You are on page 1of 9

Contract QAMP-069 - Provision of Rig & Rig Associated Services

APPENDIX 6, EQUIPMENT LIST & SPECIFICATIONS

1.0 Casing stabbing board


Casing stabbing board provided for running casing shall meet the following requirements.

a) The hoisting mechanism for the stabbing board shall meet a safety factor of 10:1 in
terms of lifting capacity.

b) The wireline used for the hoisting mechanism shall in no case be less than 3/8” in
addition to meeting the safety factor of 10: 1.
c) The hydraulic / air winch controls shall be available with the operator on the casing
stabbing board. The winch control lever shall return back to neutral when released.
Winch controls shall be clearly marked up and down.
d) The hydraulic / air winch shall have an automatic fail-safe brake. The automatic fail-safe
brake shall activate automatically when the air/ hydraulic fluid supply is interrupted. The
automatic fail-safe brake shall also operate when the load attempts to “run away” or
“free fall”.
e) The stabbing board carriage shall be equipped with a secondary safety lock which
operates automatically in the event of winch rope or brake failure. The secondary safety
lock shall automatically lock the carriage in position when the winch operating level is in
neutral position.
f) The casing stabbing board shall be equipped with upper and lower limit switches.
g) The casing stabbing board shall have a safety line attached to the mast. The casing
stabbing board shall be equipped with a fall arrester for use by the operator.
h) The casing stabbing board shall have a valid load test certificate. The casing stabbing
board shall have undergone design verification by an independent verification company
and a valid inspection certificate shall be available.
i) The casing stabbing board shall have kicker or toe-boards of a height of minimum 3
inches all around the sides at the bottom.
j) The casing stabbing board shall have a certified anchoring point behind the stabber for a
harness. A restraining system for the stabber to hang forward i.e. gut buster is required.
k) The control system for the stabbing board winch should have adequate protection to
prevent inadvertent movement of the stabbing board in case of accidental touch of the
control levers by the casing stabber.
l) The requirements of the stabbing board described above shall be tested once every
month or prior to running casing whichever is earlier. This shall include a thorough visual
and functional inspection using a checklist.
1.1 Rig Lighting
Low Pressure Sodium Discharge lighting is not acceptable. All lighting on the mast
(including but not limited to the aviation warning on the crown block), mud tanks,
substructure and rig carrier, and all zone 1 and zone 2 hazardous areas as defined by IP
Model Code -15 shall be heavy duty, vapour tight, fluorescent lighting system certified for
use in Zone 1 or 2 areas as defined by IP Model code of safe practice – Part 15 – Area
Classification code for installations handling inflammable fluids – 3rd edition July 2005. In
addition to the above requirements the supplied lighting shall be designed and certified for
use in an ambient temperature of 55 deg C and shall meet Temperature classification
T3(200 deg C) or T4(135 deg C) or T5(100 deg C) or T6 (85 deg C). The allowed
protection principles as used for light fittings for Hazardous Area Zone 1 and 2 are : EEx d,
EEx e, EEx m and EEx q or EE edqm. For EEx e light fittings, the internal components need
to be separately certified according to one of the recognized principles e.g. Eex d, EEx q or
EEx m. The fittings need to be installed according to IEC 60364 part 1 to 5 and additionally

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 1 of 9
Contract QAMP-069 - Provision of Rig & Rig Associated Services

for hazardous area as per IEC 60079 – part 14, SP 1112 – Electrical Specification for Drilling
Rigs. Rig lighting if made to North American standards must be certified for ambient
temperature rating of 55 deg C and certified for Class I Division 1 Gas Group C & D and
must meet temperature classification T3(200 deg C) or T3A(180 deg C) or T3B (165 deg C)
or T3C (160 deg C) or T4(135 deg C) or T4A (120 deg C) or T5(100 deg C) or T6 (85 deg
C). All outdoor rig lighting shall have a suitable safety restraint installed.
In addition, any lighting supplied for outdoor lighting for Zone 1 or 2 hazardous areas must
carry either of the following marks. (Refer to * note below)

Certificate that the apparatus has been constructed and tested in


accordance with the CENELEC/EURONORM standards.

