Low Voltage Air Circuit Breakers IZM Series

Quick Selection

Comprehensive solutions
to meet and exceed the unique and
wide-ranging requirements
The power of fusion.

1874 1886 1893 1899 1906 1908 1911 1934 1962 1963 1967 1976 1977 1983 1984 1989 1999

There’s a certain energy at Eaton. It’s the power of uniting some of the
world’s most respected names to build a brand you can trust to meet
every power management need. The energy created supports our
commitment to powering business worldwide.
Eaton is dedicated to ensuring that reliable, efficient and safe power is
available when it’s needed most. With unparalleled knowledge of
electrical power management across industries, experts at Eaton deliver
customized, integrated solutions to solve our customers’ most critical
challenges. Eaton.com/SEAsia

All of the above are trademarks of Eaton Corporation or its affiliates. Eaton has
a license to use the Westinghouse brand name in Asia Pacific. ©2013 Eaton Corporation.
Low Voltage Air Circuit Breakers
IZM Series

Low Voltage Air Circuit Breakers IZM Series 1

IZM Series NES Type 2

IZM Series MWI Type 3


Low Voltage Air Circuit Breakers
Low Voltage Air Circuit Breakers IZM Series

1 IZM Series 1.1 Low Voltage Air Circuit Breakers IZM Series
Features, Benefits and Function ............................................................................................... 2
Greater safety for maintenance personnel with
Arcflash Reduction Maintenance System™.............................................................................. 3

Low Voltage Air Circuit Breakers IZM Series


Product Overview
Eaton Low Voltage Power Product Families
Circuit Breakers for Global IZM Series Air circuit breakers Each provides specific ratings IZM Series Air Circuit
Application consist of two product features and approvals to Breakers for IEC Rated
Eaton Low Voltage Air Circuit families: optimize performance when Switchboards
Breakers enable comprehensive applied in power distribution
solutions to meet and exceed NES Type Up to 690 Vac
equipment and custom
the unique and wide-ranging 200 to 6300A continuous
200A-1600A, 42kA / 50kA / enclosures.
requirements of today’s 42 to 100 kA Icu /Ics
global power distribution 65kA
systems. This powerful MWI Type
circuit breaker offering is
designed for ultimate custom 800A-6300A, 65kA / 85kA /
configuration and application 100kA
flexibility, with the needs of
the power distribution
equipment user and the
electrical equipment
manufacturer in mind.
IZM Series Low Voltage Air Circuit
Breaker Family


Low Voltage Air Circuit Breakers
Low Voltage Air Circuit Breakers IZM Series 1.1
Features, Benefits and Function 1
High interruption Two-step stored energy
ratings with current mechanism for manually
limiting performance and and electrical operated
low current let-through to breakers
reduce damaging energy Digitrip™ RMS Trip Unit
to downstream equipment family protection with
at high fault levels different models each providing
Withstand ratings up to increasing levels of
high interruption ratings protection and feature
to maximize system options for coordination,
coordination and selectivity information and
Three physical frame sizes diagnostics:
(Compact, Standard and Microprocessor-based
Double) to promote breaker rms sensing
application in compact Basic to programmable
modular enclosures and overcurrent protection
improve enclosure density and alarms
Continuous current Local display for Through-the-Door Design for Human
ratings from 200 to information, status and Interface with the Breaker
Compartment Door Closed
6300A with 100% rating diagnostics
at 104ºF (40ºC) and no Ampere, voltage and
derating on most ratings power metering
up to 122ºF (50ºC)
Power quality,
Fixed breaker mounting harmonics and
configurations with waveform capture
horizontal and optional
vertical and front Communications with
connected terminal translators to common
connections protocols
Drawout breaker Zone selective
mounting configurations interlocking for
with cassette and optional improved coordination
safety shutters Integral Arcflash
Three- and four-pole Reduction Maintenance
breaker configurations System™
Through-the-door design Breaker health High Technology Microprocessor-
for human interface with monitoring Based Digitrip RMS 1150+ Trip Units are
Available With Advanced Features Like
the breaker compartment Field-installable Programmable Overcurrent Settings,
door closed accessories Power Metering, Power Quality
and Communications
common across the
breaker frames and
designed to be easily
installed in the field to
service or modify the
breaker at the point of use
Secondary terminal
contacts mounted at the
top front of the breaker and
away from the primary
voltage areas for improved
safety and access. Finger-
safe terminal blocks
accommodate ring-tongue
or spade type terminals as
standard

2
1.1 Low Voltage Air Circuit Breakers
Low Voltage Air Circuit Breakers IZM Series

1 Greater safety for maintenance personnel with Arcflash


Reduction Maintenance System™
Personnel safety is of Major Benefits of Arcflash
paramount importance in Reduction Maintenance
today’s work environment. System™ :
Of recent concern is the
Increased personnel safety –
potential for serious injury due
by limiting the available arc
to exposure to electrical
flash energy
arcs. Eaton’s IZM Series trip
Simple to operate
units offer the patented
Enabled with circuit breaker
Arcflash Reduction Mainte-
door closed by a door
nance System™, which offers a
mounted lockable switch
non-delayed immediate
Enabled only for the time Direct ARMS activation on the
disconnection in the event of an
required to perform the circuit-breaker
arc fault. This disconnection is
desired maintenance
even faster than that of a
work
nondelayed short-circuit
Preserves overcurrent
release. This function can be
coordination under normal
activated directly on the
conditions
circuit-breaker or via an external
Reduction in incident energy
switch when maintenance
levels may permit reduced
personnel enters a hazardous
levels of Personal
area.
Protective Equipment (PPE),
therefore improving worker
comfort and mobility

Maintenance of a switchgear
system


Low Voltage Air Circuit Breakers
IZM Series NES Type

IZM Series 2.1 Standards and Certifications


IZM Series NES Type.................................................................................................................. 4
2
2.2 Catalog Number Selection
IZM Series NES Type.................................................................................................................. 7

2.3 Technical Data and Specifications


IZM Series NES Type.................................................................................................................. 12

2.4 Dimensions
IZM Series NES Type.................................................................................................................. 15

2.5 Wiring Diagrams


IZM Series NES Type.................................................................................................................. 16

IZM Series NES Type


Product Description Features, Benefits and Function Standards and Certifications
NES Type is a low voltage NES Type utilizes several Fold-up cassette—with this CEI EN 60947
air circuit breaker suitable innovative technologies: simple design, all items in BS EN 60439-1 Form 4b
for IEC switchgears and a cassette are replaceable IEC 60439-1 (low voltage
switchboards. The compact Rogowski coil—does not without removing the
saturate like iron core switchgear and controlgear
size and weight of three-pole cassette from the cell assemblies)
drawout with cassette Series sensors, and one sensor
accommodates 200–1600 “Arc chute” design IEC 60947-1 (low voltage
NES Type , allows for a Breaker-mounted racking
24.00 (609.6 mm) switchgear ampere range. You never switchgear and controlgear
have to change a sensor or levering-in device— —Part 1 general rules)
enclosure. Racking device is mounted
and CTs are not required IEC 60947-2 (low voltage
Tension clamp secondary on the breaker, decreasing switchgear and controlgear
The breaker ratings are:
terminals mounted directly the width of the cassette, —Part 2 circuit breakers)
630–1600A IEC 60947-2 because the cassette is not
from a voltage range of to fixed breaker or drawout IEC 60947-3 (switches,
cassette, they reduce burdened with the cost or
220–725 Vac parts of the lev-in disconnectors, switch-
wiring throughout disconnectors and
enclosure and provide Plug-N-Play accessories—
Application Description No special tools needed. fuse-combination units)
clean, organized wiring
NES Type is a compact Accessory comes with
schemes
globally certified low voltage plug and wires ready to
air circuit breaker. It Breaker-mounted
communication modules install
is rated for 630–1600
amperes (IEC 60947-2) —communication modules NES Type offers a life of 20,000
with an interrupting capacity for INCOM™, Modbus® mechanical operations and
of 65 kA with short time and PROFIBUS mount 10,000 electrical operations
withstand at 42 kA at the 440/ directly to the cassette, with a high degree of
480 Vac level. reducing the space and reliability.
room required in gear for
NES Type circuit breaker communication capability
provides all the capabilities “Direct Drive”
of a power circuit breaker mechanism—
in the compact size symmetrically loaded
of a molded case breaker. forces of the two-staged
It offers you the same stored energy mechanism
protection and performance improves robustness,
—along with increased reliability, and achieves
flexibility—at half the size improved breaker
of a typical power circuit life ratings
breaker. The dimensions and
design of NES Type allows
up to eight breakers in a 24-inch
(600 mm) wide structure. The
one frame size, regardless
of ampere rating, reduces
drawing conversion, structure
integration time and parts
inventory for several board,
gear and machinery
applications.

