Trouble Shooting Guide

 U3 Chassis (2 Fan Model)


Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
• Error is displayed with unit number.
• Indoor unit error is displayed on IDU info, oudoor error is displayed on Operation Info located on right upper side
• If error occurs, click the error and trouble shooting guide is provided.

Display Title Cause of Error


0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
Communication error : wired Failing to receive wired remote controller signal in
0 3 -
remote controller  indoor unit indoor unit PCB
Indoor unit related error

0 4 - Drain pump Malfunction of drain pump


Communication error : outdoor Failing to receive outdoor unit signal in indoor unit PCB
0 5 -
unit  indoor unit
Outlet pipe temperature sensor of Outlet pipe temperature sensor of indoor unit is
0 6 -
indoor unit open or short
Indoor EEPROM Error In case when the serial number marked on
0 9 -
EEPROM of Indoor unit is 0 or FFFFFF
Poor fan motor operation Disconnecting the fan motor connector/Failure of indoor
1 0 -
fan motor lock
Inlet Air temperature sensor of Air temperature sensor of indoor unit is open or
1 7 -
FAU (Fresh Air intake Unit) short
Outdoor Unit Inverter Compressor Outdoor Unit Inverter Compressor Drive IPM Fault
2 1 1 IPM Fault

Inverter Board Input Over Outdoor Unit Inverter Board Input Current excess
2 2 1
Current(RMS) of Outdoor Unit (RMS)

2 3 1 Outdoor Unit Inverter Compressor DC charging is not performed at outdoor unit after
DC link Low Voltage starting relay turn on.
Outdoor unit related error

2 4 1 Outdoor Unit High Pressure System is turned off by outdoor unit high pressure
Switch switch.
Outdoor Unit Input Voltage High/ Outdoor Unit input voltage is out of range.
2 5 1
Low Voltage
Outdoor Unit Inverter Compressor The First Start Failure by Outdoor Unit Inverter
2 6 1
Start Failure Compressor Abnormality
2 7 1 PSC/PFC Fault error When over current flows instantly at PSC/PFC
Outdoor Unit Inverter DC link High System is turned off by outdoor unit DC Voltage Over
2 8 1
Voltage Charging
Outdoor Unit Inverter Compressor Outdoor Unit Inverter Compressor Fault OR Drive
2 9 1
Over Current Fault
Outdoor Unit Inverter Compressor System is turned off by outdoor unit Inverter
3 2 1 High Discharge Temperature Compressor High Discharge Temperature
1
Display Title Cause of Error
Outdoor Unit Inverter Compressor System is turned off by outdoor unit Inverter
3 2 1 High Discharge Temperature Compressor High Discharge Temperature
High Pressure of Outdoor Unit System is turned off by excessive increase of high
3 4 1
pressure of outdoor unit
Low Pressure of Outdoor Unit System is turned off by excessive decrease of low
3 5 1
pressure of outdoor unit
3 6 1 Low pressure ratio Pressure ratio is under limit
4 0 1 Outdoor Unit Inverter Compressor Outdoor Unit Inverter Compressor CT Sensor open or
CT Sensor Fault short
Outdoor Unit Inverter Compressor Outdoor Unit Inverter Compressor Discharge
4 1 1
Discharge Temperature Sensor Fault Temperature Sensor open or short
Outdoor Unit Low Pressure Outdoor Unit Low Pressure Sensor open or short
4 2 1
Sensor Fault
4 3 1 Outdoor Unit High Pressure Outdoor Unit High Pressure Sensor open or short
Sensor Fault
Outdoor Unit Air Temperature Outdoor Unit Air Temperature Sensor open or short
4 4 1
Sensor Fault
4 5 1 Outdoor Unit Heat Exchanger Outdoor Unit Heat Exchanger Temperature
Temperature Sensor Fault Sensor Open or Short
Outdoor Unit Suction Temperature Outdoor Unit Suction Temperature Sensor open or
4 6 1
Sensor Fault short
Defective IPM Temperature Disconnection or short circuit on IPM temperature sen-
Outdoor unit related error

4 9 1 Sensor sor of the outdoor unit


Omitting connection of R, S, T Omitting connection of Outdoor unit
5 0 1 power of Outdoor unit
Excessive capacity of indoor units Excessive connection of indoor units compared to
5 1 1
capacity of outdoor unit
Communication error : inverter Failing to receive inverter signal at main PCB of
5 2 1
PCB  Main PCB Outdoor Unit
5 3 1 Communication error : indoor unit Failing to receive indoor unit signal at main PCB of out-
 main PCB of outdoor unit door Unit.
Reverse connection of R, S, T Reverse connection or omitting connection of R, S, T
5 4 1 power of Outdoor unit power of Outdoor unit
Communication error : inverter Restriction of Outdoor Unit (Inverter PCB)
5 7 1
PCB  Main PCB
6 0 1 Inverter PCB EEPROM error Check EEPROM checksum error when resetting power
6 2 1 Heat sink temperature high error When Heat sink temperature is above setting value
6 7 1 Outdoor Unit Fan Lock Restriction of Outdoor Unit Fan
7 3 1 Instant Over Current(Peak) of Instant Over Current(Peak) of Outdoor Unit PFC
Outdoor Unit PFC
8 6 1 Outdoor Unit Main PCB EEPROM Communication Fail Between Outdoor Unit Main
Error MICOM and EEPROM or omitting EEPROM
PFC PCB EEPROM Error Communication Fail Between Outdoor Unit PFC
8 8 1 MICOM and EEPROM or omitting EEPROM
Outdoor Unit Liquid pipe Liquid pipe temperature sensor of outdoor unit is open
1 1 3 1 Temperature Sensor Error or short
Outdoor Unit Subcooling Outlet Outdoor Unit Subcooling Outlet Temperature Sensor
1 1 5 1
Temperature Sensor Error open or short
Failure of operation mode conver- Pressure unbalance between outdoor units
1 5 1 1
sion at Outdoor Unit
2 4 2 1 Network error Network error of central control unit
2
 U4 Chassis (1 Fan Model)
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and red/green LED of
outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
• Error is displayed with unit number.
• Indoor unit error is displayed on IDU info, oudoor error is displayed on Operation Info located on right upper side
• If error occurs, click the error and trouble shooting guide is provided.

