Hilti MI/MQ Technical Guide

Table of Contents

Introduction 1.0 6

Corrosion 2.0 7

MI Support System 3.0 10

MQ Support System 4.0 75

Installation System Hangers 5.0 104

Reference Charts 6.0 131

Hilti North American Product Technical Guide Volumes 1 and 2 are also available.
Contact your Hilti Field Engineer about them today.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 1
Hilti MI/MQ Technical Guide

Table of Contents
Section Description Page

1.0 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Published Load Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Our Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Our Quality System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.0 Corrosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Corrosion Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.1 Suggested Corrosion Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.1.1 The Corrosion Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.2 Types of Corrosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.2.1 Direct Chemical Attack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.2.2 Electrochemical Contact Corrosion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.2.3 Special Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.0 MI Support System — Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Benefits and Applications of MI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1.1 MI System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1.2 U-frames and Goalposts — General Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1.3 Lorraine Cross — General Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.4 Supported Cantilevers — General Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1.5 Case Study . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 MI Support System — Technical Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.1 General Design Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.2 Load tables — General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.3 Dynamic Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.4 Reusability of MI Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3 MI Support System — Allowable Load Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Load tables for U-frames and goalposts on steel beams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Load tables for U-frames and goalposts on concrete. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Load tables for Lorraine cross on steel beam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Load tables for Lorraine cross on concrete. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Load tables for Unsupported cantilever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Load tables for Supported cantilever — General information. . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.4 MI Components, Allowable Load Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 39
MI Girders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
MIC-90 / 120-U Crossbeam Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
MIC-90-L Cantilever Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
MIC-T Pedestal Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
MIC-90 / 120-E Girder Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
MI Steel Connectors: Connection to steel beams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
MI Steel Connectors: Connection to steel beams or channels . . . . . . . . . . . . . . . . . . . . . . . . . 57
MI Concrete Connectors: Connection to concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
MI multi-angle connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
MI-SGC-M12 beam clamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
MI-DGC beam clamp for direct connection to steel beam . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
MIC-TRC connection for threaded rod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Pipe Attachment to MI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
MIC-PG low-friction insert for sliding support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
MIC-PS90/120 sliding support clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
MIA-B090/120-M12 fixed point U-bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
MIC-UB90 U-bolt clamps for uninsulated pipes and conduits . . . . . . . . . . . . . . . . . . . . . . . . . 68

2 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

Table of Contents
Section Description Page

3.5 MI / MQ Compatible Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69


Benefits of the MI and the MQ systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
MIC-MI/MQ-X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
MQP-45 -F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
MIC-MI/MQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Individual connecting parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
3.6 Formulas and Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
3.7 Additional MI Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Attaching MI to larger steel beams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Cross connection between MI girder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4.0 MQ Support System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.1 Hilti Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Material and Finishes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Technical Data and Strut Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Load and Support Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Beam Loading Data for Hilti Strut Profiles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Loading Conditions for Columns. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Column Loading Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
4.2 MQ System Components, Load Data and Material Specifications. . . . . . . . . . . . . . . . . . . 87
MQK Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
MQK Angle brace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
MQN Pushbutton. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
MQM Wing Nut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Channel and Spring Nut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
MQA Saddle Nut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Hilti 3-D System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
MQW-Q2 Angle Pre-assembled 90 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
MQW Angles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
MQV Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
MQV Flat Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
MQB Clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
MQP and MQV Base Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Strut Beam Clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
4.3 MQZ and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
MQZ-L Base Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
MQZ-SS Strut Tie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
MEK Strut End Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
5.0 Installation System Hangers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
5.1 Hangers and Insulation Shields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Clevis Hanger SLC (Speed Lock Clevis) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
SLC Insulation Shield MH-SLIS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Clevis Hanger SDC (Standard Duty Clevis) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
SDC Insulation Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Loop Hangers LH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 3
Hilti MI/MQ Technical Guide

Table of Contents
Section Description Page

5.2 Beam Clamps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109


BC Beam Clamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
BC-WM Wide Mouth Beam Clamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Steel C-Clamp with Lock Nut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
5.3 Split Rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Split Rings — Electro Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Split Rings — Copper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
5.4 Riser Clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
MH-SLR-LH Speed Lock Riser Clamp — Long Hinge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
MH-CSLR-LH Copper Speed Lock Riser Clamp — Long Hinge . . . . . . . . . . . . . . . . . . . . . . 113
MH-SLR-S Speed Lock Riser Clamp — Short Hinge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
MH-SLR-LS Speed Lock Riser Clamp — Long Slotted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
5.5 Strut Clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
MH-CB Strut Clamp — Copper. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Strut Clamp — Rigid (SS 316) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
MH-RBA Strut Clamp — Rigid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
MH-R45 Strut Clamp — Rigid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
MH-EMT45 Strut Clamp — 45 EMT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
MH-EMTV Strut Clamp — EMT Top Screw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
MH-UB Strut Clamp — Universal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
5.6 Eye Couplers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Eye Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Offset Eye Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
5.7 Threaded Rod and Threaded Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Rod Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
MH-SLT Speed Lock Trapeze Nut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Hex Nuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Washers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Hex Head Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
5.8 Bracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Seismic Hinge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Vertical Rod Stiffeners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
5.9 Cast-In Place . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Continuous Concrete Insert Strut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Concrete Spot Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
6.0 Reference Charts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
6.1 Pipe and Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Schedule 40 Steel Pipe Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Schedule 80 Steel Pipe Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Copper Tubing (Type L) Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Copper Tubing (Type K) Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Schedule 40 PVC Plastic Pipe Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Schedule 80 PVC Plastic Pipe Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
6.2 Metric Conversions and Equivalents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
7.0 Terms and Conditions of Sales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Terms and Conditions of Sales (U.S.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Terms and Conditions of Sales (Canada) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136

4 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
MI/MQ Support and Installation
Systems
Hilti. Outperform. Outlast.
Hilti MI/MQ Technical Guide

1.0 Introduction

1.1 Published Load Values 1.3 Our Purpose


Technical data presented herein was current as of the date We passionately create enthusiastic customers and build
of publication (see back cover). Load values are based on a better future!
testing and analytical calculations unless otherwise noted
by Hilti or by contracted testing laboratories using testing
procedures and construction materials representative of
current practice in North America. Load values obtained from
testing represent the average results of multiple identical
samples. Variations in base materials such as concrete and
local site conditions require on-site testing to determine
BDUVBMQFSGPSNBODFBUBOZTQFDJՐDTJUF%BUBNBZBMTPCF
based on national standards or professional research and
analysis.
Note that design values published in reports issued by
approval agencies (e.g., ICC-ES, COLA, etc.) may differ
from those contained in this Technical Guide. Enthusiastic Customers
The tables and diagrams in this guide are intended purely We create success for our customers by identifying their
as an aid to the user and no guarantee can be given needs and providing innovative and value-adding solutions.
regarding their correctness or accuracy when used for design Build a better future
DBMDVMBUJPOTGPSBTQFDJՐDBQQMJDBUJPO4IPVMEZPV EFTQJUFUIF We embrace our responsibility towards society
care we have taken, discover an error in the information given and environment.
here, please notify us accordingly. In any event, the static
TZTUFNPS SFTQFDUJWFMZ UIFTQFDJՐDBQQMJDBUJPONVTUBMXBZT
1.4 Our Quality System
be checked for plausibility by the user. Hilti is one of a select group
of North American companies
For information regarding updates and changes, please
to receive the ISO 9001 and
contact Hilti, Inc. (US) Technical Support at 1-877-749-6337
*40$FSUJՐDBUJPOT5IJT
or Hilti (Canada) Corporation at 1-800-363-4458.
recognition of our commitment
1.2 Units to quality ensures our customers *ISO 14001 US Only

Technical data is provided in Imperial units. Metric values, that Hilti has the systems and
when provided, use the International System of units (SI) procedures in place to maintain our position as the world
in observance with the Metric Conversion Act of 1975 as market leader, and to continually evaluate and improve our
amended by the Omnibus Trade and Competitiveness Act performance.
of 1988. MI and MQ connector and base dimensions are That’s total customer satisfaction.
converted from SI units, shown in parentheses, to Imperial For Technical Support, contact
units.
Hilti, Inc. (US) at
1-877-749-6337 or

Hilti (Canada) Corporation at


1-800-363-4458.

6 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

2.0 Corrosion

2.1 Corrosion Protection Atmosphere Mean Corrosion Rate


The most common material used for corrosion protection Industrial 5.6 μm/year
of carbon steel parts is zinc. Zinc coatings can be uniformly Urban Non-Industrial 1.5 μm/year
applied by a variety of methods to achieve a wide range of or Marine
coating thickness depending on the application. All things Suburban 1.3 μm/year
being equal, thicker coatings typically provide higher levels of Rural 0.8 μm/year
protection. Indoors Considerably less than
An estimating table for the mean corrosion rate and service 0.5 μm/year
life of zinc coatings in various atmospheres is provided to Source: ASTM B 633 Appendix X1. Service Life of Zinc

the right. These values are for reference only, due to the large
WBSJBODFTJOUIFSFTFBSDIՐOEJOHTBOETQFDJՐDQSPKFDUTJUF
2.1.1 Suggested Corrosion
DPOEJUJPOT CVUUIFZDBOQSPWJEFUIFTQFDJՐFSXJUIBCFUUFS
Resistance
understanding of the expected service life of zinc coatings.
In controlled environments where the relative humidity is low Use of AISI 316 stainless steel in environments where pitting
and no corrosive elements are present, the rate of corrosion or stress corrosion is likely should be avoided due to the
of zinc coatings is approximately 0.15 microns per year. possibility of sudden failure without visual warning. The below
table is for reference only.
Zinc coatings can be applied to steel components by different
methods. These include: Corrosion Resistance Typical Conditions of Use
Phosphate and Oil Coatings Ƚ*OUFSJPSBQQMJDBUJPOT
Ƚ"45.#ȱ4UBOEBSE4QFDJՐDBUJPOGPS
(Black Oxide) without any particular
Electrodeposited Coatings of Zinc on Iron and Steel
JOՑVFODFPGNPJTUVSF
Ƚ"45."ȱ4UBOEBSE4QFDJՐDBUJPOGPS$PBUJOHTPG
Zinc electroplated 5 – 10 μm Ƚ*OUFSJPSBQQMJDBUJPOT
Zinc Electrodeposited on Iron and Steel
(ASTM B 633, SC 1, Type III) without any particular
Ƚ"45."ȱ4UBOEBSE4QFDJՐDBUJPOGPS;JOD$PBUJOH JOՑVFODFPGNPJTUVSF
(Hot-Dip) on Iron and Steel Hardware Mechanically deposited zinc Ƚ*OUFSJPSBQQMJDBUJPOTJOEBNQ
coating 40 – 107 μm environments and near
Hot-Dip Galvanizing (HDG) > saltwater
50 μm (ASTM A 153)
Ƚ&YUFSJPSBQQMJDBUJPOTJO
Sherardizing Process> 50 μm
only slightly corrosive
atmospheres
Stainless Steel Ƚ*OUFSJPSBQQMJDBUJPOTXIFSF
(AISI 304) heavy condensation is
present

Ƚ&YUFSJPSBQQMJDBUJPOTJO
corrosive environments
Stainless Steel (AISI 316) Ƚ/FBSTBMUXBUFS

Ƚ&YUFSJPSDPSSPTJWF
environments

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 7
Hilti MI/MQ Technical Guide

2.0 Corrosion

2.1.1.1 The Corrosion Process Galvanic Series of Metals and Alloys


$PSSPTJPOJTEFՐOFEBTUIFDIFNJDBMPSFMFDUSPDIFNJDBMSFBDUJPOCFUXFFOB Corroded End (anodic, or least noble)
material, usually a metal, and its environment that produces a deterioration of Magnesium
the material and its properties (ASTM G 15). The corrosion process can be very Magnesium alloys
Zinc
complex and has many contributing factors that lead to immediate or delayed
Aluminum 1100
destructive results. In anchorage and fastener design, the most common types of Cadmium
corrosion are direct chemical attack and electrochemical contact. Aluminum 2024-T4
Steel or Iron
2.1.2 Types of Corrosion Cast Iron
Chromium-iron (active)
2.1.2.1 Direct Chemical Attack Ni-Resist cast iron
Corrosion by direct chemical attack occurs when the base material is soluble in the Type 304 Stainless (active)
corroding medium. One method of mitigating these effects is to select a product Type 316 Stainless (active)
whose base metal is not susceptible to attack by the corroding chemical. Lead tin solders
Lead
When selection of a base metal compatible with the corroding medium is not Tin
possible or economical, another solution is to provide a coating that is resistant Nickel (active)
to the corroding medium. These might include metallic coatings such as zinc or Inconel nickel-chromium alloy (active)
Hastelloy Alloy C (active)
PSHBOJDDPBUJOHTTVDIBTFQPYJFTPSՑVPSPDBSCPOT
Brasses
2.1.2.2 Electrochemical Contact Corrosion Copper
Bronzes
All metals have an electrical potential relative to each other and have been ranked Copper-nickel alloys
accordingly to form the “electromotive force series” or galvanic series of metals, Monel nickel-copper alloy
see table to the right. When metals of different potential come into contact in the Nickel (passive)
Inconel nickel-chromium alloy
presence of an electrolyte (moisture), the more active metal with more negative
(passive)
potential becomes the anode and corrodes, while the other metal becomes the
Silver solder
cathode and is galvanically protected. Chromium-iron (passive)
Type 304 Stainless (passive)
5IFTFWFSJUZBOESBUFPGBUUBDLXJMMCFJOՑVFODFECZ
Type 316 Stainless (passive)
a. Relative position of the contacting metals in the galvanic series, Hastelloy Alloy C (passive)
Silver
b. Relative surface areas of the contacting materials and, Titanium
Graphite
c. Conductivity of the electrolyte. Gold
Platinum
5IFFGGFDUTPGFMFDUSPDIFNJDBMDPOUBDUDPSSPTJPONBZCFNJUJHBUFECZ
Protected End
a. Using similar metals close together in the electromotive force series (cathodic, or most noble)
Source: IFI Fastener Standards, 6th Edition
b. Separating dissimilar metals with gaskets, plastic washers or paint with low
electrical conductivity. Materials typically used in these applications include:

1. High Density Polyethylene (HDPE)


1PMZUFUSBՑVPSPFUIZMFOF 15'&

3. Poly carbonates
4. Neoprene / chloroprene
5. Cold galvanizing compound
6. Bituminous coatings or paint
/PUF4QFDJՐFSTNVTUFOTVSFUIBUUIFTFNBUFSJBMTBSFDPNQBUJCMFXJUIPUIFS
components in the service environment.

c. Selecting materials so that the smaller component is the cathode, most noble or
protected component

d. Providing drainage or weep holes to prevent entrapment of the electrolyte

8 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

2.0 Corrosion

2.1.2.3 Special Applications


5IJTBQQMJDBUJPODIBSUPGGFSTBHFOFSBMHVJEFMJOFBEESFTTJOHFOWJSPONFOUBMDPSSPTJPO EJSFDUDIFNJDBMBUUBDL
4JUFTQFDJՐD
DPOEJUJPOTNBZJOՑVFODFUIFEFDJTJPO

Application Conditions Fastener Recommendations


"MVNJOVNGBTUFOJOHT ՑBTIJOHSPPՐOH Interior applications without Galvanic zinc plating
accessories, hand rails, grating panels, condensation
TJHOQPTUTBOENJTDFMMBOFPVTՐYUVSFT
Exterior applications with condensation Stainless steel, X-CR
Water treatment Not submerged HDG, Sherardized or Stainless steel
Submerged Stainless steel
Waste water treatment Not submerged HDG or Stainless steel
Submerged Stainless steel
Marine (salt water environments, Non-safety critical or temporary HDG
shipyards, docks, off-shore platforms) connections
High humidity with the presence of Stainless steel1
chlorides — splash zone
On the off-shore platform or rig Stainless steel
Indoor swimming pools Non-safety critical HDG
4BGFUZDSJUJDBMPSTVCKFDUFEUPIJHI Stainless steel1
concentrations of soluble chlorides
Pressure / chemically treated wood Above grade HDG
Below grade Stainless steel
Power plant stacks / chimneys Non-safety critical HDG or Stainless steel
4BGFUZDSJUJDBMPSTVCKFDUFEUPIJHI Stainless steel
concentration of soluble chlorides
5VOOFMT MJHIUJOHՐYUVSFT SBJMT HVBSE Non-safety critical HDG, Stainless steel
posts) Safety critical Stainless steel1
1 Steel selection depends on safety relevance

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 9
Hilti MI/MQ Technical Guide

3.0 MI Support System — Introduction

#FOFӏUTBOE"QQMJDBUJPOTPG.*
Cable Trays Innovative Flexible
Because the Hilti MI system ʴ &BTZJOTUBMMBUJPO SFDPOՐHVSBUJPO
does not require welding, worker and extension
safety in flame and gas-sensitive ʴ Easy “as built” tolerance
areas is improved. In addition, the compensation
standardized, modular components ʴ Integrates with Hilti MQ Support
Panel Box bolt together quickly and easily and System
typically offer load values equal to or
higher than similar welded systems.
&GՐDJFOU
The Hilti MI system is modular, ʴ Only four part types
so setting new layouts around
ʴ Fast and easy on site installation
existing structures is easy. Likewise,
by one or two people
Pipes existing Hilti MI systems are easily
ʴ No welding means no downtime in
reconfigured to meet your changing
“hot” danger zones
needs. Once the new layout is
determined, simply unbolt existing
components; add or relocate Economical
pieces as needed; bolt the new
ʴ All parts are reusable
configuration together and apply
Duct Systems ʴ Up to 50% lighter, no special lifting
load. It's that easy!
equipment required
The modular nature of the Hilti MI ʴ Hot dip galvanized, no need to
Industrial Support System helps paint
reduce planning and installation time.
Because each piece is light-weight
and reusable, there is no need for
Safety
Operating Rooms heavy equipment, and nothing needs ʴ State-of-the-art connection types
to be thrown away, adding to overall ʴ Corrosion resistant
system efficiency and potential ʴ Tested under dynamic loading
savings to your bottom line. conditions
ʴ 5PSTJPOSFTJTUBOUQSPՐMFEFTJHO

Girders Girder Connectors Steel Connectors Concrete Connectors

MI-90 and MI-120 girder sizes Using bolt holes in the girders Connections to steel are Concrete connector
for medium-and heavy-duty and interlocking teeth in the made using reliable beam baseplates can be fastened
applications are resistant connectors, MI systems are clamps. The base plates are using a variety of Hilti
to horizontal and vertical BEKVTUBCMFVQUPPOUIF designed to cover a large anchors for a secure hold.
bending stresses as well as first installation, and can be range of standard steel Choose from mechanical and
torsional effects. Add the GJOFBEKVTUFECZ"MM QSPGJMFTVQUP(JSEFS chemical anchors according
light-duty Hilti MQ system connectors are packaged clamping accommodates to loading and base material
and you have all load classes with fastening parts for TUFFMQSPGJMFT conditions.
covered! convenience.

10 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.1.1 MI System Components

Girder Girder Connector Connector Connector

MI-90 3m 00304798 MI-120 3m 00304800


MI-90 6m 00304799 MI-120 6m 00304801 MIC-90-U 00304803 MIC-120-U 00304804 MIC-90-L 00304805

Bases for connecting to concrete

1" (25) x 9/16" (14)

MIC-C90-AA 00304825 MIC-C90-U 00304826 MIC-CU-MA 00304828 MIC-C90-D 00304827 MIC-C120-D 00304829

Bases for connecting to steel beams Beam Clamp

MIC-S90-A 00304812 MIC-S120-A 00304818 MIC-SA-MA 00304815


MIC-S90-B 00304813 MIC-S120-B 00304819 MIC-SB-MA 00304816
MIC-S90-AA 00304811 MIC-S90-C 00304814 MIC-S120-C 00304820 MIC-SC-MA 00304817 MI-SGC-M12 00233859

MI connectors/braces (application) Girder to threaded rods and steel Accessories

DI

DA

M12-F Hex. 00382897


MIC-TRC-M12 00233856
Collar Nut
1/2", 5/8"
MIC-DGC 90 00233860 A13-F (Washer) 00304771
MIC-TRC-M20 00233858
MIC-T 00304807 MIC-U-MA 00340806 3/4", 5/8" MIC-DCG 120 00233861 AM 12-F 1m 00304774

MI/MQ Connectors

4 1/8" (105)

45p
9
/16" (14)

1 5/8" (41)
1 5/8" (42)

M12-F Hex.
00382897 MIA-OH-90 00304889
Collar Nut Application
MQP-45-F 00304164 MIC-MI/MQ-X 00304881 MIA-OH Bolts Choose length MIA-OH-120 00304890 MQ to MI

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 11
Hilti MI/MQ Technical Guide

3.1.2 U-frames and Goalposts — General Assembly

$POOFDUJPOTUPTUFFM.*$4"" .*$4"#$"#$
˕ ˕ ˕

$POOFDUJPOTUPDPODSFUF.*$$"" .*$$%%
˕ ˕

.*DPOOFDUPS.*$6 .*$6
˖ ˖

The MI connector must engage the girder so the end of the girder is between the connector
XFMEBOEՐSTUIPMFPSTMPU TFFQJDUVSF˕ above. The bolts should be located in the holes
DMPTFTUUPUIFDPOOFDUPSCBTFBTQPTTJCMFCVUXJUIBNJOJNVNPGGSPNUIFHJSEFSFOE
Connectors with two bolts should position the bolts perpendicular to each other.

62 ft-lb

62 ft-lb

M12 Bolt tightening torque: For connectors For beam clamps

12 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.1.3 Lorraine Cross — General Assembly

$POOFDUJPOTUPTUFFM.*$4"#$"#$
˕
˕

$POOFDUJPOTUPDPODSFUF.*$$%%
˕

.*DPOOFDUPS˖ MIC-90-L/MIA-TP ; ˗ MIC-90-L


˖ ˗

Cantilever Cantilever
on both sides on one side

The MI connector must engage the girder so the end of the girder is between the connector
XFMEBOEՐSTUIPMFPSTMPU TFFQJDUVSF˕ above. The bolts should be located in the holes
DMPTFTUUPUIFDPOOFDUPSCBTFBTQPTTJCMFCVUXJUIBNJOJNVNPGGSPNUIFHJSEFSFOE
Connectors with two bolts should position the bolts perpendicular to each other.

62 ft-lb

62 ft-lb

M12 Bolt tightening torque: For connectors For beam clamps

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 13
Hilti MI/MQ Technical Guide

3.1.4 Supported Cantilevers — General Assembly

.*$POOFDUPST
MI girder MIC-90-L MIC-U-MA
MI-90/MI-120 ˕ ˖

˖
$POOFDUJPOTUPTUFFM
Steel beam MIC-S90-A/B/C/MIC-S120-A/B/C MIC-U-MA; MIC-SA/SB/SC-MA
˕ ˖˗

˗ $POOFDUJPOTUPDPODSFUF
Concrete MIC-C90-D/MIC-C120-D MIC-CU-MA; MIC-U-MA
˕ ˖˗
˕

˗ The MI connector must engage the girder so the end of the girder is between the connector
XFMEBOEՐSTUIPMFPSTMPU TFFQJDUVSF˕ above. The bolts should be located in the holes
DMPTFTUUPUIFDPOOFDUPSCBTFBTQPTTJCMFCVUXJUIBNJOJNVNPGGSPNUIFHJSEFSFOE
Connectors with two bolts should position the bolts perpendicular to each other.

62 ft-lb

62 ft-lb

M12 Bolt tightening torque: For connectors For beam clamps

14 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.1.5 Case Study

Case Study: MI system


vs traditional welding
A piping contractor assessed the MI system by carrying out a
test installation.

5IFPCKFDUJWFXBTUPDPNQBSFUIFXFMEFETUFFMUFDIOJRVFXJUI
the innovative Hilti MI Support System, in terms of the time
requirement and costs involved, by installing representative
structures of each type.

For the purpose of this direct comparison, trapezes


constructed from welded steel and MI system components
were prepared and then anchored to the ceiling of a factory
building.

The work was carried out by two experienced fitters from the
contractor.

Assembly and installation of the welded steel


structure (W4 x 13)

2 hours and 17 minutes

Cutting Drilling Welding Installation Painting


ȽNJOVUFT ȽNJOVUFT ȽNJOVUFT ȽNJOVUFT ȽNJOVUFT

Installation of the Hilti structure

31.5 minutes

Cutting and Assembly Installation Finished!


corrosion protection ȽNJOVUFT ȽNJOVUFT
ȽNJOVUFT

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 15
Hilti MI/MQ Technical Guide

3.1.5 Case Study

Hilti MI system saved 77% of working time and 24% of


total costs compared to welded structures.

Total time Total costs


(Assembly and installation) (Pre-fabricated structure and installation)
180- 600-
$637
2 hrs 17 min 500-
51 -24%
120- 15 400-
$482

$ Dollars
Minutes

24 160 39
-77% 300-
91
98 31.5 min
426
60- 200-
3 352
16 100-
12.5
0- 0-
Steel Hilti MI System Steel Hilti MI System

˄ Assembly 1
˄ Installation ˄ Corrosion protection ˄ Material cost ˄ Labor cost 2
˄ Rework / scrap 3

1. Labor 2. Basis labor wage: 20 $/h general; 50 $/h welder


Steel: 1 general, 1 welder 3. Basis 12% scrapping costs (prefab. construction)
Hilti MI: 2 general

Comparison Data Welded Steel MI System Difference


Weight of structure 212.9 lb 89.2 lb -58%
Installation time (assembly and installation — 2 laborers) 137 min 31.5 min -77%
Material costs $2.00/lb $3.95/lb +97%
Material costs for the structure $426 $352 -17%
Total costs (material + labor + scrap) $637 $482 -24%
-BCPSUJNFTQFOUPOFOUJSFQSPKFDU JODMVEFTBODIPSJOH
 4.6 hrs 1 hr -78%

Additional benefits of the Hilti structure


31.5 minutes

Easy handling and installation thanks 0OUIFTQPUBEKVTUNFOUBWPJETOFFE Reduction of physical strain on the
to individual components for costly modification installers

16 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.2 MI Support System — Technical Preview

3.2.1 General Design Fx or Fy indicates loading permissible in one direction only.


Information Fx + Fy indicates loads applied in both directions
The loading tables and diagrams for individual parts and simultaneously.
applications for the MI system are based on the following: Regardless of attachment type, all base material and connections
– DIN 18800 NVTUCFJOEFQFOEFOUMZWFSJՐFEUPFOTVSFBMMMPBEJOHDPOEJUJPOT
– AISI S100-2007 (American Iron and Steel Institute) — North have been accounted for.
"NFSJDBO4QFDJՐDBUJPOGPSUIF%FTJHOPG$PME'PSNFE4UFFM a) MI connection to steel — Load values are based on the
Structural Members MI-SGC-M12 beam clamp as the means of attachment.
– AISC 360-05 (American Institute of Steel Construction) The clamps must always be used in pairs positioned on
4QFDJՐDBUJPOGPS4USVDUVSBM4UFFM#VJMEJOHT PQQPTJUFTJEFTPGUIFՑBOHF. The published load values are
– ASME (American Society of Mechanical Engineers) based on testing with hot-dip galvanized plate on hot-dip
– Testing and structural analysis calculations galvanized surfaces. The allowable maximum shear load can
The basic design principles in ASME B 31.3 Process Piping CFMPXFSPONBUJOHQBSUTXJUIBMPXFSDPFGՐDJFOUPGGSJDUJPO
are similar and are based to a great extent on the regulations such as painted surfaces. When in doubt, tests should be
QVCMJTIFEJO"*4$"MMWFSJՐDBUJPODBMDVMBUJPOTUBLFUIFQBSUJBM carried out to determine the applicable maximum shear load.
safety factors into account. The materials being fastened must be clean and free from oil
and grease.
The allowable loads given in the tables are calculated
according to ASD (Allowable Stress Design) and ASME 31.1. b) MI connection to concrete — Load values are based on
the published allowable load values for Kwik Bolt 3 anchors at
Safety factors for MI girders
standard embedment depth in 3000 psi uncracked concrete
UIFQSPKFDUEFTJHOFSNVTUWFSJGZUIFBQQSPQSJBUFOFTTPGUIFTF
values. The other general conditions (i.e. concrete strength,
thickness, anchor spacing and edge distance, etc.) must
comply with the applicable published technical information,
BQQSPWBMT OBUJPOBMSFHVMBUJPOTBOEWFSJՐFEGPSTVJUBCJMJUZJOUIF
TQFDJՐDBQQMJDBUJPO

c) MI connectors bolted to girders — The minimum edge


EJTUBODF FOEPGBHJSEFSUPUIFOFBSFTUCPMU
TIBMMCF5IF
connector must engage the girder such that the girder end is
CFUXFFOUIFDPOOFDUPSXFMEBOEUIFՐSTUIPMFPSTMPUJOUIF
connector. Connectors supplied with two bolts must position
Material: 34 ksi yield strength for MI girders the bolts perpendicular to each other. Bolts can otherwise be
Safety factor: 1.67 located in any holes of the connectors. Pretension M12 bolts to
an installation torque of 62 ft-lbs, maximum 66 ft-lbs. M10 bolts
To convert ASD to LRFD (Load and Resistance Factor shall be pre-tensioned to an installation torque of 44 ft-lbs. In
Design): First multiply given loads by 1.67. The values you some cases, a higher moment resistance can be achieved by
get have to be factored by the relevant resistance and load using 3 bolts.
factors according to LRFD regulations.
d) Published allowable loads for applications are based on
3.2.2 Load Tables — General static loading conditions. Non static forces, including those
Information resulting from thermal or other expansion must be taken into
%FՐOJUJPOPGGPSDFWFDUPSTBOEBYJT account during design.

e) When applicable the allowable load values given in the


tables assume use of the MIC-PG low friction insert with a
coefficient of friction of μ = 0.15.

f) Single spans and cantilevers —5IFՐHVSFTJOUIFUBCMFT


apply to purely vertical loading or, where indicated, also
Load force directions are indicated in the tables ± Fxyz with + to horizontal loads. Due to the high torsional rigidity of the
acting in the arrow direction. girders (MI 90 and MI 120) the resulting increase in tensile

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 17
Hilti MI/MQ Technical Guide

3.2 MI Support System — Technical Preview


stress or twisting associated with the published loading is J
.*TZTUFNEZOBNJDUFTUT TFFUFTUTFUVQDPOՐHVSBUJPOTCFMPX
less the 1°. Other torsional loads must be independently - Cycles: 1 million
analyzed. - Frequency: 1 Hz
- Signal Form: Sinus
3.2.3 Dynamic Loads
- Amplitude: ±5 mm (10 mm total displacement)
a) Origin and types of dynamic loads - Cyclical force applied coincident to axis of pipe
%ZOBNJDMPBETBSFEFՐOFECZUIFMPBEBNQMJUVEF GSFRVFODZ 
number of load cycles, and direction. For pipe and industrial
3.2.4 Reusability of MI
cable tray supports there are basically two different types of
Components
relevant dynamic loads: Reusing MI system components is possible as long as all of
i) Dynamic loads with high frequency and small amplitudes, the following conditions are met before reuse:
commonly referred to as vibration, caused by operating – The components must not show any signs of damage such
rotating equipment such as pumps and motors. as deformation or cracking.
ii) Dynamic loads with low frequency and large amplitudes Ȱ5IFDPNQPOFOUTNVTUOPUIBWFCFFOTVCKFDUFEUPMPBET
commonly caused by wind, start or stop of equipment, exceeding the published allowable loads during previous
thermal cycling or individual components. applications.
– The corrosion protection on MI system components must
b) Piping
be undamaged and must meet the demands of the new
International piping standards (e.g. EN 13480 or ASME B 31.3)
application.
specify that the design of a pipe run has to be analyzed to
– Low-friction inserts MIC-PG that show clear signs of wear
eliminate dynamic loads transmitted to the pipe run. Dynamic
shall not be reused.
decoupling, impact brakes, vibration dampers, etc. are typically
– In order to avoid assembly errors, the personnel carrying out
used for this task.
the work must have read the installation instructions. Genuine
c) Application of Hilti pipe support products under dynamic Hilti connecting parts (bolts, nuts, etc.) must be used.
loads Ȱ.*OVUT.'4-84DBOCFSFVTFEVQUPՐWFUJNFT
The MI M12 Self Locking Collar Hex Nut uses a metal self assuming there is no visible damage.
locking mechanism in the threads to resist loosening bolted – In order to avoid damage to the components, structures
connections. The Junker vibration test performed according should only be suitably dismantled by trained personnel.
to DIN 65151 was used to test the MI bolted connections. In
The user carries responsibility for ensuring that these points
addition to connection parts dynamically tested, MI system
are observed.
dynamic tests, (including beam clamps, the MI M12 Self
Locking Collar Nuts, girders and connectors), were also tested *GBOZPOFPGUIFTFQSFSFRVJTJUFTJTOPUGVMՐMMFE UIF
without showing evidence of any reduction in load-carrying corresponding parts should not be reused.
capacity. Contact your Hilti Field Engineer for complete details.

