You are on page 1of 11

DE-93-1 2-3

ENERGY REQUIREMENTS AND


POTENTIAL SAVINGS FOR HEATED
iNDOOR SWiMMiNG POOLS
C.C. Smith, P.E. R.W. Jones, P.E. G.O.G. LSf, Ph.D.
MemberA SHRAE Member ASHRAE

ABSTRACT indoor pool and their application to prediction of energy


savings by use of pool covers are presented.
In a series of extended tests, the rate of evaporation Evaporation rates were determined by precise measure-
from the quiet water surface of a large indoor swimming ments of water level in an unoccupiedpool over sufficient
pool has been measuredand correlated with air and water time intervals (18 to 68 hours) to achieve evaporation errors
temperature and air humidity. Precise measurements of no larger than 2%. Rates determined by level change
change in water level and of steam consumptionin the pool measurements were closely confirmed by simultaneous
water heater were both used to determine evaporation rates. measurementsof rates of heat supply to the pool water. The
Goodagreement of the two methods was observed. results confirm the form of the ASHRAE equation and the
The form of the evaporation rate equation published in dependenceof evaporation rate on the difference in vapor
the 1991 ASHRAEHandbook--HVAC Applications was pressure of water at pool temperature and at the dew point
confirmed. Actual evaporation from the quiet water surface of air in the natatorium. The rate of evaporation from an
varied from O. 020 to O. 055 lb/(h.ft2). These rates are 76% undisturbed water surface was found to be 76 %of the rate
of those obtained by use of the published equation at the obtained by use of the ASHRAE equation, with a standard
measuredconditions. It is recommended that a 73 % factor deviation of 4.5%. Measurementand correlation of evapo-
be used as a multiplier in the ASHRAE equation for evapo- ration rates from a pool in active use, conditions under
ration from quiet indoor pools at elevations less than 1,000 which considerably higher rates are expected, are planned.
feet above sea level The U.S. Departmentof Energy’s Institutional Conser-
vation Program has launched a nationwide campaign to
iNTRODUCTION Reduce SwimmingPool Energy C_osts, or RSPEC. The
initiative will focus awareness on the energy consumption
The design and operation of heating and ventilating and operating costs of the nation’s 5.9 million pools and
equipmentin a natatorium depend on accurate knowledgeof spas. Market-ready energy efficiency and renewable energy
the rate of water evaporation from the swimmingpool products will be supported through information and technol-
surface. That information is also necessary for predicting ogy transfer to institutional and commercialpool owners.
water-heating requirements and for the design of energy Programgoals are to reduce pool owners’ operating costs,
conservationfacilities. conserve our nation’s precious resources, and protect the
Energy analysts frequently employ the evaporation environment through the use of conservation and renewable
equation presented in the 1991 ASHRAEHandbook--HVAC energy.
Applications for calculating pool energy loads. This equa- ’/’he measures supported by RSPEC,including hybrid
tion was developed by Carrier in 1918. Other equations solar heating systems, pool covers, and windbreaks, must
have also been proposed. However, there is substantial be adequately assessed before pool owners can make
disagreementof 50 %to 100 %in the application and results informed investment decisions about their use. Accurate
of these equations. ’riffs disagreementlikely occurs because methods to calculate pool energy loads before and after
equations have been based on the results of tests with small measure implementation must be available. Since evapora-
evaporating pans rather than on direct measurement of tion is the primary source of heat loss in pools, typically
water loss in swimmingpools. accounting for 50%to 70%of the total, its prediction is
The disparity in evaporation equation results causes particularly important.
wide differences in predicted energy savings from pool Heating and ventilation requirements in indoor swim-
efficiency and renewable energy measures. Because of this ruing pools depend heavily on the rate of evaporation of
uncertainty in predicted energy savings, the U.S. Depart- water from the pool surface. Heat must be supplied to the
ment of Energy has sponsored a series of tests to measure water at a rate equal to the loss. Maintenanceof acceptable
evaporation rates in swimmingpools. The procedures and relative humidity in the natatorium, usually about 50%,
results of tests to measureevaporation rates from a quiet, requires removalof that moisture either by ventilation or by