Display Title Cause of Error


0 1 Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
Communication error : wired Failing to receive wired remote controller signal in
0 3
Indoor unit related error

remote controller  indoor unit indoor unit PCB


0 4 Drain pump Malfunction of drain pump
Communication error : outdoor Failing to receive outdoor unit signal in indoor unit PCB
0 5
unit  indoor unit
Outlet pipe temperature sensor of Outlet pipe temperature sensor of indoor unit is
0 6 indoor unit open or short
0 9 Indoor EEPROM Error In case when the serial number marked on
EEPROM of Indoor unit is 0 or FFFFFF
1 0 Poor fan motor operation Disconnecting the fan motor connector/Failure of indoor fan
motor lock

2 1 Outdoor Unit Inverter Compressor Outdoor Unit Inverter Compressor Drive IPM Fault
IPM Fault

2 2 Inverter Board Input Over Outdoor Unit Inverter Board Input Current excess
Current(RMS) of Outdoor Unit (RMS)
Outdoor Unit Inverter Compressor DC charging is not performed at outdoor unit after
2 3
DC link Low Voltage starting relay turn on.
Outdoor unit related error

2 4 Outdoor Unit High Pressure System is turned off by outdoor unit high pressure
Switch switch.
Outdoor Unit Input Voltage High/ Outdoor Unit input voltage is out of range.
2 5
Low Voltage
Outdoor Unit Inverter Compressor The First Start Failure by Outdoor Unit Inverter
2 6
Start Failure Compressor Abnormality
PSC/PFC Fault error When over current flows instantly at PSC/PFC
2 7

Outdoor Unit Inverter DC link High System is turned off by outdoor unit DC Voltage Over
2 8
Voltage Charging
Outdoor Unit Inverter Compressor Outdoor Unit Inverter Compressor Fault OR Drive
2 9 Over Current Fault

3
Display Title Cause of Error
Outdoor Unit Inverter Compressor System is turned off by outdoor unit Inverter
3 2 High Discharge Temperature Compressor High Discharge Temperature
High Pressure of Outdoor Unit System is turned off by excessive increase of high
3 4
pressure of outdoor unit
Low Pressure of Outdoor Unit System is turned off by excessive decrease of low
3 5
pressure of outdoor unit
3 6 Low pressure ratio Pressure ratio is under limit
4 0 Outdoor Unit Inverter Compressor Outdoor Unit Inverter Compressor CT Sensor open or
CT Sensor Fault short
Outdoor Unit Inverter Compressor Outdoor Unit Inverter Compressor Discharge
4 1
Discharge Temperature Sensor Fault Temperature Sensor open or short
Outdoor Unit Low Pressure Outdoor Unit Low Pressure Sensor open or short
4 2
Sensor Fault
4 3 Outdoor Unit High Pressure Outdoor Unit High Pressure Sensor open or short
Outdoor unit related error

Sensor Fault
Outdoor Unit Air Temperature Outdoor Unit Air Temperature Sensor open or short
4 4
Sensor Fault
4 5 Outdoor Unit Heat Exchanger Outdoor Unit Heat Exchanger Temperature
Temperature Sensor Fault Sensor Open or Short
Outdoor Unit Suction Temperature Outdoor Unit Suction Temperature Sensor open or
4 6
Sensor Fault short
Excessive capacity of indoor units Excessive connection of indoor units compared to
5 1
capacity of outdoor unit
Communication error : indoor unit Failing to receive indoor unit signal at main PCB of out-
5 3  main PCB of outdoor unit door Unit.
6 0 Inverter PCB EEPROM error Check EEPROM checksum error when resetting power
6 7 Outdoor Unit Fan Lock Restriction of Outdoor Unit Fan
Instant Over Current(Peak) of Instant Over Current(Peak) of Outdoor Unit PFC
7 3 Outdoor Unit PFC
Outdoor Unit Liquid pipe Liquid pipe temperature sensor of outdoor unit is open
1 1 3 Temperature Sensor Error or short
Outdoor Unit Subcooling Outlet Outdoor Unit Subcooling Outlet Temperature Sensor
1 1 5
Temperature Sensor Error open or short
Failure of operation mode conver- Pressure unbalance between outdoor units
1 5 1
sion at Outdoor Unit
2 4 2 Network error Network error of central control unit

4
Error
Error Type Error Point Main Reasons
No.
01 Indoor unit air sensor error
01 *FAU FAU Outlet air sensor error 1. Indoor unit PCB wrong connection
Indoor unit sensor is
02 Indoor unit pipe inlet sensor error 2. Indoor unit PCB failure
open/short
06 Indoor unit pipe outlet sensor error 3. Sensor problem (main reason)
17 *FAU FAU Inlet air sensor error
*FAU(Fresh Air intake Unit)

 Error diagnosis and countermeasure flow chart

Is sensor properly No
Connect properly to PCB
connected to PCB?