18 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S90-AA U-frames and Goalposts on steel beams

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˕ ˕1 ˖ ˗

˗
U-frame MIC-S90-AA MIC-90-U MI-90

Uniformly distributed load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx – 4000 4000 4000 3510 3000 2610 2310 2070 1870
18 2182 2176 2169 2163 2157 2150 2010 1800 1620
36 1298 1298 1298 1298 1298 1298 1298 1298 1298
with Fx
60 779 779 779 779 779 779 779 779 779
84 556 556 556 556 556 556 556 556 556

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx – 3520 2640 2110 1750 1500 1300 1150 1030 930
18 2182 2176 1830 1520 1300 1130 1000 900 810
36 1298 1298 1298 1298 1298 1130 1000 900 810
with Fx
60 779 779 779 779 779 779 779 779 779
84 556 556 556 556 556 556 556 556 556

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx – 2620 1970 1580 1310 1120 980 860 770 700
18 1091 1088 1085 1081 980 850 750 670 610
36 649 649 649 649 649 649 649 649 610
with Fx
60 389 389 389 389 389 389 389 389 389
84 278 278 278 278 278 278 278 278 278

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx – 1750 1320 1060 880 760 660 590 530 480
18 727 725 723 721 660 580 510 460 420
36 433 433 433 433 433 433 433 433 420
with Fx
60 260 260 260 260 260 260 260 260 260
84 185 185 185 185 185 185 185 185 185

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx and the applicable load table above apply.
60
84
1 Fastened to steel beam with two MI-SGC-M12 beam clamps (item 00233859)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 19
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S90-A U-frames and Goalposts on steel beams

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˖ ˗
˕ ˕1

˗
Fy
U-frame MIC-S90-A MIC-90-U MI-90

Uniformly distributed load Fz with or without simultaneous load Fx or Fy = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 5340 5300 4230 3510 3000 2610 2310 2070 1870
18 2182 2176 2169 2163 2157 2150 2010 1800 1620
36 1809 1809 1809 1809 1809 1809 1809 1800 1620
with Fx or Fy
60 1085 1085 1085 1085 1085 1085 1085 1085 1085
84 775 775 775 775 775 775 775 775 775

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3520 2640 2110 1750 1500 1300 1150 1030 930
18 2182 2176 1830 1520 1300 1130 1000 900 810
36 1809 1809 1809 1520 1300 1130 1000 900 810
with Fx or Fy
60 1085 1085 1085 1085 1085 1085 1000 900 810
84 775 775 775 775 775 775 775 775 775

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 2620 1970 1580 1310 1120 980 860 770 700
18 1091 1088 1085 1081 980 850 750 670 610
36 904 904 904 904 904 850 750 670 610
with Fx or Fy
60 543 543 543 543 543 543 543 543 543
84 388 388 388 388 388 388 388 388 388

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 1750 1320 1060 880 760 660 590 530 480
18 727 725 723 721 660 580 510 460 420
36 603 603 603 603 603 580 510 460 420
with Fx or Fy
60 362 362 362 362 362 362 362 362 362
84 258 258 258 258 258 258 258 258 258

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx and Fy –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx or Fy and the applicable load table above apply.
60
84
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

20 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S90-B U-frames and Goalposts on steel beams

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˖ ˗
˕
˕1
˖

˗
Fy
U-frame MIC-S90-B MIC-90-U MI-90

Uniformly distributed load Fz with or without simultaneous load Fx or Fy = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 4540 4540 4230 3510 3000 2610 2310 2070 1870
18 2182 2176 2169 2163 2157 2150 2010 1800 1620
36 1809 1809 1809 1809 1809 1809 1809 1800 1620
with Fx or Fy
60 1085 1085 1085 1085 1085 1085 1085 1085 1085
84 775 775 775 775 775 775 775 775 775

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3520 2640 2110 1750 1500 1300 1150 1030 930
18 2182 2176 1830 1520 1300 1130 1000 900 810
36 1809 1809 1809 1520 1300 1130 1000 900 810
with Fx or Fy
60 1085 1085 1085 1085 1085 1085 1000 900 810
84 775 775 775 775 775 775 775 775 775

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 2620 1970 1580 1310 1120 980 860 770 700
18 1091 1088 1085 1081 980 850 750 670 610
36 904 904 904 904 904 850 750 670 610
with Fx or Fy
60 543 543 543 543 543 543 543 543 543
84 388 388 388 388 388 388 388 388 388

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 1750 1320 1060 880 760 660 590 530 480
18 727 725 723 721 660 580 510 460 420
36 603 603 603 603 603 580 510 460 420
with Fx or Fy
60 362 362 362 362 362 362 362 362 362
84 258 258 258 258 258 258 258 258 258

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx and Fy –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx or Fy and the applicable load table above apply.
60
84
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 21
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S90-C U-frames and Goalposts on steel beams

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˖ ˗
˕
˕1
˖

˗
Fy
U-frame MIC-S90-C MIC-90-U MI-90

Uniformly distributed load Fz with or without simultaneous load Fx or Fy = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3080 3200 3200 3200 3000 2610 2310 2070 1870
18 1482 1476 1469 1463 1457 1450 1444 1438 1431
36 1463 1457 1450 1444 1438 1431 1425 1419 1412
with Fx or Fy
60 1085 1085 1085 1085 1085 1085 1085 1085 1085
84 775 775 775 775 775 775 775 775 775

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3080 2640 2110 1750 1500 1300 1150 1030 930
18 1482 1476 1469 1463 1300 1130 1000 900 810
36 1463 1457 1450 1444 1300 1130 1000 900 810
with Fx or Fy
60 1085 1085 1085 1085 1085 1085 1000 900 810
84 775 775 775 775 775 775 775 775 775

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 2620 1970 1580 1310 1120 980 860 770 700
18 741 738 735 731 728 725 722 670 610
36 731 728 725 722 719 716 712 670 610
with Fx or Fy
60 543 543 543 543 543 543 543 543 543
84 388 388 388 388 388 388 388 388 388

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 1750 1320 1060 880 760 660 590 530 480
18 494 492 490 488 486 483 481 460 420
36 488 486 483 481 479 477 475 460 420
with Fx or Fy
60 362 362 362 362 362 362 362 362 362
84 258 258 258 258 258 258 258 258 258

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx and Fy –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx or Fy and the applicable load table above apply.
60
84
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

22 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S120-A U-frames and Goalposts on steel beams

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˕ ˖ ˗
˕1
˖

˗
MIC-S120-A MIC-120-U MI-120
U-frame Fy

Uniformly distributed load Fz with or without simultaneous load Fx or Fy = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 6080 6080 6080 6080 5200 4530 4010 3600 3250
18 2649 2641 2632 2624 2615 2607 2598 2590 2581
36 2493 2493 2493 2493 2493 2493 2493 2493 2493
with Fx or Fy
60 1496 1496 1496 1496 1496 1496 1496 1496 1496
84 1069 1069 1069 1069 1069 1069 1069 1069 1069

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 6080 4570 3650 3040 2600 2260 2010 1800 1630
18 2649 2641 2632 2590 2210 1930 1710 1530 1390
36 2493 2493 2493 2493 2210 1930 1710 1530 1390
with Fx or Fy
60 1496 1496 1496 1496 1496 1496 1496 1496 1390
84 1069 1069 1069 1069 1069 1069 1069 1069 1069

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 4540 3410 2730 2270 1940 1700 1500 1350 1220
18 1325 1320 1316 1312 1308 1303 1280 1150 1040
36 1247 1247 1247 1247 1247 1247 1247 1150 1040
with Fx or Fy
60 748 748 748 748 748 748 748 748 748
84 534 534 534 534 534 534 534 534 534

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3030 2280 1830 1530 1310 1150 1020 920 830
18 883 880 877 875 872 869 866 780 710
36 831 831 831 831 831 831 831 780 710
with Fx or Fy
60 499 499 499 499 499 499 499 499 499
84 356 356 356 356 356 356 356 356 356

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx and Fy –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx or Fy and the applicable load table above apply.
60
84
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 23
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S120-B U-frames and Goalposts on steel beams

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˕ ˖ ˗

˕1
˖

˗
MIC-S120-B MIC-120-U MI-120
U-frame Fy

Uniformly distributed load Fz with or without simultaneous load Fx or Fy = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 5020 5020 5020 5020 5020 4530 4010 3600 3250
18 2709 2701 2692 2684 2675 2667 2658 2650 2641
36 2040 2040 2040 2040 2040 2040 2040 2040 2040
with Fx or Fy
60 1224 1224 1224 1224 1224 1224 1224 1224 1224
84 874 874 874 874 874 874 874 874 874

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 5020 4570 3650 3040 2600 2260 2010 1800 1630
18 2709 2701 2692 2590 2210 1930 1710 1530 1390
36 2040 2040 2040 2040 2040 1930 1710 1530 1390
with Fx or Fy
60 1224 1224 1224 1224 1224 1224 1224 1224 1224
84 874 874 874 874 874 874 874 874 874

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 4540 3410 2730 2270 1940 1700 1500 1350 1220
18 1355 1350 1346 1342 1338 1333 1280 1150 1040
36 1020 1020 1020 1020 1020 1020 1020 1020 1020
with Fx or Fy
60 612 612 612 612 612 612 612 612 612
84 437 437 437 437 437 437 437 437 437

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3030 2280 1830 1530 1310 1150 1020 920 830
18 903 900 897 895 892 889 870 780 710
36 680 680 680 680 680 680 680 680 680
with Fx or Fy
60 408 408 408 408 408 408 408 408 408
84 291 291 291 291 291 291 291 291 291

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx and Fy –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx or Fy and the applicable load table above apply.
60
84
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

24 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S120-C U-frames and Goalposts on steel beams

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˕ ˖ ˗

˖ ˕1

˗
MIC-S120-C MIC-120-U MI-120
U-frame Fy

Uniformly distributed load Fz with or without simultaneous load Fx or Fy = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3600 3600 3600 3600 3600 3600 3600 3600 3250
18 1589 1581 1572 1564 1555 1547 1538 1530 1521
36 1564 1555 1547 1538 1530 1521 1513 1504 1496
with Fx or Fy
60 1400 1400 1400 1400 1400 1400 1400 1400 1400
84 1000 1000 1000 1000 1000 1000 1000 1000 1000

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3600 3600 3600 3040 2600 2260 2010 1800 1630
18 1589 1581 1572 1564 1555 1547 1538 1530 1390
36 1564 1555 1547 1538 1530 1521 1513 1504 1390
with Fx or Fy
60 1400 1400 1400 1400 1400 1400 1400 1400 1390
84 1000 1000 1000 1000 1000 1000 1000 1000 1000

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3600 3410 2730 2270 1940 1700 1500 1350 1220
18 795 790 786 782 778 773 769 765 761
36 782 778 773 769 765 761 756 752 748
with Fx or Fy
60 700 700 700 700 700 700 700 700 700
84 500 500 500 500 500 500 500 500 500

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3030 2280 1830 1530 1310 1150 1020 920 830
18 530 527 524 521 518 516 513 510 507
36 521 518 516 513 510 507 504 501 499
with Fx or Fy
60 467 467 467 467 467 467 467 467 467
84 333 333 333 333 333 333 333 333 333

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx and Fy –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx or Fy and the applicable load table above apply.
60
84
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 25
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-C90-AA U-frames and Goalposts on concrete1

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˕ ˖ ˗

˖ ˕1

˗
U-frame MIC-C90-AA MIC-90-U MI-90

Uniformly distributed load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx – 3960 3960 3960 3510 3000 2610 2310 2070 1870
18 1620 1620 1620 1620 1620 1620 1620 1620 1620
36 1311 1311 1311 1311 1311 1311 1311 1311 1311
with Fx
60 787 787 787 787 787 787 787 787 787
84 562 562 562 562 562 562 562 562 562

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx – 3520 2640 2110 1750 1500 1300 1150 1030 930
18 1620 1620 1620 1620 1620 1620 1620 1620 1620
36 1311 1311 1311 1311 1311 1311 1311 1311 1311
with Fx
60 787 787 787 787 787 787 787 787 787
84 562 562 562 562 562 562 562 562 562

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx – 2620 1970 1580 1310 1120 980 860 770 700
18 1311 1311 1311 1140 980 850 750 670 610
36 656 656 656 656 656 656 656 656 610
with Fx
60 393 393 393 393 393 393 393 393 393
84 281 281 281 281 281 281 281 281 281

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx – 1750 1320 1060 880 760 660 590 530 480
18 874 874 874 770 660 580 510 460 420
36 437 437 437 437 437 437 437 437 420
with Fx
60 262 262 262 262 262 262 262 262 262
84 187 187 187 187 187 187 187 187 187

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx and the applicable load table above apply.
60
84
1 Capacity of anchorage to concrete must be evaluated separately.

26 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-C90-D U-frames and Goalposts on concrete1

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˖ ˗
˕
˕1
˖

˗
Fy MIC-C90-D MIC-90-U MI-90
U-frame

Uniformly distributed load Fz with or without simultaneous load Fx or Fy = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 5340 5300 4230 3510 3000 2610 2310 2070 1870
18 3618 3618 3618 3050 2610 2270 2010 1800 1620
36 1809 1809 1809 1809 1809 1809 1809 1800 1620
with Fx or Fy
60 1085 1085 1085 1085 1085 1085 1085 1085 1085
84 775 775 775 775 775 775 775 775 775

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3520 2640 2110 1750 1500 1300 1150 1030 930
18 3060 2300 1830 1520 1300 1130 1000 900 810
36 1809 1809 1809 1520 1300 1130 1000 900 810
with Fx or Fy
60 1085 1085 1085 1085 1085 1085 1000 900 810
84 775 775 775 775 775 775 775 775 775

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 2620 1970 1580 1310 1120 980 860 770 700
18 1809 1720 1370 1140 980 850 750 670 610
36 904 904 904 904 904 850 750 670 610
with Fx or Fy
60 543 543 543 543 543 543 543 543 543
84 388 388 388 388 388 388 388 388 388

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 1750 1320 1060 880 760 660 590 530 480
18 1206 1150 920 770 660 580 510 460 420
36 603 603 603 603 603 580 510 460 420
with Fx or Fy
60 362 362 362 362 362 362 362 362 362
84 258 258 258 258 258 258 258 258 258

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx and Fy –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx or Fy and the applicable load table above apply.
60
84
1 Capacity of anchorage to concrete must be evaluated separately.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 27
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-C120-D U-frames and Goalposts on concrete1

Crossbeam simply supported, columns restrained. Loads Fz and Fx in direction shown.


˕ ˖ ˗
˕1
˖

˗
MIC-C120-D MIC-120-U MI-120
U-frame Fy

Uniformly distributed load Fz with or without simultaneous load Fx or Fy = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 6080 6080 6080 6080 5200 4530 4010 3600 3250
18 5022 5022 5022 5022 4430 3870 3420 3070 2770
36 2511 2511 2511 2511 2511 2511 2511 2511 2511
with Fx or Fy
60 1507 1507 1507 1507 1507 1507 1507 1507 1507
84 1076 1076 1076 1076 1076 1076 1076 1076 1076

One load Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 6080 4570 3650 3040 2600 2260 2010 1800 1630
18 5022 3900 3120 2590 2210 1930 1710 1530 1390
36 2511 2511 2511 2511 2210 1930 1710 1530 1390
with Fx or Fy
60 1507 1507 1507 1507 1507 1507 1507 1507 1390
84 1076 1076 1076 1076 1076 1076 1076 1076 1076

Two loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 4540 3410 2730 2270 1940 1700 1500 1350 1220
18 2511 2511 2330 1940 1660 1450 1280 1150 1040
36 1256 1256 1256 1256 1256 1256 1256 1150 1040
with Fx or Fy
60 753 753 753 753 753 753 753 753 753
84 538 538 538 538 538 538 538 538 538

Three loads Fz with or without simultaneous load Fx = 0.15 x Fz


ɏ JO
36 48 60 72 84 96 108 120 132
Configuration Load (lb) h (in.)
without Fx and Fy – 3030 2280 1830 1530 1310 1150 1020 920 830
18 1674 1674 1560 1300 1120 980 870 780 710
36 837 837 837 837 837 837 837 780 710
with Fx or Fy
60 502 502 502 502 502 502 502 502 502
84 359 359 359 359 359 359 359 359 359

(PBMQPTU$POՐHVSBUJPO
Configuration Load (lb) ɏ JO
36 48 60 72 84 96 108 120 132
h (in.)
without Fx and Fy –
18
The above U-frames can be inverted into a goal post configuration
36
with Fx or Fy and the applicable load table above apply.
60
84
1 Capacity of anchorage to concrete must be evaluated separately.

28 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S90-A Lorraine Cross on steel beam


˕
˖ ˗
˕1

˗
˖

Lorraine cross MIC-S90-A MIC-90-L MI-90

Load Fz with or without simultaneous load Fx = 0.15 x Fz. Load values are based on an unbalanced loading condition.

Loading condition 1 Loading condition 2 Loading condition 3 Loading condition 4 Loading condition 5
Height and uniform loading
Configuration Length (inch) Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

ɏI 18 24 36 18 24 36 18 24 36 18 24 36 18 24 36

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 533 533 533 533 352 352 352 267 267 267 178 178 178
with Fx
18 485 485 485 485 485 485 243 243 243 243 243 243 162 162 162

12 407 407 407 407 407 407 204 204 204 204 204 204 136 136 136
without Fx
18 271 271 271 271 271 271 136 136 136 136 136 136 90 90 90

12 352 352 243 352 352 243 176 176 176 176 176 121 117 117 81
with Fx
18 243 243 243 243 243 243 121 121 121 121 121 121 81 81 81

12 370 370 370 370 370 370 370 370 370 185 185 185 123 123 123
without Fx
18 370 370 370 370 370 370 258 258 258 185 185 185 123 123 123

12 364 273 182 364 273 182 364 273 182 182 137 91 121 91 61
with Fx
18 364 273 182 364 273 182 258 258 182 182 137 91 121 91 61

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 364 533 533 364 387 387 364 267 267 182 178 178 121
with Fx
18 516 516 364 516 516 364 258 258 258 258 258 182 172 172 121

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 243 182 121 243 182 121 243 182 121 121 91 61 81 61 40
with Fx
18 243 182 121 243 182 121 243 182 121 121 91 61 81 61 40
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 29
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S90-B Lorraine Cross on steel beam


˕

˕1 ˖ ˗

˗
˖
115/16" (50)

39/16"
˗ (90)
1/2" (14)

1" (25)
39/16" t = 10 ga
(3.5)
(90)

Lorraine cross MIC-S90-B MIC-90-L MI-90

Load Fz with or without simultaneous load Fx = 0.15 x Fz. Load values are based on an unbalanced loading condition.

Loading condition 1 Loading condition 2 Loading condition 3 Loading condition 4 Loading condition 5
Height and uniform loading
Configuration Length (inch) Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

ɏI 18 24 36 18 24 36 18 24 36 18 24 36 18 24 36

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 453 533 533 533 352 352 352 267 267 267 178 178 178
with Fx
18 485 485 453 485 485 485 243 243 243 243 243 243 162 162 162

12 407 407 407 407 407 407 204 204 204 204 204 204 136 136 136
without Fx
18 271 271 271 271 271 271 136 136 136 136 136 136 90 90 90

12 302 227 151 302 227 151 176 176 151 151 113 76 101 76 50
with Fx
18 243 227 151 243 227 151 121 121 121 121 113 76 81 76 50

12 273 273 273 273 273 273 273 273 273 137 137 137 91 91 91
without Fx
18 273 273 273 273 273 273 258 258 258 137 137 137 91 91 91

12 227 170 113 227 170 113 227 170 113 113 85 57 76 57 38
with Fx
18 227 170 113 227 170 113 227 170 113 113 85 57 76 57 38

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 410 340 227 410 340 227 410 340 227 205 170 113 137 113 76
with Fx
18 410 340 227 410 340 227 387 340 227 205 170 113 137 113 76

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 151 113 76 151 113 76 151 113 76 76 57 38 50 38 25


with Fx
18 151 113 76 151 113 76 151 113 76 76 57 38 50 38 25
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

30 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S90-C Lorraine Cross on steel beam


˕
˕1 ˖ ˗

˗
115/16" (50)
˖
39/16"

˗ (90)
1/2" (14)

1" (25)
39/16" t = 10 ga
(3.5)
(90)

Lorraine cross MIC-S90-C MIC-90-L MI-90

Load Fz with or without simultaneous load Fx = 0.15 x Fz. Load values are based on an unbalanced loading condition.

Loading condition 1 Loading condition 2 Loading condition 3 Loading condition 4 Loading condition 5
Height and uniform loading
Configuration Length (inch) Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

ɏI 18 24 36 18 24 36 18 24 36 18 24 36 18 24 36

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 171 171 171

12 533 533 373 533 533 373 372 372 372 267 267 267 178 178 178
with Fx
18 513 513 373 513 513 373 257 257 257 257 257 257 172 172 172

12 335 335 335 335 335 335 215 215 215 168 168 168 112 112 112
without Fx
18 287 287 287 287 287 287 143 143 143 143 143 143 96 96 96

12 249 187 124 249 187 124 186 186 124 124 93 62 83 62 41
with Fx
18 249 187 124 249 187 124 186 186 124 124 93 62 83 62 41

12 223 223 223 223 223 223 223 223 223 112 112 112 74 74 74
without Fx
18 223 223 223 223 223 223 223 223 223 112 112 112 74 74 74

12 187 140 93 187 140 93 187 140 93 93 70 47 62 47 31


with Fx
18 187 140 93 187 140 93 187 140 93 93 70 47 62 47 31

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 335 280 187 335 280 187 335 280 187 168 140 93 112 93 62
with Fx
18 335 280 187 335 280 187 335 280 187 168 140 93 112 93 62

12 391 390 389 391 390 389 387 387 387 196 195 194 130 130 130
without Fx
18 388 387 386 388 387 386 258 258 258 194 194 193 129 129 129

12 124 93 62 124 93 62 124 93 62 62 47 31 41 31 21


with Fx
18 124 93 62 124 93 62 124 93 62 62 47 31 41 31 21
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 31
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S120-A Lorraine Cross on steel beam

˕ ˗
˖
˕1
˘
MI-90 ˘
˖

Lorraine cross MIC-S120-A MIC-90-L MI-120

Load Fz with or without simultaneous load Fx = 0.15 x Fz. Load values are based on an unbalanced loading condition.

Loading condition 1 Loading condition 2 Loading condition 3 Loading condition 4 Loading condition 5
Height and uniform loading
Configuration Length (inch) Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

ɏI 18 24 36 18 24 36 18 24 36 18 24 36 18 24 36

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
with Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 533 533 533 533 283 283 283 267 267 267 178 178 178
without Fx
18 377 377 377 377 377 377 188 188 188 188 188 188 126 126 126

12 486 364 243 486 364 243 245 245 243 243 182 121 162 121 81
with Fx
18 338 338 243 338 338 243 169 169 169 169 169 121 113 113 81

12 443 443 443 443 443 443 387 387 387 222 222 222 148 148 148
without Fx
18 443 443 443 443 443 443 258 258 258 222 222 222 148 148 148

12 364 273 182 364 273 182 364 273 182 182 137 91 121 91 61
with Fx
18 364 273 182 364 273 182 258 258 182 182 137 91 121 91 61

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 364 533 533 364 387 387 364 267 267 182 178 178 121
with Fx
18 516 516 364 516 516 364 258 258 258 258 258 182 172 172 121

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 243 182 121 243 182 121 243 182 121 121 91 61 81 61 40
with Fx
18 243 182 121 243 182 121 243 182 121 121 91 61 81 64 40
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

32 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S120-B Lorraine Cross on steel beam

˕ ˗
˖
˕1
˘
MI-90 ˘
˖

Lorraine cross MIC-S120-B MIC-90-L MI-120

Load Fz with or without simultaneous load Fx = 0.15 x Fz. Load values are based on an unbalanced loading condition.

Loading condition 1 Loading condition 2 Loading condition 3 Loading condition 4 Loading condition 5
Height and uniform loading
Configuration Length (inch) Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

ɏI 18 24 36 18 24 36 18 24 36 18 24 36 18 24 36

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 469 533 533 469 387 387 387 267 267 267 178 178 178
with Fx
18 516 516 469 516 516 469 258 258 258 258 258 258 172 172 172

12 435 435 435 435 435 435 277 277 277 218 218 218 145 145 145
without Fx
18 369 369 369 369 369 369 185 185 185 185 185 185 123 123 123

12 313 234 156 313 234 156 240 234 156 156 117 78 104 78 52
with Fx
18 313 234 156 313 234 156 166 166 156 156 117 78 104 78 52

12 290 290 290 290 290 290 290 290 290 145 145 145 97 97 97
without Fx
18 290 290 290 290 290 290 258 258 258 145 145 145 97 97 97

12 234 176 117 234 176 117 234 176 117 117 88 59 78 59 39
with Fx
18 234 176 117 234 176 117 234 176 117 117 88 59 78 59 39

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 435 352 234 435 352 234 387 352 234 218 176 117 145 117 78
with Fx
18 435 352 234 435 352 234 258 258 234 218 176 117 145 117 78

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 156 117 78 156 117 78 156 117 78 78 59 39 52 39 26


with Fx
18 156 117 78 156 117 78 156 117 78 78 59 39 52 39 26
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 33
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-S120-C Lorraine Cross on steel beam

˕ ˗
˖
˕1
˘ MI-90
˘
˖

Lorraine cross MIC-S120-C MIC-90-L MI-120

Load Fz with or without simultaneous load Fx = 0.15 x Fz. Load values are based on an unbalanced loading condition.

Loading condition 1 Loading condition 2 Loading condition 3 Loading condition 4 Loading condition 5
Height and uniform loading
Configuration Length (inch) Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

ɏI 18 24 36 18 24 36 18 24 36 18 24 36 18 24 36

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 404 533 533 404 387 387 387 267 267 267 178 178 178
with Fx
18 516 516 404 516 516 404 258 258 258 258 258 258 172 172 172

12 365 365 365 365 365 365 233 233 233 183 183 183 122 122 122
without Fx
18 311 311 311 311 311 311 155 155 155 155 155 155 104 104 104

12 270 202 135 270 202 135 202 202 135 135 101 67 90 67 45
with Fx
18 270 202 135 270 202 135 139 139 135 135 101 67 90 67 45

12 243 243 243 243 243 243 243 243 243 122 122 122 81 81 81
without Fx
18 243 243 243 243 243 243 243 243 243 122 122 122 81 81 81

12 202 152 101 202 152 101 202 152 101 101 76 51 67 51 34
with Fx
18 202 152 101 202 152 101 202 152 101 101 76 51 67 51 34

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 365 303 202 365 303 202 365 303 202 183 152 101 122 101 67
with Fx
18 365 303 202 365 303 202 258 258 202 183 152 101 122 101 67
12 441 440 439 441 440 439 387 387 387 221 220 219 147 147 146
without Fx
18 438 437 436 438 437 436 258 258 258 219 219 218 146 146 145
12 135 101 67 135 101 67 135 101 67 67 51 34 45 34 22
with Fx
18 135 101 67 135 101 67 135 101 67 67 51 34 45 34 22
1 Fastened to steel beam with four MI-SGC-M12 beam clamps (item 00233859)

34 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-C90-D Lorraine Cross on concrete

˕ ˖ ˗
˕1

˗
˖

Lorraine cross MIC-C90-D MIC-90-L MI-90

Load Fz with or without simultaneous load Fx = 0.15 x Fz. Load values are based on an unbalanced loading condition.

Loading condition 1 Loading condition 2 Loading condition 3 Loading condition 4 Loading condition 5
Height and uniform loading
Configuration Length (inch) Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

ɏI 18 24 36 18 24 36 18 24 36 18 24 36 18 24 36

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 533 533 533 533 352 352 352 267 267 267 178 178 178
with Fx
18 485 485 485 485 485 485 243 243 243 243 243 243 162 162 162

12 407 407 407 407 407 407 204 204 204 204 204 204 136 136 136
without Fx
18 271 271 271 271 271 271 136 136 136 136 136 136 90 90 90

12 352 352 301 352 352 301 176 176 176 176 176 151 117 117 100
with Fx
18 243 243 243 243 243 243 121 121 121 121 121 121 81 81 81

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 452 339 226 452 339 226 387 339 226 226 170 113 151 113 75
with Fx
18 452 339 226 452 339 226 258 258 226 226 170 113 151 113 75

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 452 533 533 452 387 387 387 267 267 226 178 178 151
with Fx
18 516 516 452 516 516 452 258 258 258 258 258 226 172 172 151

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 301 226 151 301 226 151 301 226 151 151 113 75 100 75 50
with Fx
18 301 226 151 301 226 151 301 226 151 151 113 75 100 75 50
1 Capactiy of anchorage to concrete must be evaluated separately.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 35
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for MIC-C120-D Lorraine Cross on concrete

˕ ˗
˖
˕1
˘
MI-90
˘
˖

Lorraine cross MIC-S120-D MIC-90-L MI-120

Load Fz with or without simultaneous load Fx = 0.15 x Fz. Load values are based on an unbalanced loading condition.

Loading condition 1 Loading condition 2 Loading condition 3 Loading condition 4 Loading condition 5
Height and uniform loading
Configuration Length (inch) Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

ɏI 18 24 36 18 24 36 18 24 36 18 24 36 18 24 36

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
with Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 533 533 533 533 283 283 283 267 267 267 178 178 178
without Fx
18 377 377 377 377 377 377 188 188 188 188 188 188 126 126 126

12 489 452 301 489 452 301 245 245 245 245 226 151 163 151 100
with Fx
18 338 338 301 338 338 301 169 169 169 169 169 151 113 113 100

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 452 339 226 452 339 226 387 339 226 226 170 113 151 113 75
with Fx
18 452 339 226 452 339 226 258 258 226 226 170 113 151 113 75

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 533 533 452 533 533 452 387 387 387 267 267 226 178 178 151
with Fx
18 516 516 452 516 516 452 258 258 258 258 258 226 172 172 151

12 533 533 533 533 533 533 387 387 387 267 267 267 178 178 178
without Fx
18 516 516 516 516 516 516 258 258 258 258 258 258 172 172 172

12 301 226 151 301 226 151 301 226 151 151 113 75 100 75 50
with Fx
18 301 226 151 301 226 151 301 226 151 151 113 75 100 75 50
1 Capactiy of anchorage to concrete must be evaluated separately.

36 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables

Allowable load tables for Unsupported Cantilever MI-90 / 120

Load Fz with or without simultaneous load Fx = 0.15 x Fz

MI-90/MI-120

Loading Loading Loading Loading Loading


MIC-90-L condition 1 condition 2 condition 3 condition 4 condition 5
uniform single load
Cantilever length1 loading
Cantilever
connector type ɏ JO
Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)

12 808 808 401 401 265

MIC-90-L without Fx 18 533 533 262 262 171

MI-90 36 252 252 117 117 71

12 527 527 380 260 171

MIC-90-L with Fx 18 506 506 248 248 162

36 239 239 110 110 67

18 533 533 262 262 171


MIC-S90-A/B/C without Fx
36 252 252 117 117 71

18 533 533 262 262 171


MIC-S90-A/B/C with Fx
36 252 252 117 117 71

18 744 744 367 367 242


MIC-S120-A/B/C without Fx
MI-90/ 36 358 358 169 169 107
MI-120
MIC-S90/120-A 18 744 744 367 367 242
MIC-S90/120-B
MIC-S90/120-C
MIC-S120-A/B/C with Fx
36 358 358 169 169 107

18 533 533 262 262 171


MIC-C90-D without Fx
36 252 252 117 117 71

18 533 533 262 262 171


MIC-C90-D with Fx
36 252 252 117 117 71

18 744 744 367 367 242


MI-90/
MIC-C120-D without Fx
MI-120 36 358 358 169 169 107

MIC-C90-D 18 744 744 367 367 242


MIC-C120-D MIC-C120-D with Fx
36 358 358 169 169 107

%FGPSNBUJPOPGɏJTBEIFSFEUPJOBMMDBTFT NFBTVSFEBUUIFPVUFSNPTUBDUJOHMPBE
Connectors
Loads account for horizontal cantilever component only; capacity of base structure must be evaluated separately.
For anchoring to concrete, capacity of anchorage to concrete must be evaluated separately.
For connection to steel beams use four MI-SGC-M12 beam clamps (item 00233859).

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 37
Hilti MI/MQ Technical Guide

3.3 MI Support System — Allowable Load Tables


Allowable load tables for Supported Cantilever MI-90 / 120

Load Fz with or without simultaneous load Fx = 0.15 x Fz

MI-90/MI-120 MIC-90-L

Loading Loading Loading Loading Loading


Cantilever length1 condition 1 condition 2 condition 3 condition 4 condition 5
Cantilever connector type ɏ JO
Fz (lb) Fz (lb) Fz (lb) Fz (lb) Fz (lb)
MI-90
MIC-U-MA without Fx 18 2443 2443 1221 1221 814
MIC-90-L
with Fx 36 2777 2777 1388 1388 926

MI-90
without Fx 18 590 590 315 290 190
MIC-90-L
with Fx 36 305 305 143 143 89

without Fx 18 2067 2067 1033 1033 689


MIC-S90/120-A, MIC-SA-MA
with Fx 36 2348 2348 1174 1174 783

without Fx 18 2067 2067 1033 1033 689


MIC-S90/120-A MIC-S90/120-A, MIC-SA-MA
MIC-S90/120-B 1790 1790 1174 1174 783
with Fx 36
MIC-S90/120-C

without Fx 18 2067 2067 1033 1033 689


MIC-S90/120-B, MIC-SA-MA
with Fx 36 2348 2348 1174 1174 783

MI-90 without Fx 18 2067 2067 1033 1033 689


MI-120 MIC-S90/120-B, MIC-SA-MA
with Fx 36 1790 1790 1174 1174 783
MIC-U-MA
MIC-SA /SB/SC-MA without Fx 18 2067 2067 1033 1033 689
MI-90 MIC-S90/120-C, MIC-SA-MA
with Fx 36 2348 2348 1174 1174 783

without Fx 18 2067 2067 1033 1033 689


MIC-S90/120-C, MIC-SA-MA
with Fx 36 1634 1634 1174 1174 783

MIC-C90/120-D
without Fx 18 2443 2443 1222 1222 814
MIC-C90/120-D, MIC-SA-MA
with Fx 36 2777 2777 1389 1389 926
MI-90
MI-120
without Fx 18 2443 2443 1222 1222 814

MIC-C90/120-D, MIC-SA-MA
MI-90
MIC-CU-MA MIC-U-MA with Fx 36 1790 1790 1389 1389 926

%FGPSNBUJPOPGɏJTBEIFSFEUPJOBMMDBTFT NFBTVSFEBUUIFPVUFSNPTUBDUJOHMPBE
Connectors
Loads account for horizontal cantilever and support component only; capacity of base structure must be evaluated separately.
For anchoring to concrete, capacity of anchorage to concrete must be evaluated separately.
For connection to steel beams use four MI-SGC-M12 beam clamps (item 00233859).

44 in.
in.