4
2.1 Low Voltage Air Circuit Breakers
IZM Series NES Type

IZM Series NES Type

IZM Series NES Type Standard Scope of Delivery as Expanded Standard Scope of Other Benefits of the NES Type
The innovative concept of the NES Type Usual Delivery for NES Type • The design of the main terminal offers
makes it possible to install two with- • With the new NES Type , you select a Some order types from the past can no maximum flexibility. The horizontal
drawable circuit-breakers in a 600 mm basic device that is already fitted with an longer be found since the following terminal can be rotated simply at the
wide section. This enables more economical electronic release. options are now already part of the installation so that it can also be used
section design, and performance in a • The standard mounting is on a horizontal standard scope of delivery: as a vertical connection. With
minimum of space goes far beyond the mounting plate or on horizontal traverses • The door escutcheon is now always withdrawable units, additional terminal
standard available worldwide. in the switching horizontal traverses in included in the scope of delivery.With pieces can.even be dispensed with. The
the switching cabinet. The NES Type withdrawable designs this is supplied cassette of the NES Type offers an
Applications can also be fastened to vertical mounting with the cassette (withrawable unit). integrated flange terminal to connected
The circuit-breakers can be used in plates. • On withdrawable units the circuit- directly. For this reason, the main
four main application areas depending • With four-pole devices, the neutral breaker can be pulled out to inspect terminal pieces for NES Type are not part
on the type of equipment to be conductor is arranged on the left (front the arc chutes. With fixed units, it is of the standard scope of delivery. Don’t
protected: view). recommended that sufficient space is forget to order additionally required
• System protection, • The neutral conductor can be provided above the circuitbreaker to terminal pieces if needed.
• Motor protection, loaded 100% like the phase conductors. enable inspection. An additional cover is • Thanks to the separate mounting
• Transformer protection, • The circuit-breakers are provided not required. position, a switching operations counter
• Transformer protection, with a standard mechanical reclosing • All basic devices that are provided with can now be used also independently of a
These key applications make different lockout. After an overload trip,the fault is universal protection (with Digitrip 520M motor operator.
demands on the switches, which are usually examined first of all. After the …), now feature a display. • Withdrawable unit operation: The unit
met with a range of control units. fault is identified and rectified, the • On each circuit-breaker the integrated is actuated with a hand crank supplied
mechanical reclosing lockout is reset by Digitrip electronic release is factory as a standard feature and has a secure
Switches with Closing Release pressing the red mechanical trip indicator fitted with a sealable protective cover. position in the basic device. This is now
They are particularly suitable on the front of the circuit-breaker. • If a motor operator is ordered, the possible also with a standard tool
forsynchronization tasks. • An “Automatic Reset” can be ordered as “Spring-operated stored energy (square drive socket 1/4").
an option. This enables the circuit-breaker tensioned” indicator switch is
Coupler Switches to be restored to operation immediately automatically provided. External 24 V Supply
Besides the NES Typecircuit-breakers, at any time after the spring-operated • The standard protection functions
IN91 switch-disconnectors are available. stored energy mechanism is retensioned. of the NES Type operate generally
These are used, forexample, as coupler In these applications compulsory fault independently of an external control
switchesbetween different power supplies. analysis is intentionally avoided. voltage supply. The power supply of the
• The number of control cable terminals electronics unit, for example for overload
Modular Design depends on the accessories fitted. and short-circuit protection, is
The retrofitting of accessories is made • If a cassette is ordered without the implemented via the current
considerably easy thanks to the basic device, this can be already fitted transformers integrated in the circuit
efficient “plug & work” technology. with the maximum number of control breaker.
Accessory drawers and snap-fit cable terminals. For cost effectiveness • The universal release unit with display
mechanisms make it possible to fit in plants, the cassette is also offered can be fed with a 24 V DC supply if
the latest accessories with virtually no tools. without control circuit terminals so required so that the display function can
This allows you to respond flexibly to that fitting can be carried out later at also be used without a load. An external
changing requirements within your system. the installation or when the required 24 V DC power supply is needed if
accessories are determined at a later communication functions are required.
time.
• 2 changeover contacts are provided
as standard for ON/OFF status indication.
• A coding mechanism between the basic
device and the cassette prevents
impermissible combinations (“Rejection
Interlock”).


Low Voltage Air Circuit Breakers
IZM Series NES Type 2.1
Configuration

Components for NES Type Modbus Configuration 2


PROFIBUS-DP Modbus Communication Communications module MCAM
For the NES Type , PROFIBUS-DP or Modbus has a plug-in screw terminal for connection
Modbus RTU are optionally available as to Modbus. The module operates as a
fieldbus connections. Communication Modbus slave.
modules PCAM and MCAM are compact • Baud rate, data format and address
units for direct mounting in the auxiliary (max. 247) for Modbus are set with the
terminal strip. On retrofitting, four modular input keys of the trip unit. The maximum
PCAM terminals are replaced with one cable length is 1.2 km.
MCAM
communication module. This is possible for • The Modbus must be terminated with a
both for fixed and withdrawable units. 120¡terminating resistor.
The terminals provide all data available in • To operate the PCAM, a supply
the trip block to the fieldbus, including voltage of 24 V DC is required.
switching state, current, voltage, power, • The data connection to the circuit-
with 1150i or 520M trip energy, and diagnostic information such breaker is implemented internally
as overcurrent, phase asymmetry and through a serial high-speed data
overvoltage.Through the bus the motor connection.
operator can also be remotely controlled.
Data Access Via Modbus
Requirements The data is contained in comprehensive data
The communications modules can be used tables. Each data point is available as
NES Type in combination with circuitbreakers floating-point (IEEE) or fixed-point value.
with 1150i or 520M trip …520M or …1150i…circuit-breakers. This variance allows the integration of the
NES Type to be adapted to the Modbus
PROFIBUS-DP Configuration architecture. This enables a simple means of
Communications module PCAM has implementing a data filter, which facilitates
a 9-pin D-Sub socket for connection to the integration of NES Type data in the
PROFIBUS. The module works as a slave control system.
on PROFIBUS-DP; the data is defined
through a standardized device master data
file, which permits smooth integration of
NES Type in a DP line.
• On the PROFIBUS-DP side the module
Communication Capability Selection Criteria for NES Type supports automatic baud rate
The communication-capability of the NES Type Circuit-Breakers detection;
circuit-breakers open up new possibilities in Fundamental criteria for the selection of The PROFIBUS-DP bus address is set
power distribution. It provides all important circuit-breakers: through the trip unit’s display. The
operational information and passes this on. • Max short-circuit current I the maximum cable length is 2.4 km.
This increases system transparency and circuit-breaker’ point of installation: • To operate the PCAM, a supply
shortens the response times to states such this value determines the short- circuit voltage of 24 V DC is required.
as overcurrent, phase asymmetry and breaking capacity or the short-circuit • The data connection to the
overvoltage. current carrying capacity of the circuit- circuit-breaker is implemented
breaker. It iscompared with the Lcu,lcs and internally through a serial high--speed
A rapid intervention in a process can, for Lcwvalues of the switch and essentially data connection.
example, prevent downtimes and help to determines its size (see Technical data).
schedule maintenance activities and • Rated operational current Ln should
therefore boost plant availability. flow through the respective branch Data Access Via PROFIBUS-DP
circuit:This value must not be greater The data on PROFIBUS-DP are offered
A Modbus interface is offered as an than the maximum switch rated according to the profile for low-voltage
alternative in addition to the Profibus operational current of the circuit breaker. switchgear (LVSG) of PROFIBUS
interface. The rated operational current can be International (PROFIBUS and PROFINET User
adjusted down using additional rated Group). Five different data structures with
operational current modules. varying numbers of parameters are
• Ambient temperature of the available through the device master data
circuitbreaker: This is generally the file. This allows a data filter to be easily
internal temperature in the control implemented, which simplifies integration
panel.Observe the derating values with of the ACB data into the control system.
increased ambient temperature (see
Technical data).
• Circuit-breaker type: fixed mounted or
withdrawable units, 3 or 4 pole.
• Minimum short-circuit current, which
flows through the switching device: The
release must recognize this value as a
short-circuit and may react with a trip.
• Protection functions of the This is
determined by the selection of the
respective overcurrent release.

6
2.2 Low Voltage Air Circuit Breakers
IZM Series NES Type

Catalog Number Selection

2 IZM Series NES Type


1

N E S6 08 3 W 52 8 R T R N 4 5 N 4 X
Breaker Frame Size
N = Type NF, 630–1600A,

Standard, Mechanism, Device


E = IEC 60947-2

Fault Current Rating Future Use


S4 = 42 kA at 415 Vac IEC X = All product
S5 = 50 kA at 415 Vac IEC
S6 = 65 kA at 415 Vac IEC
UVR, Second Shunt Trip Drawout Breaker Shipping,
N = None Fixed Breaker Terminals
Frame Rating (Amperes) (Door Frame Kit ships as
A = 110–125 Vac/Vdc UVR
07 = 630 R = 220–250 Vac/Vdc UVR standard unless noted
08 = 800 L = 24 Vdc UVR otherwise)
10 = 1000 H = 48 Vdc UVR
13 = 1250 S = 60 Vdc UVR D = Drawout (or parent) breaker
16 = 1600 G = 32 Vdc UVR shipping alone, without door
1 = 110–127 Vac/Vdc second shunt trip frame kit
2 = 208–240 Vac/Vdc second shunt trip 4 = Drawout breaker in cassette,
Poles, Phasing 4 = 24 Vdc second shunt trip with shutters, short vertical/
3 = Three-pole, ABC 8 = 48 Vdc second shunt trip horizontal
4 = Four-pole, NABC F = Fixed terminal adapters for
Spring Release, rear connect, with mounting
Mounting Configuration Latch Check Switch feet, short vertical/
W = Drawout horizontal
N = No spring release, no LCS
B = Fixed mount rear connect, mounting bracket, E = No spring release, LCS wired external
with secondary terminal row A = 110–127 Vac/Vdc, no LCS
B = 110–127 Vac/Vdc, spring release LCS
C = 110–127 Vac/Vdc, LCS wired external
Trip Unit, Power Supply
R = 208–240 Vac/Vdc, no LCS
SW = Switch—no MCR—42 kA for IEC S = 208–240 Vac/Vdc, spring release LCS
22 = 520 LI, no ZSI T = 208–240 Vac/Vdc, LCS wired external
52 = 520 LSI, no ZSI L = 24 Vdc, no LCS
53 = 520 LSI, with ZSI P = 24 Vdc, spring release LCS
5G = 520 LSIG, no ZSI Q = 24 Vdc, LCS wired external
5H = 520 LSIG, with ZSI H = 48 Vdc, no LCS
M2 = 520M LSI, no ZSI, 24 Vdc J = 48 Vdc, spring release LCS
M3 = 520M LSI, with ZSI, 24 Vdc K = 48 Vdc, LCS wired external
MA = 520M LSIA, no ZSI, 24 Vdc
MB = 520M LSIA, with ZSI, 24 Vdc
MG = 520M LSIG, no ZSI, 24 Vdc Motor Operator
MH = 520M LSIG, with ZSI, 24 Vdc M = Manually operated Auxiliary, Switches,
R2 = 520M LSI, no ZSI, 24 Vdc, with ARMS B = 110–125 Vac/dc Label Language
R3 = 520M LSI, with ZSI, 24 Vdc, with ARMS T = 208–250 Vac/dc E = No auxiliary switches,
RA = 520M LSIA, no ZSI, 24 Vdc, with ARMS L = 24 Vdc no label (parent)
RB = 520M LSIA, with ZSI, 24 Vdc, with ARMS H = 48 Vdc 4 = 4 Form C, English
RG = 520M LSIG, no ZSI, 24 Vdc, with ARMS
RH = 520M LSIG, with ZSI, 24 Vdc, with ARMS
Trip Indicator OTS Secondary
Rating Plug(Amperes) and Bell Alarm Terminal Blocks
1 = 200 5 = 500 A = 1000 N None None Per breaker options 2
2 = 250 7 = 630 C = 1250 5 Interlock trip indicator 2 Form C Full complement 2
4 = 400 8 = 800 D = 1600
0 = No rating plug, Padlock Key Lock 3 Operations
Non-auto switch Provisions Provisions Counter
N No None No
Shunt Trip A No None Provided
B Yes (plastic/plastic) None No
N = No shunt trip
J Yes (plastic/plastic) None Provided
A = 110–127 Vac/Vdc
R = 208–240 Vac/Vdc
L = 24 Vdc
H = 48 Vdc

Note
1 Exclusionary rules apply. Refer to price list. Confirm all final part numbers with Eaton. Format structure subject to modifications and additions without notice.

