TECHNICAL SPECIFICATION
Medium Voltage, Single Core XLPE-Insulation Cable
12/20 (24) kV N2XSY (Cu/XLPE/CWS/PVC)

AGREEMENT

DATE

SIGNATURE

Rev. Note Designed by Checked by Approved by

0
TECHNICAL SPECIFICATION
Medium Voltage, Single Core XLPE-Insulation Cable
12/20 (24) kV N2XSY (Cu/XLPE/CWS/PVC)

1. Applicable standard
The construction of cables shall be based on SPLN 43-5-3 : 1995.

2. Construction details and materials

Item Details and materials

Compacted circular stranded of annealed copper wires, complied with SPLN 41-1.
Conductor
All inter-sticks of the conductor shall filled with water blocking powder.

Extruded semi-conductive compound, bonded type.


Conductor screen
Minimum average thickness 0.5 mm.

Extruded of 90°C grade natural XLPE (Cross-linked Polyethylene).


The average thickness of the insulation shall be not less than the nominal value given in the
Insulation
attached table and the minimum thickness at any point shall be not fall bellow 90% of the nominal
value by more than 0.1 mm.

Insulation screen Extruded semi-conductive compound, strippable type. Minimum average thickness 0.5 mm.

Semi-conductive One layer of semi-conductive water blocking tape applied helical over the insulation screen
water blocking tape (black-colour).
Annealed copper wires applied concentrically and uncoated copper tape applied helical open lap as
Metallic screen
a binder.
Non-conductive One layer of non-conductive water blocking tape applied helical over the metallic screen (white –
water blocking tape colour).

Extruded of Red PVC (Polyvinyl Chloride).


The average thickness of the outer sheath shall be not less than the nominal value given in the
Outer sheath
attached table and the minimum thickness at any point shall be not fall below 85% of the nominal
value by more than 0.1 mm.

3. Cable identification
One lines of a distinctive marking shall be performed continuously on a suitable place of the surface of the
outer sheath by embossing or printing.

SPLN 43 VOKSEL N2XSY 1 x 50 cm/16 mm² 12/20 kV <>LMK<>

4. Test
The following test shall be carried out on complete cable and sample in accordance with SPLN 43-5-3 : 1995
and the manufacturer standard.

1. Construction test
2. Conductor resistance test
3. AC voltage test
4. Partial discharge test

www.voksel.co.id All Rights Reserved Copyright © 2016 Page 1 of 3 pages


5. Packing
The completed cable shall be wound on a strong reel and lagged securely in order to protect from any
possibilities damage during transportation.
The following information shall be provided on the outside of the flange:
1. The name of the manufacturer
2. The type, voltage grade and size of the cable
3. Cable length
4. Net & Gross weight
5. Arrow showing the direction for rolling
6. The indication of the cable end position
7. Drum number
The cable end shall be sealed with end cap in order to avoid water penetration.

www.voksel.co.id All Rights Reserved Copyright © 2016 Page 2 of 3 pages


6. Construction & Electrical table

Type of cable Unit Proposed & Guarantee

CONSTRUCTION DATA
Type of cable N2XSY (Cu/XLPE/CWS/PVC)
Rated voltage kV 12/20 (24)

Conductor
- Material - Annealed copper wire

- Shape of conductor - Round compacted stranded


- Number of core no 1 1 1

- Nominal size mm² 50 70 240

- Approximate diameter of conductor mm 8.3 10.10 18.0

Conductor screen
- Material - Type bonded semi-conducting compound

- Minimum thickness mm 0.5 0.5 0.5

Insulation
- Material - XLPE

- Nominal thickness mm 5.5 5.5 5.5

Insulation screen
- Material - Type strippable semi-conducting compound
- Minimum thickness mm 0.5 0.5 0.5

Separator under metallic screen


- Material - Swelling semi-conductive water blocking tape

Metallic screen
- Material - Annealed copper wires

- Cross sectional area mm 16 16 25

Separator over metallic screen


- Material - Swelling non-conductive water blocking tape

Outer sheath
- Material - PVC

- Nominal thickness mm 3.0 3.0 3.0

- Color - RED

Approximate overall diameter of cable mm 32.0 34.0 41.5

Approximate weight of cable kg/km 1,325 1,575 3,470


ELECTRICAL DATA
Max DC resistance of conductor at 20°C Ω/km 0.387 0.268 0.0754

AC voltage test for 5 minutes (2.5 U0) kV 30

Partial discharge (1.5 U0) pC/kV 10/18

Max. Current carrying capacity at 20 °C (In ground) Flat spaced A 203 246 470

Adiabatic Short circuit current of conductor for 1 second kA 7.15 10.02 34.34

Capacitance µF/km 0.209 0.238 0.363

Minimum allowable bending radius xD (Outer Diameter) mm 15D 15D 15D

www.voksel.co.id All Rights Reserved Copyright © 2016 Page 3 of 3 pages