Charles C. Smithis a research scientist and GeorgeO.G.LiJf is professor emeritus at the Solar EnergyApplications Laboratory,
ColoradoState University, Ft. Collins. RandyW.Jones is a mechanicalengineer in the Department
of Energy,DenverSupportOffice,
Denver, CO.
864 ASHRAE
Transactions: Symposia
operation of dehumidification exluipment. If ventilation is specifications and for predicting the reduction in energy use
used, the incoming air must be heated during most of the to be realized by covering the pool.
year at rates dependenton air quantity, prevailing tempera- Energy costs can be substantially reduced by the
ture, and humidity conditions. Moisture removed by placement of floating covers on the water surface whenthe
dehumidification requires electric energy for compressor pool is not in use. Evaporation is prevented and water
operation. The cost of energy for an indoor pool is a large heating is not needed during those periods. Ventilation and
componentof its operating budget, and the potential for air heating can also be curtailed whenthe pool is covered.
savings by use of effective conservation measures is The prediction of energy savings that can be achieved by
substantial. coveting pools is an important factor in determining
The design of heating and ventilating equipment, the whetherthe use of pool covers is cost-effective in specific
prediction of energy requirements, and decisions on energy instances.
conservation proposals require reliable information on pool Evaporation rates have been estimated by using equa-
evaporation rates. In numerousinvestigations, the specific tions based on data obtained in manysmall-scale evaoora-
rate of evaporation has been found to be directly propor- tion experiments reported in the technical literature. The
tional to the difference in vapor pressure of water at pool Carrier equation, published in ASHRAE Applications, is
temperature and at the air dewpoint. The rate also increas- W = (95 + .425v)(Pw -pa)/Y (1)
es with surface air velocity. The widely used evaporation where
formula of Carrier has been published in manyeditions of
the ASHRAE Applications Handbook. W = evaporationrate, lb/0a-ft2);
Most of the published equations, including Carrier’s, v = air velocity at water surface, fpm;
are based on measurementsof evaporation from undisturbed Pw = saturation vapor pressure at water temperature, in.
water surfaces in small shallow pans exposedto streams of Hg;
air at knowntemperature, humidity, and velocity. Evapora- Pa = saturation vapor pressure at the air dew point, in.
tion from large water surfaces such as lakes occurs at a Hg (also partial pressure of water in pool atmo-
lower rate than from small test pans, but the same variables sphere);
have been found to apply. Y = latent heat at pool temperature, Btu/lb.
Although the ASHRAEHandbookhas long stated that
the Carrier equation is applicable to swimmingpools, Other investigators have obtained data that conform
measurements of evaporation in an actual pool under reasonably well with the earlier work and the ASHRAE
controlled and monitored conditions have not been pub- equation, but in someinstances, substantially higher rates
lished. Reports of rates of heat supply to pool water and of have been reported. With few exceptions, previous investi-
condensate collection from dehumidifiers have been pub- gators have correlated their evaporation measurementswith
lished, but variation in operating conditions and lack of equations similar to Carrier’s, differing only in the values
conformity of heat supply and condensate recovery with of the coefficients A and B in the relationship W= (A
actual evaporation rates maketheir use unreliable. Bv)(pw - pa)/Y. Table 1 is a summaryof several reported
Lack of accurate data on evaporation from an actual coefficients, converted to uniformunits.
pool has resulted in ambiguity and disagreement on the Table 1 shows that although there is agreement on the
applicability of the Carrier equation. There are, for exam- factors affecting evaporation rate and on the form of the
ple, discrepancies in the 1987 and 1991 ASHRAE Applica- equation, the measured rates differ as muchas twofold.
tions as to whetherthe equation should be applied to pools Someof the differences are apparently due to variation in
in use or to undisturbed water surfaces. Thesediscrepancies the shape and size of the evaporating surface, factors
need to be resolved, both for reliable heating and ventilating receiving only limited quantitative evaluation.

TABLE1
EvaporationRate Equations
Investiqator ~ear ~ ~ Notes
Carrier 1918 95 .425 (I)
Rohwer 1931 90 .277 (2)
Himus & Hinchley 1924 165 °376
Lurie & Michailoff 1936 117 .468
Meyer (tanks) 1931 ii0 .253 (3)
Meyer (reservoirs) 1931 81 .185 (3)

NOTES:
(I) Equation also in ASHRAE Handbooks,
(2) Based on several hundred measurements in wind tunnel and
outdoor test pans,
(3) Meyer’s e~*atlons based on air velocity at 30 ft. height.
Values of B in table are computed by asstn~ing surface velocity
is one-half the velocity at 30 ft.