38 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MI Girder 90/120 ˕
.BUFSJBM4QFDJՐDBUJPOT 15
1 /16" (50)

Material S235 JRG2 DIN 10025, (ASTM A283 (D))


39/16"
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN
 (90)
1/2" (14)
DIN EN ISO 1461, (ASTM A123)
1" (25)
Ordering Information 39/16" t = 10 ga
(3.5)
(90)
Metal
˖
1 15/16" (50)
Section Height Thickness Weight lb/ft
Description in (mm) Length ft (m) Gauge (mm) (kg/m) Item No.
MI-90 3m ˕  
 
10 (3.5) 6.3 (9.4) 00304798
MI-90 6m ˕  
 
10 (3.5) 6.3 (9.4) 00304799
MI-120 3m ˖  
 
8 (4) 8.4 (12.6) 00304800 4 3 /4 " 1/2" (14)
(120)
MI-120 6m ˖  
 
8 (4) 8.4 (12.6) 00304801
1" (25)

Technical Data 9
3 /16" s = 8 ga
(4)
Values for cross sections include reduction of four square holes (90)

y y

x x x x

y
Technical Data MI-90 MI-120
Material thickness t (in) 0.1378 (~10 ga) 0.1575 (~8 ga)
Cross sectional area — net A (in2) 1.55 2.13
Weight of girder (lb/ft) 6.34 8.47
Lengths available (ft)  
Material
Yield strength fy, k (ksi) 34 34
Allowable tensile stress ƚ LTJ
20.40 20.40
Allowable shear stress ƛ LTJ
11.80 11.80
Modulus of elasticity E (ksi) 30388 30388
Shear modulus G (ksi) 11721 11721
Cross section values1
X-axis
Moment of inertia űx (in4) 2.77 6.38
Section modulus Sx (in3) 1.56 2.70
Radius of gyration rx (in) 1.33 1.73
Allowable moment Mx ƀ MCGU
2650 4585
y-axis
Moment of inertia űy (in4) 2.77 4.17
Section modulus Sy (in3) 1.56 2.35
Radius of gyration ry (in) 1.33 1.40
Allowable moment My ƀ MCGU
2650 3995
Torsion values
Torsional moment of inertia űt (in4) 3.73 7.13
Torsional section modulus S(in3) 2.76 4.37
1 Cross section values are based on the gross section less the four square holes 14 mm x metal thickness 3.5 mm (MI 90) or 4 mm (MI 120) respectively.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 39
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Recommended buckling loads for MI Girders


Technical Data
Values for cross sections
Buckling Loads

Effective Length (K x L) KxL MI-90 MI-120


(in) (ft) (lb) (lb)
12 1 29,430 40,380
24 2 29,430 40,380
36 3 28,850 39,710
48 4 28,170 38,830
60 5 27,390 37,840
72 6 26,470 36,680
84 7 25,350 35,300
96 8 23,980 33,620
108 9 22,330 31,600
120 10 20,470 29,260
132 11 18,500 26,720
144 12 16,580 24,150
156 13 14,800 21,700
168 14 13,200 19,460
180 15 11,800 17,460
192 16 10,580 15,700
204 17 9,530 14,160
216 18 8,610 12,810
228 19 7,810 11,640
240 20 7,110 10,610
252 21 6,500 9,710
264 22 5,970 8,910
276 23 5,490 8,210
288 24 5,070 7,580
300 25 4,690 7,020
312 26 4,360 6,520
324 27 4,060 6,070

F F F F F

Approximate values of effective


length factor, K

Support Condition Rotation fixed and Rotation free and Rotation free and Rotation fixed and Rotation fixed and
translation fixed on translation fixed at the translation fixed at translation free at the translation free at the
both ends. top and rotation fixed both ends. top and rotation fixed top and rotation free
and translation fixed and translation fixed and translation fixed
at the base. at the base. at the base.
Theoretical K value 0.5 0.7 1.0 1.0 2.0
Recommended design value when
0.65 0.8 1.0 1.2 2.0
ideal conditions are approximated

40 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Single-span with bending load in one axis MI-90


F1BUɪɏ'2BUɪɏ'3BUɪɏ'BUƚall including weight of girder
ɪEFՑFDUJPO
ƚall = allowable stress

MI-90, uniformly distributed load .* POFQPJOUMPBEBUɏ


F F

'8Ƚɏ

Length of w F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO
 Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO

span (ft) (lb/in) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ

2 443 10630 0.02 - - - - - - 2 5260 0.02 - - - - - -


3 197 7080 0.05 - - - - - - 3 3520 0.04 - - - - - -
4 110 5300 0.09 - - - - - - 4 2640 0.07 - - - - - -
5 71 4230 0.14 - - - - - - 5 2110 0.11 - - - - - -
6 49 3510 0.20 - - - - 3440 0.20 6 1750 0.16 - - - - - -
7 36 3000 0.28 - - - - 2510 0.23 7 1500 0.22 - - - - - -
8 27 2610 0.36 - - - - 1900 0.27 8 1300 0.29 - - - - 1190 0.27
9 21 2310 0.46 - - 2260 0.45 1490 0.30 9 1150 0.37 - - - - 930 0.30
10 17 2070 0.57 - - 1810 0.50 1190 0.33 10 1030 0.46 - - - - 740 0.33
11 14 1870 0.69 - - 1480 0.55 970 0.37 11 930 0.55 - - 930 0.55 600 0.37
12 12 1700 0.82 1660 0.80 1230 0.60 790 0.40 12 850 0.66 - - 770 0.60 500 0.40
13 10 1560 0.96 1400 0.87 1030 0.65 660 0.43 13 780 0.78 - - 640 0.65 410 0.43
14 9 1430 1.11 1190 0.93 870 0.70 550 0.47 14 720 0.90 - - 540 0.70 350 0.47
15 7 1330 1.28 1020 1.00 740 0.75 460 0.50 15 660 1.04 640 1.00 460 0.75 290 0.50
16 6 1230 1.45 880 1.07 630 0.80 390 0.53 16 620 1.18 550 1.07 400 0.80 240 0.53
17 6 1150 1.64 760 1.13 540 0.85 330 0.57 17 570 1.34 480 1.13 340 0.85 210 0.57
18 5 1070 1.84 660 1.20 470 0.90 280 0.60 18 540 1.51 410 1.20 290 0.90 170 0.60
19 4 1000 2.05 580 1.27 400 0.95 230 0.63 19 500 1.68 360 1.27 250 0.95 140 0.63
20 4 940 2.27 500 1.33 350 1.00 190 0.67 20 470 1.87 310 1.33 220 1.00 120 0.67

.* UXPQPJOUMPBETBUɏ .* UISFFQPJOUMPBETBUɏ


F F

Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO
 Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO

span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ

2 3890 0.02 - - - - - - 2 2590 0.02 - - - - - -


3 2620 0.05 - - - - - - 3 1750 0.05 - - - - - -
4 1970 0.09 - - - - - - 4 1320 0.09 - - - - - -
5 1580 0.14 - - - - - - 5 1060 0.13 - - - - - -
6 1310 0.21 - - - - - - 6 880 0.19 - - - - - -
7 1120 0.28 - - - - 920 0.23 7 760 0.26 - - - - 670 0.23
8 980 0.37 - - - - 700 0.27 8 660 0.34 - - - - 510 0.27
9 860 0.47 - - - - 550 0.30 9 590 0.44 - - - - 400 0.30
10 770 0.58 - - - - 440 0.33 10 530 0.54 - - 490 0.5 330 0.33
11 700 0.70 - - 540 0.55 350 0.37 11 480 0.65 - - 410 0.55 270 0.37
12 640 0.83 610 0.8 450 0.60 290 0.40 12 440 0.77 440 0.8 340 0.6 230 0.40
13 580 0.98 510 0.87 380 0.65 240 0.43 13 410 0.91 370 0.87 290 0.65 190 0.43
14 540 1.14 440 0.93 320 0.70 200 0.47 14 380 1.05 310 0.93 250 0.70 170 0.47
15 500 1.30 370 1.00 270 0.75 170 0.50 15 350 1.21 270 1.00 220 0.75 140 0.50
16 460 1.48 320 1.07 230 0.80 140 0.53 16 330 1.37 230 1.07 190 0.80 130 0.53
17 430 1.67 280 1.13 200 0.85 120 0.57 17 310 1.55 200 1.13 170 0.85 110 0.57
18 400 1.88 240 1.20 170 0.90 100 0.60 18 290 1.73 170 1.20 150 0.90 100 0.60
19 380 2.09 210 1.27 150 0.95 80 0.63 19 280 1.93 150 1.27 130 0.95 90 0.63
20 350 2.32 180 1.33 130 1.00 70 0.67 20 260 2.13 130 1.33 120 1.00 80 0.67

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 41
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Single-span with bending load in one axis MI-120


F1BUɪɏ'2BUɪɏ'3BUɪɏ'BUƚall including weight of girder
ɪEFՑFDUJPO
ƚall = allowable stress
MI-120, uniformly distributed load MI-120 POFQPJOUMPBEBUɏ
F F

'8Ƚɏ

Length of w F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO
 Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO

span (ft) (lb/in) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ

2 765 18370 0.02 - - - - - - 2 9080 0.01 - - - - - -


3 340 12230 0.04 - - - - - - 3 6090 0.03 - - - - - -
4 191 9160 0.07 - - - - - - 4 4570 0.05 - - - - - -
5 122 7310 0.11 - - - - - - 5 3650 0.09 - - - - - -
6 84 6080 0.15 - - - - - - 6 3040 0.12 - - - - - -
7 62 5200 0.21 - - - - - - 7 2600 0.17 - - - - - -
8 47 4530 0.27 - - - - 4440 0.27 8 2260 0.22 - - - - - -
9 37 4010 0.34 - - - - 3480 0.30 9 2010 0.28 - - - - - -
10 30 3600 0.43 - - - - 2800 0.33 10 1800 0.34 - - - - 1750 0.33
11 25 3250 0.52 - - - - 2290 0.37 11 1630 0.41 - - - - 1430 0.37
12 21 2970 0.61 - - 2900 0.60 1900 0.40 12 1480 0.49 - - - - 1190 0.40
13 17 2720 0.72 - - 2450 0.65 1600 0.43 13 1360 0.58 - - - - 1000 0.43
14 15 2510 0.83 - - 2090 0.70 1350 0.47 14 1260 0.67 - - - - 850 0.47
15 13 2330 0.96 - - 1800 0.75 1160 0.50 15 1160 0.78 - - 1120 0.75 720 0.50
16 11 2170 1.09 2120 1.07 1560 0.80 990 0.53 16 1080 0.88 - - 970 0.80 620 0.53
17 10 2020 1.23 1850 1.13 1360 0.85 860 0.57 17 1010 1.00 - - 850 0.85 540 0.57
18 9 1890 1.38 1630 1.20 1190 0.90 740 0.60 18 950 1.12 - - 740 0.90 460 0.60
19 7 1780 1.54 1440 1.27 1040 0.95 640 0.63 19 890 1.25 - - 650 0.95 400 0.63
20 6 1670 1.70 1280 1.33 920 1.00 560 0.67 20 840 1.39 800 1.33 570 1.00 350 0.67

MI-120 UXPQPJOUMPBETBUɏ MI-120 UISFFQPJOUMPBETBUɏ


F F

Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO
 Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO

span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ

2 6720 0.02 - - - - - - 2 4480 0.02 - - - - - -


3 4540 0.04 - - - - - - 3 3030 0.04 - - - - - -
4 3410 0.07 - - - - - - 4 2280 0.06 - - - - - -
5 2730 0.11 - - - - - - 5 1830 0.10 - - - - - -
6 2270 0.16 - - - - - - 6 1530 0.15 - - - - - -
7 1940 0.21 - - - - - - 7 1310 0.20 - - - - - -
8 1700 0.28 - - - - - - 8 1150 0.26 - - - - - -
9 1500 0.35 - - - - - - 9 1020 0.33 - - - - 930 0.30
10 1350 0.43 - - - - 1030 0.33 10 920 0.40 - - - - 760 0.33
11 1220 0.53 - - - - 840 0.37 11 830 0.49 - - - - 620 0.37
12 1110 0.63 - - 1060 0.60 700 0.40 12 760 0.58 - - - - 520 0.40
13 1020 0.73 - - 900 0.65 590 0.43 13 700 0.68 - - 670 0.65 450 0.43
14 940 0.85 - - 770 0.70 500 0.47 14 650 0.79 - - 580 0.70 380 0.47
15 870 0.98 - - 660 0.75 420 0.50 15 610 0.91 - - 500 0.75 330 0.50
16 810 1.11 780 1.07 570 0.80 360 0.53 16 570 1.03 560 1.07 440 0.80 290 0.53
17 760 1.26 680 1.13 500 0.85 310 0.57 17 540 1.16 490 1.13 390 0.85 260 0.57
18 710 1.41 600 1.20 430 0.90 270 0.60 18 510 1.30 430 1.20 350 0.90 230 0.60
19 670 1.57 530 1.27 380 0.95 240 0.63 19 480 1.45 380 1.27 310 0.95 210 0.63
20 630 1.74 470 1.33 340 1.00 200 0.67 20 460 1.60 340 1.33 280 1.00 190 0.67

42 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Single-span with bending load in one axis


'8Ƚɏ
Selection of girder for single span with maximum load at ɪ < ɏ/180
uniformly distributed load including weight of girder ℓ
Load F (lb)

MI-120

MI-90

20" 70" 120" (10 ft) 170" 220" (20 ft)


Length of span

Selection of girder for single span with maximum load at ɪ < ɏ/180
point load at ɏ/2 including weight of girder
Load F (lb)

MI-120

MI-90

20" 70" 120" (10 ft) 170" 220" (20 ft)


Length of span

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 43
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Single-span with bending load in one axis

Selection of girder for single span with maximum load at ɪ < ɏ/180
2 point loads at ɏ/3 including weight of girder
Load F (lb)

MI-120

MI-90
20" 70" 120" (10 ft) 170" 220" (20 ft)

Length of span

Selection of girder for single span with maximum load at ɪ < ɏ/180
3 point loads at ɏ/4 including weight of girder
Load F (lb)

MI-120

MI-90

20" 70" 120" (10 ft) 170" 220" (20 ft)

Length of span

44 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Single-span with bending load in two axes (Fx = F*0.15) MI-90


F1BUɪɏ'2BUɪɏ'3BUɪɏ'BUƚall including weight of girder
ɪEFՑFDUJPO
ƚall = allowable stress

MI-90, uniformly distributed load MI-90, one point load at ɏ/2


F F

Fx Fx
'8Ƚɏ

Length of w F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO
 Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO

span (ft) (lb/in) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ

2 385 9240 0.02 - - - - - - 2 4580 0.02 - - - - - -


3 171 6150 0.04 - - - - - - 3 3060 0.04 - - - - - -
4 96 4600 0.08 - - - - - - 4 2300 0.06 - - - - - -
5 61 3670 0.12 - - - - - - 5 1830 0.10 - - - - - -
6 42 3050 0.18 - - - - - - 6 1520 0.14 - - - - - -
7 31 2610 0.24 - - - - 2510 0.23 7 1300 0.19 - - - - - -
8 24 2270 0.32 - - - - 1900 0.27 8 1130 0.25 - - - - - -
9 19 2010 0.40 - - - - 1490 0.30 9 1000 0.32 - - - - 930 0.30
10 15 1800 0.50 - - - - 1190 0.33 10 900 0.40 - - - - 740 0.33
11 12 1620 0.60 - - 1480 0.55 970 0.37 11 810 0.49 - - - - 600 0.37
12 10 1480 0.72 - - 1230 0.60 790 0.40 12 740 0.58 - - - - 500 0.40
13 9 1350 0.84 - - 1030 0.65 660 0.43 13 680 0.68 - - 640 0.65 410 0.43
14 7 1250 0.98 1190 0.93 870 0.70 550 0.47 14 620 0.79 - - 540 0.70 350 0.47
15 6 1150 1.12 1020 1.00 740 0.75 460 0.50 15 580 0.91 - - 460 0.75 290 0.50
16 6 1070 1.28 880 1.07 630 0.80 390 0.53 16 540 1.04 - - 400 0.80 240 0.53
17 5 1000 1.44 760 1.13 540 0.85 330 0.57 17 500 1.18 480 1.13 340 0.85 210 0.57
18 4 930 1.62 660 1.20 470 0.90 280 0.60 18 470 1.33 410 1.20 290 0.90 170 0.60
19 4 870 1.81 580 1.27 400 0.95 230 0.63 19 440 1.49 360 1.27 250 0.95 140 0.63
20 3 820 2.01 500 1.33 350 1.00 190 0.67 20 410 1.66 310 1.33 220 1.00 120 0.67

MI-90, two point loads at ɏ/3 MI-90, three point loads at ɏ/4
F F

Fx Fx

Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO
 Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO

span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ

2 3400 0.02 - - - - - - 2 2270 0.02 - - - - - -


3 2290 0.05 - - - - - - 3 1530 0.04 - - - - - -
4 1720 0.08 - - - - - - 4 1150 0.07 - - - - - -
5 1370 0.13 - - - - - - 5 920 0.12 - - - - - -
6 1140 0.18 - - - - - - 6 770 0.17 - - - - - -
7 980 0.25 - - - - 920 0.23 7 660 0.23 - - - - - -
8 850 0.32 - - - - 700 0.27 8 580 0.30 - - - - 510 0.27
9 750 0.41 - - - - 550 0.30 9 510 0.38 - - - - 400 0.30
10 670 0.51 - - - - 440 0.33 10 460 0.47 - - - - 330 0.33
11 610 0.61 - - 540 0.55 350 0.37 11 420 0.57 - - 410 0.55 270 0.37
12 550 0.73 - - 450 0.60 290 0.40 12 380 0.67 - - 340 0.60 230 0.40
13 510 0.86 - - 380 0.65 240 0.43 13 350 0.79 - - 290 0.65 190 0.43
14 470 1.00 440 0.93 320 0.70 200 0.47 14 330 0.91 310 0.93 250 0.70 170 0.47
15 430 1.14 370 1.00 270 0.75 170 0.50 15 310 1.05 270 1.00 220 0.75 140 0.50
16 400 1.30 320 1.07 230 0.80 140 0.53 16 290 1.19 230 1.07 190 0.80 130 0.53
17 370 1.47 280 1.13 200 0.85 120 0.57 17 270 1.34 200 1.13 170 0.85 110 0.57
18 350 1.65 240 1.20 170 0.90 100 0.60 18 250 1.51 170 1.20 150 0.90 100 0.60
19 330 1.85 210 1.27 150 0.95 80 0.63 19 240 1.68 150 1.27 130 0.95 90 0.63
20 310 2.05 180 1.33 130 1.00 70 0.67 20 230 1.85 130 1.33 120 1.00 80 0.67

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 45
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Single-span with bending load in two axis (Fx=F*0.15) MI-120


F1BUɪɏ'2BUɪɏ'3BUɪɏ'BUƚall including weight of girder
ɪEFՑFDUJPO
ƚall = allowable stress
MI-120, uniformly distributed load MI-120, one point load at ɏ/2
F F

F F
'8Ƚɏ

Length of w (lb/ F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO
 Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO

span (ft) in) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ

2 653 15670 0.01 - - - - - - 2 7770 0.01 - - - - - -


3 290 10440 0.03 - - - - - - 3 5200 0.03 - - - - - -
4 163 7820 0.06 - - - - - - 4 3900 0.05 - - - - - -
5 104 6240 0.09 - - - - - - 5 3120 0.07 - - - - - -
6 72 5190 0.13 - - - - - - 6 2590 0.10 - - - - - -
7 53 4430 0.18 - - - - - - 7 2210 0.14 - - - - - -
8 40 3870 0.23 - - - - - - 8 1930 0.19 - - - - - -
9 32 3420 0.30 - - - - - - 9 1710 0.24 - - - - - -
10 26 3070 0.36 - - - - 2800 0.33 10 1530 0.29 - - - - - -
11 21 2770 0.44 - - - - 2290 0.37 11 1390 0.36 - - - - - -
12 18 2530 0.53 - - - - 1900 0.40 12 1260 0.42 - - - - 1190 0.40
13 15 2320 0.62 - - - - 1600 0.43 13 1160 0.50 - - - - 1000 0.43
14 13 2140 0.72 - - 2090 0.70 1350 0.47 14 1070 0.58 - - - - 850 0.47
15 11 1990 0.82 - - 1800 0.75 1160 0.50 15 990 0.67 - - - - 720 0.50
16 10 1850 0.94 - - 1560 0.80 990 0.53 16 920 0.76 - - - - 620 0.53
17 8 1730 1.06 - - 1360 0.85 860 0.57 17 860 0.87 - - 850 0.85 540 0.57
18 8 1620 1.19 - - 1190 0.90 740 0.60 18 810 0.97 - - 740 0.90 460 0.60
19 7 1520 1.33 1440 1.27 1040 0.95 640 0.63 19 760 1.09 - - 650 0.95 400 0.63
20 6 1430 1.48 1280 1.33 920 1.00 560 0.67 20 710 1.21 - - 570 1.00 350 0.67

MI-120, two point loads at ɏ/3 MI-120, three point loads at ɏ/4
F F

F F

Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO
 Length of F ɪ JO
 F1 ɪ JO
 F2 ɪ JO
 F3 ɪ JO

span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ span (ft) (lb) BUƚall (lb) ɺɏ (lb) ɺɏ (lb) ɺɏ

2 5770 0.01 - - - - - - 2 3850 0.01 - - - - - -


3 3880 0.03 - - - - - - 3 2590 0.03 - - - - - -
4 2920 0.06 - - - - - - 4 1950 0.05 - - - - - -
5 2330 0.09 - - - - - - 5 1560 0.09 - - - - - -
6 1940 0.13 - - - - - - 6 1300 0.12 - - - - - -
7 1660 0.18 - - - - - - 7 1120 0.17 - - - - - -
8 1450 0.24 - - - - - - 8 980 0.22 - - - - - -
9 1280 0.30 - - - - - - 9 870 0.28 - - - - - -
10 1150 0.37 - - - - 1030 0.33 10 780 0.34 - - - - 760 0.33
11 1040 0.45 - - - - 840 0.37 11 710 0.42 - - - - 620 0.37
12 950 0.54 - - - - 700 0.40 12 650 0.50 - - - - 520 0.40
13 870 0.63 - - - - 590 0.43 13 600 0.58 - - - - 450 0.43
14 800 0.73 - - 770 0.70 500 0.47 14 560 0.67 - - - - 380 0.47
15 740 0.84 - - 660 0.75 420 0.50 15 520 0.77 - - 500 0.75 330 0.50
16 690 0.96 - - 570 0.80 360 0.53 16 490 0.88 - - 440 0.80 290 0.53
17 650 1.08 - - 500 0.85 310 0.57 17 460 0.99 - - 390 0.85 260 0.57
18 610 1.22 600 1.20 430 0.90 270 0.60 18 430 1.11 430 1.20 350 0.90 230 0.60
19 570 1.36 530 1.27 380 0.95 240 0.63 19 410 1.24 380 1.27 310 0.95 210 0.63
20 540 1.50 470 1.33 340 1.00 200 0.67 20 390 1.37 340 1.33 280 1.00 190 0.67

46 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Single-span with bending load in two axes (Fx = F*0.15)


'8Ƚɏ
Selection of girder for single span with maximum load at ɪ < ɏ/180
uniformly distributed load including weight of girder ℓ
Load F (lb)

MI-120

MI-90

20" 70" 120" (10 ft) 170" 220" (20 ft)


Length of span

Selection of girder for single span with maximum load at ɪ < ɏ/180
point load at ɏ/2 including weight of girder
Load F (lb)

MI-120

MI-90
20" 70" 120" (10 ft) 170" 220" (20 ft)
Length of span

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 47
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

Single-span with bending load in two axes (Fx = F*0.15)

Selection of girder for single span with maximum load at ɪ < ɏ/180
2 point loads at ɏ/3 including weight of girder
Load F (lb)

MI-120

MI-90

20" 70" 120" (10 ft) 170" 220" (20 ft)


Length of span

Selection of girder for single span with maximum load at ɪ < ɏ/180
3 point loads at ɏ/4 including weight of girder
Load F (lb)

MI-120

MI-90

20" 70" 120" (10 ft) 170" 220" (20 ft)


Length of span

48 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MIC-90 / 120-U Crossbeam Connector1


.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025)


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.
MIC-90-U MI-90 5.2 (2.3) 4 00304803
MIC-120-U MI-120 6.1 (2.7) 4 00304804

Technical Data
MIC-90-U
or MIC-120-U
on MI-90/1202 girder
˕ MI-90
˖ MI-120

˕ MI-90 Allowable loads


5/ " (8)
16 -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)
Fy+Fx+Fz 2150 380 2670

˖ MI-1202 Allowable loads


-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)
Fy+Fx+Fz 2290 380 3040

1 Connector must not be used to resist moments.


2 When mounting to 120 mm width of MI-120 girder, order separately bolt MIA-EH-120, item 00304888.

Items in set

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 49
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MIC-90-L Cantilever Connector1


.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025)


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.
MIC-90-L MI-90 8.7 (3.9) 2 00304805

Technical Data
MIC-90-L
on MI-90 or
MI-120 girder2

-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)


Fx - 1830 - - - -
Fy + Fz 2930 - 4130 - - -
Fy + Mz 130 - - - - 109
Fz + My - - 1130 407 - -
Fx + My - 780 - 407 - -
Fx + Fy + Mz 90 310 - - - 73
Fy + Mx 560 - - - 364 -
Fz + Mx - - 560 - 364 -
LF1 2930 690 4130 407 73 -
LF2a - 1400 440 - 364 -
LF2b 440 1400 - - 364 -
LF3 oST 80 - 560 401 22 58
1 Connector designed to resist moments.
2 When mounting to 120 mm width, of MI-120 girder, order separately bolt MIA-EH-120, item 00304888.

Items in set .PNFOUTBOEMPBEJOHDPOՐHVSBUJPOT  -'


GPS.*$-PO.*
LF1 and LF2 represent tee or lorraine cross supports. LF3 represents a cantilever.
FV = vertical load and FH = horizontal load
LF1 LF2 LF3

LF2a = Moment Mx LF3oST = cantilever


induced by Fz without
LF2b = Moment Mx support
induced by Fy

50 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MIC-T pedestal connector


.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025)


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.
MIC-T MI-90/MI-120 4.4 (2.0) 2 1 00304807

Technical Data
MIC-T
on MI-90 or MI-120

Allowable loads2
Maximum gap -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)
between MI
girders: Fx - 2180 -
.* 

.* 
Fy 310 - -
Fz - - 4440
 

Fx+Fz - 1330 2220


Fx+Fy+Fz 220 780 2220
1 Two sets per sales package.
2 MIC-T connector must be used in pairs (on opposite sides of the girder).

Items in set

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 51
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MIC-90 / 120-E girder extension


.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.
MIC-90-E ˕ MI-90 7.8 (3.5) 2 00304809
MIC-120-E ˖ MI-120 9.5 (4.3) 2 00304810

Items in set ˕ Items in set ˖

MIC Girder Extension

Allowable loads
Technical Data -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
MIC-90-E Fx 7550
- - - - -
MI-90 extension
Fy + Fz 970 1
- 970 1
- - -
˕2
Mz - - - - - 729
My - - - 729 - -
Mx - - - - 1326 -
Fy + Fz + My + Mz 970 1
- 970* 729 - 729

Allowable loads
-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
MIC-120-E Fx - 8570 - - - -
MI-120 extension Fy + Fz 970 1
- 1480 1
- - -
˖2
Mz - - - - - 729
My - - - 1215 - -
Mx - - - - 1807 -
Fy + Fz + My + Mz 9701 - 14801 1215 - 729
1 The loads apply at mid span to a maximum span length of 36 inches. For information on greater span lengths, please contact
Hilti technical services department.
2 The end of each girder extension must be fastened with 4 bolts inserted perpendicular each direction as shown below.
3 Ends of girder must be cut through the center of a square hole.

Assembly Instructions for MIC-90-E / MIC-120-E3


˕ ˖

52 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

.*TUFFMDPOOFDUPST$POOFDUJPOUPTUFFMCFBN

.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153

Items in set

Ordering Information
Steel Beam Width B C D
Description For Girder Type in (mm) in (mm) in (mm) Weight Per Set lb (kg) Qty Item No.
MIC-S90-AA ˕ MI-90 Ȱ Ȱ
 
 
9.6 (4.3) 2 304811
MIC-S90-A ˖ MI-90 Ȱ Ȱ
 
 
15.7 (7.1) 2 304812
MIC-S90-B ˖ MI-90 Ȱ Ȱ
 
 
18.9 (8.5) 2 304813
MIC-S90-C ˖ MI-90 Ȱ Ȱ
 
 
22.5 (10.2) 2 304814
MIC-S120-A ˗ MI-120 Ȱ Ȱ
 
 
16.6 (7.5) 2 304818
MIC-S120-B ˗ MI-120 Ȱ Ȱ
 
 
19.8 (8.9) 2 304819
MIC-S120-C ˗ MI-120 Ȱ Ȱ
 
 
23.4 (10.6) 2 304820

1/
˕ 2" (12)
5 1/2" (140) ˖ ˗
2 3/8" (60) x 1/2" (13) D D
C C
B B
1/ 1/
2" (12) 2" (12)

5 1/2" (140) 5 1/2" (140)


11 3/16" (300)

B MI-120
5 7/8" (150)
5 7/8" (150)

6 1/8" (155)
6 1/8" (155)

8 11/16" (220)
8 11/16" (220)

MI-90
MI-90
9
9
/16" (14) /16" (14)

15
3
2 /8" (60) x 1/2" (13) 2 3/8" (60) x 1/2" (13)
3 /16" (100)

Connectors designed to resist moments.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 53
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

.*TUFFMDPOOFDUPST.*$4"""DPOOFDUJPOUPTUFFMCFBN

MIC-S90-AA1 Allowable loads


-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 2000 - - - -
Fy or Fz 670 - 670 - - -
Fy + Fz 470 - 470 - - -
Fy + Mz 490 - - - - 364
Fz + My - - 490 401 - -
Fx + My - 1110 - 292 - -
Fy + Fx + Mz 270 1110 - - - 219
Fy + Mx 110 - - - 76 -
Fz + Mx - - 110 - 76 -
Fy + Fx + Fz + My 350 1110 350 292 - -
1 Fastened with two MI-SGC-M12 beam clamps (item 00233859), order separately.

Allowable loads
-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
MIC-S90-A2
Fx - 3260 - - - -
Fy or Fz 1330 - 1330 - - -
Fy + Fz 940 - 940 - - -
Fz + My - - 980 407 (534)3 - -
Fy + Mz 530 - - - - 407
Fy + Fx + Mz 890 1110 - - - 407
Fx + Fz + My - 1110 980 407 (481)3 - -
5 1/2" (140)
Fz + Mx - - 180 - 343 -
Fy + Mx 180 - - - 343 -
LF1 310 1110 310 306 153 306
LF2a - 1930 240 - 200 -
LF2b 240 1930 - - 200 -
LF3 oST 150 - 960 407 (534)3 - 87
LF3 ST 330 1550 920 - - 407
LF4 690 3260 690 - - -
2 Fastened with four MI-SGC-M12 beam clamps (item 00233859), order separately.
3 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-90 item 304889) must be ordered
separately.

.PNFOUTBOEMPBEJOHDPOՐHVSBUJPOT  -'
GPS.*$4"""POTUFFMCFBNT
LF1 and LF2 represent tee or lorraine cross supports. LF3 and LF4 represent cantilevers.
FV = vertical load and FH = horizontal load
LF1 LF2 LF3 LF4

LF2a = Moment Mx LF3ST = cantilever LF4 = cantilever with


induced by Fz with support vertical and
LF2b = Moment Mx LF3oST = cantilever horizontal supports
induced by Fy without
support

54 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

.*TUFFMDPOOFDUPST.*$4#$DPOOFDUJPOUPTUFFMCFBN

MIC-S90-B1 Allowable loads


-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 2270 - - - -
Fy or Fz 1330 - 1330 - - -
Fy + Fz 940 - 940 - - -
Fz + My - - 980 407 (534)2 - -
Fy + Mz 710 - - - - 407
5 1/2" (140)
Fy + Fx + Mz 890 1110 - - - 407
Fx + Fz + My - 1110 980 407 (459)2 - -
Fz + Mx - - 410 - 339 -
Fy + Mx 410 - - - 339 -
LF1 380 970 380 2552 153 255
LF2a - 1930 300 - 246 -
LF2b 300 1930 - - 246 -
LF3 oST 150 - 980 407 (534)2 - 95
LF3 ST 330 1060 920 - - 407
LF4 690 2270 690 - - -
1 Fastened with four MI-SGC-M12 beam clamps (item 00233859), order separately.
2 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-90 item 00304889) must be ordered
additionally.

MIC-S90-C3 Allowable loads


-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 1600 - - - -
Fy or Fz 1330 - 1330 - - -
Fy + Fz 940 - 940 - - -
Fz + My - - 980 407 (534)4 - -
Fy + Mz 840 - - - - 407
Fy + Fx + Mz 890 910 - - - 364
Fx + Fz + My - 760 980 407 (481)4 - -
5 1/2" (140)
Fz + Mx - - 470 - 383 -
Fy + Mx 470 - - - 383 -
LF1 440 790 200 2044 153 204
LF2a - 1600 250 - 343 -
LF2b 250 1600 - - 343 -
LF3 oST 150 - 980 407 (534)4 - 102
LF3 ST 330 860 920 - - 372
LF4 690 1600 690 - - -
3 Fastened with four MI-SGC-M12 beam clamps (item 00233859), order separately.
4 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-90 item 00304889) must be ordered
additionally.

.PNFOUTBOEMPBEJOHDPOՐHVSBUJPOT  -'
GPS.*$4#$POTUFFMCFBNT
LF1 and LF2 represent tee or lorraine cross supports. LF3 and LF4 represent cantilevers.
FV = vertical load and FH = horizontal load
LF1 LF2 LF3 LF4

LF2a = Moment Mx LF3ST = cantilever LF4 = cantilever with


induced by Fz with support vertical and
LF2b = Moment Mx LF3oST = cantilever horizontal supports
induced by Fy without
support

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 55
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

.*TUFFMDPOOFDUPST.*$4"#DPOOFDUJPOUPTUFFMCFBN
MIC-S120-A Allowable loads
-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 3660 - - - -
Fy or Fz* 1330 - 1330 - - -
Fy + Fz 940 - 940 - - -
5 1/2" (140) Fz + My - - 980 565 (777)2 - -
Fy + Mz 620 - - - - 407
Fy + Fx + Mz 890 1330 - - - 407
Fx + Fz + My - 1350 980 561 - -
Fz + Mx - - 180 - 343 -
Fy + Mx 180 - - - 343 -
LF1 310 1330 310 357 153 357
LF2a - 2150 240 - 200 -
LF2b 240 2150 - - 200 -
LF3 oST 150 - 980 565 (729)2 - 109
LF3 ST 330 1550 920 - - 407
LF4 690 3660 690 - - -
1 Fastened with four MI-SGC-M12 beam clamps (item 00233859), order separately.
2 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-90 item 00304889) must be ordered
additionally.

