HARMONIC FILTERING.
MEDIUM AND HIGH VOLTAGE SOLUTIONS.
This document may be subject to changes.
Contact ARTECHE to confirm the characteristics and
availability of the products described here.
Moving together
CONTENTS
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
1. METAL ENCLOSED
CAPACITOR BANKS AND
HARMONIC FILTERS
4 Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
1. METAL ENCLOSED CAPACITOR BANKS AND HARMONIC FILTERS
› Metal Enclosed
Systems.
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions 5
1. METAL ENCLOSED CAPACITOR BANKS AND HARMONIC FILTERS
APPLICABLE STANDARDS
ARTECHE standard designs meet among
others, with the two main international
standards:
› IEC 60871, IEC 60549.
› IEEE STD 18 and CSA ratings.
› Metal Enclosed
Systems.
6 Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
1. METAL ENCLOSED CAPACITOR BANKS AND HARMONIC FILTERS
GENERAL DESCRIPTION
POWER CAPACITOR: SWITCHING ELEMENTS:
ARTECHE supplies single phase or three Switching elements are specially designed for
phase capacitors with stainless steel cases. handling capacitive loads. ARTECHE offers
Capacitors are free of PCB’s and available in the best technical solution on project basis,
powers from 50 up to 1.000 kVAr (individual and supplies capacitor switches, contactors,
units). These capacitors can be either or circuit breakers depending on the specific
externally fused or internally fused. Each unit application.
has a discharge resistor to reduce the voltage
between the terminals to 50 V in five minutes SURGE ARRESTERS:
or 75 V in ten minutes according to IEEE and
Surge Arresters protect the capacitor banks
IEC standards respectively.
from voltage surges and lightning.
TUNING REACTORS:
ZERO VOLTAGE CONTROL:
Tuning reactors are added in harmonic filters.
Available with capacitor switches, this type of
These reactors are generally iron core type
technology is not a standard design and must
and are an integral part of the capacitor bank.
be requested specifically. Capacitor switching
As an option, ARTECHE is able to supply air
phenomena are minimized.
core reactors which are enclosed separately
upon request.
GROUNDING SWITCH:
INRUSH REACTORS: The grounding switch ensures that capacitors
are fully discharged for maintenance.
Inrush reactors are necessary in the capacitor
banks for the purpose of limiting inrush
CONTROL AND PROTECTION SYSTEM:
currents and back-to-back switching events.
The main protections are neutral unbalance
CURRENT LIMITING FUSES: and overcurrent protection. Other schemes
are available.
These are provided for the protection of short
circuit currents, and internal faults in the
capacitors.
INSTRUMENT TRANSFORMERS:
Automatic capacitor banks require voltage
and current signals which may be provided
by the customer or obtained from the bus
through instrument transformers already
in place. Current transformers or voltage
transformers can be supplied for neutral
unbalance protection depending on the bank
connection type.
› Power Factor
Correction Capacitors.
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions 7
1. METAL ENCLOSED CAPACITOR BANKS AND HARMONIC FILTERS
TECHNICAL CHARACTERISTICS
CONTENTS
Voltage Up to 38 kV
Frequency 50 Hz or 60 Hz
Fixed
Type Automatic
Automatic Multistep
Enclosure IP or NEMA
› Metal Enclosed
Systems.
8 Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
ARTECHE POWER QUALITY
Customized solutions.
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions 9
2. RACK MOUNT CAPACITOR
BANKS AND HARMONIC
FILTERS
10 Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
2. RACK MOUNT CAPACITOR BANKS AND HARMONIC FILTERS
SUBSTATION SUITABILITY
Capacitor systems for reactive compensation
and harmonic filter systems are available in
rack mount configurations for use in either
covered or open construction substation
applications. Rack mounts are manufactured
with hot zinc immersion galvanized steel or
aluminium.
APPLICABLE STANDARDS
ARTECHE standard designs meet among
others, with the two main international
standards:
› IEC 60871, IEC 60549.
› IEEE STD 18 and CSA ratings.
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions 11
2. RACK MOUNT CAPACITOR BANKS AND HARMONIC FILTERS
GENERAL DESCRIPTION
CAPACITORS: ZERO VOLTAGE CONTROL:
ARTECHE supplies single phase or three Available with capacitor switches, this type of
phase capacitors with stainless steel cases. equipment is not a standard design and must
Capacitors are free of PCB’s and available in be requested specifically. Capacitor switching
powers from 50 up to 1.000 kVAr (individual phenomena are minimized.
units). These capacitors can be either
externally fused, internally fused, or fuseless. INSULATORS:
Each unit has a discharge resistor to reduce
Porcelain station post insulators meet IEC or
the voltage between the terminals to 50 V in
ANSI standards.
five minutes or 75 V in ten minutes according
to IEEE and IEC standards respectively.