Certificate that the apparatus has been tested by Underwriters Laboratories.

Certificate that the apparatus has been tested by CSA International


Canada.

Note * - QAMP only accepts and recognizes rig lighting certified by the following
certification agencies:
UL – USA , CSA – Canada, LCIE – France, INERIS – France, BAM – Germany, DMT –
Germany, DOS – Germany, FSA – Germany, IBExU – Germany, PTB – Germany, TUV(Nord
Cert) – Germany,
SEE – Luxembourg, KEMA – Netherlands, SP – Sweden, LOM – Spain, EECS(BASEFA) – UK,
SCS – UK
There shall be an isolation switch available to isolate all non-explosion proof , non-
intrinsically safe lighting installed on the rig carrier and substructure for transportation
purposes(e.g. brake lights , reversing lights for self propelled rigs with battery fed 12/ 24 V
road light fittings) so that the same can be isolated prior to spotting a rig on location.
Electrical lighting operating outside hazardous area zone 2 as defined by IP Model Code –
Part 15 shall be industrial heavy duty, vapour tight, fluorescent lighting system (Low
Pressure Sodium Discharge lighting is not acceptable and shall meet IP 54 Ingress
Protection to IEC 60529 , certified as Class I or II equipment as per IEC 60536 and certified
for use in an ambient temperature of 55 deg C.

1.2 Electrical Motors

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 2 of 9
Contract QAMP-069 - Provision of Rig & Rig Associated Services

All electrical motors used in hazardous area Zone 1 or 2 as defined by IP Model code of
safe practice – Part 15 – Area Classification code for installations handling inflammable
fluids – 3rd edition July 2005 including but not limited to motors placed in draw-works,
rotary table, mud pumps, mud tanks, topdrive, mast shall be constructed and certified
according to one of the mentioned explosion proof principles EEx d or EEx e or EEx de
and shall be certified for use in ambient temperature rating of 55 deg C. Electric motors
which are not protected according to one of the above-mentioned explosion proof
principles can be protected by “overpressure” with an “overpressure” monitoring system
for loss of pressure and flow rate. Electrical motors shall meet Temperature classification
T3(200 deg C) or T4(135 deg C) or T5(100 deg C) or T6 (85 deg C). For electrical
motors that can generate sparks, like commutators and carbon brushes for DC motors,
must be equipped with certified spark arresters when blowing air inside a Zone 1 or 2
area as defined by IP Model code of safe practice – Part 15. Air intake must always be
outside Zone 2 hazardous area as defined by IP Model code of safe practice – Part 15.
Any ducting installed for the purpose of air intake shall extend outside zone 2 and shall
be leaktight and made of flameproof material.
Electrical motors must be certified for use in hazardous areas Zone 1 or 2 must carry the
markings and must be certified by any one of the following agencies :
UL – USA, CSA – Canada, LCIE – France, INERIS – France, BAM – Germany, DMT –
Germany, DOS – Germany, FSA – Germany, IBExU – Germany, PTB – Germany,
TUV(Nord Cert) – Germany, SEE – Luxembourg, KEMA – Netherlands, SP – Sweden, LOM
– Spain, EECS(BASEFA) – UK, SCS – UK.
1.3 Low voltage switchgear and distribution boxes
Outdoor switchgear and distribution boxes shall have at least IP 54 ingress protection to
IEC 60529 and be protected by a rain canopy. Indoor switchgear and distribution boxes
shall have at least IP43 ingress protection to IEC60529. Live parts, which are accessible
when a door of a switchgear assembly is opened, shall have at least IP-20 ingress
protection to IEC 60529. Serviceable parts, e.g. fuses, shall be removable without
affecting the IP-20 ingress protection.
Switching devices on a drilling rig and rig camp accommodation shall switch all phases or
poles, i.e., 4-pole type for 3 phase + neutral systems, 3 pole type for 3 phase without
neutral systems and 2-pole type for single phase systems. For repair or maintenance
work, upstream of any electric circuit or group of circuits shall be provided at least one
means of isolation (and an additional padlock facility) which simultaneously disconnects
all phases or poles, e.g. a switching device with padlock facilities in the "OFF" position
and a fuse-isolator or in case a lockable repair switch is in the control circuit it must be of
a so called “Safety Circuit” as defined by IEC 60364 part 1 to 5.

