27 𝑐𝑚²
4
𝐴𝑆𝐿 39.27
𝑁 𝑏𝑎𝑟𝑟𝑎𝑠 = = = 7.75 ≅ 8 𝑏𝑎𝑟𝑟𝑎𝑠
Á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑏𝑎𝑟𝑟𝑎 5.07
• 4 𝑐𝑚
𝑅𝑒𝑐𝑢𝑏 = 7.5 𝑐𝑚
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
Ahora, la separación centro a centro a la que serán colocadas las barras es:
𝜋𝐷² 𝜋(100)2
𝐴= = = 7853.98 𝑐𝑚²
4 4
𝜋𝐷𝑐 ² 𝜋(85)2
𝐴𝑐ℎ = = = 5674.50 𝑐𝑚²
4 4
f′c Ag 1.4P
ρs = 0.25 � �� − 1� �0.5 + �
fyh Ach f′c Ag
𝑃𝑢 84
𝑃= = = 28 𝑡𝑜𝑛
3 3
f′c 1.4P 280 1.4 × 28 × 1000
ρs = 0.12 � � �0.5 + � = 0.12 � � �0.5 + � = 0.0041
fyh f′c Ag 4200 280 × 7853.98
CABEZALES
1.65 + 4.2
𝑑= = 2.93 ≅ 2.9 𝑚
2
ℎ = 2.9 + 0.1 = 3 𝑚
3. Fuerza de tracción
𝑃𝑢 𝑆 84 × 3.5
𝑇𝑥 = = = 33.79 𝑡𝑜𝑛
3𝑑 3 × 2.9
4. Diseño estructural
𝑇𝑥 33.79 × 1000
𝐴𝑠 = = = 10.73 𝑐𝑚2
𝜑 𝑓𝑦 0.75 × 4200
Se comprueba que esta sea mayor que el acero mínimo requerido; donde
para barras con 𝑓𝑦 = 4200 𝑘𝑔/𝑐𝑚², 𝜌 ≥ 0.0018
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
• Dirección X
• Dirección Y
• 𝑑𝑏 = 2.54 𝑐𝑚
• 2.5 𝑐𝑚
• Dirección Y
• 𝑑𝑏 = 2.54 𝑐𝑚
• 2.5 𝑐𝑚
52.73
𝐴𝑠 𝑙𝑎𝑡𝑒𝑟𝑎𝑙 1 𝑐𝑎𝑟𝑎 = = 26.36 𝑐𝑚2
2
ℎ − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑆𝑒𝑝 = × á𝑟𝑒𝑎 𝑑𝑒 𝑙𝑎 𝑐𝑎𝑏𝑖𝑙𝑙𝑎
𝐴𝑠 𝑙𝑎𝑡𝑒𝑟𝑎𝑙 1 𝑐𝑎𝑟𝑎
300 − (2 × 10)
𝑆𝑒𝑝 = × 2.85 = 30.27 ≅ 30 𝑐𝑚
26.36
ℎ − (2 × 𝑟𝑒𝑐𝑢𝑏𝑟𝑖𝑚𝑖𝑒𝑛𝑡𝑜)
𝑁𝑐𝑎𝑏 =
𝑆𝑒𝑝
300 − (2 × 10)
𝑁𝑐𝑎𝑏 = = 9.33 ≅ 10 𝑏𝑎𝑟𝑟𝑎𝑠
30
6. Punzonado
Columna central
6.1.1. Resistencia
αs = 40
0.7
𝛽𝑐 = =1
0.7
2 2
a. 𝑉c = 0.53 �1 + 𝛽𝑐
� 𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.53 × �1 + 1� × 1 × √280 × 1440 × 290
αs d 40×290
b. 𝑉c = 0.27 �2+ �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.27 �2 + �× 1 × √280 × 1440 × 290
bo 1440
𝑉𝑐 𝑐 = 7686.56 𝑡𝑜𝑛
𝑉𝑢𝑐 = 𝑃𝑢 = 84 𝑡𝑜𝑛
6.1.3. Chequeo
6.2.1. Resistencia
𝑑 1 2.9
𝑏𝑜 = 2𝜋 �𝑟 + � = 2𝜋 × � + � = 12.25 𝑚
2 2 2
2 2
a. 𝑉c = 0.53 �1 + �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.53 × �1 + 1� × 1 × √280 × 1225 × 290
𝛽𝑐
αs d 40×290
b. 𝑉c = 0.27 �2+ �𝜆 �f´c × 𝑏𝑜 × 𝑑 = 0.27 �2 + �× 1 × √280 × 1225 × 290
bo 1225
𝑉𝑐 𝑝 = 6540.10 𝑡𝑜𝑛
𝑃𝑢 84
𝑉𝑢 𝑝 = = = 28 𝑡𝑜𝑛
𝑛 3
Dónde:
6.2.3. Chequeo
𝑉𝑢 𝑝 < 𝜑𝑉𝑐 𝑝
7. Aplastamiento
7.1. Determinación del área cargada
𝐴2 367500
� =� =9>2
𝐴1 4900
𝐴
Se toma �𝐴2 = 2
1
𝐴2
𝐹𝐴 𝑐𝑎𝑏𝑒𝑧𝑎𝑙 = 𝜑�0.85𝑓 ′ 𝑐 𝐴1 �� = 0.65(0.85 × 280 × 4900) × 2 = 1516060 𝑘𝑔 = 1516.06 𝑡𝑜𝑛
𝐴1
Diplomado en Diseño Geotécnico y Estructural de Cimentaciones
7.5. Chequeo
𝑃𝑢 = 84 𝑡𝑜𝑛
𝑃𝑢 < 𝐹𝐴 𝑐𝑜𝑙𝑢𝑚𝑛𝑎
𝑃𝑢 < 𝐹𝐴 𝑐𝑎𝑏𝑒𝑧𝑎𝑙
Zona No Confinada.
Espirales 3/8” cada 20 cm.