ASHRAE
Transactions: Symposia 865
Recent reports from the U.S. and Geunany show supply 100% fresh outdoor air when relative humidity
evaporation rates lower than indicated in Table 1 and large increases to an upper setpoint. Fans are turned off when
differences in the rates from active and inactive indoor relative humidity decreases to a level approximately 5%
pools. Equations that include additional parameters and below the upper setpoint. During testing, humidity in the
nonlinear variation with vapor pressures have also been natatorium was usually within +3%of the average,
proposed. Evaporation was assumed to be equal to mea- occasionally reaching a maximum departure of 5 %. Exhaust
sured condensate recovery from dehumidifiers, but air fans operate simultaneously with air supply fans. Air
leakage, condensation on building surfaces, other water temperature varied from the average by less than 2°F.
losses, and variation in pool conditions adversely affect the
accuracy of the results. Method and Procedure
The current ASHRAE recommendations are to assume
that the equation applies to pools in active use and that Evaporation measurementsby themselves are not useful
evaporation from a quiet pool is about half that rate. Data in verifying or establishing a relationship with other
supporting these recommendationshave not been published, variables unless they are controlled and monitored. The
however. The object of the present investigation has been variables are the rate of air movementacross the water
the procurementof reliable information on evaporation rate, surface, water temperature, air temperature, and air
energy requirements, and conservation potential in indoor humidity. Accurate measurementof those quantities and of
swimmingpools. the evaporation itself provides the information necessaryfor
establishing a reliable evaporation equation.
DESCRIPTIONOF THE TEST FACILITY The evaporation mass. flux from a water surface cannot
be measured directly by practical means. It can be mea-
The facility used for the tests is a modemswimming sured, however, by the liquid volumeloss during the test
pool with a surface area of 4,340 ft 2 in a natatorium 120 period under consideration. At typical conditions in indoor
feet by 110 feet by 20 feet in height. Water temperature is pools, evaporation rates of about 0.04 poundsof water per
normally maintained at 82°F by thermostat, air temperature hour per square foot of quiet water surface maybe expect-
at 80°F, and air humidity at approximately 60%by means ed. At this rate, the water level in a pool will decrease
of humidistat-controlledventilation. Air-to-air heat recovery about one-fifth inch per day. With suitable equipment,
is used requiring 17.5 horsepowerfor fan power. Automatic water levels can be measured to an accuracy of :t:0.002
swimmingpool covers are normally used when the pool is inch, so the evaporation over a one-day period can be
not occupied. measured to an accuracy of 1% to 2%. Other means of
Pool water is circulated by conventional equipment water addition or discharge are monitoredor, as in this test,
through filters and through heat exchangers supplied with prevented.
steam from a central boiler plant. Condensatefrom the pool In a test of 68 hours duration, the pool water level was
water heaters (along with condensate from shower water determined by a micrometer hook gauge rigidly mountedto
heaters) is returned by pumpsto the central boiler plant. the pool side. This gaugeis read visually to 0.005 inch, so
Automatic water makeupto compensate for pool evapora- the 0.52-inch change in level was measured with an
tion is provided, but that feature can be disabled manually accuracy of about 1.5%. In tests of shorter duration, a
to ensure no change in water level other than by evapora- micrometer gauge was used. This gauge has a higher
tion. Side gutters for overflow of pool water drain into the precision adjustment and senses electrical contact with the
recirculation system, but maintenance of the pool level water surface instead of a visual indication of contact. Level
slightly belowthe gutter lip during the measurements avoids observations were repeated until two or more agreed to
the need for returning overflow water through an open within .002 inch. Measurementswere made inside a small
surge tank. cylinder partially submergedbelow the surface to suppress
Condensate from the steam heating system can be any wavemotion during observations (stilling well).
measured by calibrating the automatic steam trap and A second measurement method is to monitor energy
recording the frequency of discharge to the condensate input to the pool water and makecorrections for the small
return pumps. There are, therefore, two methods for quantities of energy dissipated from the pool by other
determining evaporation rate, one being the water level mechanisms(primarily radiant and convective heat losses
change in the pool and the other being the calculation of from the pool surface. The evaporation rate is determined
heat supply rate by measurement of condensate from the by applying the heat of vaporization of water at the pool
pool water heaters. temperature, which, for the testing conditions, was 1,045
Btu/lb.
Temperature and Humidity Control Pool heat input was monitored by weighing the conden-
sate collected from a steam-to-pool water heat exchanger.
~’!
Pool water temperatureis maintainedby a thermostati- ;~i Steamenters the heater as saturated vapor at 19 psi absolute
cally controlled valve on a steam line entering the pool pressure and 225°F. Liquid condensate leaves at 150°F.
water heater. Ventilation is controlled by a humidistat to The resulting enthalpy difference is 1,038 Btu/lb. Conden-