2 Position 17, ACB (with digitrip) must choose”5”, switch-disconnector must choose”N”.

3 Order key lock provisions separately in miscellaneous accessories.

7
Low Voltage Air Circuit Breakers
IZM Series NES Type 2.2
Catalog Number Selection
NES Type Frame Cassette
2
NE 16 3 G A B N S F N N C

Cassette Family and Breaker Frame Cassette Shipping


NE = IEC N-Frame C = Cassette only

Continuous Ampere Range Future


16 = 630–1600 (IEC) N = None

Arc Hood
Future
Poles and Phasing A = Arc hood installed (default)
(Facing Front of Breaker) N = None
3 = Three-pole ABC Door Frame Gasket and Rejection Kits
4 = Four-pole NABC Secondary Contact Terminals Installed
B = Door kit included (default), with rejection kit
F = Full complement
Load Terminal Connections
TOC Switches
G = With vertical/horizontal bus adapter kit (short style) (Truck Operated Cell) Shutters
N = Not included (default) S = Included

Note
Only supply 2 types cassettes for IEC standard: 3 poles, NE163GABNSFNNC, 4 poles, NE164GABNSFNNC.

8
2.2 Low Voltage Air Circuit Breakers
IZM Series NES Type

Catalog Number Selection

2 IZM Series NES Type — Catalog Position 1–8


Note: Phasing left to right when facing front of breaker (ABC or NABC). Neutral is rated 100% of continuous current.

NES Type NES Type Frame Basic Device


Switching Capacity Continuous Three-Pole Configuration Four-Pole Configuration
Icu/Ics Current
kA Icw /1-sec Rating Catalog Number Catalog Number Available
(440 Vac) kA (40°C) Position 1–8 Position 1–8 Sensor Rating Plug (A)
Drawout-Mounted Configuration
42/42 42 630 NES4073W NES4074W 630, 500, 400, 250, 200
800 NES4083W NES4084W 800
1000 NES4103W NES4104W 1000
1250 NES4133W NES4134W 1250
1600 NES4163W NES4164W 1600
50/50 42 630 NES5073W NES5074W 630, 500, 400, 250, 200
800 NES5083W NES5084W 800
1000 NES5103W NES5104W 1000
1250 NES5133W NES5134W 1250
1600 NES5163W NES5164W 1600
65/50 42 630 NES6073W NES6074W 630, 500, 400, 250, 200
800 NES6083W NES6084W 800
1000 NES6103W NES6104W 1000
1250 NES6133W NES6134W 1250
1600 NES6163W NES6164W 1600
Fixed-Mounted (with Mounting Feet)
42/42 42 630 NES4073B NES4074B 630, 500, 400, 250, 200
800 NES4083B NES4084B 800
1000 NES4103B NES4104B 1000
1250 NES4133B NES4134B 1250
1600 NES4163B NES4164B 1600
50/50 42 630 NES5073B NES5074B 630, 500, 400, 250, 200
800 NES5083B NES5084B 800
1000 NES5103B NES5104B 1000
1250 NES5133B NES5134B 1250
1600 NES5163B NES5164B 1600
65/50 42 630 NES6073B NES6074B 630, 500, 400, 250, 200
800 NES6083B NES6084B 800
1000 NES6103B NES6104B 1000
1250 NES6133B NES6134B 1250
1600 NES6163B NES6164B 1600

9 
Low Voltage Air Circuit Breakers
IZM Series NES Type 2.2
Catalog Number Selection
Trip Units of NES Type Digitrip 520 LSI(G) Digitrip 520M LSI(G)
2

Rated current range 200A-1600A 200A-1600A


RMS value

Protection and coordination


Overview
Options LSI,LSIG LSI,LSIG LSIA
Rated current plug (ln)
Over-temperature trip
Long time delay protection L
Long time delay operating value 0.5-1.0X(In) 0.5-1.0X(In)
Long time delay delay-time tr (at 6* lr) 2-24s 2-24s
Long time delay thermal memory
Short time delay protection S
Short time delay operating value 200-1000%X(Ir) 200-1000%X(Ir)

Short time delay delay-time tsd , l2t at 8* lr 100-500ms 100-500ms


Short time delay, fixed time 100-500ms 100-500ms
Short time delay zone interlock ZSI
Non-delayed protection I 200-1200%x(In) 200-1200%x(In)
Non-delayed operating value
Non-delayed switch-off function
Closing release mechanism (MCR)
Ground fault protection G 1)

Ground fault alarming


Ground fault operating value 25-100%x(In)3) 25-100%x(In)3)
Ground fault delay time tg at 0.625 lr, ,l2t 100-500ms 100-500ms
Ground fault delay time, fixed time lag 100-500ms 100-500ms
Ground fault zone interlock ZSI
Ground fault thermal memory
Neutral conductor protection N

System diagnosis
Status/Overload LED display
Trip signal light
Current at trip point 1)

Long-distance ground fault release/alarming contact 1)

Long-distance overload alarm contact 1)

System monitoring
Digital display four-digit LCD display

Communication protocol Options: Modbus or Profibus

Additional functions
Testing method 2) Test unit Test unit
ARMS maintenance system 1)

Ln =rating plug = rated operational current transformer 2) test units for secondary plugging Standard
Lr=Set value of long delay time operating 3) In combination with ARMS function limited to 1200A Optional
1) Requires external 24 VDC auxiliary power supply module

10
2.2 Low Voltage Air Circuit Breakers
IZM Series NES Type

Catalog Number Selection


NES Type Miscellaneous Accessories
2
External Neutral Current Sensor (for Residual Ground)
Catalog Number
NFNCTKIT

Mechanical Interlock Assembly Kits


Type of Interlock Kit
Catalog Number Breaker Type Comments

NFMI2F Fixed Cable Type 2 Kit also requires 1 Cable Kit


NFMI31F Fixed Cable Type 31 Kit also requires 2 Cable Kits
NFMI32F Fixed Cable Type 32 Kit also requires 3 Cable Kits
NFMI33F Fixed Cable Type 33 Kit also requires 3 Cable Kits
NFMI2D Drawout Cable Type 2 Kit also requires 1 Cable Kit
NFMI31D Drawout Cable Type 31 Kit also requires 2 Cable Kits
NFMI32D Drawout Cable Type 32 Kit also requires 3 Cable Kits
NFMI33D Drawout Cable Type 33 Kit also requires 3 Cable Kits

Cable Kits for Mechanical Interlock


Catalog Number Comments

NRXMIC5 NRX - Cable for Mech. Interlock Kit 1520mm


NRXMIC6 NRX - Cable for Mech. Interlock Kit 1830mm
NRXMIC8 NRX - Cable for Mech. Interlock Kit 2440mm
NRXMIC10 NRX - Cable for Mech. Interlock Kit 3050mm

Cassette Cell Switch Kit


Catalog Number Comments
NRXCSKT Cell switch

Key Lock Provision Kit


Catalog Number Comments

NKIRKKIT Kirk
NRONISKIT Ronis
NCASTELLKIT Castell
NCESKIT CES
Note: Lock cylinder and key are not supplied.

Time Delay Undervoltage Module


Catalog Number Comments

70C1316G01 120 VAC


70C1316G02 230 VAC

Communication Module Rated


Control voltage
Catalog Number Comments Us V For use with Notes

MCAM MODBUS communication – NES Type Four separately secondary terminal blocks are
module needed if ordered
PCAM Profibus communication module NES Type Four separately secondary terminal blocks are

needed if ordered additionally
EASY400-POW Power supply NES Type Input voltage: 50/60HZ, 115V/230V,

212319 output voltage:24VD(±3%);
output current: 1.25A
Note: Miscellaneous accessories are not in 20 digital part numbers, need to be ordered separately.

11
Low Voltage Air Circuit Breakers
IZM Series NES Type 2.3
Technical Data and Specifications

Mounting and Load Connection Configurations 2


Rear-Connected
Horizontal/Vertical Adapter Kit
Breaker Breaker Standard Bus With and Without Cover
Type Mechanism Connection Provisions (Kits Shipped Unassembled)
Drawout Breaker Stored energy Finger clusters —

Cassette — Rear-connected
pre-drilled bus pads

Fixed Stored energy Rear-connected


pre-drilled bus pads

IEC 60947-2 Ratings


Description Rating Rating Rating
Continuous current rating (amperes) 630 and 800 1000 and 1250 1600
Shor t- circuit rati ng (k A) I cu Ics I cu I cs Icu I cs
240/254 Vac 85 50 85 50 85 50
415/435 Vac 65 50 65 50 65 50
690/725 Vac 42 42 42 42 42 42
Short-time withstand = Icw (kA) / 1sec 42 42 42 42 42 42

Note
1 35 kAIC short-time withstand at 635V level only. All other voltages 42 kAIC short-time withstand.