Yes

Is the resistance value No


Change the sensor
of sensor normal?*

Yes

Change the PCB

* In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin)  Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ

CN-PIPE/IN: Pipe inlet temp sensor


CN-PIPE/Mid: Inlet Air temp sensor
CN-PIPE/Out: Pipe outlet temp sensor
CN-ROOM: Outlet Air temp sensor

5
Error
Error Type Error Point Main Reasons
No.

1. Remote controller fault


The remote controller
03 No transmission between cabled did not receive the sig- 2. Indoor unit PCB fault
remote controller & indoor unit nal from indoor unit 3. Connector fault, Wrong connection
during specific time 4. transmission cable problem

 Error diagnosis and countermeasure flow chart

Does the error happens No Replace cabled remote


again if the remote
controller
controller is replaced?*

Yes

Does the error occurred No


when the cable of remote Check connection &
controller is replaced? transmission cable **

Yes

Replace indoor unit PCB ***

* If there is no remote controller to replace : Use another unitʼs remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
 make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unitʼs address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing

6
Error
Error Type Error Point Main Reasons
No.

Float switch is open due to 1. Drain pump/float switch fault


rising of condensate water 2. Improper drain pipe location, clog-
04 Drain pump error level because of drain ging of drain pipe
pump fault or drain pipe
3. Indoor unit PCB fault
clogging

 Error diagnosis and countermeasure flow chart

Is the drain pan filled Is Float switch short


No No
half with condensate On measuring its Replace float switch
water? (half level of resistance?
float switch)*
%es
%es

Replace Indoor PCB or


reconnect the connector

In indoor unit PCB


Is drain pump working? No Does the terminal voltage No
(Sound/drain noise/ Replace indoor unit PCB
for drain pump has
contact etc.) 220V output?**
%es %es

Replace Drain Pump

Mn
Drain pump blocked by Bgdbjsgdcq`hmgd`cgdhfgs
foreign particles? `mcrknod)))

%es Bgdbjhmfekn`s
rvhsbg
'Knvonrhshnm‡rgnqs /ngl(

Remove it & clean the pump

7
Error
Error Type Error Point Main Reasons
No.

1. Auto addressing is not done


2. transmission cable is not connected
3. Short circuit of transmission cable
No signal transmission 4. Indoor unit transmission circuit fault
05 Indoor & Outdoor unit between indoor & outdoor 5. Outdoor unit transmission circuit fault
transmission error units. 6. Not enough distance between power and trans-
mission cable?

 Error diagnosis and countermeasure flow chart


Replace the PCB of indoor unit
No Is total number of indoor No displayed error
Does all the IDUs show
units connected displayed
same error code CH05? Re-connect after check the
after auto addressing?
transmission cable of indoor
Yes unit displayed error
END
Replace outdoor PCB after
No Check the main power No checking
Is outdoor PCB LED
supply at the ODU
blinking?
terminal block? Replace TRANS after checking

Yes
Yes

No Check the insulation of inverter


Is main circuit breaker off? / constant compressor and replace
if required
Yes
Check the capacity of main circuit
breaker and replace if required
Improper connection of power supply cable
If all ok,
Turn on main circuit breaker
Main power supply problem

Check if the
transmission cable is
properly connected No
Re connect transmission cable
to indoor / outdoor
terminal block?*
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking

8
Error
Error Type Error Point Main Reasons
No.

1. Error developed in transmission between the


09 Indoor unit EEPROM micro- processor and the EEPROM on the sur-
error face of the PCB.
2. ERROR due to the EEPROM damage

 Error diagnosis and countermeasure flow chart

- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control

9
Error
Error Type Error Point Main Reasons
No.

Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault

 Error diagnosis and countermeasure flow chart

Is connector No
connection proper? Connect properly

Yes

Is fan motor No
Replace indoor unit fan motor
normal?*

Yes

Replace indoor unit PCB **

* It is normal when check hall sensor of indoor fan motor as shown below
** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the
address of central control
(Notice: The connection of motor connector to PCB should be done under no power
supplying to PCB)

10
Error
Error Type Error Point Main Reasons
No.

1.Over current detection at Inverter compres-


sor(U,V,W)
IPM self protection circuit 2.Compressor damaged (insulation dam-
21 Inverter PCB Assembly IPM activation aged/Motor damaged)
Fault occur (Overcurrent/IPM overheat- 3.Inverter compressor terminal disconnected
ing/Vcc low voltage) or loose
5.Inverter PCB assembly damaged
6.ODU input current low

 Error diagnosis and countermeasure flow chart


1. Check resistance between each terminal of compressor
Are the resistance (Refer to P.53)
Between each phase and No 2. Check insulation resistance between compressor
insulation resistance of Inverter terminal and pipe (over 50MΩ )
compressor normal? → Replace compressor if abnormality found

Yes
1.Check inverter PCB assembly U,V,W connector
Is compressor connection condition
No 2. Check wire disconnection and wiring
Wire connection
condition normal? 3. Check compressor terminal connection condition
(bad contact)
→ Reassemble if abnormality found
Yes

No Check inverter PCB assembly IPM normality.


Is inverter PCB assembly
→ Replace inverter PCB assembly if abnormality found.
normal?

Yes

Recheck power and installation condition

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
11
Error
Error Type Error Point Main Reasons
No.

1. Overload operation (Pipe


clogging/Covering/EEV defect/Ref.
Inverter PCB Assembly input overcharge)
power current is over limited 2. Compressor damage(Insulation
22 AC Input Current Over Error value damage/Motor damage)
* 1 PHASE : 29A rms 3. Input voltage low
* 3 PHASE : 13A rms 4. Power Line Misconnection
5. Inverter PCB Assembly damage
(Input current sensing part)

 Error Diagnosis and Countermeasure Flow Chart

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
Is installation No 3. Check EEV connector assemble condition/normal
condition normal?
operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes
1. Check resistance between each terminal of compressor
Are the resistance (Refer to P.53)
Between each phase and No 2. Check insulation resistance between compressor
insulation resistance of Inverter terminal and pipe (over 50MΩ )
compressor normal? → Replace compressor if abnormality found

Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
Is compressor
No 2. Check wire disconnection and wiring
Wire connection
3. Check compressor terminal connection condition
condition normal?
(bad contact)
→ Reassemble if abnormality found
Yes

No Check connection between inverter PCB assembly and


Is inverter PCB assembly
bridge diode(misconnection, disconnection)
power connection normal?
→ wiring again if abnormality found

Yes
Check
1. R-S,S-T,T-R phase are 380V±10%
No R-N,S-N,T-N phase are 220V±10%
Is input voltage normal?
L-N phase are 220V ±10% (for 1 phase model)
→ Check connection condition and wiring if power is
abnormal
Yes

Is inverter PCB assembly No Check inverter PCB assembly IPM normality


normal? → Replace inverter PCB assembly

Yes

Recheck power and installation condition

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
12
Error
Error Type Error Point Main Reasons
No.