866 ASHRAE
Transactions: Symposia
sate is discharged from a receiver tank by a pump in temperature, and 56% relative humidity, are shown in
response to a level switch. Five condensatedischarge cycles Table 2 and Figure 1. Summarizedin the table are data on
were measured and averaged at 88.6 pounds per cycle. A temperature, humidity, pool water level, water heat supply
digital readout counter was connected to the pumpswitching rate, and measuredand calculated evaporation rate. Figure
contacts, which totaled the discharge cycles during the test 1 showsthe history of water temperature and air tempera-
period. Testing began and ended with the condensate ture and humidity during the Test III period.
receiver empty. Since the hot water heaters serving showers Goodcontrol of temperatures and humidity is evident,
had been turned off, only pool-heating condensate was thereby making possible a meaningful correlation of
admitted to the receiver during the test period. evaporation rates with those parameters. The bottom line in
Air velocity across the pool surface is another variable Table 2 shows the measured hourly rate of evaporation
that must be determined. Since the vdocity is low, a averaged 0.039 pounds per square foot and the evaporation
sensitive methodof measurementwas required. Periodical- 2.
based on an adjusted heat supply rate of 0.044 lb/h-ft
ly, air velocity at the pool surface was measured by Evaporation rates, based on measurementsover short
releasing balloons of neutral buoyancy(helium-filled and periods (as seen in the first three intervals in Table2), are
counterweighted) over the center of the pool and timing not representative because very small errors in measuring
their movement.Measurementswere made when ventilation water levels can be large fractions of the actual level
fans were operating and when they were shut down. changes, and changes of a few tenths of a degree in pool
temperature can account for sizable portions of steam
Temperature and Humidity Measurement condensate (heat supplied) for only a few hours. An error
of only 0.01 inch in measuring the 0.004-foot level charge
So that the pool evaporation rate could be reliably during the first 3.6 hours would result in an evaporation
correlated with the conditions in the pool, high-quality error of 25 %. Similarly, a pool temperature change of only
instruments were used and operating conditions were 0.20F (commonlyobserved) represents about 300,000 Btu
maintained at sufficiently constant levels over the test of stored heat. The average pool heat supply rate is about
periods to validate the computational comparison. Air and 250,000 BtuPa, so evaporation based on steam condensate
water conditions were monitored and recorded at six-minute measurementsspanning only four hours would be in error
intervals using a desktop computer. Pool water and air dry- by almost 30 %.
bulb and wet-bulb temperatures were measured with T-type Errors are minimized, however, over the long periods
thermocouple welded junctions. These temperature sensors used in the tests reported here. Table 2 showsthe develop-
agreed to within 0.5°F with a precision scientific mercury- ment of constancy in evaporation rates determined by both
in-glass thermometer, and the thermocouples agreed with methods.
each other to within 0.2°F. This precision includes the Figure 2 showstotal water evaporated during Test III
electronic signal conditioning and was repeatable during the as measured by the change in pool level and as measuredby
testing period. steam supply to the pool heater. The difference in the two
The primary method of humidity measurement was by results is due to energy factors, whichare described below
obtaining air wet-bulb and dry-bulb temperatures. These in detail. Also shown in Figure 2 is total evaporation
temperature sensors were mountedin the draft of a small computed by use of the ASHRAE equation.
(40-watt) fan, with the wet-bulb sensors located in a wick Air movement at the pool surface, shownin Table 3,
wetted with distilled water. The wet-and dry-bulb sensors was observed three times during Test III, at 3 hours, 29
were located at the pool side, 12 inches above the water hours, and 58 hours. Air movement was in random direc-
surface. A recording hair hygrometer and a mercury-in- tions when the ventilation fans were not operating.
glass sling psychrometer were also used. All methods An estimate of the duration of ventilation time was
agreed consistently within 3 %relative humidity. Periodic made from observing air humidity records (Figure 1).
measurements with a sling psychrometer showed relative Humidity rises whenthe ventilation is off and falls when
humidity variation of about 3 %around the 13001perimeter. the fans are running. It appears that the on and off periods
Pool water temperature was monitored by a single are nearly equivalent, and air movement was equally
thermocouple probe with the sensor tip submerged four divided between the two conditions. At air velocities in this
inches below the pool surface. Prior to testing and twice range, the ASHRAE equation shows ah almost negligible
during the test period, a mercury-in-glass maximum/mini- effect on evaporation (a 2% increase for a doubling of
mumthermometer was moved throughout the pool water velocity), so an average air velocity of 5.3 fpmwas used as
volumeto determine temperature variation. The thermome- a constant value in the ASHRAE calculation.
ter indicated constancyof temperature within 1 °F. Tests at four other pool operating conditions were
conducted for varying periods of time. Table 4 contains a
RESULTS summaryof the conditions and results of all five evapora-
tion tests. All conditions for these tests were identical
Detailed results of Test III, conducted for 68 hours except for air temperature and relative humidity. As
under conditions averaging 82°F pool temperature, 78 °F air described above, outdoor air was automatically supplied

ASHRAE
Transactions: Symposia 867
TABLE2
Resultsof PoolEvaporation,
Test III
ELAPSED TEMPERATURES - DEG F AIR RH ~APOR PRESSURE-IN MM HG
TIME HRS AIR DB AIR WB WATER WATER AIR DIFF

2.4 78 67 83 59 i. 14 0.57 0.57


3.6 78 68 83 61 I. 14 0.60 0.54
8.7 79 67 83 57 I. 14 0.55 0.59
20.9 76 67 83 64 i. 14 0.58 0.56
26.8 77 65 83 55 I. 14 0.52 0.62
28.9 78 66 83 55 i. 14 0.54 0.60
32.4 80 68 83 57 i. 14 0.58 0.56
45.4 77 67 83 61 i. 14 O. 58 0.56
52.2 77 68 83 65 i. 14 0.61 0.53
56.4 78 66 83 55 I. 14 ,0.54 0.60
68.4 76 66 83 59 I, 14 0.52 0.62

.LEVEL CUM EVAP* ,EVAP RATE* CUM HEAT** HEAT EVAP** EVAP RATE**
LBS 2
LB_L_~HR-FT 2BTU/__~T 2
LBS/HR-F~T

0.686
0.683 813 0,078 241 231 0.092
0.682 1084 0.069 321 306 0.081
0.680 1626 0.043 642 605 0.066
0 ¯ 672 3794 0.042 1231 1141 0.052
0 ¯ 669 4607 0.040 1633 1518 0.054
0. 667 5149 0.041 1753 1629 0.054
0.666 5420 0.039 1954 1815 0.053
0. 658 7588 0.039 2623 2428 0.051
0.654 8672 0.038 2804 2580 0.047
0.650 9756 0.040 2829 2586 0.044
0.643 11696 0.039*** 3480 3186 O.044*ee
~_o~/~:
Determined by water level change
Determined by adjusted heat supply rate
Final results of test

Air ’-- Pool

1oo
# 9O
I
8 8o
~ 7o
~ 6o
~ ~o

~ 3o

10
I I J I _.J.~_m.L__ I

8 16 24 32 40 48 56 64 72

Hours From Start of Test

Figure The recorded trends of temperature and relative humidity during a 68-hour test period (Test III).