12
2.3 Low Voltage Air Circuit Breakers
IZM Series NES Type

Technical Data and Specifications

2 Shunt Trip
Control Operational Voltage Inrush/Continuous Power Opening Time
Voltages Frequency Range 70–110% Consumption (VA) (ms)
24 DC 17–26 500/5 25
48 DC 34–53 530/5 25
110–127 50–60 Hz 77–140 540/5 25
110–125 DC 77–138 540/5 25
208–240 50–60 Hz 146–264 500/5 25
220–250 DC 154–275 515/5 25

UVR
Control Operational Voltage Dropout Volts Inrush/Continuous Power Opening Time
Voltages Frequency Range 85–110% 35–60% Consumption (VA) (ms)
24 DC 20–26 8–14 500/5 50
32 DC 27–35 11–19 620/5 50
48 DC 41–53 17–29 850/5 50
110–127 50–60 Hz 94–140 44–94 890/5 50
110–125 DC 94–138 44–94 890/5 50
208–240 50–60 Hz 177–264 84–125 910/5 50
220–250 DC 187–275 88–132 910/5 50
380–415 AC 323–457 145–228 960/5 50

Spring Release
Control Operational Voltage Inrush Power Closing Time
Voltages Frequency Range 70–110% Consumption (VA) (ms)
24 DC 17–26 500 25
48 DC 34–53 530 25
110–127 50–60 Hz 77–140 540 25
110–125 DC 77–138 540 25
208–240 50–60 Hz 146–264 500 25
220–250 DC 154–275 515 25

OCT/OTS
Control Contact Rating
Voltages Frequency (Amperes)
250 50–60 Hz 10
125 DC 0.5
250 DC 0.25

Auxiliary Switch
Control Contact Rating
Voltages Frequency (Amperes)
250 50–60 Hz 10
125 DC 0.5
250 DC 0.25

13 
Low Voltage Air Circuit Breakers
IZM Series NES Type 2.3
Technical Data and Specifications

Breaker Position/Continuity 2
Breaker Continuity Between Continuity Between
Position Red and Black Lead Pairs Blue and Black Lead Pairs
Open NO 45 and 43
NO 46 and 47
NO 51 and 49
NO 52 and 53
Closed 44 and 43 NO
48 and 47 NO
50 and 49 NO
54 and 53 NO

Motor Operator
Control Operational Voltage Running Current Typical Inrush Power Consumption Maximum Charging
Voltages Frequency Range 85–110% (A) Current (VA) Time (Sec)
24 DC 20–26 5 500% 150 3
48 DC 41–53 3 500% 150 3
110–127 50–60 Hz 94–140 2 300% 280 3
110–125 DC 94–138 1 500% 150 3
208–240 50–60 Hz 177–264 1 1000% 280 4
220–250 DC 187–275 1 1000% 280 4

Control Voltages and Currents


Control Voltages 24 Vdc 48 Vdc 110–125 Vdc 110–127 Vac 220–250 Vdc 208–240 Vac
Current
Close current (inrush) 21 11 5 5 2 2
Shunt trip current (ST)—(inrush/continuous) 21 / .2 11 / .1 5 / .04 5 / .04 2 / .02 2 / .02
Charge motor current—(inrush/continuous) TBD TBD 5/1 6/2 10 / 1 10 / 1
Operating Voltage Rating
Close 17–26 34–53 77–138 77–140 154–275 146–264
Trip 17–26 34–53 77–138 77–140 154–275 146–264
Charge 20–26 41–53 94–138 94–140 187–275 177–264

Dimensions
Approximate Dimensions in Inches (mm)

NES Type Three-Pole Drawout with Cassette


Height Width Depth Lbs (kg)
14.18 (360.2) 10.02 (254.5) 10.68 (271.3) 85.00 (38.59)

Fixed Circuit Breaker and Drawout with Cassette


Breaker Type Height Width Depth Lbs (kg)
Fixed
Three-pole 13.18 (334.8) 8.25 (209.6) 7.15 (181.6) 33.58 (15.23)
Four-pole 13.18 (334.8) 11.00 (279.4) 7.15 (181.6) 44.40 (20.14)
Drawout with Cassette
Three-pole 14.18 (360.2) 10.02 (254.5) 10.69 (271.5) 85.20 (38.65)
Four-pole 14.18 (360.2) 12.69 (322.3) 10.69 (271.5) 104.00 (47.17)

14
2.4 Low Voltage Air Circuit Breakers
IZM Series NES Type

Dimensions

2 NES Type Fixed Mounted


NES...F

NES Type Drawout


NES...W

Current Transformer of Neutral Conductor of NES Type

Unit: mm

Polarity mark

15 
Low Voltage Air Circuit Breakers
IZM Series NES Type 2.5
Wiring Diagrams

2
Internal Terminals
(Front view from left to right))

Shunt release
2 ST2 1 ST1
Undervoltage release
UV2 UV1
(2. Shunt releases) 4
(STS2)
3
(STS1)

Overload trip switch 1 (OTS) 6 OT1M 5 OT1C

8 OT2B 7 OT1B
Overload trip switch 2 (OTS)
10 OT2M 9 OT2C
12 ALM1
Alarm 11 ALMC

14 13 ALM2

Current transformer, Neutral conductor


16 N2 15 N1

Core-balance transformer, transformer


18 G2 17 G1

Enable transformer star point signal


Control unit Digitrip

20 SGF1 19 SGF2

Control voltage supply 24 V DC


22 AGND 21 +24V Communication
wiring ECAM,
24 CMM2 23 CMM1
MCAM, PCAM
Communication
26 CMM4 25 CMM3

Zone selectivity ZSI 28 ZCOM 27 ZOUT

30 29 ZIN

32 31

Activation Maintenance mode (ARMS)


34 ARMS1 33 ARMS2

Closing releases
36 SR2 35 SR1

Motor operator M
38 E02 37 E01

Message “Spring energy store tensioned“


40 LCB 39 SC
Latch check switch
42 LCM 41 LCC
44 A1
43 C1

46 B2 45 B1

48 A2 47 C2
Auxiliary contacts on/off
50 A3
49 C3

52 B4 51 B3

54 A4 53 C4

16
Low Voltage Air Circuit Breakers
IZM Series MWI Type

MWI Type
3.1 Standards and Certifications
IZM Series MWI Type................................................................................................................. 17

3.2 Catalog Number Selection


3 IZM Series MWI Type................................................................................................................. 20

3.3 Technical Data and Specifications


IZM Series MWI Type................................................................................................................. 27

3.4 Dimensions
IZM Series MWI Type................................................................................................................. 29

3.5 Wiring Diagrams


IZM Series MWI Type................................................................................................................. 32

IZM Series MWI Type


Product Description Standards and Certifications
MWI Type Air Circuit Breakers
are designed to enable global IEC Test Certifications Approvals and Marks
power distribution solutions MWI Type Air Circuit Breakers MWI Type Air Circuit Breakers
in IEC switchboards and other meet or exceed the carry the following approvals
custom enclosures. applicable IEC standards, and approval marks:
including:
MWI Type Air Circuit CE
Breakers have interrupting EN/IEC 60947-2 American Bureau of
ratings up to 100 kA at Shipping (ABS)
690 Vac with continuous Comprehensive Enclosure
Solutions Det Norske Veritas (DNV)
current ratings up to 6300A
MWI Type Air Circuit Breakers Lloyds of London
MWI Type Air Circuit
Breaker continuous current have proven performance in South African Bureau of
frames are 100% rated. IEC switchboards and custom Standards (SABS)
No thermal de-rating is enclosures manufactured by For a complete and
required when applying the Eaton and Low Voltage comprehensive listing of all
breaker in the low voltage Systems Builders (OEMs) to low voltage power
systems enclosure at the following standards: breakers, please visit
ambient temperatures EN/IEC 60947-1 www.eaton.com/SEAsia
of 104ºF (40°C)
EN/IEC 60439-1