1. DC Link terminal misconnection/terminal


contact fault
2. Starting relay damage
Inverter Compressor DC DC Voltage isn't charged
23 3. Condenser damage
Link Low Voltage after starting relay on
4. Inverter PCB assembly damage
(DC Link voltage sensing part)
5. Input voltage low

 Error Diagnosis and Countermeasure Flow Chart

Check
No R-S,S-T,T-R phase are 380V±10%
Is input voltage normal? R-N,S-N,T-N phase are 220V±10%
L-N phase are 220V ±10% (for 1 phase model)
→ Check connection condition and wiring if power is
abnormal
Yes

Check connection from terminal block to inverter PCB


Is inverter PCB assembly No
assembly
power connection normal?
→ wiring again if abnormality found

Yes

No Check inverter PCB assembly IPM normality


Is inverter PCB assembly normal? → Replace inverter PCB assembly

Yes

Recheck power and installation condition

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
13
Error
Error Type Error Point Main Reasons
No.

1. Defective high pressure switch


2. Defective fan of indoor unit or outdoor unit
3. Check valve of compressor clogged
4. Pipe distortion due to the pipe damage
Excessive rise of discharge Compressor off due to the 5. Refrigerant overcharge
24 6. Defective EEV at the indoor or outdoor unit .
pressure in outdoor com- high pressure switch in
pressor outdoor unit 7. Covering or clogging(Outdoor covering during
the cooling mode /Indoor unit filter clogging
during the heating mode)
8. SVC valve clogging
9. Defective outdoor PCB

 Error diagnosis and countermeasure flow chart

Is high pressure switch No


connector connected Connect securely
to PCB?*

Yes

Is high pressure switch No


connector short Replace high pressure switch
during off time?**

Yes

No
Is SVC valve open? Open SVC valve

Yes

Is this error appeared No Re-check momentary


again after reset? problem or not

Yes

Is high pressure No
more than 2500kPa Replace PCB
at manifold gauge?

Yes

Is high pressure of No
LGMV similar as Replace high pressure sensor
at manifold gauge?
Yes

Check pipe is blocked or


not and take measure

14
Error
Error Type Error Point Main Reasons
No.

Input voltage is over limited 1. Input voltage abnormal (R-N or T-N)(L-N)


25 Input Voltage high/low value of the product (173V 2. Outdoor unit inverter PCB assembly dam-
or less, 289V or more) age (input voltage sensing part)

 Error Diagnosis and Countermeasure Flow Chart

Check
No R-S,S-T,T-R phase are 380V10%
Is input voltage normal? R-N,S-N,T-N phase are 220V10%
L-N phase are 220V 10% (for 1 phase model)
’ Check connection condition and wiring if power is
Yes abnormal

No
Is inverter PCB assembly normal? Replace inverter PCB assembly

Yes

Recheck power and installation condition

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
15
Error
Error Type Error Point Main Reasons
No.

1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref.
overcharge)
Inverter compressor starting Starting failure because of
26 2. Compressor damage
failure Error compressor abnormality
(Insulation damage/Motor damage)
3. Compressor wiring fault
4. ODU inverter PCB damage (CT)

 Error Diagnosis and Countermeasure Flow Chart

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
Is installation No 3. Check EEV connector assemble condition/normal
condition normal? operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes

Are the resistance 1. Check resistance between each terminal of compressor


Between each phase and No (Refer to P.53)
insulation resistance of Inverter 2. Check insulation resistance between compressor
compressor normal? terminal and pipe (over 50MΩ )
→ Replace compressor if abnormality found
Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
Is compressor 2. Check wire disconnection and wiring
No
Wire connection 3. Check compressor terminal connection condition
condition normal? (bad contact)
→ Reassemble if abnormality found
Yes

No Check inverter PCB assembly IPM normality


Is inverter PCB assembly normal? → Replace inverter PCB assembly

Yes

Recheck power and installation condition

16
Error
Error Type Error Point Main Reasons
No.

1.Overload operation (Pipe clogging/


Covering/EEV defect/Ref. overcharge)
Inverter PCB input power 2.Compressor damage (Insulation
AC input instant over cur- current is over damage/Motor damage)
27
rent error * 1 PHASE : 100A peak 3.Input voltage abnormal (L,N)(R,S,T,N)
* 3 PHASE : 47A peak 4.Power line assemble condition abnormal
5.Inverter PCB assembly Damage (input cur-
rent sensing part)

 Error Diagnosis and Countermeasure Flow Chart


1.Check Pipe clogging/distortion
No 2.Check Covering (Indoor/Outdoor Unit)
Is installation
3.Check EEV connector assemble condition/normal operation
condition normal?
4.Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes

Check
No R-S,S-T,T-R phase are 380V±10%
Is input voltage normal? R-N,S-N,T-N phase are 220V±10%
L-N phase are 220V ±10% (for 1 phase model)
→ Check connection condition and wiring if power is abnormal
Yes

No 1.Check L,N connection condition


Is AC input Wire connection 2.Check wire disconnection and wiring
condition normal? → Reassemble if abnormality found

Yes

No 1.Check inverter PCB assembly U,V,W connector connection condition


Is compressor
2.Check wire disconnection and wiring
Wire connection
3.Check compressor terminal connection condition(bad contact)
condition normal?
→ Reassemble if abnormality found
Yes

No
Is inverter PCB assembly Check inverter PCB assembly PFCM normality
normal? → Replace inverter PCB assembly

Yes

Recheck power and


installation condition

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
17
Error
Error Type Error Point Main Reasons
No.