868 ASHRAE
Transactions:Syrnposia
-- Heat Input ...... Level Change --- ASHRAE
to Pool of Pool Calculation

2
0
6 12 18 24 30 36 42 48 54 60 66 72

Hours From Start of Test

Figure 2 Total evaporation (pounds of water) trends during a 68-hour testing period (Test III in Table 4*). (*Adjusted
for pumpenergy and heat losses other than evaporation.)

TABLE3
Observations
of Air Movement OverPool Surface
(fpmair velocity)

Space Ventilation Status


Time of Fans Fans
Observation Off O__n_

3 Hrs. 3 9
29 Hrs. 1 I0
58 Hrs. 2 7

TABLE4
AverageTest ConditionsandResults
2)
Evap. (Lb/Hr-Ft
Test No. Temperatures Rel. Vapor Pres.
[Hrs Air Air WB Pool H~n~idity Difference Level Heat
Duration] (°F) (%) (In-Hg) Change Supply

I [18] 82 76 83 72 .31 .020 .022


II [18] 82 74 83 73 .35 .024 .028
III [68] 78 66 83 57 .59 .039 .044
IV [24] 73 61 83 53 .70 .050 .057
V [20] 71 59 83 51 .75 .055 .059

ASHRAE
Transactions: Symposia 869
wheneverthe humidity reached a high limit and switched Evaporation Determination by Pool
off whenthe humidity reached a low limit. Air temperature Heat inputs and Losses
was not controlled, but it remainednearly constant through-
out each test period. Evaporation rates calculated by the use of measured
Also shownin Table 4 are evaporation rates determined heating energy input to the pool are shownin Figure 3 by
by measurementof pool-level changes and by measurement circled points. These measurementsserved as useful checks
(and adjustment) of heat supply rates. A nearly threefold on the accuracy of the water-loss measurements. Correc-
variation is observed, corresponding to a similar range in tions for heat transfer by convection and radiation and for
vapor pressure differences. Also evident is satisfactory pumpenergy addition and pool water temperature change
agreement between these two completely different methods were made.
for determining evaporation rates. 11ae steam condensate measurement required prior
Relative humidity and air temperatures in Table 4 cover calibration of the steam trap discharge quantity and the
a comparatively wide range of vapor pressure differences. measurement of the temperatures of entering steam and
Figure 3 is a presentation of measuredevaporation rates as leaving condensate. The condensate discharge was weighed
a function of the vapor pressure differences. Evaporation on a beambalance scale five times. Quantities ranged from
results based on pool level change and on heat supply rate 87 to 90.5 lbs, with an average of 88.6 lbs. This range
in the five tests are shownas data points. Also presented in indicates a potential error of 3.5 lbs, or 3.9 %.
Figure 3 is the straight-line ASHRAE relationship. The accuracy of a scientific mercury-in-glass thermom-
Alinear fit to the level measurement data (cross points) eter for measuring steam and condensate temperatures was
is shown in Figure 3; the correlating equation is W :hl°F, resulting in a potential overall enthalpy error of
0.19 %. The combined maximumerror in the heat supply
= 74(pw - pa)/Y. The difference in slope of the two lines
indicates that the ~active pool evaporation rate is 76 %of measurements was thus 4.1%.
the ASHRAE prediction. Other heat losses (and gains) contribute to the small
At the low air velocities in an indoor pool, the influ- difference between the results of the two measurement
ence of the velocity term is almost negligible. Insufficient methods. For the conditions in the pool and natatorium, the
velocity variation preventedits evaluation in this investiga- following heat-transfer equations were used.
tion, but in subsequent measurements on an outdoor pool
(Jones et al. 1993), the coefficient of the velocity term was Radiation from pool to natatorium surfaces:
found to be 0.36. Using that value and an average air
velocity of 5.3 fpmduring the indoor tests, the evaporation qr = 0.173 × Io-SA~F(T~- 714w)
rate equation is where

W = (72 + o36V) (Pw-Pa) /Y" qr = radiant heat-transfer rate (Btu/h.ft2);

+ Level 0 Energy Input --- ASHRAE


Measurement Measurement * Calculation
0.08

0.07

0.06

0.05

0.04

0.03

0.02
~.~’ Toot polnto from Table IV
0.01

0.00
0.00 0.I0 0.20 0.30 0.40 0.50 0.60 0.70 0.80
Vapor Pressure Difference-In Hg