17 
Low Voltage Air Circuit Breakers
IZM Series MWI Type 3.1
Expansion of Standardequipment External Control Voltage Supply
Supplied for MWI Type • The standard protection functions of
Some order types from the past can no the MWI Type , operate generally
longer be found since the following options independently of an external control
are now already part of the standard scope voltage supply. The power supply of the
of delivery: electronics unit, for example for overload 3
• The door escutcheon is now always and short-circuit protection, is
included in the scope of delivery. With implemented via the current
withdrawable designs this is supplied transformers integrated in the
with the cassette (withdrawable unit). circuit-breaker.
• On withdrawable units the circuitbreaker • The universal release unit with display
can be pulled out to inspect the arc can be fed with a 24 V DC/48 V DC
chutes. With fixed units, it is supply or a 120 V AC or 240 V AC supply
recommended that sufficient space is if required so that the display function
provided above the circuitbreaker to can also be used without a load. An
enable inspection. An additional cover is external power supply is needed if
not required. communication functions are required.
• On each circuit-breaker the integrated • The 1150i prelease unit should always be
Digitrip electronicrelease is factory fitted operated with an external power supply
with a sealable protective cover. as it is normally selected due to its
• If a motor operator is ordered, the extensive control voltage dependent
“Spring-operated stored energy functions.
mechanism tensioned” indicator switch is
automatically provided. Communication Capability
The communication-capability of the
Other Benefits of the MWI Type MWI Type circuit- breakers enable them to
• There are three main variants of open up new possibilities in power
MWI Type : Robust Safety Standard Scope of Delivery overcurrent release units, 520, 520M, distribution. They can thus provide and
Eaton's MWI Type , circuit-breakers offer a as Usual 1150 Series. On Digitrip 1150) , transmit all important operational
proven and complete range of air • The standard mounting is on a the power measurement is information. This increases system
circuit-breakers up to 6300 A. Four sizes horizontal mounting plate or on transparency and shortens the response
already an integral part of the electronic
enable the ideal circuit-breaker to be horizontal traverses in the switching
release. times to states such as overcurrent, phase
selected economically for any project. In this cabinet.
• With four-pole devices, the neutral • The voltage tap-off for power asymmetry and overvoltage. A rapid
way, only the module width increases with measurement is integrated in the device intervention in a process can,for example,
conductor is arranged on the left
the required rated operational current, (front view). so that an additional external voltage prevent downtimes and help to schedule
enabling the most compact and economical • The neutral conductor can be transformer is unnecessary. This solution maintenance activities and there fore boost
size to be selected. loaded 100% like the phase saves costs, space and installation effort. plant availability.A Modbus interface is
The particularly rugged circuit-breakers are conductors. • Certain applications require the use of an offered as an alternative in addition to the
already in use 100,000 times in harsh • The circuit-breakers are provided interface to the external control voltage Profibus interface.
industrial environments worldwide. Large with a standard mechanical supply (see below). A new feature is that
material thicknesses and a high short-time reclosing lockout. After an overload the electronic release can be prepared Selection Criteria for MWI Type
withstand current are its characteristic trip, the fault is usually examined for an external control voltage supply of
first of all. After the fault is identified Circuit-Breakers
features. 120 V AC or 240 V AC (order option).
and rectified, the mechanical Fundamental criteria for the selection
• A switching operations counter can now of circuit-breakers:
Applications reclosing lockout is reset by
be used thanks to the separate mounting • Max short-circuit current Ik max at the
pressing the red mechanical trip
The circuit-breakers can be used in four position, also independently of a motor circuit-breaker’s point of installation:
indicator on the front of the circuit-
main application areas depending on the breaker. operator. this value determines the short-circuit
type of equipment to be protected: • An “Automatic Reset” can be • Withdrawable unit operation: The unit is breaking capacity or the short-circuit
• System protection, ordered as an option. This enables actuated with a hand crank supplied. current carrying capacity of the
• Motor protection, the circuit-breaker to be restored to This is now possible also with a circuit-breaker. It is compared to the Icu,Ics
• Transformer protection, operation immediately at any time standard tool (square drive socket 3/8"). and Icw values of the circuit-breaker and
• Generator protection. after the spring-operated stored • The entire rated operational determines essentially its size (see
These key applications make different These energy mechanism is retensioned. current range from 800 A to 6300 A can Technical data).
key applications make different demands on In these applications compulsory be covered with two sizes. • Rated operational current In which should
the switches, which are met with a range of fault analysis is intentionally • Sizes ACB 6300A are produced in
avoided. flow through the respective branch
trip units. simple terms by doubling ACB 3200A. circuit: This value must not be greater
• If a cassette is ordered without the This consequently provides on the
basic device, this is already fitted than the maximum switch rated
Switches with Closing Release ACB 6300A two terminals for each phase operational current of the circuit-breaker.
They are particularly suitable for with the maximum number of control
on the incoming side and on the The rated operational current can be
cable terminals.
synchronization tasks. outgoing side. This facilitates the adjusted down using additional rated
• A coding mechanism between the
basic device and the cassette pre- thermal design of the switchboard and in operational current modules.
Coupler Switches vents impermissible combinations some switchboard systems simplifies • Ambient temperature of the circuit-
Beside the MWI Type . circuit-breakers, (“Rejection Interlock”). production and reduces the number of breaker: This is generally the internal
MWI Type switch-disconnectors are available. busbar adapter variants. temperature in the control panel. Observe
These are used, for example, as coupler • The phase sequence for the ACB 6300A the derating values with increased
switches between different power supplies. is as follows: (NN)AABBCC. ambient temperature (see Technical data).
• The ACB 6300A is now offered with • Circuit-breaker type: fixed mounted or
Modular Design horizontal connection as standard, thus withdrawable units, 3 or 4 pole.
Because components are installed from the considerably simplifying the busbar • Minimum short-circuit current, which
front, retrofitting accessories is especially connection for most switchboard flows through the switching device: The
quick and easy. This allows flexible systems. release must recognize this value as a
response to changing requirements within shortcircuit and may react with a trip.
the system. • Protection functions of the circuitbreaker:
This is determined by the selection of the
respective overcurrent release.
18
3.1 Low Voltage Air Circuit Breakers
IZM Series MWI Type

Components for MWI Type Communication Data access via PROFIBUS-DP


The MWI Type series devices can be connected to a PROFIBUS-DP or Modbus RTU The data on PROFIBUS-DP are offered according to the profile for low-voltage
filed bus. Interfaces PMINT and MMINT are compact devices for mounting switchgear (LVSG) of PROFIBUS International (PROFIBUS and PROFINET User
on top-hat rails, i.e. independently of the switch. They output all information Group). Five different data structures with varying numbers of parameters are
available in the trip unit to the fieldbus, including switch status, current, voltage, available through the device master data file. This allows a data filter to be easily
3 power, and energy, as well as diagnostic information such as overcurrent, phase implemented, which simplifies integration of the IZM data into the control
asymmetry and overvoltage. The fieldbus also facilitates actuation of the motor system.
operator and therefore its remote operation.
Modbus configuration
Requirements
The communications modules can be used in combination with MWI Type…520MC
or 1150i… circuit-breakers.

Modbus
PROFIBUS-DP configuration

PROFIBUS-DP

MMINT

INCOM
1 2 3 32
PMINT

INCOM

MWI Type
with 520MC or 1150i trip

MWI Type
with 520MC or 1150i trip Communications module MMINT has a plug-in screw terminal for connection
to Modbus. The module operates as a Modbus slave. The interface to the circuit-
breaker can be operated as a bus, so that up to 32 MWI Type units can be connected to
an MMINT. This makes the use of the IZM with the Modbus architecture
specially efficient.

Modbus
Communications module PMINT has a 9-pin D-Sub socket for connection to • The baud rate for Modbus communications is selectable with coding switches on
PROFIBUS. The module works as a slave on PROFIBUS-DP; the data is defined the MMINT; the bus address (up to 247) is set through the display of the trip
through a standardized device master data file, which permits smooth integration unit. The maximum cable length is 1.2 km.
of the IZM in a DP line. • The Modbus must be terminated with a 120 Ω terminating resistor. If the
MMINT is the last device in the network, a built-in terminating resistor
can be activated there with a coding switch.
PROFIBUS
• To operate the MMINT, a supply voltage of 24-125VDC or 120VAC is required.
• On the PROFIBUS-DP side the module supports automatic baud rate detection;
the PROFIBUS-DP bus address is set through the trip unit’s display. The maximum
cable length is 2.4 km. INCOM
• To operate the PMINT, a supply voltage of 24-125VDC or 100-240VAC(50/60Hz) • The data connection to the circuit-breaker is implemented through a serial
is required. INCOM bus connection. A shielded, twisted-pair data cable (recommended
are Belden 9463 or 3073F) can be used.
INCOM • The INCOM bus must be terminated with a 100 Ω terminating resistor, connected
• The data connection to the circuit-breaker is implemented through a serial between the two cable strands at the circuit-breaker end.
INCOM data connection. A shielded, twisted-pair data cable (recommended are • The maximum cable length is 3 km.
Belden 9463 or 3073F) can be used.
• The INCOM bus must be terminated with a 100 Ω terminating resistor, connected Data access via Modbus
between the two cable strands at the circuit-breaker end.
• The maximum cable length is 3 km. The data for each circuit-breaker connected to the INCOM bus is contained in
comprehensive data tables. Each data point is available as floating-point (IEEE) or
fixed--point value. This variance allows the integration of the IZM to be adapted to
the Modbus architecture. This allows a data filter to be easily implemented, which
simplifies integration of the IZM data into the control system.