MIC-S120-B3 Allowable loads


-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 2510 - - - -
Fy or Fz* 1330 - 1330 - - -
Fy + Fz 940 - 940 - - -
Fz + My - - 980 565 (777)4 - -
5 1/2" (140)
Fy + Mz 980 - - - - 407
Fy + Fx + Mz 890 1330 - - - 407
Fx + Fz + My - 1380 980 459 - -
Fz + Mx - - 410 - 339 -
Fy + Mx 410 - - - 339 -
LF1 380 970 380 255 153 255
LF2a - 2150 300 - 246 -
LF2b 300 2150 - - 246 -
LF3 oST 150 - 980 565 (729)4 - 109
LF3 ST 330 1060 920 - - 407
LF4 690 2510 690 - - -
3 Fastened with four MI-SGC-M12 beam clamps (item 00233859), order separately.
4 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-90 item 00304889) must be ordered
additionally.

.PNFOUTBOEMPBEJOHDPOՐHVSBUJPOT  -'
GPS.*$4"#POTUFFMCFBNT
LF1 and LF2 represent tee or lorraine cross supports. LF3 and LF4 represent cantilevers.
FV = vertical load and FH = horizontal load
LF1 LF2 LF3 LF4

LF2a = Moment Mx LF3ST = cantilever LF4 = cantilever with


induced by Fz with support vertical and
LF2b = Moment Mx LF3oST = cantilever horizontal supports
induced by Fy without
support

56 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

.*TUFFMDPOOFDUPST.*$4$DPOOFDUJPOUPTUFFMCFBN
Allowable loads
MIC-S120-C1 -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 1800 - - - -
Fy or Fz 1330 - 1330 - - -
Fy + Fz 940 - 940 - - -
Fz + My - - 980 565 (777)2 - -
5 1/2" (140) Fy + Mz 890 - - - - 407
Fy + Fx + Mz 890 970 - - - 364
Fx + Fz + My - 820 980 525 - -
Fz + Mx - - 470 - 383 -
Fy + Mx 470 - - - 383 -
LF1 440 790 200 204 153 204
LF2a - 1800 250 - 343 -
LF2b 250 1800 - - 343
LF3 oST 150 - 980 565 (729)2 - 109
LF3 ST 330 860 920 - - 372
LF4 690 1800 690 - - -
1 Fastened with four MI-SGC-M12 beam clamps (item 00233859), order separately.
2 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-90 item 00304889) must be ordered
additionally.

.PNFOUTBOEMPBEJOHDPOՐHVSBUJPOT  -'
GPS.*$4$POTUFFMCFBNT
LF1 and LF2 represent tee or lorraine cross supports. LF3 and LF4 represent cantilevers.
FV = vertical load and FH = horizontal load
LF1 LF2 LF3 LF4

LF2a = Moment Mx LF3ST = cantilever LF4 = cantilever with


induced by Fz with support vertical and
LF2b = Moment Mx LF3oST = cantilever horizontal supports
induced by Fy without
support

.*TUFFMDPOOFDUPST.*$4"#$1 connection to steel beams or channels


Ordering Information
Connection
Description Information Qty Item No.

MIC-S (A/B/C)1 ˕ To suit beam size 1 00304812/00304813/003048141


MIB-S (A/B/C)1 ˖ To suit beam size 1 00304821/00304822/003048231
AM 12-F ˗ M12-F threaded rod 4 00304774
M12-F-SL WS 3/4 ˘ Self-locking nuts 8 00382897
1 Choose A, B or C according to steel beam or channel size, see section 3.4.6 ordering information

Technical Data
Allowable loads
˕ -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)

˗ Fx - See connector MIC-S (A/B/C) -


˘ Fy or Fz 1330 - 1300
Fy + Fz 940 - 920

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 57
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

.*DPODSFUFDPOOFDUPST.*$$61 connection to concrete


.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.

MIC-C90-U1 MI-90 5.0 (2.2) 2 00304826

1 Always to be used at both ends of a girder.

MIC-C90-U

Items in set

Technical Data Allowable loads


MIC-C90-U -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)
crossbeam connector
Fx - 380 -
Fy or Fz 1310 - 2430
Fy + Fz 1310 - 2050

58 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

.*DPODSFUFDPOOFDUPST.*$$""DPOOFDUJPOUPDPODSFUF
POUPDPODSFUF
.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.

MIC-C90-AA1 ˕ MI-90 7.7 (3.5) 2 00304825


MIC-C90-D1 ˖ MI-90 16.1 (7.3) 2 00304827
MIC-C120-D1 ˗ MI-120 16.9 (7.6) 2 00304829

˕1 3 15/16" (100) ˖1 9 1
/1 ˗1 9 1
6 " (2 /1
30) 6 " (2
6 1 6 1 30)
/8 " /8 "
(15 (15
6) 9/ " (15) 6)
1 9
5 /2" (140) 1 16 /16" (15)
/2" (12)
1 5 1/2" (140)
5 /2" (140)
7 7/8" (200)

MI-90

6 1/8" (156)
6 1/8" (156)
9 1/16" (230)

9 1/16" (230)
MI-90

1" (25) x 9/16"(14)


1 7/8" (47) x 11/16" (17) 1 7/8" (47) x 11/16" (17)

1 ˕ ˖and˗
Connectors designed to resist moments.

Technical Data Allowable loads


MIC-C90-AA connector -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 1980 - - - -
Fy or Fz 1960 - 2430 - - -
Fy + Fz 1960 - 1440 - - 729
Fx + Fz - 1570 1120 - - -
Fz + My - - 560 407 (534)2 1326 -
Fx + My 810 450 - - 729
LF3 360 810 360 295 - -
2 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-90 item 00304889) must be
ordered additionally.

.PNFOUTBOEMPBEJOHDPOՐHVSBUJPOT  -'
GPS.*$$""POTUFFMCFBNT
Items in set LF3 represent cantilever support.
FV = vertical load and FH = horizontal load
LF3

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 59
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

.*DPODSFUFDPOOFDUPST
MIC-C90-D / 120-D connection to concrete

MIC-C90-D Allowable loads


-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 5490 - - - -
Fy + Fz 5980 - 5980 - - -
Fz + My - - 1600 407 (534)1 - -
5 1/2" (140)
Fy + Mz 1600 - - - - 407
Fy + Fx + Mz 1260 1550 - - - 407
Fy + Fx + My - 1550 1260 407 (534)1 - -
Fz + Mx - - 2920 - 1329 -
Fy + Mx 2920 - - - 1329 -
LF1 600 1640 600 407 (488)1 153 407
LF2a - 1930 440 - 364 -
LF2b 440 1930 - - 364 -
LF3 oST 440 - 1550 407 (534)1 - 168
LF3 ST 560 1550 1550 - - 407
LF4 330 2670 3330 - - -
1 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-120 item 00304890) must be ordered
additionally.

MIC-C120-D Allowable loads


-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) ± My (ft-lb) ± Mx (ft-lb) ± Mz (ft-lb)
Fx - 6330 - - - -
Fy + Fz 5980 - 5980 - - -
Fz + My - - 1750 565 (777)2 - -
Fy + Mz 1750 - - - - 407
Fy + Fx + Mz 1260 1800 - - - 407
Fy + Fx + My - 1800 1260 565 (678)2 - -
Fz + Mx - - 2920 - 1401 -
Fy + Mx 2920 - - - 1401 -
LF1 600 2020 600 565 (777)2 153 407
LF2a - 2150 440 - 364 -
LF2b 440 2150 - - 364 -
LF3 oST 440 - 1550 565 (777)2 - 175
LF3 ST 560 1550 1550 - - 407
LF4 330 2670 3330 - - -
2 Values in brackets ( ) apply to use of three bolts in girder connection. The third bolt (MIA-OH-120 item 00304890) must be ordered
additionally.

.PNFOUTBOEMPBEJOHDPOՐHVSBUJPOT  -'
GPS.*$$%PODPODSFUF
LF1 and LF2 represent tee or lorraine cross supports. LF3 and LF4 represent cantilevers.
FV = vertical load and FH = horizontal load
LF1 LF2 LF3 LF4

LF2a = Moment Mx LF3ST = cantilever LF4 = cantilever with


induced by Fz with support vertical and
LF2b = Moment Mx LF3oST = cantilever horizontal supports
induced by Fy without
support

60 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MI multi-angle connectors
For concrete connection see 3.4.8
.BUFSJBM4QFDJՐDBUJPOT For steel connection see 3.4.6

Material S235 JRG2 (DIN 10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153

˕
˖ steel connection
˗ concrete connection

Girder to girder 5
/16" (8)
4 3/4" (120) Items in set

˕
Ordering Information
MI angle connectors for girder
Description For Girder Type Weight Per Set lb (kg) Qty Item No.
7 3/4" (197.5)
MIC-U-MA ˕ MI-90/MI-120 5.5 (2.5) 2 sets
1 00304806 1/ (12.5)
2"

1 Connector must always be used in pairs on opposite sides of the girder. Edge distance
GSPNBOHMFDPOOFDUPSCPMUBOEFOEPGHJSEFSNVTUCFɻ NN

3 1/8" (80)

Girder to steel
Ordering Information
MI angle connectors for steel
Steel Beam Width B C D
Description For Girder Type in (mm) in (mm) in (mm) Weight Per Set lb (kg) Qty Item No.
MIC-SA-MA ˖ MI-90/MI-120 Ȱ Ȱ
 
 
13.8 (6.2) 4 00304815
MIC-SB-MA ˖ MI-90/MI-120 Ȱ Ȱ
 
 
17.0 (7.7) 2 00304816
MIC-SC-MA ˖ MI-90/MI-120 Ȱ Ȱ
 
 
20.7 (9.4) 2 00304817

Girder to concrete D Items in set


C
B
˖

3 5/8"
(92)

3 1/8" (80)
6 1/8" (155)
8 11/16" (220)

1
/2" (12.5)

1/
4" (6)
3 15/16"
(100)
3
2 /8" (60) x 1/2" (13) 9/
16" (14)

5/
16" (8)
7 7
/8 "
(20 Items in set
5 7 0)
/8 "
(15
0)
˗
3 5 /8 "
(92)
Ordering Information 3 1/8" (80)
MI angle connectors for concrete 3 15/16" (100)
1/
2" (12.5)
Description For Girder Type Weight Per Set lb (kg) Qty Item No.
1" (25) x 9/16" (14)
MIC-CU-MA ˗ MI-90/MI-120 4.4 (2.0) 4 00304828 1
/4" (6)
15
3 /16" (100)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 61
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MI multi-angle connectors
Girder to girder
Technical Data
MIC-U-MA angle connection to girder
MIC-U-MA1 Allowable loads
on MI-90/MI-120 MIC-U-MA
girder connector
F ±F (lb)
0° 5330
30° 2269
45° 1570
90° 60° 1020
45° 90° 0
1 Always to be used in pairs on opposite sides of the girder.

Girder to steel
MIC-SA/SB/SC-MA angle connection to steel
MIC-SA-MA/ Allowable loads2
MIC-SB-MA/MIC-SC-MA
MIC-SA-MA MIC-SB-MA MIC-SC-MA
for MI-90/MI-120 steel connector steel connector steel connector
±F (lb) ±F (lb) ±F (lb)
0° 3550 2670 1780
30° 2220 2220 1780
45° 1550 1550 1550
45° compression only -F = 1880 -F = 1880 -F = 1880
60° 1330 1330 1330
1/
2" (12.5) 90° 1110 1110 1110
2 The allowable load is limited by fastening to the steel beam with four MI-SGC-M12 beam clamps (item 00233859).

Girder to concrete
MIC-CU-MA angle connection to concrete
MIC-CU-MA Allowable loads3
for MI-90/MI-120 MIC-CU-MA
±F (lb)
0° 1580
30° 1110
45° 1110
45° compression only -F = 2220
1/ 60° 1110
2" (12.5)
1" (25) x 9/16" (14) 90° 1220

3 Capacity of anchorage to concrete must be evaluated separately.

62 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MI-SGC-M12 Beam Clamp

Advantages

Ƚ '
 PSTUFFMCFBNTXJUIՑBOHFUIJDLOFTTFTGSPNUP
 UPNN
BOEՑBOHFBOHMFPGVQUPp

Ƚ $
 PSSPTJPOQSPUFDUJPOPGTUFFMCFBNJTOPUEBNBHFECZ
beam clamp

Ƚ #FBNDMBNQJTFRVJQQFEXJUITFMGMPDLJOHOVU

.BUFSJBM4QFDJՐDBUJPOT

Material Malleable cast iron


Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

Screw M12, 8.8 grade

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.
MI-SGC M12 MI-90/MI-120 0.8 (0.4) 16 00233859

Items in set

Technical Data Allowable loads1, 2, 3, 4


MI-SGC-M12 -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)
Fx - 1290 -
Fy or Fz 330 - 330
Fy + Fz 240 - 240
Fy + Fx 240 1290 -
Fz + Fx - 1290 240
Fx+Fy+Fz 170 1290 170
1 All loads apply to 1 beam clamp
5IFTDSFXNVTUCFQPTJUJPOFEBHBJOTUUIFՑBOHFPGUIFTUFFMCFBNBOEUIFXJEFSTJEFPGUIFCFBNDMBNQPOUIFCBTF
plate of the MI connector
#FBNDMBNQTNVTUBMXBZTCFVTFEJOQBJST QPTJUJPOFEPOPQQPTJUFTJEFTPGUIFCFBNՑBOHF
4 Tightening torque = 62 ft-lb

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 63
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MI-DGC Beam Clamp for direct connection to steel beam

Advantages

Ƚ '
 PSTUFFMCFBNTXJUIՑBOHFUIJDLOFTTFTGSPNUP
 UPNN
BOEՑBOHFBOHMFPGVQUPp

Ƚ $
 PSSPTJPOQSPUFDUJPOPGTUFFMCFBNJTOPUEBNBHFECZ
beam clamp

Ƚ #FBNDMBNQJTFRVJQQFEXJUITFMGMPDLJOHOVUT

.BUFSJBM4QFDJՐDBUJPOT

Material Malleable cast iron


Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

U-bolt M12, 8.8 grade

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.
MI-DGC 90 ˕ MI-90 7.5 (3.4) 4 00233860
MI-DGC Beam Clamp
MI-DGC 120 ˖ MI-120 8.0 (3.6) 4 00233861

Items in set ˕ Items in set ˖


Fz

/PUFFor U-bolt dimensions see MIA-BO90 and BO120 items 00304840 and 00304841 respectively, see 3.4.13.3.

Technical Data
Allowable loads1
Fy 5 3/16" (131) -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)
Fx - 2770 -
Fy or Fz 1350 - 1350
1 All loads apply to 1 pair. Beam clamps must always be used in pairs positioned on op-
QPTJUFTJEFTPGUIFՑBOHFBTTIPXOBCPWF
5IF6CPMUNVTUCFQPTJUJPOFEBHBJOTUUIFՑBOHFPGUIFTUFFMCFBN
3 Tightening torque 62 ft-lb.

Fx

1 1/2" (75)

1" (25) Fz
min.
64 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MIC-TRC Threaded Rod Connector

Advantages

Ƚ 0
 QQPTJUFTJEFPG.*HJSEFSTUJMMVTBCMFGPSPUIFS
applications

Ƚ $
 POOFDUPSDBOCFVTFEPOUPQ BTTIPXOBUSJHIU
PS
bottom of MI girder

Ƚ 8
 JUI.* NN
IFJHIUBEKVTUBCJMJUZGPS
.* NN

.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153
Connecting bolt M12 (connection to MI girder) see 3.4.15

Ordering Information
Description For Girder Type For Threaded Rod Sizes1 Weight Per Set lb (kg) Qty Item No.

MIC-TRC M12-1/2 ˕ MI-90/MI-120 .   2.1 (0.9) 2 00233856


MIC-TRC M20-3/4 ˖ MI-90/MI-120 .   2.2 (1.0) 2 00233858
 6
 TFXJUIUISFBEFESPETJ[FTTIPXOBOEUXPOVUTBOEXBTIFSTPOFOVUXBTIFSTVQQMJFEFYDFQUGPS 
items ordered separately.

Items in set ˕ Items in set ˖

1x M12
1x M20

1x 1/2" 1x
1x 3/4" 1x
1x 1x
1x 1x
1x 1x

Technical Data
   Allowable loads2 MIC-TRC M12, 1/2", M16, 5/8"
M12, M16, M20
-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)
Fz – – 2800
MI-90:
15
1 /16” (50)
Allowable loads2 MIC-TRC M20, 3/4"
MI-120:
13/8” (35) -PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb)
Fz – – 2200
2 Threaded rod opacity must be evaluated separately.

215/16” (75)

Fz

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 65
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MIC-PG Low Friction Insert For Sliding Support


.BUFSJBM4QFDJՐDBUJPOT

Material PE-UHMW
Friction value = 0.15
Temperature resistance -238°F to 176°F

Ordering Information
Description For Girder Type Weight Per Set lb (kg) Qty Item No.1

MIC-PG MI-90/MI-120 0.8 (0.4) 16 00304842


1 Includes sixteen Kwik Togs to secure MIC-PG to a girder hole.

Kwik Tog
Technical Data MIC-PG

Allowable loads
-PBEJOH ± Fy (lb) ± Fx (lb) + Fz (lb)
Fz – – 6740

MIC-PS90/120 Sliding Support Clamps


.BUFSJBM4QFDJՐDBUJPOT

Material S235JRG2 (DIN EN10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

Ordering Information
Weight Per Set
Description For Girder Type lb (kg) Qty Item No.
MIC-PS90 ˕ MI-90 3.9 (1.8) 4 pairs 00304838
MIC-PSP-6MM ˖ MI-90/MI-120 0.7 (0.3) 5 pairs 00283594

Technical Data

˕ ˖
1
4 " (102) /2" (13)
Note: pipe ring sold separately. 1 3/
4" (45)
5 1/8" (130) 4 " (102)
1/
Allowable loads 1, 2, 3 2" (12)
11/
16" (18)
1
/4" (6)
-PBEJOH ± Fy (lb) ± Fx (lb) ± Fz (lb) 5 1/8" (130)
1 3/16" (30)
Fx or Fz** – 940 -1350 + 6740 3 9/16" (90)
11
1 Values apply only to one clamp. Install appropriate spacers so there is no clamping force /16" (18)
between the attached parts thus allowing unrestricted movement in the y-axis (i.e., Fy = 0).
2 Must be used in pairs.
3 Tightening torque = 62 ft-lb.

66 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MIA-B090/120-M12 Fixed Point U-Bolts


.BUFSJBM4QFDJՐDBUJPOT

Material S235JRG2 (DIN EN10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

Ordering Information
Weight Per Set
Description For Girder Type lb (kg) Qty Item No.
MIA-B090-M12 MI-90 1.3 (0.6) 8 pairs 00304840
MIA-B0120-M12 MI-120 1.4 (0.6) 8 pairs 00304841

Technical Data

MIA-B090-M12
for MI-90

MIA-B120-M12
for MI-120

Note: pipe ring sold separately.4

Allowable loads1, 2, 3, 4
-PBEJOH ± Fy (lb) ± Fx (lb) Fz (lb)
Fy or Fx or Fz 2690 2250 -2250
1 Values apply only to one clamp.
2 Must be used in pairs.
3 Tightening torque = 62 ft-lb.
4 Capacity of connected parts must be evaluated separately.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 67
Hilti MI/MQ Technical Guide

.*$PNQPOFOUT "MMPXBCMF-PBE%BUBBOE4QFDJӏDBUJPOT

MIC-UB90 U-Bolt Clamps For Uninsulated Pipes & Conduits


.BUFSJBM4QFDJՐDBUJPOT

Material S235 JRG2 (DIN 10025),


ASTM A1011 (36)
Galvanizing )PUEJQHBMWBOJ[FENJMT ƓN

DIN EN ISO 1461, ASTM A153
Connecting screws M12 (connection to MI-girder) see 3.4.15

Ordering Information
Weight Per Set
Description For Girder Type lb (kg) Diameter U-Bolt Qty Item No.
MIC-UB90 ˕ MI-90 2.7 (1.2) ɺ 10 pairs 00304831
MIC-UB120 ˖ MI-120 3.0 (1.3) ɺ 10 pairs 00304833
MIC-UB90-M16 ˗ MI-90 2.7 (1.2)  6 pairs 00304834
MIC-UB120-M16 ˘ MI-120 2.9 (1.3)  6 pairs 00304835

Technical Data
for MI-90 ˕ for MI-120 ˖
2 9/16" (65) x 1/2" (13) 1 15
/16" (49) 2 9/16" (65) x 1/2" (13)
1 15/16" (49)

1 " (26) x 9/16" (13.5)


1 " (26) x 9/16" (13.5)
3 9/16" (90)
3 3/4" (96)
3 9/
16" (90)
3 9/16" (90)

for MI-90 ˗ for MI-120 ˘


2 9/16" (65) x 11/16" (17) 2 9/16" (65) x 11/16" (17) 1 15/16" (49)
1 15/16" (49)

1 " (26) x 9/16" (13.5)


1 " (26) x 9/16" (13.5)
3 9/16" (90) 3 3/4" (96)

3 9/16" (90) 3 9/16" (90)

Allowable loads1, 2
Items in set ˕˖˗˘
-PBEJOH˕˖˗˘ ± Fy (lb) ± Fx (lb) ± Fz (lb)
Fy or Fz 112 - 225
1 Values apply to one pair, must be used in pairs
2 U-bolt sold separately

68 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.5 MI / MQ Compatible Systems

#FOFՐUTPGUIF.*BOE.24ZTUFNT

˕ MI System
Easy to install and extremely dependable, this system
requires no welding. The Hilti MI system is a modular
system for medium to heavy loads and an ideal solution for
pipes and cable trays.

˖ MQ System
The well-proven Hilti MQ Strut System for light to medium
1 loads is the versatile extension of the MI system. Ideal for
supporting pipes and cable trays, MQ system components
integrate easily with MI structures for comprehensive
support solution.
2
˗ The right connection
With the strength of welded structures, but much more
3
FGՐDJFOUBVOJRVF MPOHJUVEJOBMTXBHFEJOEFOUBUJPOJT
part of the Hilti MI girder design. This indentation ensures
proper nesting of all MI and MQ components. This feature
helps provide the strength of a welded structure while being
DPNQMFUFMZNPEVMBSBOEDBOFBTJMZCFSFDPOՐHVSFEBTZPVS
support needs change.

MI System MQ System

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 69
Hilti MI/MQ Technical Guide

3.5 MI / MQ Compatible Systems

MI /MQ Connectors
.BUFSJBM4QFDJՐDBUJPOT

Material S235JRG2 (DIN EN10025), ASTM A1011 (36)


Galvanizing Hot-dip galvanized 2.2 mils (55 μm)
DIN EN ISO 1461, ASTM A153

Ordering Information
Weight Per Set
Description For Attaching Strut1 lb (kg) Qty Item No.
MIC-MI/MQ-X ˕ .2' )%( .2' )%( 0.7 (0.3) 16 00304881
MIA-OH90 (Bolt) ˗ all strut except B2B, (back to back) 0.2 (0.1) 10 00304889
M12-F-SL WS 3/4 (Nut) ˘ - 0.0 (0.0) 100 00382897
MQP-45°-F ˖ .2' )%( .2' )%( 0.7 (0.3) 10 00304164
MQN electro-galvanized 0.15 (0.07) 50 00369623
MQN-F all hot-dip galvanized 0.19 (0.09) 25 00304130
MQN-R all stainless steel 0.17 (0.08) 25 00304012
1 MQ Strut and MQN Pushbutton ordering information, see 4.1.3 and 4.3.

Technical Data
MIC-MI/MQ-X 2

on MI-90 or 120 girder3


Sturt1 "MMPXBCMF-PBE ± Fy (lb) + Fx (lb) ± Fz (lb)
13/16" (21) Fy or Fx or Fz 1120 560 270
1-5/8" (41) Fy or Fx or Fz* 1120 560 270
2 Bolt M10 tightening torque = 44 ft-lb. Use with appropriate MQN Pushbuttons (sold separately).
8IFONPVOUJOHUPNNXJEUI VTFBQQSPQSJBUFMFOHUI NN NJOJNVN
. 
CPMU

Items in set ˕
Allowable loads MQN M10
.2/ Tension (lb)4 Shear (lb)5
MQN 1800 1100
MQN-F 1800 400
MQN-R 1800 1100
4 Based on 12 gauge strut and a safety factor of 2.2
5 Applies to a single fastening using Hilti serrated strut

MQP-45°-F Items in set ˖


on MI-906 or 120 girder7 9
/16˜ 

Allowable loads MQP-45 °F


-PBEJOH ± FR (lb) ± FH (lb) 1
4 /8" (105)

FR or FH 945 670 45°


1 9/16 
1 9/16  

4 1/
8" (105) 6 When mounting to 90 mm width, order 00283595 Hex Head Bolt 9
/16" (14)
M12 x 120-F/8.8 and M12 nut item 382897.
45°
9
/16" (14) 7 When mounting to 120 mm width, order separately 1 5/8" (42)
1 5/8" (41)
bolt MIA-EH120 item 00304888 and M12 nut item 00382897,
1 5/8" (41)
see 3.4.15.
1 5/8" (42) Note: Use with appropriate MQN Pushbutton (sold
separately) to attach strut to connector.

Allowable loads8
MIC-MI/MQ
-PBEJOH MQ strut gauge ± Fy (lb) ± Fx (lb) ± Fz (lb)
on MI-90 or 120 girder9
Fy or Fx or Fz 14 645 1970 2240
Fy or Fx or Fz 12 1110 1815 3435
7BMVFTBQQMZPOMZUP.2TUSVUDPOOFDUFEVTJOHUXPCPMUTBU
spacing. Bolt tightening torque = 62 ft-lb. Other connected parts Item 9 ˗ Item ˘
must be evaluated separately.
9 When mounting to 120 mm width, order separately
bolt MIA-OH 120 item 00304890, see page 73.

70 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.5 MI / MQ Compatible Systems

Individual connecting parts


1 7/16" 1 7/16"
.BUFSJBM4QFDJՐDBUJPOT (36.6) (36.6)

˕ ˖ ˗
Material EN-GJMW-400-5 (DIN EN 1562), 1 7/16"
3 3/4"
1 7/16"
malleable cast iron or ASTM A1011 (36.6) (36.6)
(95)
3
4 / 4"
Screws/Bolts HSBEFUISFBEMFOHUINN 
(120) (M12)
5 7/8"
Nuts 8 grade DIN 1661, self locking (M12)
(150)

Galvanizing 1.8 mils (45 μm)


(M12)
Material-Plastic Moplen EP 240H -22°F to +194°F (-30°C to +90°C)

Ordering Information ˘ ˙
For Girder Weight Per Each 2 13/16" (72)
Description Type lb (kg) Qty Item No.
MIA-EH90 ˕ 90 0.3 (0.16) 10 00304887 5"
(127)
MIA-EH120 ˖ 120 0.4 (0.19) 10 00304888
MIA-OH90 ˗ 90 0.2 (0.10) 10 00304889 1 15/16"
(M12) (50)
MIA-OH120 ˘ 120 0.2 (0.13) 10 00304890
MIA-EH-P ˙ 90/120 0.6 (0.28) 10 00304891
M12-F-SL WS 3/4" nut ˚ 90/120 0.04 (0.02) 100 00382897 1
/2” (13) 1/ " (12.2)
2 x 1/2" (12.2)
MIA-TP ˛ 90/120 0.1 (0.06) 20 00305707 15
˚ /16” (24)
˛
Hex. Head Bolt M12x120-F/8.8 90/120 0.2 (0.10) 40 00283595 1/
4" (7)

A 13-F Washer 90/120 0.01 (0.005) 100 00304771


(M12) 1 7/16" (36.6) 1 7/16" (36.6)
Threaded Rod AM 12-F 1M (3.28 ft.) - 1.6 (.073) 15 00304774
3
/4” (19)

Ordering Information1 ˜1 ˝ 9 1
D /1
6 " (2
For Girder Weight Per Each 6 1 30)
/8 "
Description Type lb (kg) Qty Item No. C (15
6) 9
B /16" (15)
MIB-SA ˜ 90/120 12.0 (5.4) 2 00304821 1/
5 7/8" (150)

2" (12)
MIB-SB ˜ 90/120 15.2 (6.9) 2 00304822
MIB-SC ˜ 90/120 18.8 (8.5) 2 00304823

9 1/16" (230)
MIB-CD ˝ 90/120 12.9 (5.8) 2 00304830

6 1/8" (156)
MIC-SC90 ˞ 90 3.1 (1.4) 10 00304824

6 1/8" (155)
8 11/16" (220)
9 1 7/8" (47) x 11/16" (17)
/16" (14)

2 3/8" (60) x 1/2"(13)

Connector for welding to steel 1 See section 3.4.6 for dimensions of B, C, and D.