Non-armoured cables applied in TN-S systems shall be protected by a residual current


protection device(RCD) operating at 30 mA residual current, unless these cables are
adequately protected against physical damage, e.g. by means of cable trays/ladder with
metallic covers. Residual current devices(RCD) shall be tested at least once every 6
months using proper RCD test equipment. All outdoor power cables shall be heavy duty
industrial quality, armoured or screened, UV and oil-resistant.

Company prefers armoured cables to prevent physical damage when the cables are not
sufficiently protected, e.g. not laid in cable trays, or when protection cannot be
guaranteed because of the rough environment. For fixed installation in the mast or under
the substructure for zone 1 and 2 cables should be armoured (one-time installation) and
for movable temporary rubber cable "screened" cables (as per IEC 60079-14 / IEC
60364) would be acceptable if the screen is grounded. When laid inside cable trays,
normal standard cables of a heavy duty industrial quality, UV and oil resistant and
protected by steel cable trays, that are earthed is acceptable.

1.4 Drawworks

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 3 of 9
Contract QAMP-069 - Provision of Rig & Rig Associated Services

All drawworks shall be fitted with a secondary braking device (e.g. eddy current or
hydromatic). Drawworks fitted with an eddy current brake should have an auxiliary
powered back-up supply in the event of a main power failure. An emergency stop device
shall be provided for the drawworks, within easy reach of the Driller. This device shall be
tested at least once every two weeks.
There shall always be a sufficient number of wraps of hoisting line remaining on the
drum to eliminate any strain being transmitted directly to the fastening device. The
minimum wraps for a given drawworks is given in the manufacturer's operating manual.
The installation of a top drive will require additional wraps. The installation of disk brakes
or callipers (as opposed to conventional band brakes) on drawworks will require
additional wraps as disk brakes are prone to abrupt braking as compared to conventional
band brakes.
A rigorous inspection schedule, including NDT, of the main drawworks brake, brake
bands and brake linkage as per PR-1312 Well Engineering Equipment Inspection
Procedure is mandatory.
Brake bands shall not be repaired. Brake blocks shall be made of non-asbestos material.
In case disk brakes or calliper brakes are provided as an alternative to conventional band
brakes, a minimum of 6 disk brakes or calliper brakes (including both drawworks drum
flanges) shall be provided. At least 2 of the 6 disk brakes or calliper brakes shall function
as parking brakes. The emergency braking button when activated shall activate at least 4
of the 6 disk brakes or calliper brakes provided.
Contractor shall fit a flow sensor and temperature alarm to the draw works cooling water
return line. As a minimum, loss of cooling water pressure shall be indicated by an audio-
visual alarm on the Driller's console. A low level alarm on the cooling water tank is
recommended.
1.5 Crown and floor protection
Contractor shall provide a crown-o-matic or other similar automatic fail-safe emergency
stop device to prevent accidentally hoisting the travelling block against the crown block. If
timber blocks are used as shock absorbing devices, they shall be covered with wire mesh
and secured in such a way that impact does not dislodge them. Contractor shall provide a
floor-saver or other similar automatic fail-safe emergency stop device to prevent accidental
lowering of the travelling block to the rotary table level. Company requires the installation
of a Kinetic Energy Monitoring System (KEMS) for anti-collision in addition to the crown-o-
matic.
Contractor shall install Jumper bars to prevent drilling line from jumping out of the crown
sheaves so that no section more than 100 of arc is unprotected.
1.6 Deadline anchor / Weight indicator
Deadline anchors for hoisting lines shall be constructed and installed (bolted/welded) such
that their strength equals or exceeds the working strength of the hoisting line. Systems will
not rely on bolts being in tension. The system should be designed such that a bolt failure
does not result in the anchor flying.
Contractor shall carry out regular checks for cracks and significant corrosion to ascertain
proper functioning and structural integrity of the equipment. Critical welds or other securing
devices shall be regularly inspected as per PR-1312 Well Engineering Equipment Inspection
Procedure.
A weight indicator shall be installed on every drilling and workover rig and it shall be
maintained such that it registers an accurate indication of the hook load suspended (within
5 per cent at maximum hook load). The weight indicator shall be checked regularly for
calibration by comparing its reading with the calculated drill pipe or tubing string weight.
Contractor shall inspect the load cell gap on every shift.