19
Low Voltage Air Circuit Breakers
IZM Series MWI Type 3.2
Catalog Number Selection
MWI Type Breaker Product Family 1

MW I 8 12 4 L E A - 12 MT R P R N 4 L N N N W X 3

Breaker Frame Future Use


I = Standard X = All ACBs
or double
ACB Shipping Instructions
Interrupting Icu A = Fixed ACB with door kit
6 = 65 kA A = D/O ACB only without
8 = 85 kA door kit
C = 100 kA Trip Unit and Protection, W = D/O ACB in cassette
(and External Control (pre-wired and shutters)
Voltage When Required) Double frame D/O ACBs ship
Continuous Amperes Shunt Trip
NN = Non-automatic (no trip unit) without cassette
and Phasing (Facing Attachment (STA)
22 = 520 LI
Front of Breaker)
52 = 520 LSI N = None
08 = 800 ABC 5W = 520i LSIG A = 110–127 Vac/Vdc Latch Check Switch/Trip Unit
10 = 1000 ABC MT = 520M LSI (24–48 Vdc) R = 208–240 Vac/Vdc Metering Voltage Connection
12 = 1250 ABC MU = 520M LSI (120 Vac) C = 24 Vdc for Digitrip 1150 Trip Unit
16 = 1600 ABC MV = 520M LSI (240 Vac) H = 48 Vdc Latch Check 1150 Voltage
20 = 2000 ABC MJ = 520Mi LSIG (24–48 Vdc) B = 110–127 Vac/Vdc Switch Connection
25 = 2500 ABC MK = 520Mi LSIG (120 Vac) (100% duty) N = None Upper terminals
32 = 3200 ABC ML = 520Mi LSIG (240 Vac) S = 220–250 Vac/Vdc L = LCS wired to SRD Upper terminals
41 = 4000 ABC (standard ME = 520M LSIA (24–48 Vdc) (100% duty) C = LCS wired external Upper terminals
drawout only) MC = 520M LSIA (120 Vac) D = 24 Vdc (100% duty)
4N = 4000 AABBCC MF = 520M LSIA (240 Vac) K = 48 Vdc (100% duty)
5N = 5000 AABBCC CT = 520MC LSI (24–48 Vdc) Operations Counter and/or
6N = 6300 AABBCC CU = 520MC LSI (120 Vac) Keylock Provisions
CV = 520MC LSI (240 Vac) Motor Operator
Counter Keylock
CE = 520MC LSIA (24–48 Vdc) M = Manual operated Provisions
Poles and Neutral CC = 520MC LSIA (120 Vac) N = 110–125 Vac (5-sec)
(Facing Front of Breaker) CF = 520MC LSIA (240 Vac) N = No counter No locks
W = 110–125 Vdc (5-sec)
3 = Three CJ = 520MCi LSIG (24–48 Vdc) K = No counter Kirk lock
T = 220–250 Vdc (5-sec)
4 = Four (neutral left) C = No counter Castell lock
CK = 520MCi LSIG (120 Vac) P = 220–240 Vac (5-sec)
R = No counter Ronis lock
CL = 520MCi LSIG (240 Vac) L = 24 Vdc (5-sec)
A = Counter No lock
C1 = 520MC ARMS LSI (24–48 Vdc) K = 48 Vdc (5-sec)
Mounting Configuration Y = Counter Kirk lock
C2 = 520MC ARMS LSI (120 Vac)
and Load Terminals L = Counter Castell lock
C3 = 520MC ARMS LSI (240 Vac) Spring Release
H = Fixed horizontal H = Counter Ronis lock
C4 = 520MC ARMS LSIA (24–48 Vdc) Device (SRD)
V = Fixed vertical C5 = 520MC ARMS LSIA (120 Vac)
L = Drawout horizontal C6 = 520MC ARMS LSIA (240 Vac) N = None
(Vertical for 4000A C7 = 520MC ARMS LSIG (24–48 Vdc) A = 110–127 Vac/Vdc Padlock Provisions for Blocking Close
standard frame) C8 = 520MC ARMS LSIG (120 Vac) R = 208–240 Vac/Vdc and/or Open ACB Manual Pushbuttons
C9 = 520MC ARMS LSIG (240 Vac) C = 24 Vdc N = None
1W = 1150i LSI (24–48 Vdc) H = 48 Vdc P = Plastic (block close and open)
Nameplate Language
1N = 1150i LSI (120 Vac)
E = English
1P = 1150i LSI (240 Vac) Undervoltage Release (UVR) or
1R = 1150i LSIG/A (24–48 Vdc) 2nd Shunt Trip (ST) Bell Alarms Switch (OTS) with 2a/2b
1S = 1150i LSIG/A (120 Vac) Contacts and/or Mechanical Trip Indicator
Sensor and Rating Plug Rating N = None
1T = 1150i LSIG/A (240 Vac) A = UVR (110–127 Vac) OTS 2a/2b Trip Indicator
NN = None 16 = 1600
02 = 200 12 = 1150i ARMS LSI (24-48VDC) R = UVR (208–240 Vac) E = No OTS No indicator 2
20 = 2000
05 = 250 13 = 1150i ARMS LSI (120VAC) C = UVR (24 Vdc) L = With OTS With interlocked indicator
25 = 2500
04 = 400 14 = 1150i ARMS LSI (240VAC) H = UVR (48 Vdc)
32 = 3200
07 = 630 15 = 1150i ARMS LSI (125VDC) E = UVR (110–125 Vdc)
40 = 4000
08 = 800 16 = 1150i ARMS LSIG/A (24-48VDC) F = UVR (220–250 Vdc) Auxiliary Switch
50 = 5000
10 = 1000 63 = 6300 17 = 1150i ARMS LSIG/A (120VAC) G = UVR (32 Vdc) N = None
13 = 1250 18 = 1150i ARMS LSIG/A (240VAC) X = UVR (380–415 Vac) 4 = 4A/4B
19 = 1150i ARMS LSIG/A (125VDC) J = UVR (480 Vac) 6 = 6A/6B
K = UVR (600 Vac)
1 = 2nd ST (110–127 Vac/Vdc)
2 = 2nd ST (208–250 Vac/Vdc)
3 = 2nd ST (24 Vdc)
4 = 2nd ST (48 Vdc)
B = 2nd ST (110–127 Vac/Vdc
100% duty)
O = 2nd ST (220–250 Vac/Vdc
100% duty)
I = 2nd ST (24 Vdc 100% duty)
Q = 2nd ST (48 Vdc 100% duty)

Note
1 Exclusionary rules apply. Refer to price list. Confirm all final part numbers with Eaton. Format structure subject to modifications and additions without notice.

2 Position 20, ACB (with digitrip) must choose”L”, switch-disconnector must choose”E”.

20
3.2 Low Voltage Air Circuit Breakers
IZM Series MWI Type

Catalog Number Selection


Cassette MWI Type Breaker Product Family 1

3 E N 32 4 H A D N S N N N W C

Cassette Family Cassette Shipping


E = Standard or double frame IEC C = Cassette only

Future Use Cassette Wiring


N = All cassettes W = Cassette wired

Continuous Amperes Future Use


20 = Up to 2000A N = All cassettes
32 = 2500–3000A
41 = 4000A standard frame
Future Use
40 = 4000A
63 = 5000–6000A N = All cassettes

Poles Future Use


3 = Three-pole N = All cassettes
4 = Four-pole
Shutters
Rear Terminals S = Shutters installed
H = Horizontal stabs (upper
and lower terminals) Future Use
N = All cassettes
Arc Hood
A = Arc hood for 690 Vac Door Frame and Gasket Kit
D = Includes door kit

Note
1 Exclusionary rules apply. Refer to price list. Confirm all final part numbers with Eaton. Format structure subject to modifications and additions without notice.

21
Low Voltage Air Circuit Breakers
IZM Series MWI Type 3.2
Catalog Number Selection
MWI Type ACB—Drawout Circuit Breaker
Interrupting Icw Withstand Continuous Magnum ACB 3-Pole Catalog 3-Pole 3 4-Pole Catalog 4-Pole 3
Rating (kA) at Rating (kA) Current Rating Frame Type Number Phasing Number Phasing 3
440V Icu/Ics 2 1-Sec/3-Sec Amps at 40°C 1 Positions 1-10 (Left to Right) Positions 1-10 (Left to Right)
Standard Frame Drawout Circuit Breaker 5
65/65 65/-- 800 Standard MWI6083LEA ABC MWI6084LEA NABC
65/65 65/-- 1000 Standard MWI6103LEA ABC MWI6104LEA NABC
65/65 65/-- 1250 Standard MWI6123LEA ABC MWI6124LEA NABC
65/65 65/-- 1600 Standard MWI6163LEA ABC MWI6164LEA NABC
65/65 65/50 2000 Standard MWI6203LEA ABC MWI6204LEA NABC
65/65 65/50 2500 Standard MWI6253LEA ABC MWI6254LEA NABC
65/65 65/50 3200 Standard MWI6323LEA ABC MWI6324LEA NABC
65/65 65/50 4000 Standard MWI6413LEA ABC MWI6414LEA NABC
85/85 85/65 800 Standard MWI8083LEA ABC MWI8084LEA NABC
85/85 85/65 1000 Standard MWI8103LEA ABC MWI8104LEA NABC
85/85 85/65 1250 Standard MWI8123LEA ABC MWI8124LEA NABC
85/85 85/65 1600 Standard MWI8163LEA ABC MWI8164LEA NABC
85/85 85/65 2000 Standard MWI8203LEA ABC MWI8204LEA NABC
85/85 85/65 2500 Standard MWI8253LEA ABC MWI8254LEA NABC
85/85 85/65 3200 Standard MWI8323LEA ABC MWI8324LEA NABC
85/85 85/65 4000 Standard MWI8413LEA ABC MWI8414LEA NABC
100/100 4 85/65 800 Standard MWIC083LEA ABC MWIC084LEA NABC
100/100 4 85/65 1000 Standard MWIC103LEA ABC MWIC104LEA NABC
100/100 4 85/65 1250 Standard MWIC123LEA ABC MWIC124LEA NABC
100/100 4 85/65 1600 Standard MWIC163LEA ABC MWIC164LEA NABC
100/100 4 85/65 2000 Standard MWIC203LEA ABC MWIC204LEA NABC
100/100 4 85/65 2500 Standard MWIC253LEA ABC MWIC254LEA NABC
100/100 4 85/65 3200 Standard MWIC323LEA ABC MWIC324LEA NABC
105/105 4 85/65 4000 Standard MWIC413LEA ABC MWIC414LEA NABC
Double Frame Drawout Circuit Breaker 5
85/85 85/65 4000 Double MWI84N3LEA AABBCC MWI84N4LEA NNAABBCC
85/85 85/65 5000 Double MWI85N3LEA AABBCC MWI85N4LEA NNAABBCC
85/85 85/65 6300 Double MWI86N3LEA AABBCC MWI86N4LEA NNAABBCC
100/100 100/85 4000 Double MWIC4N3LEA AABBCC MWIC4N4LEA NNAABBCC
100/100 100/85 5000 Double MWIC5N3LEA AABBCC MWIC5N4LEA NNAABBCC
100/100 100/85 6300 Double MWIC6N3LEA AABBCC MWIC6N4LEA NNAABBCC
Notes
1 MWI air circuit breakers are 100% thermal rated (no de-rating necessary when properly applied in a specified enclosure).
2 Interrupting ratings shown are also applicable at 380V/415V/440V/500V/690V unless otherwise indicated.
3 Phasing left to right when facing front of breaker. Neutral is rated 100% kf continuous current.
4 Icu and Ics are 100kA at 440Vac and 85kA at 690Vac (except Icu and Ics of MWIC413LEA and MWIC414KEA are 105KA at 440Vac and 85kA at 690Vac).
5 MWI ACBs carry an IT rating at 440Vac per EN 60947-2 Annex H. Contact Cutler-Hammer for 690Vac IT applications.