Figure 3 Evaporation rate test results from level (water loss) and energy input measurementscomparedwith ASHRAE
equation as a function of water vapor pressure difference.* (*Adjusted for pumpenergy and heat losses other
than evaporation.)
’ 870 ASHRAE
Transactions: Symposia
surface area of pool water (ft2); It is possible, also, that the consistently higher values
water surface emissivity, 0.9; of evaporation based on steam condensate measurement
radiation shape factor from pool surface to sur- could have been the result of a small and unmeasured
roundings, 1.0; amountof moisture in the saturated steam supply.
pool water temperature (R);
temperature of walls and ceiling (R). Error Potential in ASHRAE
EvaporationDetermination
The computedradiation loss term ranged from 1 to 11
Btu/h.ft 2, corresponding to 4%to 15%of the total heat Error in determiningthe coefficients in the evaporation
supply rate. equation is dependent on temperature sensor error and the
averaging of temperatures across the entire pool area
Convection from pool surface to air over pool: relative to the values at the sensor locations.
The temperature sensors (T-type welded thermocouple
junctions) were placed in a temperaturebath prior to testing
qc = hh(tp - ta), and agreed to within ±0.2°F. The air dry-bulb and wet-
1/ bulb temperature variation around the pool perimeter was
h 3,
= 0.22(tp-ta)
observed to be less than 2°F. Pool water temperature
where variation was within I°F. Airflow movementcould be in
error by 3 to 4 feet per minute, as seen from Table 3.
qc = convectiveheat-transfer rate (BtuPa.ft2), By combining the above errors in the ASHRAE
h = convectionheat-transfer coefficient (Btu/h.ft 2. °F), equation at a typical condition (pool temperature83 °F, air
tp = pool water temperature (°F), dry-bulb temperature 78 °F, air wet-bulb temperature 67 °F,
ta = air temperature over pool (°F). and air velocity 7.5 fpm), the error in the compu~xl
evaporation rate is 4.2%.
In addition to the above losses, there is an estimated
2.
loss from the heat exchangerand pipeworkof 0.1 Btu/h.ft DISCUSSION
Finally, there is an energy gain resulting from recirculation
pumpwork equal to 3.9 BtuPa.fi 2. The combined energy Evaporation rate accurately measured by water-level
adjustments for each test condition are reflected in the change in an unoccupied indoor swimmingpool has been
values shown in Table 4 and Figure 3. An example of found directly proportional to the difference in vapor
calculated losses and gain is represented in Table 5. pressure of water at pool temperature and at air dew point.
The small difference between evaporation rates deter- The proportionality constant is 76 %of the value determined
mined by water level change and heat supply rate, ranging by Carrier in pan evaporation tests with undisturbed water.
between8 %and 15 %, provides confidence in their validity. Identification of the sources of differences amongthe
Inaccuracies in estimating radiation, convection, and the publishedrelationships is not within the scopeof this paper,
fractional degree variation in temperatureof a large massof but one major factor is evident. The size of the evaporating
pool water are considered principal sources of the differenc- surface in most of the previous investigations was very
es. For example, a pool temperature rise of only 0.2°F small, from a few square inches to a few square feet. Edge
from the start to the end of a 24-hour test represents more effects, airflow instabilities, and other factors are likely to
than 300,000 Btu, corresponding to 12,500 BtuPa. This have contributed to the differences. Measurementson larger
quantity is almost 6 %of a typical hourly heat supply rate outdoor water surfaces, although not as accurate, have
of 220,000 Btu. shown lower rates than found in pan tests. Estimates of

TABLE5
EnergyGainsandLossesunderTypical
Conditions
in IndoorPool
Pool Temperature 83°F
Air Temperature 78°F
ceiling Temperature 66°F (Estimated)
Steam Supply Pressure, psia 19 psia
Steam supply temperature 225°F
Condensate discharge temperature 150°F
Condensate rate .0483 ibs/hr
Total heat supply 50.1 Btu/hr - Sq Ft
Radiation Loss 5.7 Btu/hr - Sq Ft
Convection loss 2.4 Btu/hr - Sq Ft
Piping heat loss 0.I Btu/hr - Sq Ft
Recirculation pump energy gain (3.9 gain) Btu/hr - Sq