5 1/2" (140)

2 13/16"
(72)

2 13/16"
Flexy Pack Fabrication of Ec- Application (72)
centric Bases Flexy Pack

11
/16" (17)
End Caps Ordering Information
11
For Girder Weight Per Each /16" (17)
Description Type lb (kg) Qty Item No.
˟ ˠ
MIA-EC-90 ˟ 90 0.06 (0.02) 25 00432077
MIC-EC-120 ˠ 120 0.08 (0.03) 25 00432078 4 3/4"
9/ " (120.4)
3 16
(90.4)
3 9/16" (90.4)
3 9/16" (90.4)

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 71
Hilti MI/MQ Technical Guide

3.6 Formulas and Terminology

Single span formulas

-PBEJOHDPOEJUJPO

4JOHMFTQBOXJUIVOJGPSNMPBE EJTUBODFCFUXFFOTVQQPSUTɏ

w *ɏ2 8 *ƚall * S
Mmax = ______ ƚall * S w = __________
ℓ 8 ɏ2

5 w *ɏ4 384 E * I *ɪmax


ɪmax = ____ * ______ w = ____ * __________
384 E *ƭ 5 ɏ4

-PBEJOHDPOEJUJPO

4JOHMFTQBOXJUITJOHMFMPBEJODFOUFSPGTQBOɏ

F *ɏ 4 *ƚall * S
Mmax = ______ ƚall * S F = __________
4 ɏ

1 F *ɏ3 E * I *ɪmax
ɪmax = ____ * ______ F = 48 * __________
48 E *ƭ ɏ3

-PBEJOHDPOEJUJPO

4JOHMFTQBOXJUIMPBET FBDIBUɏ
F *ɏ 3 *ƚall * S
Mmax = ______ ƚall * S F = __________
3 ɏ

23 F *ɏ3 648 E * I *ɪmax


ɪmax = ____ * ______ F = ____ * __________
648 E *ƭ 23 ɏ3

-PBEJOHDPOEJUJPO

4JOHMFTQBOXJUIMPBET FBDIBUɏ

F *ɏ 2 *ƚall * S
Mmax = ______ ƚall * S F = __________
2 ɏ

38 F *ɏ3 768 E * I *ɪmax


ɪmax = ____ * ______ F = ____ * __________
768 E *ƭ 38 ɏ3

M = Bending Moment ɏ (JSEFS-FOHUI ű .PNFOUPG*OFSUJB


F = Single Load ƚall = Allowable Stress S = Section Modulus
w = Uniform Load E = Modulus of Elasticity ɪ %FՑFDUJPO

72 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

3.6 Formulas and Terminology

Cantilever formulas

-PBEJOHDPOEJUJPO

$BOUJMFWFSXJUIVOJGPSNMPBE DBOUJMFWFSMFOHUIɏ
w *ɏ2 2 *ƚall * S
M = _____ ƚall * S w = __________
2 ɏ2

1 w *ɏ4 E * I *ɪmax
ɪmax = ___ * ______ w = 8 * __________
8 E *ƭ ɏ4

-PBEJOHDPOEJUJPO

$BOUJMFWFSXJUITJOHMFMPBEJODFOUFSPGDBOUJMFWFSMFOHUIɏ
2 *ƚall * S
M = F *ɏƚall * S F = __________
ɏ

1 F *ɏ3 E * I *ɪmax
ɪmax = ___ * ______ F = 24 * __________
24 E *ƭ ɏ3

-PBEJOHDPOEJUJPO

$BOUJMFWFSXJUITJOHMFMPBEBUFOEPGDBOUJMFWFSMFOHUIɏ
ƚall * S
M = F *ɏƚall * S F = _______
ɏ

1 F *ɏ3 E * I *ɪmax
ɪmax = ___ * ______ F = 3 * __________
3 E *ƭ ɏ3

-PBEJOHDPOEJUJPO

$BOUJMFWFSXJUIMPBET FBDIBUɏ
ƚall * S
M = F *ɏ F = _______
ɏ

7 F *ɏ3 54 E * I *ɪmax
ɪmax = ___ * ______ F = ____ * __________
54 E *ƭ 7 ɏ3

-PBEJOHDPOEJUJPO

$BOUJMFWFSXJUIMPBET FBDIBUɏ
3 * F *ɏ 2ƚall * S
M = ________ ƚall * S F = ________
2 3 *ɏ

31 F *ɏ3 128 E * I *ɪmax


ɪmax = ____ * ______ F = ____ * __________
128 E *ƭ 31 ɏ3

M = Bending Moment ɏ (JSEFS-FOHUI ű .PNFOUPG*OFSUJB


F = Single Load ƚall = Allowable Stress S = Section Modulus
w = Uniform Load E = Modulus of Elasticity ɪ %FՑFDUJPO

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 73
Hilti MI/MQ Technical Guide

3.7 Additional MI Connection Examples

Attaching MI to larger steel beams

Ordering Information
Description Information Qty Item No.
MI-90 ˕ .JOJNVNMFOHUICFBNIFJHIU  2 00304799
MIC-UB90-M12 ˖ 8 00304831
Hex. Head Screw M12x120F/8.8 ˗ 4 00283595
M12-F Hex. Collar Nut ˘ Self-locking nuts 12 00382897
AM 12-F ˙ M12-F threaded rod 4 00304774

˕
˘
˙

Cross connection between MI girder

Ordering Information
Description Information Qty Item No.
MIB-SA ˕ 1 00304821
MIA-EH-P ˖ 4 00304891
A13-F ˗ 4 00304771
M12x130F/8.8 Hex. Screw ˘ Special order 4 00283596
M12 Hex. Collar Nut ˙ Self-locking nut 4 00382897

˕ ˘
˙

˖
˙

74 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

4.0 MQ Support System

4.1 Hilti Strut


Product Description
$1SPՐMF$IBOOFM Features

)JMUJTUSVUDPOTJTUTPGB$QSPՐMF Ƚ$1SPՐMFXJUITFSSBUFE
channel with serrated open edges edges for greater hold
rolled inwards. The strut provides an BOEBEKVTUBCJMJUZ
economical solution for mechanical,
Ƚ4DBMFEUJDLNBSLT
electrical and industrial supports.
FWFSZUPBTTJTUXJUI
measurement, cutting
and installation
Back-to-Back

Ƚ'VMMTMPUGPSHSFBUFS
ՑFYJCJMJUZJOBODIPSJOH

Ƚ-POHJUVEJOBMTXBHJOHGPSHSFBUFS
strength

$1SPՐMF

Material and Finishes


Material BEKBDFOU[JODQMBUJOHXIJDIBDUTBTB uniform layer of green colored epoxy
TBDSJՐDJBMBOPEFJNQFEJOHDPSSPTJPOPG resin on the surface of plain carbon steel
Hot rolled sheet steel per ASTM A1011
the raw edges. PG conforms to ASTM strut. This process occurs after the
and cold formed per ASTM A568.
653 galvanizing, with a G-90 coating strut is cold formed. The thermal fusion
Manufactured to MFMA-4.
(0.90 ounces zinc per square foot of process is in accordance to
Carbon Steel steel). ASTM F1043. Testing has been
conducted to verify the performance
ASTM A653, Grade 33 Hot Dipped Galvanized (HDG)
PGUIFՐOJTIJOBTBMUTQSBZ GPH

Hot dipped galvanized strut is
Stainless Steel environment per ASTM B117.
manufactured similar to PG strut except
SAE SS 316 Ti (1.4571 (A5)) — Ti is that the zinc coating process occurs Electro-galvanized (EG)
titanium to improve welding properties after cold forming and punching. The Electro-galvanized, or zinc plated,
channel is pretreated, pickled, and bonds a minimum 0.5 mil zinc coating
SAE SS 316 L (1.4404)
then dipped into tanks of molten zinc, to carbon steel through an electrolysis
Finishes creating an electrolyzed bond. HDG process. Most connectors and
provides increased corrosion resistance miscellaneous hardware are electro-
Pre-galvanized (PG) (PGS)
compared to PG material. HDG galvanized.
Pre-galvanized strut is manufactured by
conforms to ASTM A123 galvanizing
passing sheet steel through a molten Plain
for strut and ASTM A153 galvanizing
zinc bath. Afterwards, the sheets are 1MBJOՐOJTIJTQJDLMFE IPUSPMMFETUFFM
for connectors, bases, splices, and
DPMEGPSNFEJOUP$TIBQFQSPՐMFTBOE XJUIBMJHIUPJMՐOJTI
fasteners.
slots are punched hence the name “pre
galvanized”. PG is pre galvanized strut Electro Deposition Coating (GR
with punched slots and PGS is solid E-coat)
strut. Surfaces of the punched and cut Electro-deposition, or E-coat, uses
portions are somewhat protected by the electricity to deposit a smooth, thin,

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 75
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

Ordering Information
Strut 13/16 in-12 gauge
Hole Weight per Item No. Qty Item No.
Description $POՐHVSBUJPO piece (lb) Qty Single piece (VIP) VIP Pack

Strut 13/16 in-12 ga/PG 10 ft ˕ 2-1/2 in x 9/16 in 12.2 1 00407543 50 03453066


Strut 13/16 in-12 ga/PG 20 ft ˕ 2-1/2 in x 9/16 in 24.3 1 00407544 50 03453067
Strut 13/16 in-12 ga/PGS 10 ft ˕ solid 15.4 1 00407545 50 03453064
Strut 13/16 in-12 ga/PGS 20 ft ˕ solid 30.8 1 00407546 50 03453065
Strut 13/16 in-12 ga/HDG 10 ft 2-1/2 in x 9/16 in 12.8 1 00407569 50 03453650 ˕

Strut 1-5/8 in-12 gauge


Strut 1-5/8 in-12 ga/PG 2 ft Kwik Cut ˖ 2-1/2 in x 9/16 in 3.6 1 00407551 50 03453075
Strut 1-5/8 in-12 ga/PG 4 ft Kwik Cut ˖ 2-1/2 in x 9/16 in 7.2 1 00407552 50 03453076
Strut 1-5/8 in-12 ga/PG 6 ft Kwik Cut ˖ 2-1/2 in x 9/16 in 10.8 1 00407553 50 03453077
Strut 1-5/8 in-12 ga/PG 6 ft 8 in Kwik Cut ˖ 2-1/2 in x 9/16 in 12.0 1 00407554 50 03453078
Strut 1-5/8 in-12 ga/PG 10 ft ˖ 2-1/2 in x 9/16 in 18.0 1 00407555 50 03453079
Strut 1-5/8 in-12 ga/PG 10 ft (11/16" slot) 2-1/2 in x 11/16 in 18.0 1 00407560 50 03453081
Strut 1-5/8 in-12 ga/PG 20 ft ˖ 2-1/2 in x 9/16 in 36.0 1 00407557 50 03453080 ˖

Strut 1-5/8 in-12 ga/PGS 10 ft ˖ solid 18.5 1 00407561 50 03453073


Strut 1-5/8 in-12 ga/PGS 20 ft ˖ solid 37.0 1 00407562 50 03453074
Strut 1-5/8 in-12 ga/GR E-coat 10 ft ˖ 2-1/2 in x 9/16 in 18.0 1 00407558 50 03453083
Strut 1-5/8 in-12 ga/GR E-coat 20 ft ˖ 2-1/2 in x 9/16 in 36.0 1 00407559 50 03453084
Strut 1-5/8 in-12 ga/HDG 10 ft 2-1/2 in x 9/16 in 18.8 1 00407570 50 03453082
Strut 1-5/8 in-12 ga/SS316 Ti 10 ft 2-1/2 in x 9/16 in 18.8 1 03424527 12 03424528
Strut 2-7/16 in-12 gauge ˗

Strut 2-7/16 in-12 ga/PG 10 ft ˗ 2-1/2 in x 9/16 in 24.5 1 00407566 40 03453087


Strut 2-7/16 in-12 ga/PG 20 ft ˗ 2-1/2 in x 9/16 in 49.0 1 00407567 40 03453088
Strut 2-7/16 in-12 ga/PG 20 ft (11/16" slot) 2-1/2 in x 11/16 in 48.5 1 00407568 - -
Strut 13/16 in-14 gauge
˘
Strut 13/16 in-14 ga/PG 10 ft ˘ 2-1/2 in x 9/16 in 8.7 1 00407547 50 03453070
Strut 13/16 in-14 ga/PG 20 ft ˘ 2-1/2 in x 9/16 in 17.4 1 00407548 50 03453071
Strut 13/16 in-14 ga/PGS 10 ft ˘ solid 9.7 1 00407549 50 03453069
Strut 13/16 in-14 ga/PG GR E-coat 10 ft ˘ 2-1/2 in x 9/16 in 8.7 1 00407550 50 03453072
Strut 13/16 in-14 ga/SS316 Ti 10 ft ˘ 2-1/2 in x 9/16 in 9.9 1 03445372 - -
Strut 1-5/8 in-14 gauge ˙
Strut 1-5/8 in-14 ga/PG 10 ft ˙ 2-1/2 in x 9/16 in 13.6 1 00407563 50 03453085
Strut 1-5/8 in-14 ga/PG 20 ft ˙ 2-1/2 in x 9/16 in 27.2 1 00407564 50 03453086
Strut 1-5/8 in-14 ga/PGS 10 ft ˙ solid 13.9 1 00407565 50 03453089

Strut 13/16 in-12 gauge back-to-back


Hole Weight per Item No.
Description $POՐHVSBUJPO piece (lb) Qty Single piece ˚
Strut 13/16 in-12 ga/PG back-to-back (10 ft) ˚ 2-1/2 in x 9/16 in 23.0 1 02007081

Strut 1-5/8 in-12 gauge back-to-back


Hole Weight per Item No.
Description $POՐHVSBUJPO piece (lb) Qty Single piece

Strut 1-5/8 in-12 ga/PG back-to-back (10 ft) ˛ 2-1/2 in x 9/16 in 35.9 1 02007082
Strut 1-5/8 in-12 ga/PG back-to-back (20 ft) ˛ 2-1/2 in x 9/16 in 80.8 1 02007083 ˛
Strut 1-5/8 in-12 ga/SS316 Ti back-to-back (10 ft 1 in) ˛ 2-1/2 in x 9/16 in 35.9 1 03424529
Strut 1-5/8 in -12 ga/ HDG back-to-back (10 ft) ˛ 2-1/2 in x 9/16 in 37.6 1 02007087
Strut 1-5/8 in -12 ga/ PG back-to-back (20 ft) - 11/16” slot ˛ 2-1/2 in x 11/16 in 36.0 1 02007086

Strut 2 7/16 in -12 gauge back-to-back


Hole Weight per Item No.
Description $POՐHVSBUJPO piece (lb) Qty Single piece

Strut 2 7/16 in -12 ga/ PG back-to-back (20 ft) - 11/16” slot 2-1/2 in x 11/16 in 97.0 1 02007084

76 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

5FDIOJDBMEBUBBOETUSVUQSPՐMFT

14 ga
14 ga

12 Gauge 1316 158 2716 1316 B2B 158 B2B 2716 B2B

Profile Weight 1.287 lb/ft 1.92 kg/m 1.881 lb/ft 2.80 kg/m 2.471 lb/ft 3.68 kg/m 2.533 lb/ft 3.77 kg/m 3.588 lb/ft 5.34 kg/m 4.946 lb/ft 7.36 kg/m

Area of section 0.378 in2 2.44 cm2 0.552 in2 3.56 cm2 0.725 in2 4.68 cm2 0.729 in2 4.70 cm2 1.060 in2 6.84 cm2 1.452 in2 9.37 cm2

Moment of inertia Ix 0.031 in4 1.28 cm4 0.184 in4 7.65 cm4 0.517 in4 21.53 cm4 0.137 in4 5.70 cm4 0.892 in4 37.13 cm4 2.805 in4 116.76 cm4

Moment of inertia Iy 0.136 in4 5.67 cm4 0.235 in4 9.76 cm4 0.332 in4 13.83 cm4 0.264 in4 10.97 cm4 0.454 in4 18.91 cm4 0.669 in4 27.83 cm4

Section Modulus Sx 0.065 in 3


1.06 cm3
0.203 in 3
3.33 cm3
0.392 in3
6.42 cm 3
0.170 in3
2.79 cm 3
0.549 in 3
9.00 cm3
1.151 in 3
18.86 cm3

Section Modulus Sy 0.168 in3 2.75 cm3 0.288 in3 4.73 cm3 0.409 in3 6.70 cm3 0.324 in3 5.31 cm3 0.559 in3 9.16 cm3 0.823 in3 13.48 cm3

Radius of Gyration Rx 0.285 in. 0.72 cm 0.577 in. 1.47 cm 0.845 in. 2.15 cm 0.437 in. 1.11 cm 0.917 in. 2.33 cm 1.390 in. 3.53 cm

Radius of Gyration Ry 0.601 in. 1.53 cm 0.652 in. 1.66 cm 0.677 in. 1.72 cm 0.602 in. 1.53 cm 0.654 in. 1.66 cm 0.679 in. 1.73 cm

Gravity Axis e1 0.476 in. 1.21 cm 0.904 in. 2.30 cm 1.320 in. 3.35 cm 0.811 in. 2.06 cm 1.626 in. 4.13 cm 2.437 in. 6.19 cm

Gravity Axis e2 0.335 in. 0.85 cm 0.722 in. 1.83 cm 1.116 in. 2.84 cm 0.811 in. 2.06 cm 1.626 in. 4.13 cm 2.437 in. 6.19 cm
Ƚ /PNJOBMUIJDLOFTTPGHBVHFTUSJQTUFFMJTJODIFT NN

Ƚ .PEVMFTPGFMBTUJDJUZ  QTJ


Technical Data
and Strut Profile

14 ga
4MPU$POՐHVSBUJPOT
14 ga

14 Gauge 1316 158

Profile Weight 1.004 lb/ft 1.49 kg/m 1.445 lb/ft 2.15 kg/m

Area of section 0.295 in2 1.90 cm2 0.424 in2 2.74 cm2

Moment of inertia Ix 0.026 in 4


1.08 cm 4
0.148 in 4
6.16 cm4

Moment of inertia Iy 0.109 in4 4.55 cm4 0.185 in4 7.70 cm4

Section Modulus Sx 0.055 in3 0.91 cm3 0.165 in3 2.71 cm3

9/16" or 11/16" Section Modulus Sy 0.134 in 3


2.20 cm 3
0.228 in 3
3.73 cm3

Radius of Gyration Rx 0.297 in. 0.75 cm 0.591 in. 1.50 cm


Hilti Full Slot Radius of Gyration Ry 0.609 in. 1.55 cm 0.660 in. 1.68 cm

Gravity Axis e1 0.470 in. 1.19 cm 0.895 in. 2.27 cm

Gravity Axis e2 0.341 in. 0.87 cm 0.731 in. 1.86 cm


Ƚ /PNJOBMUIJDLOFTTPGHBVHFTUSJQTUFFMJTJODIFT NN

Ƚ .PEVMFTPGFMBTUJDJUZ  QTJ

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 77
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

Load and support condition


Load Factor Deflection Factor

Simple Beam – Uniform Load 1.00 1.00

Simple Beam – Concentrated Load at Center 0.50 0.80

F F

Simple Beam – Two Equal Concentrated Loads at 1/4 Points 1.00 1.10

Beam Fixed at Both Ends – Uniform Load 1.50 0.30

Beam Fixed at Both Ends – Concentrated Load at Center 1.00 0.4

Cantilever Beam – Uniform Load 0.25 2.40

Cantilever Beam – Concentrated Load at End 0.12 3.20

Continuous Beam – Two Equal Spans, Uniform Load on One Span 1.30 0.92

Continuous Beam – Two Equal Spans, Uniform Load on Both Spans 1.00 0.42

Continuous Beam – Two Equal Spans, Concentrated Load at Center of One Span 0.62 0.71

Continuous Beam – Two Equal Spans, Concentrated Load at Center of Both Spans 0.67 0.48

The beam load tables are for single-span simply supported beams with uniform loading. Common arrangements of other load and support conditions are presented in the above table. Loads
BOEEFՑFDUJPOTGPSUIFTFDPOEJUJPOTDBOCFEFUFSNJOFECZNVMUJQMZJOHUIFMPBEWBMVFGSPNUIFUBCMFTCZUIFHJWFOMPBEPSEFՑFDUJPOGBDUPS

&YBNQMF%FUFSNJOFUIFNBYJNVNBMMPXBCMFMPBEBOEEFՑFDUJPOGPSBGPPUDBOUJMFWFSCFBNXJUIBDPODFOUSBUFEMPBEPOPOFFOEBOEOPEFՑFDUJPOSFRVJSFNFOU

'SPNCFBNUBCMF JOTQBO UIFNBYJNVNBMMPXBCMFMPBEBOEEFՑFDUJPO


for a simply supported span with uniform loading is 829 lb and 0.22 in. Using the factors from the above table:

Max. allowable load = (Max. allowable uniform load – self weight) x load factor
Max. allowable load = (829 lb –1.881 lb/ft x 4 ft) x 0.12 = 98 lbs

.BYEFՑFDUJPOEFՑFDUJPOBUVOJGPSNMPBEYEFՑFDUJPOGBDUPS
.BYEFՑFDUJPOJOYJO

Additional reduction factors for pierced strut may apply. See note 4 of tables in section 4.1 pages 79-82.

78 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

#FBNMPBEJOHEBUBGPS)JMUJTUSVUQSPՐMFT1, 2, 3, 4
Slot Max Allow Deflection at Uniform Loading at Deflections
Reduction Beam Span Uniform Load Uniform Load 1/180 Span 1/240 Span 1/360 Span
Strut Factor in. (ft) mm lb kN in. mm lb kN lb kN lb kN

STRUT-1316-12 A 527 2.389 0.10 2.6 527 2.389 510 2.312 340 1.541

STRUT-158-12 A 1,658 7.520 0.05 1.4 1,658 7.520 1,658 7.520 1,658 7.520

STRUT-2716-12 A 3,196 14.496 0.04 0.9 3,196 14.496 3,196 14.496 3,196 14.496

STRUT-1316 B2B-12 B 1,530 6.733 0.06 1.5 1,530 6.733 1,530 6.733 1,530 6.733
24
610
(2)
STRUT-158 B2B-12 B 4,972 21.876 0.03 0.8 4,972 21.876 4,972 21.876 4,972 21.876

STRUT-2716 B2B-12 5,220 22.968 0.01 0.3 5,220 22.968 5,220 22.968 5,220 22.968

STRUT-1316-14 A 452 2.049 0.10 2.7 452 2.049 432 1.960 288 1.306

STRUT-158-14 A 1,349 6.119 0.05 1.4 1,349 6.119 1,349 6.119 1,349 6.119

STRUT-1316-12 A 351 1.593 0.23 5.9 302 1.370 227 1.027 151 0.685

STRUT-158-12 A 1,105 5.013 0.12 3.1 1,105 5.013 1,105 5.013 904 4.098

STRUT-2716-12 A 2,131 9.663 0.08 2.1 2,131 9.663 2,131 9.663 2,131 9.663

STRUT-1316 B2B-12 B 1,020 4.489 0.14 3.5 1,020 4.489 1,020 4.489 748 3.292
36
914
(3)
STRUT-158 B2B-12 B 3,315 14.584 0.07 1.7 3,315 14.584 3,315 14.584 3,315 14.584

STRUT-2716 B2B-12 5,220 22.968 0.04 1.0 5,220 22.968 5,220 22.968 5,220 22.968

STRUT-1316-14 A 301 1.366 0.24 6.0 256 1.161 192 0.871 128 0.580

STRUT-158-14 A 900 4.079 0.12 3.1 900 4.079 900 4.079 728 3.301

STRUT-1316-12 A 263 1.194 0.41 10.5 170 0.770 127 0.578 85 0.385

STRUT-158-12 A 829 3.759 0.22 5.5 829 3.759 763 3.457 508 2.305

STRUT-2716-12 A 1,598 7.247 0.15 3.8 1,598 7.247 1,598 7.247 1,431 6.487

STRUT-1316 B2B-12 B 765 3.366 0.24 6.2 765 3.366 631 2.778 421 1.852
48
1,219
(4)
STRUT-158 B2B-12 B 2,486 10.938 0.12 3.1 2,486 10.938 2,486 10.938 2,486 10.938

STRUT-2716 B2B-12 4,820 21.208 0.08 2.0 4,820 21.208 4,820 21.208 4,820 21.208

STRUT-1316-14 A 226 1.024 0.42 10.6 144 0.653 108 0.490 72 0.326

STRUT-158-14 A 675 3.059 0.22 5.6 675 3.059 614 2.785 410 1.857

1 Based on simple beam condition using an AISI allowable design stress of 25000 psi (172 Mpa) about the x-axis with adequate lateral bracing.
2 Refer to section 4.1 page 78, for different load and support condition reduction factors and 4.1 pages 83-86, for column loading data.
3 The strut member weight must be subtracted from the Allowable Uniform Load.
4 Beam load values are listed for solid strut. For pierced strut multiply the beam load by the following factor:
"
'PSYQJFSDFETUSVUNVMUJQMZUIFCFBNMPBECZ
#
'PSUFMFDPNYQJFSDFETUSVUNVMUJQMZUIFCFBNMPBECZ

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 79
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

#FBNMPBEJOHEBUBGPS)JMUJTUSVUQSPՐMFT1, 2, 3, 4
Slot Max Allow Deflection at Uniform Loading at Deflections
Reduction Beam Span Uniform Load Uniform Load 1/180 Span 1/240 Span 1/360 Span
Strut Factor in. (ft) mm lb kN in. mm lb kN lb kN lb kN

STRUT-1316-12 A 211 0.955 0.65 16.4 109 0.493 82 0.369 54 0.246

STRUT-158-12 A 663 3.007 0.34 8.6 651 2.950 488 2.212 325 1.475

STRUT-2716-12 A 1,279 5.797 0.23 5.9 1,279 5.797 1,279 5.797 916 4.151

STRUT-1316 B2B-12 B 612 2.693 0.38 9.6 539 2.370 404 1.778 269 1.185
60
1,524
(5)
STRUT-158 B2B-12 B 1,989 8.750 0.19 4.8 1,989 8.750 1,989 8.750 1,755 7.721

STRUT-2716 B2B-12 3,860 16.984 0.13 3.3 3,860 16.984 3,860 16.984 3,860 16.984

STRUT-1316-14 A 181 0.819 0.65 16.6 92 0.418 69 0.313 46 0.209

STRUT-158-14 A 540 2.447 0.34 8.7 524 2.377 393 1.782 262 1.188

STRUT-1316-12 A 176 0.796 0.93 23.6 76 0.342 57 0.256 38 0.171

STRUT-158-12 A 553 2.506 0.49 12.4 452 2.048 339 1.536 226 1.024

STRUT-2716-12 A 1,065 4.831 0.34 8.5 1,065 4.831 954 4.324 636 2.882

STRUT-1316 B2B-12 B 510 2.244 0.55 13.9 374 1.646 281 1.235 187 0.823
72
1,829
(6)
STRUT-158 B2B-12 B 1,657 7.292 0.27 6.9 1,657 7.292 1,657 7.292 1,219 5.362

STRUT-2716 B2B-12 3,220 14.168 0.19 4.8 3,220 14.168 3,220 14.168 3,220 14.168

STRUT-1316-14 A 151 0.682 0.94 23.9 64 0.290 48 0.217 32 0.145

STRUT-158-14 A 450 2.039 0.49 12.6 364 1.650 273 1.237 182 0.825

STRUT-1316-12 A 151 0.682 1.27 32.2 56 0.251 42 0.188 28 0.125

STRUT-158-12 A 474 2.147 0.67 16.9 332 1.504 249 1.128 166 0.752

STRUT-2716-12 A 913 4.140 0.46 11.6 913 4.140 701 3.176 467 2.117

STRUT-1316 B2B-12 B 437 1.924 0.74 18.9 275 1.209 206 0.907 137 0.605
84
2,134
(7)
STRUT-158 B2B-12 B 1,421 6.250 0.37 9.4 1,421 6.250 1,343 5.909 895 3.939

STRUT-2716 B2B-12 2,760 12.144 0.26 6.6 2,760 12.144 2,760 12.144 2,500 11.000

STRUT-1316-14 A 129 0.585 1.28 32.5 47 0.213 35 0.159 24 0.106

STRUT-158-14 A 386 1.748 0.67 17.1 267 1.212 201 0.909 134 0.606

1 Based on simple beam condition using an AISI allowable design stress of 25000 psi (172 Mpa) about the x-axis with adequate lateral bracing.
2 Refer to section 4.1 page 78, for different load and support condition reduction factors and 4.1 pages 83-86, for column loading data.
3 The strut member weight must be subtracted from the Allowable Uniform Load.
4 Beam load values are listed for solid strut. For pierced strut multiply the beam load by the following factor:
"
'PSYQJFSDFETUSVUNVMUJQMZUIFCFBNMPBECZ
#
'PSUFMFDPNYQJFSDFETUSVUNVMUJQMZUIFCFBNMPBECZ

80 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

#FBNMPBEJOHEBUBGPS)JMUJTUSVUQSPՐMFT1, 2, 3, 4
Slot Max Allow Deflection at Uniform Loading at Deflections
Reduction Beam Span Uniform Load Uniform Load 1/180 Span 1/240 Span 1/360 Span
Strut Factor in. (ft) mm lb kN in. mm lb kN lb kN lb kN

STRUT-1316-12 B 132 0.596 1.65 42.0 42 0.192 32 0.144 21 0.095

STRUT-158-12 B 415 1.879 0.87 22.1 254 1.151 191 0.863 127 0.575

STRUT-2716-12 799 3.622 0.60 15.1 715 3.242 536 2.431 358 1.620

STRUT-1316 B2B-12 A 383 1.683 0.97 24.6 210 0.926 158 0.694 105 0.428
96
2,438
(8)
STRUT-158 B2B-12 A 1,243 5.469 0.48 12.3 1,243 5.469 1,028 4.524 685 3.016

STRUT-2716 B2B-12 A 2,410 10.604 0.34 8.6 2,410 10.604 2,410 10.604 1,920 8.448

STRUT-1316-14 A 113 0.512 1.67 42.5 36 0.163 27 0.122 18 0.081

STRUT-158-14 A 337 1.529 0.88 22.3 205 0.928 154 0.695 102 0.463

STRUT-1316-12 B 117 0.530 2.09 53.1 34 0.151 25 0.113 17 0.075

STRUT-158-12 B 368 1.670 1.10 28.0 201 0.909 151 0.682 100 0.454

STRUT-2716-12 710 3.219 0.75 19.2 565 2.561 424 1.920 283 1.280

STRUT-1316 B2B-12 A 340 1.496 1.23 31.2 166 0.732 125 0.549 83 0.366
108
2,743
(9)
STRUT-158 B2B-12 A 1,105 4.861 0.61 15.5 1,083 4.766 812 3.574 542 2.383

STRUT-2716 B2B-12 A 2,140 9.416 0.42 10.7 2,140 9.416 2,140 9.416 1,510 6.644

STRUT-1316-14 A 100 0.455 2.12 53.8 28 0.128 21 0.096 14 0.064

STRUT-158-14 A 300 1.359 1.11 28.2 162 0.733 121 0.549 81 0.366

STRUT-1316-12 B 105 0.477 2.58 65.6 27 0.122 20 0.091 - -

STRUT-158-12 B 332 1.502 1.36 34.5 163 0.736 122 0.551 81 0.367

STRUT-2716-12 639 2.897 0.93 23.6 458 2.074 343 1.555 229 1.036

STRUT-1316 B2B-12 A 306 1.347 1.51 38.5 135 0.593 101 0.444 67 0.296
120
3,048
(10)
STRUT-158 B2B-12 A 994 4.375 0.76 19.2 877 3.860 658 2.895 439 1.930

STRUT-2716 B2B-12 1,930 8.492 0.52 13.2 1,930 8.492 1,840 8.096 1,230 5.412

STRUT-1316-14 A 90 0.409 2.61 66.4 23 0.104 17 0.078 - -

STRUT-158-14 A 270 1.223 1.37 34.9 131 0.593 98 0.444 66 0.296

1 Based on simple beam condition using an AISI allowable design stress of 25000 psi (172 Mpa) about the x-axis with adequate lateral bracing.
2 Refer to section 4.1 page 78, for different load and support condition reduction factors and 4.1 pages 83-86, for column loading data.
3 The strut member weight must be subtracted from the Allowable Uniform Load.
4 Beam load values are listed for solid strut. For pierced strut multiply the beam load by the following factor:
"
'PSYQJFSDFETUSVUNVMUJQMZUIFCFBNMPBECZ
#
'PSUFMFDPNYQJFSDFETUSVUNVMUJQMZUIFCFBNMPBECZ

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 81
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

#FBNMPBEJOHEBUBGPS)JMUJTUSVUQSPՐMFT1, 2, 3, 4
Slot Max Allow Deflection at Uniform Loading at Deflections
Reduction Beam Span Uniform Load Uniform Load 1/180 Span 1/240 Span 1/360 Span
Strut Factor in. (ft) mm lb kN in. mm lb kN lb kN lb kN

STRUT-1316-12 A 88 0.397 3.72 94.5 19 0.084 - - - -

STRUT-158-12 A 276 1.251 1.96 49.7 113 0.510 85 0.382 56 0.254

STRUT-2716-12 A 533 2.413 1.34 34.1 318 1.439 238 1.079 159 0.718

STRUT-1316 B2B-12 B 255 1.122 2.18 55.4 94 0.412 70 0.309 47 0.206


144
3,658
(12)
STRUT-158 B2B-12 B 829 3.646 1.09 27.6 609 2.681 457 2.011 305 1.340

STRUT-2716 B2B-12 1,610 7.084 0.76 19.3 1,610 7.084 1,280 5.632 850 3.740

STRUT-1316-14 A 75 0.340 3.76 95.6 16 0.072 - - - -

STRUT-158-14 A 225 1.018 1.98 50.2 91 0.411 68 0.308 46 0.205

STRUT-1316-12 A 75 0.340 5.06 128.6 - - - - - -

STRUT-158-12 A 237 1.072 2.66 67.7 83 0.374 62 0.280 42 0.186

STRUT-2716-12 A 457 2.068 1.82 46.3 234 1.056 175 0.791 117 0.527

STRUT-1316 B2B-12 B 219 0.962 2.97 75.4 69 0.302 52 0.227 - -


168
4,267
(14)
STRUT-158 B2B-12 B 710 3.125 1.48 37.6 448 1.970 336 1.477 224 0.985

STRUT-2716 B2B-12 1,380 6.072 1.03 26.2 1,250 5.500 940 4.136 630 2.772

STRUT-1316-14 A 65 0.291 5.12 130.1 - - - - - -

STRUT-158-14 A 193 0.872 2.69 68.3 67 0.301 50 0.226 33 0.150

STRUT-1316-12 A 53 0.237 10.33 262.5 - - - - - -

STRUT-158-12 A 166 0.749 5.44 138.1 41 0.181 - - - -

STRUT-2716-12 A 320 1.445 3.72 94.6 114 0.515 86 0.385 57 0.255

STRUT-1316 B2B-12 B 153 0.673 6.06 153.9 - - - - - -


240
6,096
(20)
STRUT-158 B2B-12 B 497 2.188 3.02 76.8 219 0.965 165 0.724 110 0.483

STRUT-2716 B2B-12 960 4.224 2.09 53.1 610 2.684 460 2.024 310 1.364

STRUT-1316-14 A 45 0.203 10.45 265.5 - - - - - -

STRUT-158-14 A 135 0.609 5.49 139.5 33 0.146 - - - -

1 Based on simple beam condition using an AISI allowable design stress of 25000 psi (172 Mpa) about the x-axis with adequate lateral bracing.
2 Refer to section 4.1 page 78, for different load and support condition reduction factors and 4.1 pages 83-86, for column loading data.
3 The strut member weight must be subtracted from the Allowable Uniform Load.
4 Beam load values are listed for solid strut. For pierced strut multiply the beam load by the following factor:
"
'PSYQJFSDFETUSVUNVMUJQMZUIFCFBNMPBECZ
#
'PSUFMFDPNYQJFSDFETUSVUNVMUJQMZUIFCFBNMPBECZ

82 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

Loading conditions for columns

The column loading data tables of section 4.1.4.4 reference this table for determining K. Where the slenderness ratio (K*L/r)
exceeds 200 no value is given and “-“ is denoted. Load values are based on concentric loading.