1. Input voltage abnormal (L~N)(R,S,T,N)


Inverter DC link high Inv PCB DC link voltage
28 2. ODU inverter PCB damage
voltage error supplied over 780V
(DC Link voltage sensing part)

 Error Diagnosis and Countermeasure Flow Chart

Check
R-S,S-T,T-R phase are 380V±10%
No R-N,S-N,T-N phase are 220V±10%
Is input voltage normal?
L-N phase are 220V ±10% (for 1 phase model)
’ Check connection condition and wiring if power is
abnormal
Yes

Is inverter PCB assembly normal? No


Replace inverter PCB assembly

Yes

Recheck power and installation condition

N T S R
N T S R

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
18
Error
Error Type Error Point Main Reasons
No.

1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref.
Inverter compressor input overcharge)
Inverter compressor over current is over
29 2. Compressor damage(Insulation
current * 1 PHASE : 35A peak
damage/Motor damage)
* 3 PHASE : 24A peak
3. Input voltage low
4. ODU inverter PCB assembly damage

 Error Diagnosis and Countermeasure Flow Chart

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
Is installation No 3. Check EEV connector assemble condition/normal
condition normal? operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes

1.Check resistance between each terminal of compressor


Are the resistance
No (Refer to P.53)
Between each phase and
2.Check insulation resistance between compressor terminal
insulation resistance of Inverter
and pipe (over 50MΩ )
compressor normal?
→ Replace compressor if abnormality found
Yes

1. Check inverter PCB assembly U,V,W connector


Is compressor No connection condition
Wire connection 2. Check wire disconnection and wiring
condition normal? 3. Check compressor terminal connection condition
(bad contact)
→ Reassemble if abnormality found
Yes

Check
No R-S,S-T,T-R phase are 380V±10%
Is input voltage normal?
R-N,S-N,T-N phase are 220V±10%
L~N phase voltage is 220V ±10%
→ Check connection condition and wiring if power is
Yes abnorma

No Check inverter PCB assembly IPM normality


Is inverter PCB assembly normal? → Replace inverter PCB assembly

Yes

Recheck power and installation condition

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
19
Error
Error Type Error Point Main Reasons
No.
1. Temperature sensor defect of inverter com-
Compressor is off pressor discharge pipe
Over-increase discharge
because of over-increase 2. Refrigerant shortage / leak
32 temperature of inverter com-
discharge temperature of
pressor at main outdoor unit 3. EEV defect
inverter compressor
4. Liquid injection valve defect

 Error diagnosis and countermeasure flow chart

Is the amount of No No Change the amount of


Is there pipe crack
refrigerant normal? refrigerant
or trace of leakage?
[refer refrigerant part] (Charge additive amount)
Yes Yes

Weld / reconnect the cracked


portion and recharge refrigerant

Is the resistance of discharge No Replace discharge


temperature sensor normal?* temperature sensor

Yes * Resistance value of discharge temperature sensor


10°C = 362kΩ, 25°C= 200kΩ, 50°C= 82kΩ, 100°C= 18.5kΩ

Is EEV in
outdoor unit normal No
at heating operation? Replace outdoor unit EEV
[refer electric
component part]
Yes

Does liquid injection No Check liquid injection


corresponded
corresponded
operate normally?
Yes

No Check another components


Is there pipe
and operation conditions
(strainer etc.) clogging?
/ Take measures
Yes

Replace strainer

20
Error
Error Type Error Point Main Reasons
No.
1. Defect of high pressure sensor
2. Defect of indoor or outdoor unit fan
Error happens 3. Deformation because of damage of refrigerant pipe
because of 3 times 4. Over-charged refrigerant
Over-increase of dis- successive compres- 5. Defective indoor / outdoor unit EEV
34 charge pressure of sor off due to over- 6. When blocked
compressor increase of high pres- - Outdoor unit is blocked during cooling
sure by high pressure
- Indoor unit filter is blocked during heating
sensor
7. SVC valve is clogged
8. PCB defect of outdoor unit
10. Indoor unit pipe temperature sensor defect

 Error diagnosis and countermeasure flow chart


No
Is service valve opened ? Open service valve

Yes

Are transmission No Check and repair transmission


cable / pipe connection
cable / pipe connection
normal?

Yes

Is refrigerant No
amount normal? Adjust refrigerant amount
[refer refrigerant part]
Yes

Is fan normal?
(Indoor fan during heating No
Replace related parts
Outdoor fan during cooling)

Yes

Is filter blocked
(Heating:indoor, No Clean indoor filter (heating)
Cooling:outdoor /outdoor heat exchanger (cooling)?
heat exchanger)?
Yes

Is value of high pressure No


sensor same as Manifold Replace sensor of high pressure
value(Is it high actually)?

Yes

Check indoor unit EEV


Check indoor unit PCB
Check in/outdoor installation
condition

21
Error
Error Type Error Point Main Reasons
No.
1. Defective low pressure sensor
2. Defective outdoor/indoor unit fan
Error happens 3. Refrigerant shortage/leakage
because of 3 times 4. Deformation because of damage of refrigerant pipe
Excessive drop of successive compres- 5. Defective indoor / outdoor unit EEV
discharge pressure sor off due to exces- 6. Covering / clogging
35
of compressor sive drop of low pres- (outdoor unit covering during the cooling mode/
sure by the low pres-
indoor unit filter clogging during heating mode)
sure sensor
7. SVC valve clogging
8. Defective outdoor unit PCB
9. Defective indoor unit pipe sensor

 Error diagnosis and countermeasure flow chart


Is service valve
Open service valve
opened?