Evaporation heat loss, by difference 45.8 Btu/hr - Sq Ft

ASHRAE
Transactions: Symposia 871
natural evaporation from ponds and reservoirs have, a range of altitudes (including data for Fort Collins and for
therefore, long been based on the use of reduced values of sea level), corrected for wind velocity differences in an
the rates measuredin small-scale tests. Meyer(1942), for analysis by Hickox (1944), showedagreement with Millar’s
example, recommended use of a coefficient for lake finding of evaporation rate proportional to the -0.25 power
evaporation of 74 %of that for standard pans. of atmospheric pressure. Applyingthis relationship to the
"l~ere can be no better facility for determiningevapora- Fort Collins data obtained at a 24.8-inch barometer yields
tion rates in swimmingpools than a pool itself. Direct a sea level rate 95.4% of the Fort Collins rates. The
applicability to other pools of accurately measuredwater equation applicable at low elevations (below approximately
losses in a test pool is clear. The departure of the value of 1,000 ft) is then:
the coefficient from the value found by Carrier with small
W = (69 +.34V) (Pw-Pa) /Y"
test pans is the result of the large difference in surface area
of water. Whetherthere maybe a quantitative relationship This rate is 73 % of that obtained by direct use of the
betweenwater surface area and specific evaporation rate is unadjusted Carrier/ASHRAEequation.
beyondthe scope of this paper. It is recommended that the
relationship for this 4,300-square-foot pool be considered CONCLUSIONS
applicable to all indoor pools larger than about 1,000 square
feet. 1. At knownwater temperature, air temperature, and air
Logic and limited evidence indicate that evaporation humidity, the rate of evaporation from an undisturbed
from a pool in active use is higher than from a quiet water water surface in an indoor swimming pool can be
surface. Waves,water splashes, wet deck areas surrounding reliably calculated using the equation
the pool, and wet skin of swimmersin and out of the pool
W = A(C+ .35v) (Pw-Pa) /Y,
all increase effective evaporating area. Averagesurface air
velocity mayalso increase, but that effect, if any, is small. where
The principal factor is increased wetted surface, primarily
deck space across whichpool users travel in and out of the W = lbs evaporated per hour;
pool. Althoughhighly variable, that area mayapproach half A = surface area of water, ft2;
the pool water surface. At a comparable rate from such C = a coefficient dependent on barometric pres-
areas, evaporation could be 50 % higher than whenthe pool sure, with a measuredvalue of 72 at 5,000 ft
is not in use. Condensatewas collected from dehumidifiers elevation and a computedvalue of 69 at sea
in Germanpools at substantially higher rates whenthe pools level;
were in use than whenidle, but quantifying the results is v = air velocity at water surface, in the range of 1
speculative. to 10 fpm;
It should be recognized that the energy for evaporation Pw = vapor pressure of water at pool temperature,
that occurs outside the pool itself, as from wet deck areas, in. Hg;
is not drawn from the pool water but rather from the Pa = vapor pressure of water at air dew point, in.
ventilation air. The increase in pool water heat supply is Hg;
probably the result of the greater area of turbulent water Y = latent heat of vaporization at pool temperature,
surface and possibly higher local velocities of air in contact Btu/lb.
with the water. 2. The rate of evaporation from an undisturbed water
Evaporation rates found in this investigation apply surface in an indoor pool is 76 %(73 %at sea level)
directly to requirements for energy, water, ventilation, and the rate computed by using Equation 1, page 4.7, of
heating during closed periods, typically 40%to 60%of the the 1991 ASHRAEHandbook(and the identical equa-
time. If pool covers are applied to the water surface when tion in earlier editions of ASHRAE Applications).
the pool is not used, the resulting energy savings can be 3. Evaporation rates measured by precise pool-level
accurately predicted by use of the equation developedin this differences at closely controlled conditions during five
investigation. For design of pool heaters, air exhaust/sup- tests of 18 to 68 hours duration were determined with
ply/heating facilities, dehumidifiers, and heat recovery an average error of 2 %.
units, peak evaporation rates must be knownor estimated. 4. Least-squares correlation of measuredevaporation rates
Measurements are clearly needed. Until the data are with vapor pressure differences shows a standard
available, it is recommendedthat evaporation rates from deviation of 4.5 %.
pools in typical active use be estimated 50%higher than ~ 5. Average departure of rateof evaporation by heat
from unoccupied pools under the same temperature and supply measurement from the rate measured by pool-
humidity conditions. level changeis 12 %. It is concludedthat the closeness
Although a total pressure term is seldom included in of this agreementjustifies the determinationof evapora-
evaporationrate equations, limited studies of its effect have tion rates from indoor pools by accurate measurement
been made by Rohwer(1931), Russell, Millar (1937), of the heat supply and water temperature change,
Sleight. Rohwer’sextensive evaporation measurementsover together with estimates of other energy losses.