22
3.2 Low Voltage Air Circuit Breakers
IZM Series MWI Type

Catalog Number Selection


MWI Type ACB—Fixed Circuit Breaker
Interrupting Icw Withstand Continuous Magnum ACB 3-Pole Catalog 3-Pole 4 4-Pole Catalog 4-Pole 4
3 Rating (kA) at Rating (kA) Current Rating Frame Type Number Phasing Number Phasing
440V Icu/Ics 2 1-Sec/3-Sec Amps at 40°C 1 Positions 1-10 3 (Left to Right) Positions 1-10 3 (Left to Right)
Standard Frame Fixed Circuit Breaker 6
65/65 65/-- 800 Standard MWI6083HEA ABC MWI6084HEA NABC
65/65 65/-- 1000 Standard MWI6103HEA ABC MWI6104HEA NABC
65/65 65/-- 1250 Standard MWI6123HEA ABC MWI6124HEA NABC
65/65 65/-- 1600 Standard MWI6163HEA ABC MWI6164HEA NABC
65/65 65/50 2000 Standard MWI6203HEA ABC MWI6204HEA NABC
65/65 65/50 2500 Standard MWI6253HEA ABC MWI6254HEA NABC
65/65 65/50 3200 Standard MWI6323HEA ABC MWI6324HEA NABC
85/85 85/65 800 Standard MWI8083HEA ABC MWI8084HEA NABC
85/85 85/65 1000 Standard MWI8103HEA ABC MWI8104HEA NABC
85/85 85/65 1250 Standard MWI8123HEA ABC MWI8124HEA NABC
85/85 85/65 1600 Standard MWI8163HEA ABC MWI8164HEA NABC
85/85 85/65 2000 Standard MWI8203HEA ABC MWI8204HEA NABC
85/85 85/65 2500 Standard MWI8253HEA ABC MWI8254HEA NABC
85/85 85/65 3200 Standard MWI8323HEA ABC MWI8324HEA NABC
100/100 5 85/65 800 Standard MWIC083HEA ABC MWIC084HEA NABC
100/100 5 85/65 1000 Standard MWIC103HEA ABC MWIC104HEA NABC
100/100 5 85/65 1250 Standard MWIC123HEA ABC MWIC124HEA NABC
100/100 5 85/65 1600 Standard MWIC163HEA ABC MWIC164HEA NABC
100/100 5 85/65 2000 Standard MWIC203HEA ABC MWIC204HEA NABC
100/100 5 85/65 2500 Standard MWIC253HEA ABC MWIC254HEA NABC
100/100 5 85/65 3200 Standard MWIC323HEA ABC MWIC324HEA NABC
Double Frame Fixed Circuit Breaker 6
85/85 85/65 4000 Double MWI84N3HEA AABBCC MWI84N4HEA NNAABBCC
85/85 85/65 5000 Double MWI85N3HEA AABBCC MWI85N4HEA NNAABBCC
85/85 85/65 6300 Double MWI86N3HEA AABBCC MWI86N4HEA NNAABBCC
100/100 100/85 4000 Double MWIC4N3HEA AABBCC MWIC4N4HEA NNAABBCC
100/100 100/85 5000 Double MWIC5N3HEA AABBCC MWIC5N4HEA NNAABBCC
100/100 100/85 6300 Double MWIC6N3HEA AABBCC MWIC6N4HEA NNAABBCC
Notes
1 MWI air circuit breakers are 100% thermal rated (no de-rating necessary when properly applied in a specified enclosure).
2 Interrupting ratings shown are also applicable at 380V/415V/440V/500V/690V unless otherwise indicated.
3 Fixed breakers have (H) horizontal terminals. Vertical adapters (V) are priced separately.
4 Phasing Left to Right when facing front of circuit breaker - Neutral rated 100% of continuous current.
5 Icu and Ics are 100kA at 440Vac and 85kA at 690Vac.
6 MWI ACBs carry an IT rating at 440Vac per EN 60947-2 Annex H. Contact Cutler-Hammer for 690Vac IT applications.
7
MWI standard size fixed ACB doesn't have 4000A.

23
Low Voltage Air Circuit Breakers
IZM Series MWI Type 3.2
Catalog Number Selection
Digitrip Trip Units for MWI Type ACB

Trip Unit Type Digitrip 520i Digitrip 520Mi Digitrip 520MCi Digitrip 1150i+ 1
Ampere range 200–6300A 200–6300A 200–6300A 200–6300A
Interrupting rating at 690V 40–100 kA 40–100 kA 40–100 kA 40–100 kA
rms sensing Yes Yes Yes Yes
Protection and Coordination
Protection Ordering options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed rating plug (In) Yes Yes Yes Yes
Overtemperature trip Yes Yes Yes Yes
Long delay Long delay setting 0.4–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In)
protection
Long delay time I2t at 6 x Ir 2–24 sec 2–24 sec 2–24 sec 2–24 sec
(L)
Long delay time I4t No No No 1–5 sec
IEC Type A, B, C curves No No No Yes
Long delay thermal memory Yes Yes Yes Yes
High load alarm No No No 0.7–1.0 x Ir
Short delay Short delay pickup 200–1000% x (Ir) & M1 200–1000% x (Ir) & M1 200–1000% x (Ir) & M1 150–1000% x (Ir) & M1
protection
Short delay time I2t at 8 x I r 100–500 ms 100–500 ms 100–500 ms 100–500 ms
(S)
Short delay time flat 100–500 ms 100–500 ms 100–500 ms 100–500 ms
Short delay time ZSI Yes Yes Yes Yes
Instantaneous Instantaneous pickup 200–1000% x (In) & M1 200–1000% x (In) & M1 200–1000% x (In) & M1 200–1000% x (In) & M1
protection
Making current release Yes Yes Yes Yes
(I)
Off position Yes Yes Yes Yes
Earth fault Earth fault alarm No Yes Yes Yes
protection
Earth fault pickup 25–100% x (In) 25–100% x (In) 25–100% x (In) 10–100% x (In)
(G)
Earth fault delay I2t at 0.625 x I n 100–500 ms 100–500 ms 100–500 ms 100–500 ms
Earth fault delay flat 100–500 ms 100–500 ms 100–500 ms 100–500 ms
Earth fault ZSI Yes Yes Yes Yes
Earth fault memory Yes Yes Yes Yes
Disable ground fault protection No No No Yes
Neutral protection (N) Model LSI Model LSI Model LSI Model LSI
System Diagnostics
Cause of trip LEDs Yes Yes Yes Yes
Magnitude of trip information No No No Yes
Remote signal contacts No Yes Yes Yes
Programmable contacts No No No 2

Notes
1 Over and undervoltage alarm or trip, over and underfrequency alarm or trip, voltage unbalance alarm or trip, reverse power trip and phase rotation alarm are included.

In = Rating plug rating.


Ir = LDPU setting.
i Trip units are only used on IEC breakers with earth fault.

24
3.2 Low Voltage Air Circuit Breakers
IZM Series MWI Type

Catalog Number Selection

Digitrip Trip Units for MWI Type ACB, continued

Trip Unit Type Digitrip 520i Digitrip 520Mi Digitrip 520MCi Digitrip 1150i+ 1
System Monitoring
Digital display No 4-Character LCD 4-Character LCD 24-Character LED
Current (%) full scale sensor No Yes +/– 2% Yes +/– 2% Yes +/– 1%
Voltage (%) L to L No No No Yes +/– 1%
Power and energy (%) No No No Yes +/– 2%
Apparent power kVA and demand No No No Yes
Reactive power kVAR No No No Yes
Power factor No No No Yes
Crest factor No No No Yes
Power quality—harmonics No No No Yes
% THD No No No Yes
System Communications
Type — — INCOM/PowerNet/Modbus 2 / INCOM/PowerNet/TripLink/
PROFIBUS 2 Modbus 2 /PROFIBUS 2
Power supply in breaker N/ A Optional Standard Standard
Additional Features
Trip log (three events) No No No Yes
Electronic operations counter No No No Yes
Testing method 3 Test set Test set Test set Integral and test set
Waveform capture No No No Yes
ARMs (Arcflash Reduction Maintenance System Mode) No No Yes Yes 4
Breaker health monitor No No No Yes
Programmable relay functions No No No Yes 1

Notes
1 Over and undervoltage alarm or trip, over and underfrequency alarm or trip, voltage unbalance alarm or trip, reverse power trip and phase rotation alarm are included.
2 Requires externally mounted MMINT or PMINT module.
3 Test set for secondary injection.
4 Contact Eaton for availability.

Ir = Rating plug rating.


In = LDPU setting.
i Trip units are only used on IEC breakers with earth fault.

25 
Low Voltage Air Circuit Breakers
IZM Series MWI Type 3.2
Catalog Number Selection

MWI Type Miscellaneous Accessories

Neutral Current Sensor


3
Catalog Number Sensor Rating (A) Catalog Number Sensor Rating
9253C03H01 200 9253C03H08 1200
9253C03H02 250 9253C03H15 1250
9253C03H03 300 9253C03H09 1600
9253C03H04 400 9253C03H10 2000
9253C03H05 600 9253C03H11 2500
9253C03H14 630 9253C03H12 3000
9253C03H06 800 9253C03H16 3150
9253C03H07 1000 9253C03H13 3200

Mechanical Interlock Assembly Kits Cable Kits


Type of Interlock Kit Catalog Number Comments
Catalog Number Breaker Type Comments
MIC5 Includes 2 Cables 1520 mm long (5 feet) each
M12FR Fixed Rod Type 2 Kit also requires 1 Rod Kit MIC6 Includes 2 Cables 1830 mm long (6 feet) each
M12FC Fixed Cable Type 2 Kit also requires 1 Cable Kit MIC8 Includes 2 Cables 2440 mm long 8 feet) each
MI31FC Fixed Cable Type 31 Kit also requires 2 Cable Kits MIC10 Includes 2 Cables 3050 mm long (10 feet) each
MI32FC Fixed Cable Type 32 Kit also requires 3 Cable Kits
MI33FC Fixed Cable Type 33 Kit also requires 3 Cable Kits
MI2DR Drawout Rod Type 2 Kit also requires 1 Rod Kit
MI2DC Drawout Cable Type 2 Kit also requires 1 Cable Kit
MI31DC Drawout Cable Type 31 Kit also requires 2 Cable Kits
MI32DC Drawout Cable Type 32 Kit also requires 3 Cable Kits
MI33DC Drawout Cable Type 33 Kit also requires 3 Cable Kits

Cassette Cell Switch Kit


Catalog Number Comments

M4CS Cell switch, 4CO


M8CS Cell switch, 8CO
M12CS Cell switch, 12CO

Time Delay Undervoltage Module


Catalog Number Comments

70C1316G01 120 VAC


70C1316G02 230 VAC

Communication Function of 520MC and 1150i Digitrip

Rated contro Voltage Application range


Us
Catalog Number Comments V

PMINT Converting module from INCOM protocol to Digitrip 520MC


PROFIBUS protocol, DIN mounting Digitrip 1150
MMINT Converting module from INCOM protocol to Digitrip 520MC
MODBUS protocol, DIN mounting Digitrip 1150

Note: Miscellaneous accessories are not in 25 digital part numbers and need to be ordered separately.