Yes

No
Are transmission cable/ check transmission/
piping normal? piping correction.

Yes

Is amount of refrigerant No No
Is there pipe crack or trace Adjust the amount of
normal?
of refrigerant leakage? refrigerant (Additive charge)
[refer refrigerant part]
Yes Yes

Weld / reconnect the cracked


portion and recharge refrigerant

Is fan normal? No
(in heating outdoor fan, Check and replace related parts
in cooling indoor fan)
Yes

No
Is strainer Ok?* Replace the strainer

Yes

Are the values of manifold No


and low pressure sensor same? Replace the pressure sensor
( Is the low pressure value
actually low?)

Yes
* If the temperature difference between inlet and outlet of strainer
Check indoor / outdoor unit EEV is so large that frost or ice formation can be seen or confirmed
Check Indoor unit PCB
Check indoor / outdoor unit then clogging of strainer should be checked
installation conditions (Notice: it is not full ice forming of strainer, in case that there is
not at inlet portion but at outlet portion)

22
Error
Error Type Error Point Main Reasons
No.

Transmission Error Communication Error 1. Micom defect/Circuit defect


39 Between (PFC Micom Between PFC Micom 2. Different Micom S/W Version
 INV Micom) and INV Micom. 3. ODU inverter PCB assembly damage

 Error diagnosis and countermeasure flow chart

Is PFC Micom & INV


Micom S/W Program Upgrade Micom Program
normal?
Yes

No
Is Inverter PCB assembly Replace inverter PCB assembly
normal?

Yes

Recheck power and installation


condition

23
Error
Error Type Error Point Main Reasons
No.

Micom input voltage isn't 1. Input voltage abnormal (T-N)


40 CT sensor error within 2.5V ±0.3V at initial 2. ODU inverter PCB damage
state of power supply (CT sensing part)

 Error Diagnosis and Countermeasure Flow Chart

Check
No R-S,S-T,T-R phase are 380V±10%
Is input voltage normal? R-N,S-N,T-N phase are 220V±10%
L-N phase are 220V ±10% (for 1 phase model)
→ Check connection condition and wiring if power is
abnormal
Yes

No
Is inverter PCB assembly normal? Replace inverter PCB assembly

Yes

Recheck power and installation condition

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
24
Error No. Error Type Error Point Main Reasons

1. Defective connection of the


compressor discharge pipe tem-
Compressor dis- perature sensor
charge pipe tem- Sensor measurement
41 valve is abnormal 2. Defective discharge pipe com-
perature sensor pressor sensor of the compres-
error (Open/Short)
sor (open/short)
3. Defective outdoor PCB

 Error diagnosis and countermeasure flow chart

Sensor connection to PCB No


Insert sensor connector to PCB properly
is normal?

Yes

Is the resistance of No
Replace sensor
sensor normal?*

Yes

Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes

Replace corresponding sensor

* Error is generated if the resistance is more than 5MΩ(open) and less than 2kΩ (short)

Note: Standard values of resistance of sensors at different temperatures (±5% variation)


10°C = 362kΩ : 25°C= 200kΩ : 50°C= 82kΩ : 100°C= 18.5kΩ

25
Error
Error Type Error Point Main Reasons
No.

Abnormal value of 1. Bad connection of low pressure connector


42 Sensor error of low sensor 2. Defect of low pressure connector (Open/Short)
pressure 3. Defect of outdoor PCB
(Open/Short)

Abnormal value of 1. Bad connection of high pressure connector


Sensor error of high
43 sensor 2. Defect of high pressure connector (Open/Short)
pressure
(Open/Short) 3. Defect of outdoor PCB

 Error diagnosis and countermeasure flow chart

Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly?

Yes

After replacement of No
Replace corresponding
outdoor unit main PCB
pressure sensor
is the system normal?

Yes

END

26
Error No. Error Type Error Point Main Reasons

1. Bad connection of air temperature connector


Sensor error of
44 Abnormal value of 2. Defect of air temperature
outdoor air temper-
sensor (Open/Short) connector(Open/Short)
ature
3. Defect of outdoor PCB

1. Bad connection of air temperature connector


Outdoor unit heat 2. Defect of air temperature
Abnormal value of
45 exchanger temper-
sensor (Open/Short) connector(Open/Short)
ature sensor error 3. Defect of outdoor PCB

1. Bad connection of air temperature connector


Compressor suc- 2. Defect of air temperature
Abnormal value of
46 tion temperature connector(Open/Short)
sensor (Open/Short)
sensor error 3. Defect of outdoor PCB

 Error diagnosis and countermeasure flow chart

Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??

Yes

No
Is sensor value correct?* Replace sensor

Yes
* If value is 100kΩ ↑(open) or 100 Ω↓(short), error occurs

Replace corresponding NB: Resistance value of temperature sensor change according to


outdoor unit PCB temperature
It is normal if value shown as below (±5% error)
Sensor of air temperature: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Sensor of piping temperature: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ

27
Error
Error Type Error Point Main Reasons
No.

Outdoor unit 3 phase Input voltage abnormal (R,S,T,N)


Omitting one or more of
50 Check power line connection condition
power omission error R,S,T input power
Main PCB damage

 Error Diagnosis and Countermeasure Flow Chart


1.Check Pipe clogging/distortion
No 2.Check Covering (Indoor/Outdoor Unit)
Is installation
3.Check EEV connector assemble condition/normal operation
condition normal?
4.Check refrigerant pressure
’ Reassemble or manage if abnormality found
Yes
Check
No R-S,S-T,T-R phase are 380V10%
Is input voltage normal? R-N,S-N,T-N phase are 220V10%
L-N phase are 220V 10% (for 1 phase model)
’ Check connection condition and wiring if power is abnormal
Yes

No 1.Check L,N connection condition


Is AC input Wire connection 2.Check wire disconnection and wiring
condition normal? ’ Reassemble if abnormality found

Yes

No
Is inverter PCB assembly Check inverter PCB assembly IPM normality
normal? ’ Replace inverter PCB assembly

Yes

Recheck power and


installation condition

<Note>
- Omitting connection of R power of Outdoor unit  CH 50 error
- Omitting connection of S power of Outdoor unit  CH 23 error
- Omitting connection of T power of Outdoor unit  Main PCB power OFF

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
28
Error
Error Type Error Point Main Reasons
No.