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 4 of 9
Contract QAMP-069 - Provision of Rig & Rig Associated Services

1.7 Environmental H2S Gas Detection System Specifications


1.7.1 General
1.7.1.1 This specification relates to the provision of Environmental Hydrogen Sulphide Gas Detector
Systems. The installed system shall not interfere with any other system in use on the rig.
1.7.1.2 Environmental Conditions: All equipment shall be constructed to withstand the following
conditions: -
- Temperature Range (in the shade) : 0 deg to 55 deg Celsius
- Heavy Night-time Condensation
- High solar and ultra-violet radiation levels
- Sand and dust storms
- Frequent long journeys over rough graded roads.
1.7.2 Alarms
A two-tone alarm, or alarms, should be provided such that the alarm signal is audible under
all operating conditions throughout the drilling location, including external and all internal
work spaces. The latter shall include, but shall not be limited to, the office
accommodations, rig floor or doghouse, wireline logging unit or truck, mud-loggers unit,
stores and power-house. Flashing red lights shall be installed at strategic points to
supplement the alarm in noisy areas.

1.7.3 System Specification

Instrument Power: 110-220 V AC, 50-60Hz.


A suitably sized back-up UPS system is to be connected to the H2S gas detection system to
enable detection of upto 1 hour after rig power failure.
Explosion Proof Certification: All electrical equipment located in a Hazardous
Area to be certified for use in a Zone 1 Hazardous
Area as defined by IP Model code of safe practice
– Part 15 – Area Classification code for
installations handling inflammable fluids – 3rd
edition July 2005.

Individual Hydrogen Sulphide Sensors: All sensors to be set at 10 ppm and capable of
operating up to a maximum temperature of 55
deg C. A minimum of five operational sensor
heads to be provided with each system.
System/sensor head response times required for
alarm to be triggered from a hydrogen sulphide
clear environment are:

Exposed to a 15ppm capsule the detector reading


shall rise to 7.5 ppm in less than 10 secs
and level out at 15 ppm +/- 10%

Exposed to a 60 ppm capsule the detector


reading shall rise to 30 ppm in less than 10 secs
and level out at 60 ppm +/- 10%

Sensors shall be located at bell nipple, drill floor,


shale shakers, vacuum degasser, suction tanks.

Sirens: Pneumatic: Air supply to have a maximum inlet pressure of


1700 kPa and an operating range of 300 to 500
kPa.

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 5 of 9
Contract QAMP-069 - Provision of Rig & Rig Associated Services

Electric: To comply with explosion proof standards.

A minimum of two siren units capable of


operating simultaneously and actuated from the
same system in different locations on the rig site.

The minimum output from each siren shall be 94


dB(A) at 1 m from the source.

Main Control Panel: Failure of any single detector on the system shall
initiate both an audible and a visual alarm and
shall indicate the failure mode.

Provision shall be made for the system to be


tested both with audible alarms actuated and/or
silenced without the necessity for adjusting the
operational setting. All sensors in the system shall
be calibrated during rig up and tested on a
regular basis. The maximum interval between
test/calibration shall be 14 days.