26
3.3 Low Voltage Air Circuit Breakers
IZM Series MWI Type

Technical Data and Specifications


MWI Type ACB Options and Accessories

Breaker-Mounted Options Undervoltage Release Mechanical Operations


3 and Accessories (UVR). Trips the breaker Counter. Records
Magnum breakers are when an existing voltage mechanical operations
available with a signal is lost or falls below of the breaker over its
comprehensive array of an established threshold installed life
factory-installed breaker Auxiliary Switch. Up to Key Off Lock Provisions.
options to enable configured- 6a/6b auxiliary individual Enables mounting of a
to-order solutions for dedicated contacts are single cylinder Kirk®,
specified customer available for customer use Castell or Ronis key lock
requirements. Field option to indicate if the breaker is to lock the breaker in the
kits are available to provide in the OPEN or CLOSE OPEN position
easy service, modification position Latch Check Switch.
and customization of the Mechanical Trip Indicator Provides 1 Form C
breaker at the point of use. Flag. The red trip indicator (changeover contact) that Shunt Trip, Spring Release and
Undervoltage Release Device Installed
Shunt Trip device (ST). flag pops out to provide changes state when the on Accessory Deck
Provides for remote local visual indication when breaker is ready to close.
electrically controlled the Digitrip RMS trip unit Can be wired to the Spring
breaker opening when acts to trip the breaker on Release Device for fast
energized by a rated an overcurrent condition. transfer applications
voltage input Available in two options: or wired for external
an interlocked version that ready-to-close indication
Spring Charge Motor
mechanically locks out the
(MOT). Charges the
breaker until the indicator
breaker closing springs
is manually reset and a
automatically, facilitating
non-interlocked version for
remote or local closing.
indication only.
The motor assembly Auxiliary Switches Come in Modular
includes its own cut-off Bell Alarm/Overcurrent 2a/2b Contact Stages Providing up to
Trip Switch (OTS). 6a/6b Dedicated Contacts
switch that changes state
at the end of the charging Provides 2 Form C
cycle. This contact can be (changeover) contacts that
wired out for external change state when the
indication Digitrip RMS trip unit acts
to trip the breaker on an
Spring Release device
overcurrent condition. The Arc Chutes are Easily Removable
(SR). Provides for remote for Inspection and Access to
contacts are available for
electrically controlled Breaker Contacts
external indication or
breaker closing when its
customer use and are
coils are energized by a
manually reset by the
rated voltage input
Mechanical Trip Indicator
Padlockable Pushbutton
Cover. Permits padlocking
hinged cover plates to
block access to the PUSH
ON and PUSH OFF buttons
on the breaker faceplate Heel-Toe Contact Design Provides
Demonstrated Long Life and Includes Mechanical Trip Indicator With Bell
Wear Indicator for Visual Inspection Alarm (OTS) Switches Mounted

27 
Low Voltage Air Circuit Breakers
IZM Series MWI Type 3.3
Technical Data and Specifications

MWI Type ACB Control Device Application Guide—Vdc


Breaker Control Device Nominal Voltage 24 Vdc 32 Vdc 48 Vd c 6 0 Vdc 125 Vd c 250 Vdc
Shunt Trip (ST)—Trip Circuit 3
Operational voltage range 70–110% 17–26 Vdc — 34–53 Vdc 42–66 Vdc 77–138 Vdc 154–275 Vdc
Power consumption (inrush) Required for 35 ms 1 250W — 250W 250W 450W 450W
Opening time Seconds 35 ms — 35 ms 35 ms 35 ms 35 ms
Spring Release (SR)—Close Circuit
Operational voltage range 70–110% 17–26 Vdc — 34–53 Vdc 42–66 Vdc 77–138 Vdc 154–275 Vdc
Power consumption (inrush) Required for 200 ms 250W — 250W 250W 450W 450W
Closing time Seconds 40 ms — 40 ms 40 ms 40 ms 40 ms
Spring Charge Motor (MOT)
Operational voltage range 85–110% voltage 20–26 Vdc — 41–53 Vdc 51–66 Vdc 94–138 Vdc 187–225 Vdc
Amperes (running) Running 12.0A — 5.0A 4.0A 2.0A 1.0A
Amperes (inrush) % of running 300% — 500% 500% 600% 600%
Power consumption — 300W — 250W 250W 250W 250W
Charging time Seconds 5 sec — 5 sec 5 sec 5 sec 5 sec
Undervoltage Release (UVR)
Operational voltage range 85–110% voltage 20–26 Vdc 27–35 Vdc 41–53 Vdc 51–66 Vdc 94–138 Vdc 187–275 Vdc
Dropout voltage range 30–60% voltage 7–14 Vdc 10–19 Vdc 14–29 Vdc 18–36 Vdc 33–75 Vdc 66–150 Vdc
Power consumption (inrush) Required for 200 ms 250W 275W 275W 275W 450W 450W
Power consumption (continuous) Required for 400 ms 18W 15W 18W 18W 10W 10W
Opening time Seconds 70 ms 70 ms 70 ms 70 ms 70 ms 70 ms
Auxiliary Switches
Minimum load contact rating Inductive load 0.5A — 0.5A — 0.5A 0.25A

MWI Type ACB Control Device Application Guide—Vac


Breaker Control Device Nominal Voltage 120 Vac 240 Vac 415 Vac
Shunt Trip (ST)—Trip Circuit
Operational voltage range 70 –110% 77–140 Vac 146–264 Vac —
Power consumption (inrush) Required for 35 ms 450 VA 450 VA —
Opening time Seconds 35 ms 35 ms —
Spring Release (SR)—close circuit
Operational voltage range 70–110% 77–140 Vac 146–264 Vac —
Power consumption (inrush) Required for 200 ms 450 VA 450 VA —
Closing time Seconds 40 ms 40 ms —
Spring Charge Motor (MOT)
Operational voltage range 85–110% voltage 93–140 Vdc 177–264 Vdc —
Amperes (running) Running 2.0A 1.0A —
Amperes (inrush) % of running 600% 600% —
Power consumption — 250 VA 250 VA —
Charging time Seconds 5 sec 5 sec —
Undervoltage Release (UVR)
Operational voltage range 85–110% voltage 94–140 Vac 177–264 Vac 323–457 Vac
Dropout voltage range 30–60% voltage 33–76 Vac 62–144 Vac 114–249 Vac
Power consumption (inrush) Required for 200 ms 450 VA 400 VA 480 VA
Power consumption (continuous) Required for 400 ms 10 VA 10 VA 10 VA
Opening time Seconds 70 ms 70 ms 70 ms
Auxiliary Switches
Minimum load contact rating Inductive load 10A 10A —

Note
1 100% duty shunt trips require power consumption (inrush) for 200 ms.

28
3.4 Low Voltage Air Circuit Breakers
IZM Series MWI Type

Dimensions

MWI Type Fixed 800-3200A


MWI...F...
3

A: Minimum cabinet size recommended ( not to scale)

MWI Type Neutral Conductor Current Transformer

Type Current rating

In full scale, all 2nd current rated value is 1.00A.


Insulation degree: 0.6kV, BIL:10kV(full wave)
Non-interruptive current rated value factor:
1.33 (ambient temperature at 30 degree)
1.0 (ambient temperature at 55 degree)

29 
Low Voltage Air Circuit Breakers
IZM Series MWI Type 3.4
Dimensions

MWI Type Drawout 800-3200A


MWI…W…

MWI Type Drawout 4000A


MWI…W…

30
3.4 Low Voltage Air Circuit Breakers
IZM Series MWI Type

Dimensions

MWI Type(Double-wide frame) Fixed 4000A-6300A


MWI...W...
3

MWI Type(Double-wide frame) Withdrawable 4000A-6300A


MWI…W…

A: Minimum cabinet size recommended ( not to scale)

31 
Low Voltage Air Circuit Breakers
IZM Series MWI Type 3.5
Wiring Diagrams

Internal Terminals Internal Terminals


3
Message "Spring energy store tensioned"
Overload trip switch 1 (OTS)
Digital relay-output modules
(A-Bus)
Overload trip switch 2 (OTS)

On/Off auxiliary contact unit 3


Undervoltage release
(2nd shunt trip)
Internal relay module

INCOM enable, Remote On switching


Supply, internal relay module
On/Off auxiliary contact unit 2
INCOM Internal system bus

NPOW
Current transformer, Neutral conductor
Sensor, transformer star point

Zone selectivity ZSI


On/Off auxiliary contact unit 1

Shunt release

Closing releases

Latch check switch Motor operator

32
3.5 Low Voltage Air Circuit Breakers
IZM Series MWI Type

Wiring Diagrams

Typical MWI Type Control Circuit

3 Legend:
LS Limit Switch for Closing Spring
MOT Motor for Spring Charging
ST Shunt Trip 1
SR Spring Release Close Open G Open R
UVR Undervoltage Release
OTS Overcurrent Trip Switch

Description of Operation: B12 B15 B26 B10 B24 A7 A1 A2 A3


1 — Motor is energized through
Lever
LS contact.
in Door
2 — Motor runs and charges closing Switch
spring. (Draw- a.
3 — When closing spring is fully charged, Control out Only)
LS contacts change state. Power OTS 1*
4 — Close contacts energize SR coil. SR L.S. b. ST a. UVR OTS 2*
5 — When breaker closes, “b” opens.
6 — LS contacts change state and motor MOT
recharges closing springs.

B13 B14 B27 B11 B25 A8 A4 A5 A6


Notes
* Contacts shown for breaker open (not fully charged),
not tripped.
– – – – Dotted line denotes MWI Breaker.
1 Not needed with 100% duty rated shunt.

MDSEOBKR

33 
Eaton Corporation plc is a diversified power management
company providing energy-efficient solutions that help our
customers effectively manage electrical, hydraulic and mechani-
cal power. The company is a global technology leader in electrical
products, systems and services for power quality, distribution
and control, power transmission, lighting and wiring products;
hydraulics components, systems and services for industrial and
mobile equipment; aerospace fuel, hydraulics and pneumatic
systems for commercial and military use; and truck and automo-
tive drivetrain and powertrain systems for performance, fuel
economy and safety. Eaton acquired Cooper Industries plc in
2012. The new company, Eaton Corporation plc, has approxi-
mately 100,000 employees and sells products to customers in
more than 150 countries. For more information,
visit www.eaton.com/SEAsia

Electrical Sector Asia Pacific


No.3, Lane 280, Linhong Road,
Changning District, Shanghai

Eaton Industries Pte Ltd


Electrical Sector