F F F F F

Approximates values of effective


length factor, K

Support Condition Rotation fixed and Rotation free and Rotation free and Rotation fixed and Rotation fixed and
translation fixed on translation fixed at the translation fixed at translation free at the translation free at the
both ends. top and rotation fixed both ends. top and rotation fixed top and rotation free
and translation fixed and translation fixed and translation fixed
at the base. at the base. at the base.
Theoretical K value 0.5 0.7 1.0 1.0 2.0
Recommended design value when
0.65 0.8 1.0 1.2 2.0
ideal conditions are approximated

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 83
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

Column loading data


Maximum Column Load at C.G.
Unbraced
Column Loading Data Height
K=0.65 K=0.80 K=1.0 K=1.2

in. (ft) mm lb kN lb kN lb kN lb kN

1316-12 6,769 30.7 6,769 30.7 6,769 30.7 6,769 30.7

158-12 11,298 51.2 11,298 51.2 11,298 51.2 11,298 51.2

2716-12 15,073 68.4 15,073 68.4 15,073 68.4 15,073 68.4

24
1316-12 B2B 610 14,368 65.2 14,368 65.2 14,368 65.2 14,368 65.2
(2)

158-12 B2B 21,973 99.7 21,973 99.7 21,973 99.7 21,973 99.7

1316-14 5,351 24.3 5,351 24.3 5,351 24.3 5,351 24.3

158-14 8,704 39.5 8,704 39.5 8,704 39.5 8,704 39.5

1316-12 5,455 24.7 4,443 20.1 3,292 14.9 2,466 11.2

158-12 10,662 48.4 10,167 46.1 9,406 42.7 8,522 38.6

2716-12 14,388 65.3 13,874 62.9 13,110 59.5 12,231 55.5

36
1316-12 B2B 914 13,110 59.5 12,054 54.7 10,417 47.2 8,702 39.5
(3)

158-12 B2B 20,931 94.9 20,142 91.3 18,961 86.0 17,598 79.8

1316-14 4,394 19.9 3,633 16.5 2,729 12.4 2,060 9.3

158-14 8,231 37.3 7,864 35.7 7,302 33.1 6,650 30.2

1316-12 4,024 18.2 2,982 13.5 2,063 9.4 - -

158-12 9,927 45.0 9,124 41.4 7,881 35.7 6,579 29.8

2716-12 13,631 61.8 12,830 58.2 11,579 52.5 10,156 46.1

48
1316-12 B2B 1,219 11,533 52.3 9,841 44.6 7,639 34.6 5,873 26.6
(4)

158-12 B2B 19,767 89.6 18,528 84.0 16,588 75.2 14,406 65.3

1316-14 3,309 15.0 2,480 11.2 1,728 7.8 1,256 5.7

158-14 7,686 34.9 7,094 32.2 6,173 28.0 5,193 23.6

84 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

Column loading data


Maximum Column Load at C.G.
Unbraced
Column Loading Data Height
K=0.65 K=0.80 K=1.0 K=1.2

in. (ft) mm lb kN lb kN lb kN lb kN

1316-12 2,911 13.2 2,063 9.4 - - - -

158-12 9,052 41.1 7,881 35.7 6,268 28.4 4,893 22.2

2716-12 12,758 57.9 11,579 52.5 9,788 44.4 8,006 36.3

60
1316-12 B2B 1,524 9,697 44.0 7,639 34.6 5,509 25.0 4,072 18.5
(5)

158-12 B2B 18,416 83.5 16,588 75.2 13,850 62.8 11,210 50.8

1316-14 2,422 11.0 1,728 7.8 - - - -

158-14 7,041 31.9 6,173 28.0 4,956 22.5 3,893 17.7

1316-12 2,155 9.8 - - - - - -

158-12 8,043 36.5 6,579 29.8 4,893 22.2 3,673 16.7

2716-12 11,747 53.3 10,156 46.1 8,006 36.3 6,214 28.2

72
1316-12 B2B 1,829 7,895 35.8 5,873 26.6 4,072 18.5 2,954 13.4
(6)

158-12 B2B 16,847 76.4 14,406 65.3 11,210 50.8 8,630 39.1

1316-14 1,804 8.2 1,256 5.7 - - - -

158-14 6,294 28.5 5,193 23.6 3,893 17.7 2,934 13.3

1316-12 1,646 7.5 - - - - - -

158-12 6,980 31.7 5,404 24.5 3,847 17.4 2,826 12.8

2716-12 10,612 48.1 8,698 39.4 6,481 29.4 4,870 22.1

84
1316-12 B2B 2,134 6,371 28.9 4,578 20.8 3,107 14.1 - -
(7)

158-12 B2B 15,101 68.5 12,225 55.4 9,010 40.9 6,732 30.5

1316-14 1,382 6.3 - - - - - -

158-14 5,497 24.9 4,290 19.5 3,072 13.9 2,263 10.3

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 85
Hilti MI/MQ Technical Guide

4.1 Hilti Strut

Column loading data


Maximum Column Load at C.G.
Unbraced
Column Loading Data Height
K=0.65 K=0.80 K=1.0 K=1.2

in. (ft) mm lb kN lb kN lb kN lb kN

1316-12 - - - - - - - -

158-12 5,968 27.1 4,437 20.1 3,075 13.9 2,231 10.1

2716-12 9,420 42.7 7,358 33.4 5,272 23.9 3,885 17.6

96
1316-12 B2B 2,438 5,173 23.5 3,641 16.5 - - - -
(8)

158-12 B2B 13,299 60.3 10,269 46.6 7,298 33.1 5,357 24.3

1316-14 - - - - - - - -

158-14 4,725 21.4 3,536 16.0 2,461 11.2 1,788 8.1

1316-12 - - - - - - - -

158-12 5,078 23.0 3,673 16.7 2,503 11.4 - -

2716-12 8,261 37.5 6,214 28.2 4,339 19.7 3,158 14.3

108
1316-12 B2B 2,743 4,252 19.3 2,954 13.4 - - - -
(9)

158-12 B2B 11,582 52.5 8,630 39.1 5,990 27.2 4,347 19.7

1316-14 - - - - - - - -

158-14 4,037 18.3 2,934 13.3 2,006 9.1 - -

1316-12 - - - - - - - -

158-12 4,331 19.6 3,075 13.9 - - - -

2716-12 7,204 32.7 5,272 23.9 3,619 16.4 - -

120
1316-12 B2B 3,048 3,543 16.1 - - - - - -
(10)

158-12 B2B 10,047 45.6 7,298 33.1 4,986 22.6 - -

1316-14 - - - - - - - -

158-14 3,453 15.7 2,461 11.2 - - - -

86 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQK Brackets
Product Features

Ƚ$QSPՐMFXJUITFSSBUFEFEHFTGPSJODSFBTFEIPME

Ƚ*OTUBMMBUJPOBTTJTUFECZEJNFOTJPONBSLJOH

Ƚ4MPUUFEGPSHSFBUFSՑFYJCJMJUZ

Ƚ#BDLUPCBDLCSBDLFUTXFMEFEBMMBSPVOE

.BUFSJBM4QFDJՐDBUJPOT

Materials Carbon steel, S 235 JR (DIN EN 10025), ASTM A283 (D)


Stainless steel, 1.4571 (316 Ti)
Finishes Electro-galvanized
Hot-dipped galvanized, min. 2.2 mil (56 μm)

˕
Ordering Information
MQK-21
Strut Length Strut Length Strut Section Weight per Item No. ˖
Description (in) (mm) (ga/mm) piece (lb) Qty Single piece

MQK-21/300 ˕ 11-13/16 in 300 14/2 1.48 1 00369607


MQK-21/450 ˕ 17-11/16 in 450 14/2 1.96 1 00369608

MQK-41/3
Strut Length Strut Length Strut Section Weight per Item No.
Description (in) (mm) (ga/mm) piece (lb) Qty Single piece

MQK-41/3/300 ˕ 11-13/16 in 300 12/3 2.62 1 00370595


3/8"
˗
MQK-41/3/600 ˕ 23-5/8 in 600 12/3 4.54 1 00370597 17-11/16" , 23-5/8"

13/16" x 9/16"

MQK-41/600-F HDG ˖ 23-5/8 in 600 14/2 3.46 1 00304117


MQK-41/600-R SS316 Ti ˖ 23-5/8 in 600 14/2 3.46 1 00304007 4-3/4"
6-1/2"
˘
MQK-72
2-3/8"
Strut Length Strut Length Strut Section Weight per Item No.
Description (in) (mm) (ga/mm) piece (lb) Qty Single piece

MQK-72/600 ˗ 23-5/8 in 600 12/2.75 6.90 1 00369616

MQK-21D (Double)
Strut Length Strut Length Strut Section Weight per Item No.
Description (in) (mm) (ga/mm) piece (lb) Qty Single piece ˙
MQK-21D/600 ˘ 23-5/8 in 600 14/2 4.83 1 00369619

MQK-41D (Double)
Strut Length Strut Length Strut Section Weight per Item No.
Description (in) (mm) (ga/mm) piece (lb) Qty Single piece

MQK-41D/1000-F HDG ˙ 39-3/8 in 1000 14/2 11.20 1 00304127


MQK-41D/750-R SS316 Ti ˙ 29-1/2 in 750 14/2 6.02 1 00304009

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 87
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQK Brackets
Technical Data — Allowable Loads
F1 F1
F1 = w x L
1/2 1/2

F1 F1 F1
Bracket Steel1 Fastener2 Steel1 Fastener2 Steel1 Fastener2
(continued below) L (in.) L (mm) lb N lb N lb N lb N lb N lb N
MQK-21/300 11-13/16 300 205 910 205 910 240 1070 240 1070 75 335 75 335
MQK-21/450 17-11/16 450 90 400 90 400 140 625 140 625 35 155 35 155
MQK-41/3/300 11-13/16 300 920 4095 735 3270 920 4095 735 3270 460 2045 365 1625
MQK-41/3/600 23-5/8 600 395 1755 365 1625 460 2045 365 1625 145 645 145 645
MQK-72/600 23-5/8 600 1025 4560 645 2870 1025 4560 645 2870 510 2270 320 1425
MQK-21 D/600 23-5/8 600 280 1245 280 1245 340 1510 340 1510 105 465 105 465

F2 F2 F3 F3 F3
1/3 1/3 1/3 1/4 1/4 1/4 1/4

F2 F3

Bracket Steel1 Fastener2 Steel1 Fastener2


(continued from below) L (in.) L (mm) lb N lb N lb N lb N
MQK-21/300 11-13/16 300 120 535 120 535 80 355 80 355
MQK-21/450 17-11/16 450 60 265 60 265 35 155 35 155
MQK-41/3/300 11-13/16 300 460 2045 365 1625 305 1355 245 1090
MQK-41/3/600 23-5/8 600 230 1025 180 800 150 665 120 535
MQK-72/600 23-5/8 600 510 2270 320 1425 340 1510 215 955
MQK-21 D/600 23-5/8 600 170 755 170 755 110 490 110 490
1 Loading capacity of bracket (steel load capacity)
 -PBEJOHDBQBDJUZPGCSBDLFUGBTUFOFEUPDPODSFUFXJUI,#Y XJUIBOFNCFENFOUEFQUIPGVTJOH"4%BMMPXBCMFMPBEWBMVFT

Ƚ 5IFMPBETBQQMZPOMZXIFOTUSVUPQFOJOHQPJOUJOHVQXBSETPSEPXOXBSET
Ƚ 5IFCSBDLFUȵTPXOXFJHIUIBTCFFOBDDPVOUFEGPS
Ƚ $PODSFUFTUSFOHUINJOJNVNQTJ
Ƚ 'BTUFOFSMPBETCBTFEPOOPFEHFEJTUBODFPSBODIPSTQBDJOHFGGFDUT3FGFSFODF7PM)JMUJ"ODIPSJOH5FDIOJDBM(VJEFGPSEFUBJMT
Ƚ &OHJOFFSPGSFDPSEJTSFTQPOTJCMFGPSWFSJGZJOHTVJUBCJMJUZPGUIFDPNQPOFOUT DPOOFDUJPO BODIPSTFMFDUJPOBOECBTFNBUFSJBMGPSBOZTQFDJՐDBQQMJDBUJPO
Ƚ 5IFBQQMJDBUJPOHVJEFMJOFTBQQMJDBCMFUPUIFBODIPSNVTUCFPCTFSWFE3FGFSFODF7PM)JMUJ"ODIPSJOH5FDIOJDBM(VJEF
Ƚ -PBEWBMVFTGPSTUFFMBSFCBTFEPOUIFMFTTFSPGBMMPXBCMFTUSFTT  QTJ PSBEFՑFDUJPOMJNJUPG-BUUIFPVUFSNPTUMPBEJOHQPJOU

88 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQK Angle brace


Product Features ℓ
2-15/16"
Ƚ$POTUSVDUJPOPGXBMMCSBDLFUT

Ƚ&BTJMZDVTUPNJ[FETUBOEBMPOFDPOTUSVDUJPO 7/16"

Ƚ5XPIPMFBOHMFCBTFGPS.2/QVTICVUUPO

Ƚ$IBOOFMBTTFNCMZJOUXPQPTJUJPOTQPTTJCMF

.BUFSJBM4QFDJՐDBUJPOT

Materials Carbon steel, S 235 JR (DIN EN 10025), ASTM A283 (D)


Stainless steel , 1.4571 or 1.4404, (316 Ti or 316 L)
A
H
Material width  NN

Material thickness PS NNPSNN

Finishes Electro-galvanized

1-5/16"

Ordering Information 9/16"


MQK-Angle Brace 1-9/16"
Description A in. (mm) H in. (mm) ɏJO NN

1
ƈ Qty Item No.

MQK-SK (short brace) 14 (355) 13 (328) 12-13/16 (324) 45° 10 00369622
MQK-SL (long brace) 25 (635) 20-7/8 (528) 20-1/2 (524) 45° 10 00369621
MQK-SL-R (SS316 - long brace) 25 (635) 20-7/8 (528) 20-1/2 (524) 45° 10 00304010
ɏMFOHUIEPFTOPUJODMVEFCBTFQMBUFUIJDLOFTTPG.2,#SBDLFU

Technical Data — Allowable Loads2

ℓ/2
F1 F1 F1
ℓ ℓ+ 3"

3"

Angle Bracket Strut Length F1 F1 F1


Bracket
Brace L (in.) L (mm) lb N lb N lb N
MQK-41/3/600 MQK-SL 23-5/8 600 1010 4500 785 3500 450 2000
MQK-72/600 MQK-SL 23-5/8 600 1350 6000 785 3500 560 2500
MQK-21 D/600 MQK-SL 23-5/8 600 785 3500 785 3500 335 1500
2 Loading values based on brackets and braces adequately fastened to a base material, other components must be evaluated separately.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 89
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQN Pushbutton (Connector)


Product Features

Ƚ0OFQBSUGBTUFOFSSFQMBDFTBTQSJOHOVU CPMUBOEXBTIFS
Ƚ3FNPWBCMFBOESFVTBCMF
Ƚ6OJWFSTBMȱPOF.2/1VTICVUUPOՐUTBMM)JMUJTUSVUQSPՐMFT

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Bolt M10 grade 8.8 as per DIN ISO_898 (ASTM A325)
8JEUIBDSPTTՑBUT Ɉ NN

Nut C4C as per DIN EN 10 263


Plate S 235 JR (DIN EN 10025), ASTM A283 (D)
Galvanizing Electro-galvanized
Hot-dip galvanized, min. 2.2 mil (56 μm) (HDG)
Material Stainless steel
Bolt M10 grade A4-70 as per DIN EN ISO 3506-1
8JEUIBDSPTTՑBUT 
NN 

Nut 1.4581 as per DIN EN 10 283 (316)


Plate 1.4401 (A4) as per DIN 17 440 (316)

Ordering Information
Description Weight/Piece (lb) Qty Item No.

MQN 0.145 50 00369623


MQN-F (HDG) 0.185 50 00387779
MQN-R (SS316) 0.170 25 00304012

Technical Data
Allowable Loads2
Shear single fastening Shear double fastening Tightening Torque
Tension (lb) (lb)1 (lb)1 MD (ft-lb)
Item 12 ga 14 ga 12 ga or 14 ga
MQN 1800 1120 1125 2025 30
MQN-F (HDG) 1800 1120 400 670 30
MQN-R (SS) 1800 1120 1125 2025 30
4IFBSMPBEJOHBQQMJFTUP)JMUJTFSSBUFETUSVU$POUBDU)JMUJGPSMPBEJOHJOGPSNBUJPOXIFOVTJOH)JMUJ1VTICVUUPOTJOOPOTFSSBUFETUSVUQSPՐMFT
2 Based on a safety factor of 2.2.

Installation Instructions
MQN and MQN-F Pushbuttons
1 2 3

Put in position. Press and turn. 5JHIUFOVTJOH


socket.
MQN-R Pushbutton

90 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQN Wing Nut


Product Features

Ƚ"MUFSOBUJWFUPTQSJOHOVU

Ƚ'BTU FBTZJOTUBMMBUJPOJOBMMTUSVUQSPՐMFT

Ƚ&MJNJOBUFTTUPDLJOHPGTQSJOHOVUTGPSFBDIEFQUIPGTUSVU

.BUFSJBM4QFDJՐDBUJPOT

Materials Carbon steel QS & E 380 TM SEW 92


Stainless steel (316) DIN EN 10283 (SS)
Plastic
Finishes Electro-galvanized
Hot-dipped galvanized, min. 2.2 mil (56 μm) (HDG)
ASTM A153 (HDG)

Ordering Information
Description Connection Thread Weight/Piece (lb) Qty Item No.

MQM-F 1/4"  0.077 50 00377881


MQM-F 1/4"-R (SS316)  0.060 25 00304018
MQM-F 3/8"  0.075 50 00377882
MQM-F 3/8"-F (HDG)  0.080 25 00304136
MQM-F 3/8"-R (SS316)  0.050 25 00304019
MQM-F 1/2"  0.073 50 00377883
MQM-F 1/2"-F (HDG)  0.080 25 00304137
MQM-F 1/2"-R (SS316)  0.050 25 00304020

Technical Data
Allowable Loads1 Tightening Torque
Tension (lb) Shear (lb)2 MD (ft-lb) 1/4" Tension

Item 12 ga Finish 3/ "


8 Shear
1/2"
MQM-F 1/4" 755 415 7 PG
MQM-F 1/4"-R (SS) 755 415 7 SS
MQM-F 3/8" 1800 1125 15 PG
MQM-F 3/8"-F (HDG) 1800 400 30 HDG
MQM-F 3/8"-R (SS) 1800 1125 15 SS
MQM-F 1/2" 1800 1125 30 PG
MQM-F 1/2"-F (HDG) 1800 400 30 HDG
MQM-F 1/2"-R (SS) 1800 1125 30 SS
#BTFEPOBTBGFUZGBDUPSPGXIFOVTFEXJUIHVBHFTFSSBUFETUSVUQSPՐMF
$POUBDU)JMUJGPSMPBEJOHEBUBXIFOVTJOH)JMUJ.2.'GBTUFOFSTJOOPOTFSBUFETUSVUQSPՐMFT

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 91
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

Spring Nuts and Channel Nuts


Product Features ࠧ ࠨ

Ƚ4QSJOHOVUTBOEDIBOOFMOVUTBSFGPSVTFJOTUSVU

.BUFSJBM4QFDJՐDBUJPOT

Materials Carbon steel


Finishes Electro-galvanized

Ordering Information
Description Qty Item No.

1/4" Spring Nut ࠧ 100 00258246


3/8" Spring Nut ࠧ 100 00258247
1/2" Spring Nut ࠧ 100 00258248
3/8" Channel Nut ࠨ 100 00311937
1/2" Channel Nut ࠨ 100 00311938
5/8" Channel Nut ࠨ 100 00311939
3/4" Channel Nut ࠨ 100 00311940

Technical Data
Allowable Loads1
Item Tension Shear Bolt Torque
(lbs) (lbs) (ft-lbs)
1/4" Spring Nut 450 300 6
3/8" Spring Nut 1100 800 19
1/2" Spring Nut 2000 1500 50
3/8" Channel Nut 1100 800 19
1/2" Channel Nut 2000 1500 50
5/8" Channel Nut 2000 1500 100
3/4" Channel Nut 2000 1500 125
1 Based on a safety factor of 3.

92 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQA Saddle Nut


Product Features

Ƚ"TJOHMFQBSUSFQMBDJOHTQSJOHOVUTBOECBTFQMBUFT

Ƚ'PSBMMTUSVUQSPՐMFT

.BUFSJBM4QFDJՐDBUJPOT

Materials Carbon steel QS & E 380 TM SEW 92


Stainless steel (316) DIN EN 10283 (SS)
Plastic
Finishes Electro-galvanized
Hot-dipped galvanized, min. 2.2 mil (56 μm) (HDG)
ASTM A153 (HDG)

Ordering Information
Description Connection Thread Weight/Piece (lb) Qty Item No.

MQA-F 1/4"  0.194 50 00377884


MQA-F 1/4"-R (SS316)  0.190 25 00401397
MQA-F 3/8"  0.192 50 00377885
MQA-F 3/8"-F (HDG)  0.192 25 00304143
MQA-F 3/8"-R (SS316)  0.180 25 00401398
MQA-F 1/2"  0.183 50 00377886
MQA-F 1/2"-F (HDG)  0.183 25 00304144
MQA-F 1/2"-R (SS316)  0.160 25 00401399
MQA-F 5/8"  0.185 50 00377887
MQA-F 5/8"-F (HDG)  0.185 25 00304145
MQA-F 5/8"-R (SS316)  0.170 25 00401400

Technical Data
Allowable Loads1 Tightening Torque
Tension (lb) Shear (lb)2 MD (ft-lb)
Item 12 ga Finish
1/4"
MQA-F 1/4" 755 415 7 PG
3/8" Tension
MQA-F 1/4"-R (SS) 755 415 7 SS
1/2" Shear
MQA-F 3/8" 1800 1125 15 PG
5/8"
MQA-F 3/8"-F (HDG) 1800 400 15 HDG
MQA-F 3/8"-R (SS) 1800 1125 15 SS
MQA-F 1/2" 1800 1125 30 PG
MQA-F 1/2"-F (HDG) 1800 400 30 HDG
MQA-F 1/2"-R (SS) 1800 1125 30 SS
MQA-F 5/8" 2100 1125 30 PG
MQA-F 5/8"-F (HDG) 2100 400 30 HDG
MQA-F 5/8"-R (SS) 2100 1125 30 SS
#BTFEPOBTBGFUZGBDUPSPSXIFOVTFEXJUI)JMUJHBVHFTFSSBUFETUSVUQSPՐMF
$POUBDU)JMUJGPSMPBEJOHEBUBXIFOVTJOHGBTUFOFSTJOOPOTFSBUFETUSVUQSPՐMFT

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 93
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

Hilti 3-D System Connectors


Product Features

Ƚ6OJWFSTBM GFXQBSUTGPSBMMBQQMJDBUJPOT
Ƚ2VJDLBOEFBTZUPVTF
ȽpBOHMFBOECSBDJOHXJUIQSFEFUFSNJOFECFOEJOHQPJOU
Ƚ'PSJOTUBMMBUJPOPGBOHMFTPSDPOOFDUPSTPOTJUF

.BUFSJBM4QFDJՐDBUJPOT

Materials Carbon steel


Materials Thickness  NN

Finishes Electro-galvanized
Tightening Torque 30 ft-lb (40 Nm)
2-3/8"
˕ 3-9/16" ˖

Ordering Information
Description Threaded Rod Weight/Piece (lb) Qty Item No.
1"
Diameter

MQ3D-B 3D Base Connector ˕ - 0.454 20 00369694 7/ "


8
˗ ˘
MQ3D-W90° 3D 90° Connector ˖ - 0.467 20 00369695 1-15/16"
1-15/16"
MQ3D-W45° 3D 45° Connector 1, 2
˗ - 0.337 16 00369696
45° 45°
MQ3D-A 3D Threaded Rod Brace1, 2 ˘  0.209 20 00369697
.BZCFCFOUPODFUPBEKVTUBOHMF 1-3/16
1"

2 Pre-assembled bolts may be removed and replaced with an anchor or longer 3/8 bolt when mounting to surface other than the 3D
Base Connector.
3 Based on a safety factor of 2.2.

Technical Data — Allowable Loads3


˕&˖
˖
˕
F = 560 Ib

F = 1125 lb

˕&˗ Tension/compression bracing


F = 560 Ib

˗
Variable angle

F = 1125 lb

˗ Directly to strut

fastened to strut with


– MQZ-L3/8" base plate
– 3/8"-1" (min.) hex. bolt F = 560 Ib
– MQM-F3/8" strut nut
F = 1000 Ib Variable angle

˕&˘
Tension bracing
˗ See Note 2
F = 560 Ib

Variable
˕ F = 1125 lb angle

See Note 2
˕
˘ Directly to strut

˘ fastened to strut with


– MQZ-L3/8" base plate F = 560 Ib
– 3/8"-1" (min.) hex. bolt
EJBNFUFSSPE See Note 2 – MQM-F3/8" strut nut Variable angle
˘ F = 1000 Ib

94 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQW-Q2 Angle Pre-assembled 90°


Product Features

Ƚ)FMQTSFEVDFJOWFOUPSZDPTUT

Ƚ'
 BTUBOEFBTZJOTUBMMBUJPOIFMQTDPNQMFUFKPCTNPSFRVJDLMZ
to reduce labor costs

Ƚ4JOHMFJUFNpDPOOFDUJPOȱOPMPTUQBSUT

Ƚ'JUTBMM)JMUJTUSVU

Ƚ6UJMJ[FT)JMUJ1VTICVUUPOUFDIOPMPHZ

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Electro-galvanized
Tightening torque 30 ft-lb (40 Nm)
Material thickness  NN

8JEUIBDSPTTՑBUT  NN

Ordering Information
Description Weight/Piece (lb) Qty Item No.

MQW-Q2 90° Angle 0.441 20 00369655

Technical Data — Allowable Loads1

2-3/16"

2-3/16"

1 Based on safety factor of 2.2

Installation Instructions
1 2

Press and turn. 5JHIUFOVTJOHTPDLFU

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 95
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQW Angles
Product Features

Ƚ)FMQTSFEVDFJOWFOUPSZDPTUT

Ƚ'BTUBOEFBTZJOTUBMMBUJPOIFMQTDPNQMFUFKPCTNPSFRVJDLMZ
to reduce labor costs

Ƚ4JOHMFJUFNpDPOOFDUJPOȱOPMPTUQBSUT

Ƚ'JUTBMM)JMUJTUSVU

Ƚ6UJMJ[FT)JMUJ1VTICVUUPOUFDIOPMPHZ

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Stainless Steel 1.4571 or 1.4404 (316 Ti or 316 L)
Material thickness  NN

Finish Electro-galvanized
Hot-dipped galvanized, min. 2.2 mil (56 μm),
DIN EN ISO 1461, ASTM A153

˕ ˖ ˗
Ordering Information
Description Weight/Piece (lb) Qty Item No.
2-3/8"
MQW-3 Three Hole 90° ˕ 0.353 20 00369656 4-3/8"

MQW-3-F Three Hole 90° (HDG) ˕ 0.353 20 00304172 2-3/16"


4-1/8"

MQW-3-R Three Hole 90° (SS316) ˕ 0.353 10 00304052


MQW-4 Four Hole 90° ˖ 0.485 10 00369658
MQW-8/90° Eight Hole 90° ˗ 0.926 10 00369659 ˚
˘ ˙
MQW-8/90°-F Eight Hole 90° (HDG) ˗ 0.926 10 00304175
MQW-8/90°-R Eight Hole 90° (SS316) ˗ 0.926 10 00304055
2-3/16"
MQW-3/45° Three Hole 45° ˘ 0.342 20 00369657 45°
MQW-3/45°-R Three Hole 45°(SS316) ˘ 0.342 10 00304053 4-3/16"

MQW-8/45° Eight Hole 45° ˙ 0.904 10 00369660


MQW-S/1 Single Brace Angle Bracket ˚ 1.014 10 00369664
˛ 7-7/8"
MQW-S/2 Double Brace Angle Bracket ˛ 2.602 10 00369665

7-7/8"

3-15/16"

9/ "
16

Technical Data Allowable Loads1


˕MQW-3 ˗MQW-8/90° ˙MQW-8/45° ˚MQW-S1 ˛MQW-S2
F = 1530 lb F = 560 lb F = 2025 lb F = 1125 lb F = 450 lb F = 675 lb
F = 450 lb F = 675 lb

F = 1800 lb F = 1125 lb F = 2025 lb F = 1350 lb


˖MQW-4 ˘MQW-3/45°
F = 1125 lb F = 830 lb

F = 450 lb F = 675 lb F = 900 lb F = 1350 lb

1 Loads based on safety factor of 2.2

96 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQV Connectors
Product Features

Ƚ)FMQTSFEVDFJOWFOUPSZDPTUT

Ƚ'
 BTUBOEFBTZJOTUBMMBUJPOIFMQTDPNQMFUFKPCTNPSFRVJDLMZ
to reduce labor costs

Ƚ6UJMJ[FT)JMUJ1VTICVUUPOUFDIOPMPHZ

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Stainless Steel 1.4571 or 1.4404 (316 Ti or 316 L)
Material thickness  NN

Finish Hot-dipped galvanized, min. 2.2 mil (55 μm),


DIN EN ISO 1461, ASTM A153
Electro-galvanized

Ordering Information
Description Weight/Piece (lb) Qty Item No.
˕ ˖
MQV-2/2D ˕ 0.966 10 00369638 Fz 6-1/2" Fz
6-1/2"

MQV-2/2D-R (SS316) ˕ 0.970 10 00304032


Fx Fx
MQV-3/2D ˖ 1.356 10 00369640 4-7/16"
4-7/16"
MQV-3/2D-F (HDG) ˖ 1.327 10 00304152
MQV-3/2D X ˗ 3.245 10 00339590 Fy Fy
MQV-3/3D ˘ 0.994 10 00369641
MQV-4/3D ˙ 1.698 10 00369642
MQV-12 ˚ 1.224 10 00369643 ˗ ˘ 2-3/16"

MQV-12-F (HDG) ˚ 1.285 10 00304155 Fz Fz


10-1/4"

Fx
MQV-12-R (SS316) ˚ 1.224 10 00304037 6-11/16"
Fx
4-7/16"

2"

Fy Fy
Technical Data Allowable Loads3
Description ± Fy (lb) ± Fx (lb) ± Fz (lb)
MQV-2/2D1 Fy + Fx +2025 / -1125 1125 - ˙ ˚
2-3/16"
Fz Fx
MQV-3/2D 2
Fy + Fx +2025 / -1575 1125 - 8-1/16"

MQV-3/2D X2 Fy + Fx +2025 / -2025 1125 - Fx


1-3/4"

MQV-3/3D 1
Fy + Fx + Fz 2025 1125 1125 Fz
4-7/16"

MQV-4/3D 1
Fy + Fx + Fx 2025 1125 1125 Fy
MQV-12 Fy + Fx 1800 2025 - Fy
1 Loads are for connections where strut along Fy is continuous through connectors. For other load
conditions, contact Hilti Technical Services.
2 Loads are for connections where strut along Fx is continuous through connectors. For other load
conditions, contact Hilti Technical Services.
3 Based on a safety factor of 2.2.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 97
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQV Flat Connectors


Product Features

Ƚ)FMQTSFEVDFJOWFOUPSZDPTUT

Ƚ'
 BTUBOEFBTZJOTUBMMBUJPOIFMQTDPNQMFUFKPCTNPSFRVJDLMZ
to reduce labor costs

Ƚ6UJMJ[FT)JMUJ1VTICVUUPOUFDIOPMPHZ

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Stainless Steel 1.4404 (316 L)
Material thickness  NN

Finish Hot-dipped galvanized, min. 2.2 mil (55 μm),


DIN EN ISO 1461, ASTM A153
Electro-galvanized

Ordering Information
Description Weight/Piece (lb) Qty Item No.

MQV-P4 Four Hole ˕ 0.415 10 00369644


MQV-P4-F Four Hole (HDG) ˕ 0.415 10 00304156
MQV-P2 Two Hole Tee ˖ 0.220 10 00370630
MQV-T Four Hole Tee ˗ 0.432 10 00369645
MQV-P3 Three Hole Cross ˘ 0.309 10 00370629
MQV-P5 Five Hole Cross ˙ 0.309 10 00370631

˕ 8-1/16"
˖ ˗
1-7/8"
3-3/4"

1-5/8"

˘ ˙

98 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQB Clamps
Product Features

Ƚ7BSJPVTDMBNQTJ[FT

Ƚ4VJUBCMFGPSBMMUIFEJGGFSFOUTUSVUQSPՐMFT

Ƚ6UJMJ[FT)JMUJ1VTICVUUPOUFDIOPMPHZ

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Stainless Steel 1.4404 (316 L)
Material thickness  NN

Finish Hot-dipped galvanized, min. 2.2 mil (55 μm),


DIN EN ISO 1461, ASTM A153
Electro-galvanized

Ordering Information
˕ 6-5/16" ˖ 6-5/16"
Description Weight/Piece (lb) 4USVU1SPՐMF Qty Item No.
4-3/16" 4-3/16"

MQB-21 ˕ 0.465  10 00369666


MQB-41 ˖ 0.536  10 00369668
MQB-41-R (SS316) ˖ 0.529  10 00304061
MQB-82 ˗ 0.750 #BDLUP#BDL 10 00369671
MQB-82-R (SS316) ˖ 0.750 #BDLUP#BDL 10 00304063
˗ ˘ 9-1/16"
MQB-G41 ˘ 0.807  10 00369674 6-5/16"

MQB-G41-F (HDG) ˘ 0.807  10 00304189 6-5/16"

4-3/16"

7/16" x

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 99
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

MQP / MQV Base Connectors


Product Features

Ƚ"UUBDINFOUTUPXBMMT DFJMJOHT ՑPPST

Ƚ)JHIBQQMJDBUJPOՑFYJCJMJUZ

Ƚ3FMJBCMFBOEFBTZUPVTF

Ƚ6UJMJ[FT)JMUJ1VTICVUUPOUFDIOPMPHZ

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Stainless Steel 1.4571 or 1.4404 (316 Ti or 316 L)
Material thickness  NN

Finish Hot-dipped galvanized, min. 2.2 mil (55 μm),


DIN EN ISO 1461, ASTM A153
Electro-galvanized

Ordering Information
Description Weight/Piece (lb) Qty Item No. ˕ 6-1/2"
˖ ˗
4-7/16"
MQV-2/2D-14 Wall and Ceiling ˕ 0.966 10 00369639 4-1/8"

MQV-2/2D-14-F Wall and Ceiling (HDG) ˕ 0.994 10 00304151


13/ " x 9/ "
16 16
4-7/16" 1/ "
4
13/16" x 9/16"

MQV-2/2D-14-R Wall and Ceiling (SS316) ˕ 0.970 10 00304033 9/ " x 3/ "


16 4
3-1/8"
5-5/16"
7-5/16"

MQP-1/1 Light Duty ˖ 0.243 20 00369646 2-3/8"

MQP-1/1-F Light Duty (HDG) ˖ 0.243 20 00304161 2-3/8"

MQP-21-72 Standard Duty ˗ 2.535 12 00369651


˘ ˙ ˚
MQP-21-72-F Standard Duty (HDG) ˗ 2.535 12 00304165
6"

˗ 2.535 1 00304047
4-3/16"
MQP-21-72-R Standard Duty (SS316) 13/ " x 9/ " 4-1/8"
16 16

MQP-82 1-5/8" Back-to-Back ˘ 4.145 8 00369652 5/ "


16
1-15/16"
45°

MQP-82-R 1-5/8" Back-to-Back (SS316) ˘ 4.145 1 00304048 5-7/8" 9/ "


3-15/16" 7-7/8" 16
2-15/16"

MQP-G Pivot Base ˙ 2.326 10 00369654 2-1/8" 2-15/16"


7-1/2" 1-5/8" 1-5/8"

MQP-45° Base ˚ 0.772 10 00369649


MQP-45°-F Base (HDG) ˚ 0.722 10 00304164

100 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

.24ZTUFN$PNQPOFOUTȢ-PBE%BUBBOE.BUFSJBM4QFDJӏDBUJPOT

Strut Beam Clamps


Product Features

Ƚ'PSGBTUFOJOHTUSVUUPTUFFMCFBNT
˕
Ƚ"MXBZTVTFTUSVUCFBNDMBNQTJOQBJST QPTJUJPOFEPO
PQQPTJUFTJEFTPGUIFCFBNՑBOHF

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Stainless Steel 1.4404 (316 L)
Material thickness  NN

Finish Hot-dipped galvanized, min. 2.2 mil (55 μm),


DIN EN ISO 1461, ASTM A153
Electro-galvanized

Ordering Information
Description Qty Item No.