STRUCTURE:
CAPACITOR FUSING: Galvanized steel or aluminium
In case of externally fused capacitors, fuses
INSTRUMENT TRANSFORMERS:
used are expulsion type.
Automatic capacitor banks require voltage
TUNING REACTORS: and current signals which may be provided
by the customer or obtained from the bus
For Harmonic filters tuning reactors are
through instrument transformers already
added. ARTECHE supplies reactors with iron
in place. Current transformers or voltage
core or air core as per customer request.
transformers can be supplied for neutral
unbalance protection depending on the bank
INRUSH REACTORS:
connection type.
Are necessary in the capacitor banks for the
purpose of limiting inrush currents and back- GROUNDING SWITCH:
to-back switching events..
The grounding switch ensures that capacitors
are fully discharged for maintenance.
SWITCHING ELEMENTS:
Switching elements are specially designed for CONTROL CABINET:
handling capacitive loads. ARTECHE offers
Used for capacitor banks or harmonic filters
the best technical solution on project basis,
with automatic control. Can be either outdoor
and supplies capacitor switches, contactors,
or indoor assembled. The main protections are
or circuit breakers depending on the specific
neutral unbalance and overcurrent protection.
application.
Other schemes are available.
CONTROL AND PROTECTION RELAYS:
Multifunction relay, overcurrent, voltage,
neutral, and automatic control functions are
available.
SURGE ARRESTERS:
Surge Arresters protect the capacitor banks
from voltage surges and lightning.
CUT OUTS:
Power main fuses can be used as disconnecting
switches with manual operation.
12 Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
2. RACK MOUNT CAPACITOR BANKS AND HARMONIC FILTERS
TECHNICAL CHARACTERISTICS
CONTENTS
Voltage Up to 245 kV
Frequency 50 Hz or 60 Hz
Internally fused
Fuseless
Service Outdoor
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions 13
3. POLE MOUNT CAPACITOR
BANKS
14 Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
3. POLE MOUNT CAPACITOR BANKS
GENERAL DESCRIPTION
The most effective way of reactive power Light, compact and easy to install, the
compensation is achieved when the capacitor structure that supports the equipment
banks are distributed over the entire electrical represents an important advantage when few
system, the same way inductive loads are space is available.
distributed. The reactive compensation
reduces the load on the electrical ARTECHE pole mounted capacitor banks
infrastructure installed upstream. Reactive have minimal maintenance requirements.
power compensating as close as possible to
the load leads to a better overall performance.
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions 15
3. POLE MOUNT CAPACITOR BANKS
TECHNICAL CHARACTERISTICS
CONTENTS
Frequency 50/60 Hz
Voltage Up to 38 kV
Wye
Delta
Local
Control
Remote
Communication Radio
16 Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
ARTECHE POWER QUALITY
Trust and reliability.
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions 17
4. STUDIES, SIMULATIONS AND
TECHNICAL SUPPORT
18 Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions
4. STUDIES, SIMULATIONS AND TECHNICAL SUPPORT
GENERAL DESCRIPTION
ARTECHE offers all necessary support to ARTECHE has worldwide experience in
customers to provide the best solution and analysing the integration of renewable
equipment depending on the requirements of energies into electrical networks, particularly
the system. in the wind power sector:
Our engineering team performs electrical
GRID CODE VALIDATION
studies simulating both the steady state and
transient conditions, so that the best solution Simulation of complete wind farm (WTGs,
in terms of reactive power compensation and transformers and electrical lines) to perform:
harmonics cancellation can be designed for
each individual project. › Power flow analyses to determine electrical
losses and voltage variations at the Point
ARTECHE has the most reliable software and
of Common Coupling (PCC) for different
modelling tools, such as PSS/E, DigSilent,
WTG power generation set points and
EMTP-AT, as well as our own developed and
power factors.
validated programs.
› P-Q curve generation.
Among others, the following studies can be › Analysis of external equipment needed
performed: (voltage control ancillary services).
› Protective-device coordination studies.
TOTAL HARMONIC DISTORTION
› Short circuit analysis.
› Reliability studies. › THD calculation of the wind farm at the PCC
(current harmonics and voltage harmonics).
› Switching transient studies.
› Load flow studies.
› Analysis of external equipment needed
(active or passive filters).
› Power quality analysis.
› Harmonic analysis. REACTIVE POWER GENERATION
› Voltage support studies.
› Analysis of equipment needed to accom-
› Dynamic stability studies. plish the power factor and voltage require-
› Voltage stability studies. ments of the installation at the PCC.
› System impact studies.
Power Factor Correction. Harmonic Filtering. | Medium and High Voltage Solutions 19
Moving together
ARTECHE_CT_PQ_MVHV_EN
Version: A1