All audible system alarms shall be 'latched on' and


shall only be capable of being reset by manual
intervention.

Audible alarms shall be permitted to be reset


manually, visual alarms shall only be reset when
the hazardous condition or fault has been cleared.

The main control panel shall be lockable to


prevent unauthorised access.

Provision of Spares / Test Equipment: A full set of electrical fuses shall be provided with
each alarm.

One spare hydrogen sulphide detector head shall


be provided with each system.

15ppm and 60ppm H2S test capsules for system


testing shall be provided.

Full instructions on the test method and


frequency of tests shall be made available with
each system.

All switches and indicator lamps on the main


panel shall be labelled within their respective
function(s) in English.
1.8 Hydrocarbon Gas in Mud Stream Detection Specifications
1.8.1 The Mud Stream Gas Detection system shall comprise of both a Hydrogen Sulphide and
total hydrocarbon gas detector together with a mud agitator and vacuum device to remove
the gas from the mud. This system shall be installed in the flow line or shaker ditch as close
as possible to the bell nipple. The installed system shall not interfere with any other
systems on the rig.
1.8.2 The gas trap should have an air or electrically operated mud agitator housed in a corrosion
proof container for operation in an area with a zone 1 hazardous area classification as

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 6 of 9
Contract QAMP-069 - Provision of Rig & Rig Associated Services

defined by IP Model code of safe practice – Part 15 – Area Classification code for
installations handling inflammable fluids – 3rd edition July 2005. The unit should be such so
as to enable rig site testing of the sensors.
1.8.3 The hydrocarbon detector should have a range zero to one hundred percent of gas by
volume with an accuracy of +/- 1 % for concentrations below 10% and an accuracy of at
least +/- 2% for concentrations above 10%. The Hydrogen Sulphide detector shall have a
range of at least 0 - 25 ppm and shall have an accuracy of at least +/- 2ppm. Neither
detector shall be influenced by other gases likely to be encountered in the mud stream.
1.8.4 The recording system shall incorporate a recorder that enables recording of both Hydrogen
Sulphide and total hydrocarbon gas independently, with a chart recorder which has two
colour pens and an uninterrupted recording duration of at least one day.
1.8.5 Alarms shall be specified according to the following list:
- An audible and visual gas alarm (Hydrogen Sulphide and hydrocarbons) shall be
available for alerting the driller on the rig floor only. The siren may be air or electrically
operated.
- Failure of any part of the system shall initiate an alarm and indicate the failure mode.
- Provision shall be made for the system to be tested both with the audible alarms
actuated or silenced without the necessity for adjusting the operational setting.
- All audible alarms shall be "latched on" and can only be reset by manual intervention.
- Audible alarms shall be permitted to be re-set manually, whereas visual alarms shall
only be re-set when the hazardous condition has been cleared.
1.8.6 A hydrocarbon source and a Hydrogen Sulphide generator capable of creating 10 ppm of
H2S at the sensor shall be provided. Full instructions in English on the testing method and
frequency shall be made available on each location. The maximum interval between test /
calibration shall be 14 days.
1.9 Man-riding winch
The man-riding riding system including but not limited to the winch, cable, sheaves shall
be engineered to be one compatible unit complete with the following features:
- Certified for man-riding
- Limited maximum pull of 150 Kgs
- Independent secondary braking system
- Slack line shut - off mechanism
- Control lever returns to neutral automatically when left
- Crown block sheave designed for man-riding (with suitable eyes arrangement for a
safety sling for hooking on to mast for catching the sheave in case of failure)
- Automatic spooling device
- Drum guard
- Upper and lower level limit switches
- Availability of emergency lowering facility i.e. dedicated auxiliary back-up bottle for
hydraulic winches and dedicated auxiliary air receiver for air operated winches.
- Used in combination with secondary safety line (fall arrestor), one Fall arrestor required
at drillers side and one on off driller’s side, hung off such that the arrestor is
reasonable in vertical line above the person at all times.