BC-A Beam Clamp Assembly ˕ 25 00306570


SBC 1-5/8" Strut Beam Clamp ˖ 25 00258316
SBC 2-7/16" to 3-1/4" Strut Beam Clamp ˗ 25 00314330
MQT-21-41-F Beam Clamp (HDG) (1-3/16" to 1-5/8" strut depth) 10 00304190
MQT-21-41-R Beam Clamp (SS316) (1-3/16" to 1-5/8" strut depth) 10 00304067
MQT-52-82-R Beam Clamp (SS316) (1-5/8" to 3-1/4" strut depth) 10 00304068

˕ ˖ ˗

2-3/16"
3/8" ˖TIPXO
3/8"
2-3/16"
˗TJNJMBS
3/16"
3/16"
3"
3"
5"

3-3/8"

Technical Data — Allowable Tensile Loads


Description Fallowable1 (lb) Tightening torque
per pair (ft-lb)
BC-A 1100 min. 5 max. 7.5
SBC 1-5/8" 1200 15
SBC 2-7/16" 1200 15
MQT-21-41 670 15
MQT-52-82 1000 15
1 Based on a safety factor of 3.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 101
Hilti MI/MQ Technical Guide

4.3 MQZ and Accessories

MQZ-L Base Plates


Product Features

Ƚ6TFEBTIFBWZQMBUFXBTIFSGPSTUSVU

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Stainless Steel 1.4404 (316 L)
Material thickness  NN

Finish Hot-dipped galvanized, min. 2.2 mil (55 μm),


DIN EN ISO 1461, ASTM A153
Electro-galvanized

Ordering Information 7/ "


16
9/ "
Description For Thread Weight/Piece (lb) Qty Item No. 16
11/ "
16
MQZ-L 3/8 3/8 0.203 20 00370632
2-1/16"
MQZ-L 3/8-F (HDG) 3/8 0.194 20 00304200 1-13/16"
MQZ-L 3/8-R (SS316) 3/8 0.194 20 00304076 3/ "
16
MQZ-L 1/2 1/2 0.185 20 00370633
MQZ-L 1/2-F (HDG) 1/2 0.185 20 00304201
MQZ-L 1/2-R (SS316) 1/2 0.185 20 00304077
MQZ-L 5/8 5/8 0.176 (80) 20 00370634

MQZ-SS Strut Tie


Product Features

Ƚ'PSVTFSBTTFNCMFECBDLUPCBDLTUSVUT

.BUFSJBM4QFDJՐDBUJPOT

Finish Electro-galvanized

Note: strut side cut away to show fastener

Ordering Information
Weight/
Description Width Across Flats (mm) Piece (lb) Qty Item No. y
MQZ-SS Locking device — For user-assembled 13 mm 0.006 40 00369691
B2B strut, use 13 mm socket to set

Technical Data — Allowable Loads1,2


Fy 675 lb (3.0 kN)
Fx 1125 lb (5.0 kN)
Tightening torque,MD 15ft-lb (20 Nm)
1 Based on a safety factor of 2.2
2 Fy + Fx

102 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

4.3 MQZ and Accessories

MEK Strut End Cap


Product Features

Ƚ'PSVTFXJUIBMM)JMUJTUSVUQSPՐMFT

Ƚ)FMQTQSPUFDUTIBSQFEHFTXIFOIBOEMJOHTUSVU

.BUFSJBM4QFDJՐDBUJPOT

Finish Plastic-Polypropelene (PP)

Ordering Information
Description Qty Item No.- Red Item No. - Gray

MEK - Strut End Cap 50 00244886 00313377

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 103
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.1 Hangers and Insulating Shields


Clevis Hanger SLC Speed Lock
Product Features

Ƚ6OJRVF4QFFE-PDL4ZTUFNNFBOTOPIBOHFSEJTBTTFNCMZ

Ƚ0OFQJFDFFMJNJOBUFTMPTUESPQQFEOVUTBOECPMUT

Ƚ'.BQQSPWFEBOE6- D6-MJTUFE

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Electro-galvanized
Approvals 'BDUPSZ.VUVBM '.
UP
Listings 6OEFSXSJUFST-BCPSBUPSJFTȱ 6-ȰD6-
UP
Conforms with Ƚ'FEFSBMTQFDJՐDBUJPOT88)& 5ZQF

Ƚ.BOVGBDUVSFST4UBOEBSEJ[BUJPO4PDJFUZ
MSS-SP-58 (Type 1)
Installation Install in accordance with MSS-SP-58

Ordering Information
RS MRI Max
Weight/ Pipe Rod Min. Rod Single Bulk Allowable
Description Piece (lb) Size H W CL Size Insertion A S Item No. Item No. Qty Load (lb)1

SLC-EG 2" 0.32        5/16 02008782 03475949 50 610
SLC-EG 2-1/2" 2         02008783 03475950 50 1130
SLC-EG 3" 0.69         02008784 03475951 50 1130
SLC-EG 4" 1.06         02008785 03475952 20 1130
SLC-EG 5" 1.33         02008786 03475953 20 1430
SLC-EG 6" 2.80         02008787 03475954 10 1940
SLC-EG 8" 3.75         02008788 03475955 10 2000

Open Hanger Close Hanger RS

MRI
S A
H CL

1 Maximum allowable loads based on the lower of:


B.BYJNVNTBGFMPBEPGUIFUISFBEFEIBOHFSSPEBUSPEUFNQFSBUVSFPGp'QFS.BOVGBDUVSFSȵT4UBOEBSEJ[BUJPO4PDJFUZ4UBOEBSE1SBDUJDF
b. Allowable load for SLC-EG hanger with a safety factor of 3
c. Industry standard for clevis hangers
W

104 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-SLIS Speed Lock Insulation Shield


Product Features

Ƚ5BCTMPDLJOUP4-$IBOHFSXPOȵUGBMMFWFOXIFOIBOHFSJT
opened

Ƚ1SFHBMWBOJ[FE

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Pre-galvanized

Ordering Information/Technical Data


Material
Length Thickness
Description Designation (in.) (guage Qty Item No.

Speed Lock Insulation Shield 2" .)4-*41( 12 18 50 02008613


Speed Lock Insulation Shield 2-1/2" .)4-*41( 12 18 50 02008614
Speed Lock Insulation Shield 3" .)4-*41( 12 18 25 02008615
Speed Lock Insulation Shield 4" .)4-*41( 12 18 25 02008616
Speed Lock Insulation Shield 5" .)4-*41( 12 18 25 02008617
Speed Lock Insulation Shield 6" .)4-*41( 12 16 10 02008618
Speed Lock Insulation Shield 8" .)4-*41( 12 16 10 02008619

Installation Instructions

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 105
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

Clevis Hanger SDC Standard Duty


Product Features

Ƚ4UBOEBSEEVUZ FMFDUSPHBMWBOJ[FEDMFWJTIBOHFS

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Electro-galvanized
Approvals 'BDUPSZ.VUVBM '.
UP
Listings 6OEFSXSJUFST-BCPSBUPSJFT 6-ȰD6-
UP
Conforms with Ƚ'FEFSBMTQFDJՐDBUJPO88) 5ZQF

Ƚ.BOVGBDUVSFST4UBOEBSEJ[BUJPO4PDJFUZ
MSS-SP-58 (Type 1)
Installation Install in accordance with MSS-SP-58

Ordering Information / Technical Data


Weight/ Pipe Max Allow.
Description Piece (lb) Size RS H CL MRI A Qty Item No. Load (lb)1

SDC-EG 3/4" 0.17       50 00333236 610
SDC-EG 1" 0.19       50 00333237 610
SDC-EG 1-1/4" 0.30       25 00424206 610
SDC-EG 1-1/2" 0.30       25 00333239 610
SDC-EG 2" 0.40       1 00425681 610
SDC-EG 2-1/2" 0.64       25 00333240 1130
SDC-EG 3" 0.72       1 00425682 1130
SDC-EG 4" 1.17       1 00425683 1130
SDC-EG 5" 2.17       1 00424209 1430
SDC-EG 6" 3.32       1 00306594 1940
SDC-EG 8" 4.90       1 00306595 2000
SDC-EG 10" 8.90       1 00424210 3600
SDC-EG 12" 12.00       1 00424211 3800
SDC-EG 14" 14.80       1 00424212 4200
1 Maximum allowable loads based on the lower of:
B.BYJNVNTBGFMPBEPGUIFUISFBEFEIBOHFSSPEBUSPEUFNQFSBUVSFPGp'QFS.BOVGBDUVSFSȵT4UBOEBSEJ[BUJPO4PDJFUZ4UBOEBSE1SBDUJDF
b. Allowable load for SDC-EG hanger with a safety factor of 3
c. Industry standard for clevis hangers

Installation instructions

106 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

SDC Insulation Shields


.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Pre-galvanized

Ordering Information / Technical Data


Weight per
Description ID Guage L Piece (lb) Qty Item No.

Insulation Shield 2"  18  0.70 1 00424197


Insulation Shield 2-1/2"  18  0.84 1 00424198
Insulation Shield 3"  18  1.01 1 00424199
Insulation Shield 4"  16  1.28 1 00424200
Insulation Shield 5"  16  1.60 1 00424202
Insulation Shield 6"  16  1.90 1 00424203
Insulation Shield 8"  16  3.05 1 00424204
Insulation Shield 10"  16  5.63 1 00424205

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 107
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

Loop Hangers
Product Features

.BUFSJBM4QFDJՐDBUJPOT

.BUFSJBMBOEՐOJTI Pre-galvanized carbon steel with zinc-electroplated


insert nut
Approvals Factory Mutual (FM) 1/2 to 8
Listings Underwriters Laboratories (UL–cUL)
Conforms with Ƚ'FEFSBM4QFDJՐDBUJPO88) 5ZQF

Ƚ.BOVGBDUVSFST4UBOEBSEJ[BUJPO4PDJFUZ"/4*
MSS-SP-58 (Type 10)
Installation Install in accordance with ANSI/MSS-SP-58

Ordering Information / Technical Data


Rod Max
Weight/ Pipe Size Allowable
Description Box (lb) Size A B C D Qty Item No. Load (lb)1

LH 1/2" 7      100 00257353 300


LH 3/4" 7      100 00257354 300
LH 1" 8.25      100 00337820 300
LH 1-1/4" 10  3/8    100 00257356 300
LH 1-1/2" 10     1 100 00257357 300
LH 2" 10      100 00257358 300
LH 2-1/2" 30 2-1/2  5-9/16„   100 00257359 525
LH 3" 16    4-5/8  50 00257360 525
LH 4" 16.5      50 00257362 650
LH 6 5      20 00257364 1000
LH 8" 22.5      15 00257365 1000
1 Based on a safety factor of 3.5

108 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.2 Beam Clamps


BC Beam Clamp
Product Features

Ƚ5PTFDVSFUISFBEFESPEJOTUBMMBUJPOTUPTUFFMCFBNT

Ƚ/PESJMMJOHPSXFMEJOHOFDFTTBSZ

Ƚ&BDITFUGPSBOJOTUBMMBUJPOJTDPNQMFUFMZQSFBTTFNCMFEBOE
suits all usual sizes of I-beams

Ƚ'MFYJCJMJUZBOEOPMPTTPGTQBSFQBSUT

.BUFSJBM4QFDJՐDBUJPOT

Material ASTM A536 ductile iron casting with a hardened cup


point set screw and locknut
Finish Plain or electro-galvanized
Approvals 'BDUPSZ.VUVBM '.
UISPVHI
Listings 6OEFSXSJUFST-BCPSBUPSJFT 6-ȰD6-
UISPVHI
Conforms with Ƚ'FEFSBMTQFDJՐDBUJPO88) 5ZQF

Ƚ.BOVGBDUVSFST4UBOEBSEJ[BUJPO4PDJFUZ
MSS-SP-58 (Type 19)
Installation Install in accordance with ANSI/MSS-SP-58
Note: Set screw must be tightened onto the sloped side of the I-Beam, channel or angle iron
ՑBOHF3FRVJSFEUPSRVFWBMVFTGPSUIFTFUTDSFXBSFBTTIPXOJOUIFUBCMF

Ordering Information / Technical Data


Maximum Allowable
Min. Max. Load (lb)2
Set-Screw Set-Screw Max.
Description Torque Torque Rod Pipe Box Item No. Top Bottom
(ft-lb)1 (ft-lb)1 Size Size Qty Flange Flange

BC 3/8" 5.0 7.5   100 00257366 500 250


BC 1/2" 5.0 7.5 1/2  50 00257367 950 760
BC 5/8" 10.0 15.0   50 00257368 950 760
BC 3/4" 10.0 15.0   50 00257369 950 760
BC-EG 1/4" 3.5 5.0  - 100 00258002 250 100
BC-EG 3/8" 5.0 7.5   100 00306600 500 250
BC-EG 1/2" 5.0 7.5   50 00306601 950 760
CAUTION! Correct torquing is essential for proper clamp performance
1 Note: In the absence of a torque wrench:
.*/*.6.5IFTFUTDSFXTIPVMECFՐOHFSUJHIUFOFEUPUIF*#FBNBOEUIFOBOBEEJUJPOBMPOFUIJSEUVSOBQQMJFEUPUIF
set-screw
."9*.6.5IFTFUTDSFXTIPVMECFՐOHFSUJHIUFOFEUPUIF*#FBNBOEUIFOBOBEEJUJPOBMPOFIBMGUVSOBQQMJFEUPUIF
set-screw
2 Based on a safety factor of 3.5

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 109
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

BC-WM Wide Mouth Beam Clamp


Product Features

.BUFSJBM4QFDJӏDBUJPOT

Material ASTM A536 ductile iron casting with a hardened cup


point set screw and locknut
"MUFSOBUFՐOJTI Electro-galvanized
Approvals Factory Mutual (FM)
Listings Underwriters Laboratories (UL– cUL)
Conforms with Ƚ'FEFSBMTQFDJՐDBUJPO88) 5ZQF

Ƚ.BOVGBDUVSFST4UBOEBSEJ[BUJPO4PDJFUZ
MSS-SP-58 (Type 19)
Installation Install in accordance with ANSI/MSS-SP-58
Note: Set screw must be tightened onto the sloped side of the I-Beam, channel or angle iron
ՑBOHF3FRVJSFEUPSRVFWBMVFTGPSUIFTFUTDSFXBSFBTTIPXOJOUIFUBCMF

Ordering Information / Technical Data


Maximum Allowable Load (lb)2

Description Torque (ft-lb) 1


Rod Size Max. Pipe Size Box Qty Item No. Top Flange Bottom Flange

BC-WM 3/8" 5.0   50 00306602 500 250


BC-WM 1/2" 10.0   50 00306603 950 760
CAUTION! Correct torquing is essential for proper clamp performance
1 Note: In the absence of a torque wrench:
.*/*.6.5IFTFUTDSFXTIPVMECFՐOHFSUJHIUFOFEUPUIF*#FBNBOEUIFOBOBEEJUJPOBMPOFUIJSEUVSOBQQMJFEUPUIFTFUTDSFX
."9*.6.5IFTFUTDSFXTIPVMECFՐOHFSUJHIUFOFEUPUIF*#FBNBOEUIFOBOBEEJUJPOBMPOFIBMGUVSOBQQMJFEUPUIFTFUTDSFX
2 Based on a safety factor of 3.5

Steel C-Clamp with Lock Nut


Product Features

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel with hardened steel cup point set screw
and lock nut
Approvals Factory Mutual (FM)
Listings Underwriters Laboratories (UL)
Conforms with Ƚ'FEFSBMTQFDJՐDBUJPO88) 5ZQF

Ƚ.
 BOVGBDUVSFST4UBOEBSEJ[BUJPO4PDJFUZ
MSS-SP-58 (Type 23)
Installation Install in accordance with ANSI/MSS-SP-58
Note: Set screw must be tightened onto the sloped side of the I-Beam, channel or angle iron
ՑBOHF3FRVJSFEUPSRVFWBMVFTGPSUIFTFUTDSFXBSFBTTIPXOJOUIFUBCMF

Ordering Information / Technical Data


Minimum Maximum
Torque1 Rod NFPA2 Max. MSS=SP-59 Rod Allowable
Description (ft-lb) Size Pipe Size Max.Pipe Size Insertion W Qty Item No. Load (lb)4

C-Clamp w/ Lock Nut 3/8" 5.0      100 00306571 400
C-Clamp w/ Lock Nut 1/2" 10.4      50 00306572 755
CAUTION! Correct torquing is essential for proper clamp performance
1 Note: In the absence of a torque wrench:
.*/*.6.5IFTFUTDSFXTIPVMECFՐOHFSUJHIUFOFEUPUIF*#FBNBOEUIFOBOBEEJUJPOBMPOFUIJSEUVSOBQQMJFEUPUIFTFUTDSFX
."9*.6.5IFTFUTDSFXTIPVMECFՐOHFSUJHIUFOFEUPUIF*#FBNBOEUIFOBOBEEJUJPOBMPOFIBMGUVSOBQQMJFEUPUIFTFUTDSFX
2 Per NFPA section 9.1.2, table 9.1.2.1
3 Per MSS-SP-58 section 9, table 4
4 Based on a safety factor of 3

110 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.3 Split Rings


Split Rings — Electro Galvanized
Product Features

Ƚ'PSTVTQFOEJOHVOJOTVMBUFETUBUJPOBSZQJQF"MMPXTGPS
piping runs close to ceilings or walls

.BUFSJBM4QFDJՐDBUJPOT

Material Malleable iron body, carbon steel rivet and bolt


Finish Electro-galvanized
Conforms with Ƚ'FEFSBMTQFDJՐDBUJPO88) 5ZQF

Ƚ.BOVGBDUVSFST4UBOEBSEJ[BUJPO4PDJFUZ
MSS-SP-58 (Type 12)
Installation Install in accordance with ANSI/MSS-SP-58

Ordering Information / Technical Data


Min. Rod Maximum
Weight/ Rod Size Center Insertion Allowable
Description Piece (lb) Pipe Size (RS) Line (CL) (MR) Qty Item No. Load (lb)1

SR-EG 1/2" 0.18     100 00306630 180
SR-EG 3/4" 0.22     100 00306631 180
SR-EG 1" 0.23     100 00306632 180
SR-EG 1-1/2" 0.34     50 00306633 180
SR-EG 2" 0.37     50 00306634 180
1 Based on a safety factor of 3.5

Split Rings — Copper


Product Features

Ƚ'PSTVTQFOEJOHVOJOTVMBUFETUBUJPOBSZDPQQFSUVCJOH
Allows for piping runs close to ceilings or walls

.BUFSJBM4QFDJՐDBUJPOT

Material Malleable iron body, carbon steel rivet and bolt with
DPQQFSFMFDUSPQMBUFՐOJTI
Finish Copper
Conforms with Ƚ'FEFSBMTQFDJՐDBUJPO88) 5ZQF

Ƚ.BOVGBDUVSFST4UBOEBSEJ[BUJPO4PDJFUZ
MSS-SP-58 (Type 12)
Installation Install in accordance with ANSI/MSS-SP-58
Note: This pipe support is not designed for corrosion or electrolysis resistance. Copper
QMBUJOHJTGPSJEFOUJՐDBUJPOQVSQPTFTPOMZ

Ordering Information / Technical Data


Min. Rod Maximum
Weight/ Pipe Rod Size Center Insertion Allowable
Description Piece (lb) Size (RS) Line (CL) (MR) Qty Item No. Load (lb)1

Copper SR 1/2" 0.18     100 00306623 180
Copper SR 3/4" 0.22     100 00306624 180
Copper SR 1" 0.23     100 00306625 180
Copper SR 1-1/4" 0.25     100 00306626 180
Copper SR 1-1/2" 0.34     100 00306627 180
Copper SR 2" 0.37     50 00306628 180
1 Based on a safety factor of 3.5

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 111
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.4 Riser Clamps


MH-SLR-LH Speed Lock Riser Clamp —
Long Hinged
Product Features

Ƚ-POHEFTJHOUPTQBOMBSHFSPQFOJOHTTJOHMFCPMUUISFBET
directly into clamp
Ƚ)PMFTGPSXBMMTUBOEPGGBQQMJDBUJPOT
Ƚ'BTUFSUPJOTUBMMUIBOUSBEJUJPOBMSJTFSDMBNQTFBTZ C
installation in tight spaces

.BUFSJBM4QFDJՐDBUJPOT
B
Material Carbon steel
Finish Electro-galvanized bolts
Pre-galvanized clamps
D
CL hole
A

Ordering Information / Technical Data


Allow. Tightening Height A B C D Material
Load Wrench Torque Dimension Dimension Dimension Dimension Dimension Thickness Box
Description (lb)1 Bolt Diameter x Length Size (ft-lb) (in) (in) (in) (in) (in) Gauge Qty Item No.

MH-SLR-LH 1" PG 255 6/$Y 9/16 19 1 9.0 1.8 1.3 2.5 14 25 02007545
MH-SLR-LH 1-1/4" PG 255 6/$Y 9/16 19 1 9.4 2.1 1.5 2.7 14 25 02007546
MH-SLR-LH 1-1/2" PG 255 6/$Y 9/16 19 1 9.7 2.4 1.6 2.8 14 25 02007547
MH-SLR-LH 2" PG 255 6/$Y 9/16 19  10.3 3.0 1.9 3.1 12 1 02007548
255 6/$Y 9/16 19 25 03475936
MH-SLR-LH 2-1/2" PG 390 6/$Y 9/16 19  10.9 3.5 2.2 3.4 12 1 02007549
390 6/$Y 9/16 19 25 03475937
MH-SLR-LH 3" PG 530 6/$Y 3/4 50  12.1 4.2 2.7 4.1 11 1 02007550
530 6/$Y 3/4 50 25 03475938
MH-SLR-LH 4" PG 810 6/$Y 3/4 50  13.2 5.2 3.2 4.6 11 1 02007551
810 6/$Y 3/4 50 20 03475939
#BTFEPOBTBGFUZGBDUPSPGGPSBMMTJ[FTFYDFQUGPSTJ[FTBOEBDDPSEJOHUP"*4*

Installation Instructions

112 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-CSLR-LR Copper Speed Lock Riser


Clamp — Long Hinged
Product Features

Ƚ-POHEFTJHOUPTQBOMBSHFSPQFOJOHTPOFCPMUXJUIOPMPPTF
nut on backside
Ƚ$PQQFSQBJOUFETJ[FEUPՐUDPQQFSUVCJOHBOEQJQF
Ƚ)PMFTGPSXBMMTUBOEPGGBQQMJDBUJPOT

.BUFSJBM4QFDJՐDBUJPOT C
Material Carbon steel
Finish Copper painted
B

D
CL hole
A
Ordering Information / Technical Data
Allow. Tightening Height A B C D Material
Load Wrench Torque Dimension Dimension Dimension Dimension Dimension Thickness Box
Description (lb)1 Bolt Diameter x Length Size (ft-lb) (in) (in) (in) (in) (in) Gauge Qty Item No.

MH-CSLR-L 1" Copper 120 6/$Y 9/16 19 1 9.0 1.6 1.3 2.5 14 25 02007555
MH-CSLR-L 1-1/4" 150 6/$Y 9/16 19 1 9.3 1.9 1.4 2.6 14 25 02007556
Copper
MH-CSLR-L 1-1/2" 150 6/$Y 9/16 19 1 9.6 2.1 1.6 2.8 14 25 02007557
Copper
MH-CSLR-L 2" Copper 150 6/$Y 9/16 19  10.3 2.8 1.9 3.1 12 1 02007558
150 6/$Y 9/16 19 25 03475945
MH-CSLR-L 2-1/2" 300 6/$Y 9/16 19  10.9 3.3 2.2 3.4 12 1 02007559
Copper
300 6/$Y 9/16 19 25 03475946
MH-CSLR-L 3" Copper 300 6/$Y 3/4 50  12.1 3.9 2.7 4.1 11 1 02007560
300 6/$Y 3/4 50 25 03475947
MH-CSLR-L 4" Copper 300 6/$Y 3/4 50  13.2 4.9 3.2 4.6 11 1 02007561
300 6/$Y 3/4 50 25 03475948
#BTFEPOBTBGFUZGBDUPSPGGPSBMMTJ[FTFYDFQUGPSTJ[FTBOEBDDPSEJOHUP"*4*

/PUF5IJTDMBNQJTOPUEFTJHOFEGPSDPSSPTJPOPSFMFDUSPMZTJTSFTJTUBODF$PQQFSQBJOUJOHJTGPSJEFOUJՐDBUJPOQVSQPTFTPOMZ

Installation Instructions

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 113
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-SLR-S Speed Lock Riser Clamp —


Short Hinged
Product Features

Ƚ4IPSUEFTJHOGPSUJHIUTQBDFTTJOHMFCPMUUISFBETEJSFDUMZ
into clamp
Ƚ1SFHBMWBOJ[FE
Ƚ5ISFFQBSUTNFBOTGBTUFSJOTUBMMBUJPOBOEGFXFSMPTUQJFDFT

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


C
Finish Electro-galvanized bolts
Pre-galvanized clamps

D
CL hole
A

Ordering Information / Technical Data


Allow. Tightening Height A B C D Material
Load Wrench Torque Dimension Dimension Dimension Dimension Dimension Thickness Box
Description (lb)1 Bolt Diameter x Length Size (ft-lb) (in) (in) (in) (in) (in) Gauge Qty Item No.

MH-SLR-S 1" PG 255 6/$Y 9/16 19 1 4.2 1.8 1.5 n.a. 14 25 02007398
MH-SLR-S 1-1/4" PG 255 6/$Y 9/16 19 1 4.6 2.1 1.7 n.a. 14 25 02007399
MH-SLR-S 1-1/2" PG 255 6/$Y 9/16 19 1 4.9 2.4 1.8 n.a. 14 25 02007540
MH-SLR-S 2" PG 255 6/$Y 9/16 19  5.6 3.0 2.1 n.a. 12 1 02007541
255 6/$Y 9/16 19 25 03475772
MH-SLR-S 2-1/2" PG 390 6/$Y 9/16 19  6.1 3.5 2.4 n.a. 12 1 02007542
390 6/$Y 9/16 19 25 03475933
MH-SLR-S 3" PG 530 6/$Y 3/4 50  7.4 4.2 2.9 n.a. 11 1 02007543
530 6/$Y 3/4 50 25 03475934
MH-SLR-S 4" PG 810 6/$Y 3/4 50  8.4 5.2 3.4 n.a. 11 1 02007544
810 6/$Y 3/4 50 20 03475935
#BTFEPOBTBGFUZGBDUPSPGGPSBMMTJ[FTFYDFQUGPSTJ[FTBOEBDDPSEJOHUP"*4*

Installation Instructions

114 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-SLR-LS Speed Lock Riser Clamp —


Long Slotted
Product Features

Ƚ4MPUUFEEFTJHOGPSFBTZJOTUBMMBUJPOUXPQSFNPVOUFECPMUT
threads directly into clamp
Ƚ)PMFTBMMPXGPSXBMMTUBOEPGGBQQMJDBUJPOT

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Electro-galvanized bolts
Pre-galvanized clamps

CL hole

Ordering Information / Technical Data


Allow. Tightening Height A B C D Material
Load Wrench Torque Dimension Dimension Dimension Dimension Dimension Thickness Box
Description (lb) Bolt Diameter x Length Size (ft-lb) (in) (in) (in) (in) (in) Gauge Qty Item No.

MH-SLR-LS 3" PG 530 6/$Y 3/4 19 1 3/16 11 3/4 3 7/8 3 1/9 3/4 3/16 1 02016765
530 6/$Y 3/4 19 25 03475940
MH-SLR-LS 4" PG 810 6/$Y 3/ 4 50 1 1/ 2 13 5 3 3/4 5 1/4 1/ 4 1 02016766
810 6/$Y 3/ 4 50 20 03475941
MH-SLR-LS 6" PG 1570 6/$Y 3/ 4 50 2 16 7 1/ 8 5 8/9 6 3/4 1/ 4 1 02007552
1570 6/$Y 3/ 4 50 10 03475942
MH-SLR-LS 8" PG 2500 6/$Y 15/16 75 2 18 1/4 9 3/ 8 6 7 7/8 3/ 8 1 02007553
2500 6/$Y 15/16 75 5 03475943
MH-SLR-LS 10" PG 2500 6/$Y 15/16 75 2 20 5/8 11 1/ 2 7 3/16 9 3/ 8 1 02007554
2500 6/$Y 15/16 75 5 03475944
1 Based on a safety factor of 3 according to AISI 2007

Installation Instructions

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 115
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.5 Strut Clamps


MH-CB Strut Clamps — Copper
Product Features

Ƚ4J[FEUPՐUDPQQFSUVCJOHBOEQJQFT

Ƚ$PQQFSQBJOUFE

Ƚ0OFQJFDFPVUPGUIFCPYȱTJNQMZCSFBLBQBSUBOEJOTUBMM

Ƚ*OOPWBUJWFEFTJHOSFRVJSFTOPOVUTGPSGBTUBOEFBTZ
assembly

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Load 1
Finish Copper painted

Ordering Information / Technical Data Load 2


Allowable Allowable Allowable
Load 1 Load 2 Load 3
Description (lb)1 (lb)1 (lb)1 Box Qty Item No.

MH-CB 3/8" 400 75 50 100 02008836


Load 3
MH-CB 1/2" 400 75 50 100 02008837
MH-CB 3/4" 400 75 50 100 02008838
MH-CB 1" 600 75 50 100 02008839
MH-CB 1-1/4" 600 75 50 100 02008840
MH-CB 1-1/2" 600 100 50 100 02008841
MH-CB 2" 600 100 50 50 02008842
MH-CB 2-1/2" 800 125 75 50 02008843
MH-CB 3" 800 125 75 25 02008844
MH-CB 4" 800 125 75 25 02008845
1 Based on a safety factor of 3 for Load 1 and 2.3 for Load 2 and 3 according to AISI 2007.
Allowable loads are based on loading in one direction only.

Note: This clamp is not designed for corrosion or electrolysis resistance. Copper painting is
GPSJEFOUJՐDBUJPOQVSQPTFTPOMZ

Technical Data
Tightening Material A B C
Designation Wrench Torque Thickness Dimension Dimension Dimension
Bolt Diameter x Length Size (in-lb) Gauge (in) (in) (in)

MH-CB 3/8" 6/$Y  60 16 1.73 0.54 0.62


MH-CB 1/2" 6/$Y  60 16 1.87 0.61 0.74
MH-CB 3/4" 6/$Y  60 16 2.07 0.73 0.99
MH-CB 1" 6/$Y  60 14 2.35 0.85 1.27
MH-CB 1-1/4" 6/$Y  60 14 2.62 0.98 1.52
MH-CB 1-1/2" 6/$Y  60 14 2.88 1.11 1.77
MH-CB 2" 6/$Y  60 14 3.40 1.35 2.27
MH-CB 2-1/2" 6/$Y  60 12 3.94 1.61 2.84
MH-CB 3" 6/$Y  60 12 4.45 1.85 3.34
MH-CB 4" 6/$Y  60 12 5.46 2.35 4.34

Installation Instructions

116 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

Strut Clamp — Rigid (SS 316)


Product Features

Ƚ'PSVTFXJUISJHJETUBJOMFTTTUFFMQJQFT

.BUFSJBM4QFDJՐDBUJPOT

Material 316 Stainless Steel

Ordering Information / Technical Information Load 1


Allowable Allowable Allowable
Load 1 Load 2 Load 3
Description (lb)1 (lb)1 (lb)1 Box Qty Item No.

Strut Clamp Rigid 1/2" SS316 400 75 50 50 00424215


Strut Clamp Rigid 3/4" SS316 400 75 50 50 00424216
Load 2
Strut Clamp Rigid 1" SS316 600 75 50 50 00424217
Strut Clamp Rigid 1-1/4" SS316 600 75 50 25 00424218
Strut Clamp Rigid 1-1/2" SS316 600 75 50 25 00424219 Load 3
Strut Clamp Rigid 2" SS316 600 75 50 25 00424220
Strut Clamp Rigid 2-1/2" SS316 800 75 50 10 00424221
Strut Clamp Rigid 3" SS316 800 75 50 10 00424222
Strut Clamp Rigid 4" SS316 1000 75 50 10 00424223
1 Based on a safety factor of 3. Allowable loads are based on loading in one direction only.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 117
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-RBA Strut Clamp — Rigid


Product Features

Ƚ0OFQJFDFPVUPGUIFCPY TJNQMZCSFBLBQBSUBOEJOTUBMM

Ƚ*OOPWBUJWFEFTJHOSFRVJSFTOPOVUTGPSGBTUBOEFBTZ
assembly

Ƚ4J[FEGPSNFDIBOJDBMNFUBMMJDUVCJOHBOEQJQFT

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Pre-galvanized

Ordering Information / Technical Data


Allowable Allowable Allowable Load 1
Load 1 Load 2 Load 3
Description (lb)1 (lb)1 (lb)1 Box Qty Item No.

MH-RBA 1/2" PG 400 50 40 100 02008800


MH-RBA 3/4" PG 400 50 40 100 02008801
MH-RBA 1" PG 600 75 50 100 02008802 Load 2
MH-RBA 1-1/4" PG 600 75 50 50 02008803
MH-RBA 1-1/2" PG 600 100 50 50 02008804
MH-RBA 2" PG 600 100 60 50 02008805
Load 3
MH-RBA 2-1/2" PG 800 100 60 25 02008806
MH-RBA 3" PG 800 200 150 25 02008807
MH-RBA 4" PG 800 200 150 25 02008808
MH-RBA 6" PG 1000 200 150 10 02008809
1 Based on a safety factor of 3 for Load 1 and 2.3 for Load 2 and 3 according to AISI 2007.
Allowable loads are based on loading in one direction only.