Over-Capacity 1. 130% more than outdoor unit rated capacity


(Sum of indoor unit capaci- Sum of indoor unit capaci- 2. Wrong connection of transmission
51 ty is more than outdoor ty exceed outdoor unit cable/piping
capacity) capacity specification 3. Defect of outdoor unit PCB

 Error diagnosis and countermeasure flow chart

Is capacity sum of Are quantity and capacity


No No Check transmission cables
indoor units less than of indoor units installed between indoor and outdoor
130% of outdoor unit same as the data of LGMV? unit
capacity at LGMV?

Yes
Yes Adjust the capacity of indoor
and outdoor unit
End

29
Error
Error Type Error Point Main Reasons
No.
1. Power cable or transmission cable is not
Transmission error between Main controller canʼt connected
52 receive signal from 2. Defect of outdoor Main fuse/Noise Filter
(Inverter PCB  Main PCB)
inverter controller 3. Defect of outdoor Main / inverter PCB

 Error diagnosis and countermeasure flow chart


Is transmission
LED (Yellow) of inverter No Is noise filter or fuse No
Replace noise filter or fuse
compressor normal?
PCB on?
Yes Yes

Replace inverter compressor PCB

Is transmission cable No
Re-connect transmission cable
connected correctly?

Yes

No
Is MAIN PCB normal? Replace MAIN PCB

Yes

Replace inverter compressor PCB

30
Error
Error Type Error Point Main Reasons
No.

In case Main PCB canʼt 1. Transmission cables are not connected


Transmission error
53 receive signal from indoor 2. Transmission cables are short / open
(Indoor unit  Main PCB)
unit 3. Defect of outdoor Main / indoor PCB

 Error diagnosis and countermeasure flow chart

Are quantity of indoor No Is indoor unit No


units installed same as quantity correct after
the data of LGMV? Auto Addressing?

Yes Yes

End

No
Is power supplied
Supply power
to indoor units?

Yes

Replace indoor unit PCB or


transmission PCB
after check defected indoor

In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with
same method of CH05. and additionally check as shown as below and above flow chart
• Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with
which the number of transmission is not increased with LGMV
• Although the quantity of indoor units installed is not same as LGMV data, and if transmission of the indoor unit
displayed at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at
LGMV) may have following problems
 wrong connection of transmission cable or power cable
 fault of power / PCB / transmission cable
 duplication of indoor unit number
• If transmission is not doing well wholly then the Auto Addressing is not done
• The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be
duplicated

• After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then the
central control address also should be input.
In case that only transmission PCB is replaced above process is not needed

31
Error
Error Type Error Point Main Reasons
No.

1. Main power line connectiong &


Input power line reverse disconnecting.
Input power 3 phase con-
54 connectiong &
necting error 2. Noise Filter output power line connectiong
Disconnecting.
& disconnecting.

 Error Diagnosis and Countermeasure Flow Chart

No
Is main 3phase power line Connect 3phase power line rightly
connecting right?

Yes

No
Is Noise Filter output power Connect Noise Filter output power line rightly
line connecting right?

Yes

No
Is Inverter PCB assembly Replace inverter PCB assembly
normal?

Yes

Recheck power and installation


condition

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
32
Error
Error Type Error Point Main Reasons
No.

Series Installation of Slave


59* Series Installation Error Outdoor Unit Larger Than 1. Dip Switch Setting Error
Master Capacity

 Error Diagnosis and Countermeasure Flow Chart

1. Set the most


Is Dip switch No
capacitor
setting normal?
ODU for Master
Yes
Are there setting with No
Master→Slave1→Slave2→ Set with Master→Slave1→Slave2→Slaver3
Slaver3?
Yes

Is there any error when No


1. Replace Main PCB
power reset?

Yes

Recheck installation
condition

33
Error
Error Type Error Point Main Reasons
No.

1. EEPROM contact defect/wrong insertion


Inverter PCB EEPROM EEPROM Access error and
60 2. Different EEPROM Version
error Check SUM error
3. ODU inverter PCB assembly damage

I Error Diagnosis and Countermeasure Flow Chart

1.Check EEPROM insert direction/connection condition


No
Is EEPROM insertion normal? 2.Check EEPROM Check SUM
→ Replace if abnormality found

Yes

No
Is inverter PCB assembly normal? Replace inverter PCB assembly

Yes

Recheck power and installation condition

34
Error
Error Type Error Point Main Reasons
No.

1. Cooling Fan not operating.


2. Overload operation (Pipe clogging/
Covering/EEV defect/Ref. overcharge)
Inverter PCB heatsink tem- 3. ODU fan locking
62 Heatsink High error
perature is over 95˚C 4. Heatsink assembly of INV PCB assemble
condition abnormal
5. Defect of temperature sensing circuit part
defect of INV PCB

I Error Diagnosis and Countermeasure Flow Chart


1. Check fan locking
2. Check covering of heat exchanger
Is installation No 3. Check distance between ODU and obstacles
condition normal ? 4. Check pipe distortion and abnormality
5. Check service valve is opened
→ Eliminate causes for abnormal condition
Yes

Is assemble condition Check assemble condition between INV PCB heatsink and
No
of INV PCB heatsink normal ? PFC module
→ Reassemble if abnormality found

