Professional Documents
Culture Documents
Marks
a CE
b C-Tick
Order data
Operating controls
1
2CDC 251 005 S0012
L1, L2, L3
Measuring value
L1, L2, L3 L1, L3, L2 L1, L2, L3 L1, L2 L1, L2, L3
t t t t L3 t
s v s v s
11-14
11-12
Electrical connection
L1, L2, L3 Control supply voltage = measuring voltage
L1 L2 L3 11
12 14
1SVC 110 000 F0117
12 11 14
Input circuits
Supply circuit = measuring circuit L1, L2, L3
Rated control supply voltage Us = measuring voltage 3 x 208-440 V AC
Rated control supply voltage Us tolerance -10...+10 %
Rated frequency 50/60 Hz (-10...+10 %)
Typical current / power consumption approx. 15 VA
Timing circuit
Start-up delay Ts fixed 500 ms
Tripping delay Tv fixed 500 ms
User interface
Indication of operational states
Relay status R yellow LED
Details see table ‚LEDs, status information and fault messages‘ on page 2 and ‚Function descriptions / diagrams‘ on page 3.
Output circuits
Kind of output 1 c/o (SPDT) contact
Operating principle closed-circuit principle 1)
Electrical connection
Wire size fine‑strand with wire end ferrule 2 x 0.75-1.5 mm 2 (2 x 18-16 AWG)
fine‑strand without wire end ferrule 2 x 1-1.5 mm 2 (2 x 18-16 AWG)
rigid 2 x 0.75-1.5 mm2 (2 x 18-16 AWG)
Stripping length 10 mm (0.39 in)
Tightening torque 0.6 - 0.8 Nm (5.31 - 7.08 lb.in)
Environmental data
Ambient temperature ranges operation -20...+60 °C
storage -40...+85 °C
Damp heat, cyclic (IEC 60068-2-30) 24 h cycle time, 55 °C, 93 % rel., 96 h
Operational reliability (IEC 68-2-6) 6g
Mechanical resistance (IEC 68-2-6) 10 g
Isolation data
Rated insulation voltage Ui supply circuit / measuring circuit
500 V
(VDE 0110, IEC/EN 60947-1) / output circuit
Rated impulse withstand voltage Uimp all isolated circuits
4 kV, 1.2/50 µs
(VDE 0110, IEC/EN 60664)
Test voltage between all isolated circuits (routine test) 2.5 kV, 50 Hz, 1 min.
Pollution degree (VDE 0110, IEC/EN 60664, IEC/EN 60255-5) 3
Overvoltage category (VDE 0110, IEC/EN 60664, IEC/EN 60255-5) III
Standards
Product standard IEC/EN 60255-6
Low Voltage Directive 2006/95/EC
EMC directive 2004/108/EC
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3 (6 kV / 8 kV)
radiated, radio-frequency, IEC/EN 61000-4-3 Level 3 (10 V/m)
electromagnetic field
electrical fast transient / burst IEC/EN 61000-4-4 Level 3 (2 kV / 5 kHz)
surge IEC/EN 61000-4-5 Level 4 (2 kV L-L)
conducted disturbances, induced by IEC/EN 61000-4-6 Level 3 (10 V)
radio-frequency fields
Interference emission IEC/EN 61000-6-4
V V
300 300
V 200 V 200
resistive load
resistive load
100 100
80 80
60 60
50 50
40 40
30 30
20 20
0.9
0.8
F
0.7 250 V
resistive load
0.6
0.5
2CDC 252 192 F0205
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
Contact lifetime
3.07“
78
Further documentation
Document title Document type Document number
Electronic products and relays Technical catalogue 2CDC 110 004 C020x
You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products ->
Electronic Relays and Controls -> Three Phase Monitors.
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.