Company Name: Schneider-Electric

Company Address: 10 Harris Rd, Malaga WA 6090

Order Number:

General test information: Date/Time: 2015-05-19, 12:29:20


Test device: CT-Analyzer Device Serial No.: KH026G
File name: C:\Users\sesa286234\Documents\OMICRON\CTAnalyzer\RemoteEFL\TEMP\XMLData(1).xml
Assessments: OK

Used test settings:


I-pn: 2500.0 A Location: Object:
I-sn: 1.0 A Company: Chevron Manufacturer: RS ISOLSEC
Rated burden: 20.0 VA / 0.8 Country: Australia Type: TA34
Operating burden: 20.0 VA / 0.8 Station: WDS Serial number: 13/360907/10
Applied standard: IEC 60044-1 Feeder/Bay: 0EK-12A41 Panel A1 Core number: 1
Core type (P/M): P Phase: L1-T13 Tap: S1-S2
Class: 5P IEC-ID Optional:
ALF: 20.0 Ts:
f: 50.0 Hz max. Rct: 19.056 Ω

Resistance test: Burden test:


Rmeas (17.8°C): 15.53387 Ω Burden: cos φ: Z:
Rref (75°C): 19.05562 Ω Vmeas: Imeas:

Excitation test:
V-kn: 699.418 V I-kn: 0.005341 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A ALF: >25.453765 ALFi: 25.25 ALF: >25.453765 ALFi: 25.25
Ls: 0.0281686H Lm: 524.9761 H Ts: 14.976s Ts: 14.976s
Kr: 80.91 %

Ratio test:
Ratio: 2500.0 : 1.00691 ε : 0.6908 % Δφ: 0.56 min Polarity: OK N: 2481.93
εc : 0.689 %

Excitation curve data


Excitation curve data

1000

100
Es / V

10

0.1
0.00001 0.0001 0.001 0.01 0.1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2


Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
20 VA/ 0.8 0.537 0.612 0.641 0.664 0.682 0.691 0.692 0.696
10 VA/ 0.8 0.644 0.662 0.679 0.694 0.700 0.702 0.705
5 VA/ 0.8 0.663 0.675 0.688 0.700 0.706 0.707 0.710
2.5 VA/ 1 0.681 0.688 0.696 0.705 0.710 0.711 0.713
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
20 VA/ 0.8 8.994 3.074 1.895 1.244 0.775 0.562 0.600 0.609
10 VA/ 0.8 3.153 1.978 1.285 0.793 0.581 0.539 0.596
5 VA/ 0.8 3.152 2.019 1.325 0.809 0.595 0.550 0.482
2.5 VA/ 1 3.332 2.194 1.457 0.898 0.666 0.618 0.509
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 Error Graph
Ratio 20 50 100 120 200
1.00 1.00 1.00
-1.00 -1.00 -1.00
0.800

0.700

0.600
Current deviation [%]

0.500 100% Load

50% Load
0.400

25% Load
0.300

0.200

0.100

0.000
0 50 100 150 200 250
% I-pn