kg

Density of water ρw  1000


3
m

1.5bar
Minimum Pressure for Transmission Network Ptrans   15.296m
g  ρw

1bar
Minimum Pressure for distribution Network Pdist   10.197m
g  ρw

2 Locations will be considered for Fire Hydrants at down stream node, the node will have a tag of
FH-

Private Fire Hydrant:


l l
950  15.833
minimum flow rate for private fire hydrant min s

6.9bar
 70.36m
minimum pressure at private fire hydrant g  ρw

l l l
J75-FH New Demand Q75  15.833  0.83  16.663
s s s

l l l
IN173-FH New Demand Q173  15.833  2.43  18.263
s s s

as a result of the analysis, its found that at MDD 1.3,


dia 750mm
The maximum head is 72.3m while the Q is 580.26 l/s
at flow =0 head 783.68m

based on that these values were intered as a pump curve, and the results obtained