Yes
Check resistance between No.19 pin and No.20 pin of PCB
PFC module
Is PCB temperature No → 7kΩ ±10% (at 25°C)
sensing part normal ? → Replace PCB if abnormality found

35
Error
Error Type Error Point Main Reasons
No.

1. Heatsink assembly of INV PCB assemble


Inverter PCB heatsink sen- condition abnormal
65 Heatsink TH error
sor is open or short 2. Defect of temperature sensing circuit part
defect of INV PCB

I Error Diagnosis and Countermeasure Flow Chart

Is assemble condition Check assemble condition between INV PCB heatsink and
No
of INV PCB heatsink normal ? PFC module
→ Reassemble if abnormality found

Yes

Check resistance between No.19 pin and No.20 pin of PCB


Is PCB temperature No PFC module
sensing part normal ? → 7kΩ ±10% (at 25°C)
→ Replace PCB if abnormality found

36
Error
Error Type Error Point Main Reasons
No.

1. Fan motor defect / assembly condition


Fan RPM is 10RPM or less abnormal
for 5 sec. when ODU fan 2. Wrong connection of fan motor connector
67 Fan Lock Error
starts or 40 RPM or less
3. Reversing rotation after RPM target apply
after fan starting.
4. Inverter PCB assembly defect

I Error Diagnosis and Countermeasure Flow Chart

Is ODU Fan Motor Assemble No Check ODU Fan Motor assemble condition and fan locking
condition normal? → Reassemble or replace if abnormality found

%es

1. Set the multi tester to diode mode.


No 2. Check voltage between 1pin and 4pin of Fan Motor
Is ODU Fan Motor normal? (1Ţ0.2V)
3. Replace Inverter PCB if abnormality found.

%es

Check wiring between OUD fan motor and Inverter PCB


Is wire connection of No ( Check if Hall Senor and Motor output terminal color is
ODU Fan Motor wire normal? matched)
→ Reassemble if abnormality found

%es

No Replace Inverter PCB assembly


Is Inverter PCB assembly normal?

%es

Recheck power and installation condition

• Fan Motor resistance measuring


between each phase

Check voltage betwen


1pin and 4pin of fan motor

Fan motor
connector
Tester

37
Error No. Error Type Error Point Main Reasons

1.Overload operation (Pipe clog-


ging/Covering/EEV defect/Ref.
overcharge)
Inverter PCB input power current is 2.Compressor damage(Insulation
AC input instant over cur- over 2ms damage/Motor damage)
73 rent error (Matter of soft- 3.Input voltage abnormal (L,N)
* 1 PHASE : 48A peak
ware) (R,S,T,N)
* 3 PHASE : 27A peak 4.Power line assemble condition
abnormal
5.Inverter PCB assembly
damage(input current sensing part)

※ The input voltage on LGMV means the voltage between R-N or T-N phase.
38
Error No. Error Type Error Point Main Reasons

Main PCB EEPROM 1. No EEPROM


86 EEPROM Access Error
Error 2. EEPROM wrong insertion

I Error Diagnosis and Countermeasure Flow Chart


No
Is EEPROM assemble
Reset after checking EEPROM assemble condition
condition normal?

Yes

No
Is EEPROM 24C16? Replace EEPROM with 24C16

Yes

Recheck power and


installation condition

Note : Replace after power off.

39
Error No. Error Type Error Point Main Reasons

1. Defective temperature sensor con-


Outdoor unit liquid pipe nection
Abnormal sensor resistance value
113 (condenser) temperature 2. Defective temperature sensor
(Open/Short)
sensor error (Open / Short)
3. Defective outdoor unit PCB

Error No. Error Type Error Point Main Reasons

1. Defective temperature sensor con-


Outdoor unit sub-cooling necter connection
Abnormal sensor resistance value
115 outlet temperature sensor 2. Defective temperature sensor
(Open/Short)
error (Open/Short)
3. Defective outdoor PCB

I Error diagnosis and countermeasure flow chart

Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes

Is the value of temperature No


Replace sensor
sensor resistance normal?*

Yes

Replace outdoor unit PCB

* Sensor resistance 100 kΩ over (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ

40
Error
Error Type Error Point Main Reasons
No.

1. Wrong operation of 4way valve because of sludge


etc. inflow
Function error of outdoor Function error of 4way 2. No pressure difference because of compressor
151 4way (reversing valve) (reversing valve) in Main fault
3. Wrong installation of In/outdoor common pipe
4. Defect of 4way valve

I Error diagnosis and countermeasure flow chart

Is 4-Way valve connecter No


connection are properly Reconnect it
connected?
Yes

Is 4 Way valve coil No


Change 4 Way valve coil
resistance normal?*

Yes

Is 4 way valve coil connected No


Re-insert 4 way valve coil
to 4 way valve normally?**

Yes

After reset, can we


check supply voltage at PCB No
Replace outdoor unit PCB
when starting heating
mode operation***

Yes

No Check and replace compressor,


Is compressor working
Magnet switch, corresponding PCB
normally?
[refer electric component part]
Yes

After opposite
mode operation to present No If the same error is occurred in
mode, is the same error near future replace 4way valve
occurred again?
Yes

Replace 4 way valve

41
Error
Error Type Error Point Main Reasons
No.

1. RS-485 communication wiring defect


2. Communication defect between remote controller
Network error of central and indoor unit
242 Network Error
controller 3. RS-485 dip switch setting error
4. Indoor unit addressing ssetting error on central
controller

I Error diagnosis and countermeasure flow chart

Are there any No


communication wire of
RS-485 connections 1. Reconnect RS-485 communication wire
normal?
Yes

Are there any overlap of Yes


IDU address? Reset the overlap of IDU address for single address

No

Is Simple central No
controller setting 1. Set the slave mode with Simple central controller after reset.
normal?

Yes

Recheck power and


installation condition

<RS-485 communication wire miss connection>

42