872 ASHRAE
Transactions: Symposia
6. The small coefficient of the air velocity term in the Meyer. 1942. Evaporation from lakes and reservoirs.
developed equation was not evaluated because of inade- Minnesota Resources Commission, June.
quate meansfor achieving significant variation in that Millar, F.G. 1937. Evaporation from free water surfaces.
parameter. The 0.38 value shown in the equation is Canadian Meteorological Memoirs 1: 43.
based on subsequent measurements in an outdoor pool NSPI. 1987/88. 1987 and 1988 swimming pool and spa
where the effects of air velocity variation could be industry market reports. National Spa and Pool Insti-
determined. tute.
7. Minimumventilation rates necessary for maintenanceof Reeker, J. 1971. Water evaporation in indoor swimming
constant natatorium humidity whenthe pool is not in pools. Gesutulheits-Ingenieur, March, pp. 72-80
use can be reliably determined by use of the evapora- (Germany).
tion rate equation developedin this investigation and by Rohwer, D. 1931. Evaporation from free water surfaces.
Equation 2, section 4.7, of the 1991 ASHRAEHand- Tech. Bulletin No. 271, U.S. Dept. of Agriculture.
book. Correspondingair-heating requirements can then Root, D. 1983. Howto determine the heat load of swim-
be determined by use of outdoor and indoor air temper- ruing pools. Solar Age, November,p. 20.
ature. Shah, M.M.1990. Calculated evaporation from swimming
8. Variation in pool conditions monitored at bsix-minute pools. Heating, Piping, a~l Air Conditioning, Decem-
intervals throughout a test period resulted in maximum ber, p. 103.
departures of 5.5% from the average vapor pressure
difference. Computedand measured evaporation rates APPENDIX
were, therefore, essentially constant in each test.
9. Measurementsof pool-level change over periods of at Exampleof Evaporation Reduction and Cost
least 16 hours by use of micrometer gauges can pro- Savings by Use of Pool Cover
vide evaporation rate results with maximum errors less
than 2%. PoolStatistics
10. The equations developed in this investigation maybe Pool surface area 23,000 ft
used with confidence in predicting reductions in water- Surrounding deck area 21,000 ft
heating and air-heating requirements by use of covers Water temperature 800F
on indoor swimmingpools. Air temperature 80°F
Relative humidity in natatorium 50 %
REFERENCES Hours closed per year 4,500
Annual average atmospheric temperature 45°F
ASHRAE.1991. 1991 ASHRAEhandbook--HVAC applica- Powerto exhaust and fresh air fan 10 kW
tions, p. 4.7. Atlanta: AmericanSociety of Heating, Heat source, natural gas 3
1,000 Btu/ft
Refrigerating and Air-Conditioning Engineers, Inc. Average air movementover water surface 5 fpm
Biasin, V.K., and W. Krumme.1974. Evaporation in an Roomair dew point (from psychrometric chart) 61.5°F
indoor swimmingpool. Electrowarme International, From vapor pressure tables, at 80°F Pw = 1.033 in. Hg
May, pp. al15-a129 (Germany). at 61.5°F Pa = 0.550 in. Hg
Brambley, M.R., and S.E. Wells. 1983. Energy conserva- (Convenient source of vapor pressure data is tables in
tion measures for indoor swimmingpools. Energy8(6): ASHRAEFutMamentals. )
403.
Carrier, W.H. 1918. The temperature of evaporation. Calculations
ASHVETransactions 24: 25.
Hickox, G.H. 1944. Evaporation from free water surfaces. Water-Heating Saving
Papers, AmericanSociety of Civil Engineers, p. 1297,
October. Using evaporation equation, W= (72 + .36v)(Pw pa)/Y,
Himus, G.W., and J.W. Hinchley. 1924. The effect of a Evaporation heat = (72 + .36 × 5)(1.033 - 0.550)
current of air on the rate of evaporation of water below 235.7 Btu/h.ft
the boiling point. Chemistryand Irulustry 43: 840. Water heating saved by covering pool = 35.7 × 3000 ×
Jones, R., C.C. Smith, and G. Lrf. 1993. Measurement 4500 = 483 mmBtu per year
and analysis of evaporation from an inactive outdoor
swimmingpool. Proceedings of the 1993 Conference of Air-Heating Saving
the AmericanSolar Energy Society, p. 399.
Lrf, G.O.G. 1991. Evaporation from swimming pools. Evaporation rate = 36.2/1048 × 3000 = 103.6 lb/h
Letter in Heating, Piping, and Air Conditioning, Humidity ratio at 82°C, 50%RH= 0.0117 lb/lb
October, p. 39. Humidity ratio winter average = 0.0020 lb/lb
Lurie, M., and N. Michailoff. 1936. Evaporation from free Minimumventilation rate = 103.6/[60 × .075 × (0.0117
water surfaces. Ind. atut Eng. Chem.28(3): 345. - .0020)] = 2,373 cfm

ASHRAE
Transactions: Symposia 873
Minimumair heating saved = 60 x 2373 x 0.018 x (82 DISCUSSION
- 45) x 4500 = 427 mmBtu/yr
S.A. Sherif, Assodate Professor, Department of Me-
MinimumTotal Heat Saving chanical Engineering, University of Florida, Gainesville:
The accuracy of the water level measurementsin the pool
483 mm+ 427 mm= 910 mmBtu saved/yr seems to be quite high (+0.02 in.). Can the authors speak
At 70%combustion efficiency, natural gas saving = 910 moreto this issue and describe the instruments they used to
ram/100,000 × 0.70 = 13,000 ccf/yr carry out the level measurements?
Value of gas saved at $0.50/ccf = 0.5 × 13,000 =
$6,500/yr C.C. Smith: Measurementsof water level are taken by a
micrometerwith a scale readable to .001 inch. The microm-
Electricity Saving eter is securely mountedto the side of the pool and is inside
a stilling well to suppress waves. The sharp tip of the
Fan energy reduction = 10 kW × 4500 h = 45,000 micrometerpoint is sprayed with silicon oil to reduce water
kWh/yr adhesion. Thepoint is lowereduntil it visually contacts the
Value of electric saving at $0.05/kWh= $2,250/yr water surface. The measurementis repeated until consistent
readings are found to ±0.01 inch.
Total Annual Energy Saving

Total saving = $6500 + $2250 = $8750/yr

Alternate Saving Based on Ventilation Rate


in ASHRAE Standard 69-1989, p. 5

Recommendedventilation rate = 0.5(3000 + 6000)


4500 cfm
Air heating saving based on ASHRAE rate:
60 x 4500 x 0.018 x (82 - 45) x 4500 = 809
Btu/yr
Total heat saving = 809 mm + 483 mm = 1292 mm
Btu/yr
Value of total heat saving = 1292 nun X .50/70,000 =
$9,229/yr
Total gas and electricity saving = $9229 + $2250 =
$11,479/yr

Economic Evaluation

At typical installed cost of fully automatic swimming


pool covers providing 95 %suppression of evaporation when
pool is not in use,

$36,000 total installed cost/0.95 × $8750= 4.33 years


simple payback
Based on ASHRAEStandard 69-1989, $36,000/0.95 ×
$11,479 = 3.30 years simple payback

NOTE:

Savings resulting from reduction in water treatment costs


(primarily reduced chlo6ne requirements) and from reduced
moisture damageto structure and equipment not included.

874 ASHRAE
Transactions: Symposia

You might also like