The man-riding winch shall not be used for any other purpose other than man-riding. The
man-riding winch and pedestal shall be subjected to inspection as per PR-1312 Well
Engineering Equipment Inspection Procedure.

1.10 Top Drive


The topdrive shall be certified for use in Zone 1 or 2 hazardous area (as the case may
be) as defined by the IP Model code of safe practice – Part 15 – Area Classification code

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 7 of 9
Contract QAMP-069 - Provision of Rig & Rig Associated Services

for installations handling inflammable fluids – 3rd edition July 2005. The entire topdrive
unit has to be designed, constructed and certified for this purpose.

- In general the electric motors are to be rated to work in a 55 deg C ambient


temperature rating and protected against explosions by a certified purge and
overpressure system; the purge, overpressure and cooling air has to be suctioned
outside the hazardous area, the exhausting air can be brought outside the
hazardous area, or exhaust inside the hazardous area, but then the exhaust needs
to be equipped with adequate certified spark arrestors as part of the overall Ex
certification.
- The electrical connections, the single wire power cables and the multi core control
cables have to be connected to the electric motor by means of explosion proof
certified plugs and receptacles or fixed installed on terminals in an explosion proof
junction box(es) or in a purged and pressurized connection box as part of the
overpressure system of the motor.
- The auxiliaries installed on the top drive unit, like hydraulic pumps, solenoid valves
also have to be of a certified explosion proof construction.

Electric motors for top drives shall meet specifications described in Article 1.2 of this
document. Company prefers that topdrives made in North America be ATEX certified. In
addition to the above requirement, top drives shall be equipped with a camera (to enable
stabbing in of pin to make connections) certified for use in hazardous area Zone 1 or 2 as
defined by IP Model code of safe practice – Part 15 – Area Classification code for
installations handling inflammable fluids – 3rd edition July 2005. Certification
requirements for the camera shall be the same as the certification requirements of
electric motors.

The TDS shall also be able to make controlled Left hand turns to enable string back-off or
fishing with a left-hand string.

Soft torque system for Top drive: The system should be compatible with the
installed TDS. After commissioning the system should be surveyed & inspected yearly.

1.11 Rotary Table


Rotary table shall be fitted with a suitable braking system to arrest uncontrolled release
of back-torque when the rotary table stalls. A mechanical lock shall be installed on the
rotary table to arrest movement in both forward and reverse directions (e.g. when
making up and breaking up bit). Rotary table shall be equipped with a split type master
bushing made of solid steel (hollow steel is not acceptable). Insert bushings shall be
available to accommodate slips for running pipe sizes ranging from 1.99” to 20”. The
master bushing and insert bushing shall be flush with remainder of the rig floor to avoid
trip hazards. There shall be a provision for locking the insert bushing to the master
bushing. There shall be a provision for locking the Kelly bushing to the master bushing.
The rotary table shall be equipped with a table torque sensor that reads “True Torque” in
Nm or daN.m. Read-out of “Relative Torque” in % torque only on mechanical rigs is not
acceptable. Readout of rotary torque in DC amps only on electrical rigs is not acceptable.

1.12 Gooseneck
The wireline entry port on the Gooseneck of the swivel shall be non-threaded type. A 3”
FIG 1502 WECO connection shall be used for the gooseneck wireline entry. The wireline
entry port shall have a minimum ID of 3”. No NPT or any threaded connections shall be
acceptable. This shall be applicable for both kelly and topdrive rigs.
1.13 Rig and Campsite Accommodation
All doors in the caravans at the rig and rig campsite including but not limited to offices,
toilets, mess, recreation room, personnel accommodation shall be equipped with

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 8 of 9
Contract QAMP-069 - Provision of Rig & Rig Associated Services

hydraulic door dampeners / closers. Door restraints (e.g. rubber, springs) in lieu of the
above are not acceptable.

Section C4, Scope of Work – Appendix 6, Equipment list & specifications Page 9 of 9

You might also like