Technical Data
Tightening Material A B C
Designation Wrench Torque Thickness Dimension Dimension Dimension
Bolt Diameter x Length Size (in-lb) Gauge (in) (in) (in)

MH-RBA 1/2" PG 6/$Y  60 16 2.02 0.70 0.96


MH-RBA 3/4" PG 6/$Y  60 16 2.25 0.81 1.17
MH-RBA 1" PG 6/$Y  60 14 2.55 0.94 1.46
MH-RBA 1-1/4" PG 6/$Y  60 14 2.91 1.11 1.81
MH-RBA 1-1/2" PG 6/$Y  60 14 3.16 1.23 2.05
MH-RBA 2" PG 6/$Y  60 14 3.64 1.47 2.52
MH-RBA 2-1/2" PG 6/$Y  60 12 4.19 1.72 3.09
MH-RBA 3" PG 6/$Y  60 12 4.81 2.03 3.71
MH-RBA 4" PG 6/$Y  60 12 5.82 2.53 4.71
MH-RBA 6" PG 6/$Y  60 10 7.97 3.59 6.89

Installation Instructions

118 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-R45 Strut Clamps — Rigid


Product Features

Ƚ5JHIUFOJOHTDSFXBUpBOHMFGPSFBTZBDDFTT

Ƚ4J[FEGPSSJHJEQJQFT

Ƚ0OFQJFDFPVUPGUIFCPY TJNQMZCSFBLBQBSUBOEJOTUBMM

Ƚ*OOPWBUJWFEFTJHOSFRVJSFTOPOVUTGPSGBTUBOEFBTZ
assembly

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Pre-galvanized

Ordering Information / Technical Data


Allowable Allowable Allowable
Load 1 Load 2 Load 3
Description (lb)1 (lb)1 (lb)1 Box Qty Item No.

MH-R45 1/2" PG 400 50 40 100 02008810


Load 1
MH-R45 3/4" PG 400 50 40 100 02008811
MH-R45 1" PG 600 75 50 100 02008812
MH-R45 1-1/4" PG 600 75 50 50 02008813
MH-R45 1-1/2" PG 600 100 50 50 02008814
MH-R45 2" PG 600 100 60 50 02008815 Load 2
MH-R45 2-1/2" PG 800 100 60 25 02008816
MH-R45 3" PG 800 100 150 25 02008817
MH-R45 4" PG 800 100 150 25 02008818 Load 3
MH-R45 6" PG 1000 100 150 10 02008819
MH-R45 8" PG 1000 100 150 10 02008820
1 Based on a safety factor of 3 for Load 1 and 2.3 for Load 2 and 3 according to AISI 2007.
Allowable loads are based on loading in one direction only.

Technical Data
Tightening Material A B C
Wrench Torque Thickness Dimension Dimension Dimension
Designation Bolt Diameter x Length Size (in-lb) Gauge (in) (in) (in)

MH-R45 1/2" PG 6/$Y  60 16 2.15 0.71 0.96


MH-R45 3/4" PG 6/$Y  60 16 2.35 0.82 1.17
MH-R45 1" PG 6/$Y  60 14 2.68 0.95 1.46
MH-R45 1-1/4" PG 6/$Y  60 14 3.08 1.11 1.81
MH-R45 1-1/2" PG 6/$Y  60 14 3.28 1.23 2.05
MH-R45 2" PG 6/$Y  60 14 3.73 1.47 2.52
MH-R45 2-1/2" PG 6/$Y  60 12 4.32 1.70 3.09
MH-R45 3" PG 6/$Y  60 12 5.01 2.03 3.71
MH-R45 4" PG 6/$Y  60 12 6.04 2.54 4.71
MH-R45 6" PG 6/$Y  60 10 8.03 3.55 6.89
MH-R45 8" PG 6/$Y  60 10 10.26 4.54 8.88

Installation Instructions

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 119
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-EMT Strut Clamp — 45EMT


Product Features

Ƚ1SFBTTFNCMFEPVUPGCPYUJHIUFOJOHTDSFXBUpBOHMFGPS
easy access

Ƚ4J[FEGPSFMFDUSJDBMNFUBMMJDUVCJOH &.5

Ƚ1SFHBMWBOJ[FE

Ƚ*OOPWBUJWFEFTJHOSFRVJSFTOPOVUTGPSGBTUBOEFBTZ
assembly

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Pre-galvanized

Ordering Information / Technical Data


Allowable Allowable Allowable
Load 1 Load 2 Load 3
Description (lb)1 (lb)1 (lb)1 Box Qty Item No.

MH-EMT45 1/2" PG 200 50 30 100 02008821


MH-EMT45 3/4" PG 200 50 30 100 02008822
MH-EMT45 1" PG 200 75 40 100 02008823
MH-EMT45 1-1/4" PG 200 75 40 50 02008824 Load 1
MH-EMT45 1-1/2" PG 200 100 40 50 02008825
MH-EMT45 2" PG 200 100 50 50 02008826
1 Based on a safety factor of 3 for Load 1 and 2.3 for Load 2 and 3 according to AISI 2007.
Allowable loads are based on loading in one direction only.
Load 2
Technical Data
Tightening Material A B C
Designation Wrench Torque Thickness Dimension Dimension Dimension
Load 3
Bolt Diameter x Length Size (in-lb) Gauge (in) (in) (in)

MH-EMT45 1/2" PG 6/$Y  60 16 1.98 0.65 0.82


MH-EMT45 3/4" PG 6/$Y  60 16 2.20 0.75 1.04
MH-EMT45 1" PG 6/$Y  60 14 2.47 0.87 1.31
MH-EMT45 1-1/4" PG 6/$Y  60 14 2.81 1.05 1.66
MH-EMT45 1-1/2" PG 6/$Y  60 14 3.05 1.17 1.89
MH-EMT45 2" PG 6/$Y  60 14 3.50 1.39 2.35

Installation Instructions

120 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-EMTV Strut Clamps — EMT Top Screw


Product Features

Ƚ1SFBTTFNCMFEPVUPGCPY

Ƚ5JHIUFOJOHTDSFXPOUPQGPSFBTZBDDFTT

Ƚ4J[FEGPS&.5 SJHJEBOEՑFYJCMFQJQFT

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Pre-galvanized

Ordering Information / Technical Data


Allowable Allowable Allowable
Load 1 Load 2 Load 3
Description (lb)1 (lb)1 (lb)1 Box Qty Item No. Load 1
MH-EMTV 1/2" PG 200 50 30 100 02008827
MH-EMTV 3/4" PG 200 50 30 100 02008828
MH-EMTV 1" PG 200 75 40 50 02008829
MH-EMTV 1-1/4" PG 200 75 40 50 02008830 Load 2
MH-EMTV 1-1/2" PG 200 75 40 50 02008831
MH-EMTV 2" PG 200 75 50 25 02008832
Load 3
MH-EMTV 2" FLEX 200 75 50 25 02016764
MH-EMTV 2-1/2" PG 350 75 50 25 02008833
MH-EMTV 3" PG 350 75 50 10 02008834
MH-EMTV 4" PG 350 75 50 10 02008835

1 Based on a safety factor of 3 for Load 1 and 2.3 for Load 2 and 3 according to AISI 2007.
Allowable loads are based on loading in one direction only.

Technical Data
Strut Pipe
Clamp Clamp
Tightening Material Material A B C D
Designation Wrench Torque Thickness Thickness Dimension Dimension Dimension Dimension
Bolt Diameter x Length Size (in-lb) Gauge Gauge (in) (in) (in) (in)

MH-EMTV 1/2" PG 6/$Y  30 16 18 1.75 2.50 0.57 1.14


MH-EMTV 3/4" PG 6/$Y  30 16 18 1.99 0.71 0.53 1.32
MH-EMTV 1" PG 6/$Y  30 14 18 2.35 0.67 0.49 1.53
MH-EMTV 1-1/4" PG 6/$Y  30 14 18 2.65 0.73 0.55 1.87
MH-EMTV 1-1/2" PG 6/$Y  30 14 18 2.87 0.73 0.55 2.11
MH-EMTV 2" PG 6/$Y  30 14 18 3.34 0.87 0.70 2.47
MH-EMTV 2" FLEX 6/$Y  30 14 16 3.58 4.30 0.54 2.73
MH-EMTV 2-1/2" PG 6/$Y  30 12 16 4.36 5.17 0.64 3.34
MH-EMTV 3" PG 6/$Y  30 12 16 4.87 5.68 0.63 3.91
MH-EMTV 4" PG 6/$Y  30 12 16 5.81 6.62 0.63 4.93

Installation Instructions

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 121
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-UB Strut Clamp — Universal


Product Features

Ƚ4J[FEUPՐUCPUISJHJEQJQFTBOE&.5

Ƚ1SFHBMWBOJ[FE

Ƚ0OFQJFDFPVUPGUIFCPY TJNQMZCSFBLBQBSUBOEJOTUBMM

Ƚ*OOPWBUJWFEFTJHOSFRVJSFTOPOVUTGPSGBTUBOEFBTZ
assembly

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon steel


Finish Pre-galvanized

Load 1
Ordering Information / Technical Data
Allowable Allowable Allowable
Load 1 Load 2 Load 3
Description (lb)1 (lb)1 (lb)1 Box Qty Item No. Load 2
MH-UB 1/2" PG 200 75 50 100 2008846
MH-UB 3/4" PG 200 75 50 100 2008847
MH-UB 1" PG 200 75 50 50 2008848
Load 3
MH-UB 1 1/4" PG 200 75 50 50 2008849
MH-UB 1 1/2" PG 200 100 50 50 2008850
MH-UB 2" PG 200 100 50 50 2008851
1 Based on a safety factor of 3 for Load 1 and 2.3 for Load 2 and 3 according to AISI 2007.
Allowable loads are based on loading in one direction only.

Technical Data
Tightening Material A B C
Designation Wrench Torque Thickness Dimension Dimension Dimension
Bolt Diameter x Length Size (in-lb) Gauge (in) (in) (in)

MH-UB 1/2" PG 6/$Y  60 16 1.96 0.68 0.96-0.82


MH-UB 3/4" PG 6/$Y  60 16 2.19 0.79 1.17-1.04
MH-UB 1" PG 6/$Y  60 14 2.47 0.91 1.46-1.31
MH-UB 1 1/4" PG 6/$Y  60 14 2.84 1.09 1.81-1.66
MH-UB 1 1/2" PG 6/$Y  60 14 3.08 1.20 2.05-1.89
MH-UB 2" PG 6/$Y  60 14 3.56 1.44 2.52-2.35

Installation Instructions

122 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.6 Eye Couplers


Eye Coupler
Product Features

Ƚ"TUSVDUVSBMBUUBDINFOUVTFEUPKPJOIBOHFSSPEUPB
structure

.BUFSJBM4QFDJՐDBUJPOT

.BUFSJBMBOEՐOJTI Pre-galvanized carbon steel


Approvals Factory Mutual (FM)
Listings Underwriters Laboratories (UL–cUL)

Ordering Information / Technical Data


Rod Size Minimum Rod Max Pipe Max Allowable
Description (RS) H HS1 HS2 Insertion (MR) W Size Qty Item No. Load (lb)1

Eye Coupler 3/8"         250 00258317 250
1 Capacity of eye coupler loaded axially. Based on safety factor of 3.5. RS

Offset Eye Coupler


Product Features

Ƚ"TUSVDUVSBMBUUBDINFOUVTFEUPKPJOIBOHFSSPEUPB
TUSVDUVSF1SPWJEFTVOMJNJUFEWFSUJDBMSPEBEKVTUNFOU

.BUFSJBM4QFDJՐDBUJPOT

.BUFSJBMBOEՐOJTI Pre-galvanized carbon steel


Approvals Factory Mutual (FM)
RS
Listings Underwriters Laboratories (UL–cUL)

Ordering Information / Technical Data


Rod Max
Rod Minimum Max Allowable
Size Insertion Pipe Box Load
Description (RS) H HS1 HS2 (MR) W Size Qty Item No. (lb)1

Offset Eye Coupler 3/8"        250 00258318 250
1 Capacity of offset eye coupler loaded axially. Based on safety factor of 3.5.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 123
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.7 Threaded Rod and Threaded Accessories


Threaded Rod
.BUFSJBM4QFDJՐDBUJPOT

Material Low Carbon Steel, Fy = 36,000 psi; Fu = 48,000 psi


Stainless Steel 316/ASTM A276 Class 1
Finish Plain and zinc electroplated to ASTM B 633-98,
SC 1 Type III

Ordering Information / Technical Data


MSS-SP-581
Allowable AISC2
Weight Weight (lbs) Tensile Load at Allowable
Description Qty (Pack) (Lb/ft) per pkg. Diameter (in) Item No. 650°F Tensile Load (lb)

1/4" x 6' Threaded Rod (Zinc) 50 0.12 35.7 1/4-20 00257963 300 780
1/4" x 10' Threaded Rod (Zinc) 50 0.12 59.5 1/4-20 00309386 300 780
1/4" x 10' Threaded Rod (Plain) 50 0.12 59.5 1/4-20 00309391 300 780
3/8" x 6' Threaded Rod (Zinc) 25 0.3 42.6 3/8-16 00257964 730 1750
3/8" x 6' Threaded Rod (Plain) 25 0.3 42.6 3/8-16 00257969 730 1750
3/8" x 10' Threaded Rod (Zinc) 25 0.3 71.3 3/8-16 00309387 730 1750
3/8" x 10' Threaded Rod (Plain) 25 0.3 71.3 3/8-16 00309392 730 1750
3/8" x 12' Threaded Rod (SS316) 10 0.3 36 3/8-16 03445331 730 2720
1/2" x 6' Threaded Rod (Zinc) 12 0.5 38.8 1/2-13 00257965 1350 3110
1/2" x 10' Threaded Rod (Zinc) 12 0.5 61.4 1/2-13 00309388 1350 3110
1/2" x 10' Threaded Rod (Plain) 12 0.5 61.4 1/2-13 00309393 1350 3110
5/8" x 10' Threaded Rod (Zinc) 8 0.84 66.5 5/8-11 00309389 2160 4860
5/8" x 10' Threaded Rod (Plain) 8 0.84 66.5 5/8-11 00309394 2160 4860
3/4" x 10' Threaded Rod (Zinc) 5 1.2 60 3/4-10 00309390 3230 6700
3/4" x 10' Threaded Rod (Plain) 5 1.2 60 3/4-10 00309395 3230 6700
1 Per MSS-SP-58-2002, the ultimate tensile loads are based on a tensile stress of 50,000 psi multiplied by the threaded rod root area based on coarse thread UNC.
2 AISC Allowable Tensile load = 0.33 x Fu x Anom
AISC Allowable Shear load = 0.17 x Fu x Anom

124 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

MH-SLT Speed Lock Trapeze Nut


Product Features

Ƚ/VUBOEXBTIFSDBOCFJOTUBMMFEBUBOZQPTJUJPOPOUIF
threaded rod, for quick and accurate trapeze building

Ƚ&MFDUSPHBMWBOJ[FE

Ƚ6TFTQMJUOVUPOMZJODPOKVODUJPOXJUITMPUUFEXBTIFSBOE
1-5/8” wide strut

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon Steel


Finish Electro-galvanized

A B

/PUF4QMJU/VU "
NVTUBMXBZTCFVTFEXJUI4MPUUFE8BTIFS #
&OHBHFCZUJHIUFOJOHUPTQFDJՐFEUPSRVF

Ordering Information
Description Designation Torque (MD) Qty Item No.

3/8" Split Nut and Slot Square Washer .)4-5&( 180 in-lb / 15 ft-lb 40 02008780
1/2" Split Nut and Slot Square Washer .)4-5&( 265 in-lb / 22 ft-lb 40 02008781

Technical Data
Allow. Tightening A B C D Plate
Load Wrench Torque Dimension Dimension Dimension Dimension Thickness
Description (lb) Size (ft-lb) (in) (in) (in) (in) mm / (in)

MH-SLT 3/8" EG 745  15 1.77 1.89 0.75 0.55 3 / (1/8)


MH-SLT 1/2" EG 1350  22 1.77 1.89 0.75 0.55 3 / (1/8)

Based on a safety factor of 3

Installation Instructions

Place nut at any location on Squeeze nut onto rod Insert slotted washer between Repeat steps 1-3 on top of 5JHIUFOUPTQFDJՐFEUPSRVF MH-SLT is not intended for
threaded rod. nut and strut strut value shear loading

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 125
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

Hex Nuts
.BUFSJBM4QFDJՐDBUJPOT

Material ASTM A 563 Grade A;


Stainless Steel 316
Dimensions ASME/ANSI B18.2.2 - 1986
Finish ASTM B 633-98, SC 1 Type I
Thread $MBTT"ՐU$MBTT#UISE"4.&#

Ordering Information
Description Width Across Flats Qty Item No.

Hex Nut-Heavy 1/4"  1000 00335549


Hex Nut-Standard 1/4" (SS316)  200 00411774
Hex Nut-Heavy 3/8"  1000 00335550
Hex Nut-Standard 3/8" (SS316)  100 00411775
Hex Nut-Heavy 1/2"  1000 00335551
Hex Nut-Standard 1/2" (SS316)  100 00411776
Hex Nut-5/8"  250 00336402
Hex Nut-Standard 5/8" (SS316)  50 00411777
Hex Nut-3/4"  250 00336403
Hex Nut-Standard 3/4" (SS316)  25 00411778

Washers
.BUFSJBM4QFDJՐDBUJPOT

Material AISI 1005 through 1035;


Stainless Steel 316
Dimensions ASME/ANSI B18.22.1 Type A - 1986
Finish ASTM B 633-98, SC 1 Type I

Ordering Information
Description Inside Diameter Outside Diameter Qty Item No.

Washer 1/4" 0.312 0.734 1000 00335552


Washer 1/4" (SS316) 0.281 0.625 200 00411779
Washer 3/8" 0.438 1.000 1000 00335553
Washer 3/8" (SS316) 0.406 0.875 200 00411780
Washer 1/2" 0.562 1.375 1000 00335554
Washer 1/2" (SS316) 0.531 1.250 100 00411781
Washer 5/8" 0.656 1.312 250 00336404
Washer 5/8" (SS316) 0.656 1.312 100 00411782
Washer 3/4" 0.812 1.469 250 00336405
Washer 3/4" (SS316) 0.812 1.500 50 00411783
Fender Washer 1/4" 0.281 1.250 1000 00313068
Fender Washer 1/4" (SS316) 0.281 1.250 100 00411784
Fender Washer 3/8" 0.406 1.500 1000 00313069
Fender Washer 3/8" (SS316) 0.406 1.500 100 00411785
Fender Washer 1/2" 0.531 2.000 100 00411763
Fender Washer 1/2" (SS316) 0.531 2.000 100 00411787

126 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

Rod Couplers
.BUFSJBM4QFDJՐDBUJPOT

Material ASTM A563, Grade A carbon steel;


Stainless Steel 316
Finish Zinc electroplated to ASTM B 633-98, SC 1, Type I
Thread $MBTT"ՐU$MBTT#UISFBE

Ordering Information
Width across MSS-SP-581 Allowable AISC2
Description Length ՑBUT Qty Item No. Tensile Load at 650°F Allowable Load (lb)

1/4" Rod Coupler   100 00411746 300 780


3/8" Rod Coupler   50 00411747 730 1750
3/8" Rod Coupler (SS316)   50 00411770 - 2720
1/2" Rod Coupler   500 00257985 1350 3110
1/2" Rod Coupler (SS316)   50 00411771 - 4830
5/8" Rod Coupler   300 00257986 2160 4860
5/8" Rod Coupler (SS316)   50 00411772 - 7550
3/4" Rod Coupler   200 00411750 3230 6700
1 Per MSS-SP-58-2002, the ultimate tensile loads are based on a tensile stress of 50,000 psi multiplied by the threaded rod root area based on coarse thread UNC.
2 AISC Allowable Tensile load = 0.33 x Fu x Anom
AISC Allowable Shear load = 0.17 x Fu x Anom

Hex Head Bolts


.BUFSJBM4QFDJՐDBUJPOT

Material ASTM A 307; Stainless Steel 316


Dimensions ASME/ANSI B18.2.1 1981
Finish Zinc electroplated to ASTM B 633-98, SC 1, Type I
Thread $MBTT"ՐU$MBTT#UISE"4.&#

Ordering Information
Description Qty Item No.

Hex Head Bolt 3/8" x 1-1/4" 500 00311951


Hex Head Bolt 3/8" x 1-1/4" (SS316) 50 00411788
Hex Head Bolt 3/8" x 1-1/2" 500 00311952
Hex Head Bolt 3/8" x 1-1/2" (SS316) 50 00411789
Hex Head Bolt 1/2" x 1" 250 00311953
Hex Head Bolt 1/2" x 1" (SS316) 50 03445355
Hex Head Bolt 1/2" x 1-1/4" 50 00411767
Hex Head Bolt 1/2" x 1-1/4" (SS316) 50 03445356
Hex Head Bolt 1/2" x 1-1/2" 50 00411768
Hex Head Bolt 1/2" x 1-1/2" (SS316) 50 00411792

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 127
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.8 Bracing
Vertical Rod Stiffeners
Product Features

Ƚ6TFGPSTFJTNJDDPNQSFTTJPOCSBDJOHPGUISFBEFESPET

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon Steel


Finish Electro-Galvanized

Ordering Information
Hanger Rod/ Bolt
Description Diameter Qty Item No.

Hilti Rod Stiffener — Internal (rod in strut) Ȱ 25 00311943

Technical Data
Threaded Rod Diameter Rod Stiffener Bolt Max. Spacing Between Allowable Threaded Rod
(inches) Torque (ft-lb) Rod Stiffeners1 (inches) Compression Load (lb)
3/8 8 15 255
1/2 8 20 475
5/8 8 26 760
1. Minimum of two rod stiffeners per channel to restrain buckling of the threaded rod
2. Compression load based on 13th Edition AISC (360-05)
3. Minimum threaded rod yield strength Fy = 36,000 psi
4. See detail for construction dimensional details

Seismic Hinge
Product Features

Ƚ'PSVTFXJUI)JMUJDIBOOFMQSPՐMFT DPODSFUFBODIPST CPMUFE


to structural steel or threaded drop rods to brace against
lateral loads

.BUFSJBM4QFDJՐDBUJPOT

Material Carbon Steel, A36


Finish Electro-Galvanized per ASTM B633 SC1
Conforms with Ƚ#PMUDPOGPSNTUP"/4*#
Ƚ/VUDPOGPSNTUP"/4*#

Ordering Information
Hanger Rod/ Bolt
Description Diameter Qty Item No.

Seismic Hinge, Strut Half w/ Bolt & Nut ˕  10 00333309


Seismic Hinge, Base/ Hanger Half, 3/8" 1 ˖  10 00369714 ˕ ˖

Seismic Hinge, Base/ Hanger Half, 1/2" 1


˖  10 00333308
Seismic Hinge, Base/ Hanger Half, 5/8" 1 ˖  10 00369715
Seismic Hinge, Base/ Hanger Half, 3/4" 1 ˖  10 00369716

Technical Data — Allowable Loads2


Base Hanger Half to Strut Base Hanger Half to Strut Strut Nut
Hinge Angle X.2.MC X.2.MC Tightening Torque ft-lb
90 1125 2025 30
90 1200 - 50
45 1200 1815 30
45 1500 - 50
0 1800 1800 30
1 Capacity of hanger rod/anchor to concrete must be evaluated separately.
2 Based on a safety factor of 2.2.

128 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

5.9 Cast In
Continuous Concrete Insert Strut
Product Features

Ƚ6TFXJUIBWBSJFUZPG)JMUJGBTUFOFSTUPIBOHUISFBEFESPE

Ƚ17GPBNJOTFSULFFQTXFUDPODSFUFPVUPGDIBOOFMBOE
removes easily in one piece once concrete is cured

.BUFSJBM4QFDJՐDBUJPOT

.BUFSJBMBOEՐOJTI ASTM A1011 (replaces A570) Grade 33 Carbon Steel


Pre-galvanized to G90

Ordering Information
Description Qty Item No.

Cast In Strut 1 3/8" x 12 ga x 20' 10 03448648


Cast In Strut 13/16" x 12 ga x 20' 10 03448649
Note: Allow two to three weeks for delivery.

Technical Data — Allowable Loads1, 2, 3


Nut Allowable Tension Allowable Shear Bolt Torque
Description Thickness Box Qty Item No. (Pullout) (lbs) (Slip) (lbs) (ft-lbs)

MQM-F 1/4” n.a. 50 00377881 755 2002 7 See pag


es
MQM-F 3/8” n.a. 50 00377882 1800 5502 15 91 and 9
2
MQM-F 1/2” n.a. 50 00377883 1800 5502 30 for addit
ional
1/4" Spring Nut 1/4” 100 00258246 450 300 6 product
3/8" Spring Nut  100 00258247 1100 800 19 informati
1/2" Spring Nut  100 00258248 2000 1500 50 on.
3/8" Channel Nut 3/8” 100 00311937 1100 800 19
1/2" Channel Nut  100 00311938 2000 1500 50
5/8" Channel Nut  100 00311939 2000 1500 100
3/4" Channel Nut  100 00311940 2000 1500 125
1 MQM Wing Nuts should be used in tension applications only. Standard Channel or Spring Nuts can be used in shear and/or tension applications.
2 See technical data for the individual part for safety factor and other load data.
3 Values are for galvanized strut and MQM Wing Nuts.

Technical Data General Notes


Allowable tensile load capacity is 2000 lbs/ft based on minimum concrete
compressive strength of 3000 psi NW and a safety factor of 2.5. Applied loads
NVTUCFGSPNUIFFOEPGTUSVU5IFNJOJNVNEJTUBODFCFUXFFOUIF$*4TUSVU
DFOUFSMJOFBOEUIFDPODSFUFFEHFJT5IFNJOJNVNDVUMFOHUIPGTUSVUJTUP
achieve the allowable load. Hilti end caps item 00313377 must be used on field
cut ends. Field cuts must be located at typical locations as shown in the picture Cast-In end caps

to the right. Shorter lengths require “cast in end caps” and result in lower load
values.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 129
Hilti MI/MQ Technical Guide

5.0 Installation System Hangers

Concrete Spot Insert


Product Features

Ƚ6TFBTBTUSVDUVSBMBUUBDINFOUJODPODSFUF,OPDLPVUIFMQT
keep interior empty during pour.

.BUFSJBM4QFDJՐDBUJPOT

.BUFSJBMBOEՐOJTI Carbon Steel Electro-Galvanized meeting ASTM B633


SC3 Type I
Conforms with 'FEFSBM4QFDJՐDBUJPO88) 5ZQF
BOE
Manufacturers Standardization Society ANSI/
MSS-SP-58 (Type 18). Not UL or FM Listed
Installation Install in accordance with ANSI/MSS-SP-58. Place
knockout side down on form and nail in place. After
concrete pour, knockout can be removed with a
screwdriver. Rod should be threaded through the
inset nut until it tightens against the top of the insert.

Ordering and Technical Information


Concrete Insert
Description Max. Allowable Tensile Load (lb)1 Qty Item No.

Concrete Insert EG 600 25 03442103

1 Based on a safety factor of 3

Square Nut for Insert


Description Qty Item No.

Insert Nut 1/4" 100 3448644


Insert Nut 3/8" 100 3448645
Insert Nut 1/2" 100 3448646
Insert Nut 5/8" 100 3448647
Note — Available on special order basis. Please contact Hilti for pricing and delivery. Not returnable.

130 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

6.0 Reference Charts

6.1 Pipe and Tubing


Schedule 40 Steel Pipe Data
Weight of Pipe Recommended
Nominal Pipe Size Pipe O.D. Wall Thickness Weight of Pipe Filled with Water Maximum Span1 Hanger Rod1
In. mm In. mm In. mm Lbs./Ft. kg/m Lbs./Ft. kg/m Ft. Meter Sizes
 (10) .675 (17.1) .091 (2.3) .6 (.9) .7 (1.0) 7 (2.13) 
 (15) .840 (21.3) . 109 (2.7) .8 (1.2) .9 (1.3) 7 (2.13) 
 (20) 1.050 (26.7) .113 (2.9) 1.1 (1.7) 1.3 (2.0) 7 (2.13) 
 (25) 1.315 (33.4) .133 (3.4) 1.7 (2.5) 2.1 (3.0) 7 (2.13) 
 (32) 1.660 (42.1) .140 (3.5) 2.3 (3.4) 2.9 (4.3) 7 (2.13) 
 (40) 1.900 (48.2) .145 (3.7) 2.7 (4.0) 3.6 (5.3) 9 (2.74) 
 (50) 2.375 (60.3) .154 (3.9) 3.6 (5.4) 5.0 (7.5) 10 (3.05) 
 (65) 2.875 (73.0) .203 (5.1) 5.8 (8.6) 7.9 (11.7) 11 (3.35) 
 (80) 3.500 (88.9) .216 (5.5) 7.6 (11.2) 10.8 (15.9) 12 (3.66) 
 (90) 4.000 (101.6) .226 (5.7) 9.1 (13.5) 13.4 (19.8) 13 (3.96) 
 (100) 4.500 (114.3) .237 (6.0) 10.8 (16.0) 16.3 (24.2) 14 (4.27) 
 (125) 5.563 (141.3) .258 (6.5) 14.6 (21.7) 23.2 (34.6) 16 (4.87) 
 (150) 6.625 (168.3) .280 (7.1) 19.0 (28.2) 31.5 (46.8) 17 (5.18) 
 (200) 8.625 (219.1) .322 (8.2) 28.5 (42.5) 50.1 (74.6) 19 (5.79) 
 (250) 10.750 (273.0) .365 (9.3) 40.5 (60.2) 74.6 (110.9) 22 (6.69) 
 (300) 12.750 (323.8) .406 (10.3) 51.1 (75.9) 102.1 (151.9) 23 (7.01) 
 (350) 14.000 (355.6) .437 (11.1) 63.0 (93.7) 121.5 (180.7) 25 (7.62) 
 (400) 16.000 (406.4) .500 (12.7) 83.0 (123.5) 159.5 (237.3) 27 (8.23) 
 (450) 18.000 (457.2) .563 (14.3) 105.0 (156.2) 202.2 (300.8) 28 (8.53) 
 (500) 20.000 (508.0) .593 (15.1) 123.0 (183.0) 243.4 (361.8) 30 (9.14) 
 (600) 24.000 (609.6) .687 (17.4) 171.0 (254.5) 345.2 (513.7) 32 (9.75) 

Schedule 80 Steel Pipe Data


Weight of Pipe Recommended
Nominal Pipe Size Pipe O.D. Wall Thickness Weight of Pipe Filled with Water Maximum Span1 Hanger Rod1
In. mm In. mm In. mm Lbs./Ft. kg/m Lbs./Ft. kg/m Ft. Meter Sizes
 (10) .675 (17.1) .126 (3.2) .7 (1.1) .8 (1.2) 7 (2.13) 
 (15) .840 (21.3) .147 (3.7) 1.1 (1.6) 1.2 (1.7) 7 (2.13) 
 (20) 1.050 (26.7) .154 (3.9) 1.5 (2.2) 1.7 (2.5) 7 (2.13) 
 (25) 1.315 (33.4) .179 (4.5) 2.2 (3.2) 2.5 (3.6) 7 (2.13) 
 (32) 1.660 (42.1) .191 (4.8) 3.0 (4.4) 3.5 (5.2) 7 (2.13) 
 (40) 1.900 (48.2) .200 (5.1) 3.6 (5.4) 4.3 (6.5) 9 (2.74) 
 (50) 2.375 (60.3) .218 (5.5) 5.0 (7.5) 6.3 (9.4) 10 (3.05) 
 (65) 2.875 (73.0) .276 (7.0) 7.6 (11.4) 9.4 (14.1) 11 (3.35) 
 (80) 3.500 (88.9) .300 (7.6) 10.2 (15.2) 13.0 (19.4) 12 (3.66) 
 (90) 4.000 (101.6) .318 (8.1) 12.5 (18.6) 16.3 (24.3) 13 (3.96) 
 (100) 4.500 (114.3) .337 (8.5) 15.0 (22.3) 20.0 (29.7) 14 (4.27) 
 (125) 5.563 (141.3) .375 (9.5) 20.8 (30.9) 28.7 (42.6) 16 (4.87) 
 (150) 6.625 (168.3) .432 (11.0) 28.6 (42.5) 39.9 (59.3) 17 (5.18) 
 (200) 8.625 (219.1) .500 (12.7) 43.4 (64.5) 63.1 (93.9) 19 (5.79) 
 (250) 10.750 (273.0) .593 (15.0) 64.4 (95.8) 95.5 (142.1) 22 (6.69) 
 (300) 12.750 (323.8) .687 (17.4) 88.6 (131.8) 132.6 (197.3) 23 (7.01) 
 (350) 14.000 (355.6) .750 (19.0) 107.0 (159.2) 158.2 (235.4) 25 (7.62) 
 (400) 16.000 (406.4) .843 (21.4) 137.0 (203.9) 206.7 (306.6) 27 (8.23) 
 (450) 18.000 (457.2) .937 (23.8) 171.0 (254.5) 259.5 (386.2) 28 (8.53) 
 (500) 20.000 (508.0) 1.031 (26.2) 209.0 (311.0) 318.4 (473.8) 30 (9.14) 
 (600) 24.000 (609.6) 1.218 (30.9) 297.0 (442.0) 455.2 (677.4) 32 (9.75) 
Based on ASTM A53-86. 1. Based on MSS SP-58 Table 3 & 4.
1 cubic ft. of water weighs 62.41 lbs. Many codes require pipe hangers to be spaced every 10' (3.048 meters)
1 gallon (U.S.) weighs 8.335 lbs. regardless of size. Check local codes.
1 cubic meter of water weighs 999.97 kg. 4QBDJOHBOEDBQBDJUJFTBSFCBTFEPOXBUFSՐMMFEQJQF$MPTFSIBOHFSTQBDJOH
1 liter weighs .999 kg. NBZCFSFRVJSFEXIFSFBEEJUJPOBMWBMWFTBOEՐUUJOHTJODSFBTFUIFMPBE

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 131
Hilti MI/MQ Technical Guide

6.0 Reference Charts

Copper Tubing (Type L) Data


Weight of Pipe
Nominal Tubing Size O.D. Size Wall Thickness Weight of Tubing Filled with Water
In. mm In. mm In. mm Lbs./Ft. kg/m Lbs./Ft. kg/m
 (6) .375 (9.5) .030 (.7) .12 (.17) .15 (.21)
 (10) .500 (12.7) .035 (.9) .20 (.30) .26 (.39)
 (15) .625 (15.9) .040 (1.0) .28 (.41) .38 (.56)
 (17) .750 (19.0) .042 (1.0) .36 (.53) .51 (.75)
 (20) .875 (22.2) .045 (1.1) .45 (.67) .66 (.98)
 (25) 1.125 (28.6) .050 (1.3) .65 (.97) 1.01 (1.50)
 (32) 1.375 (34.9) .055 (1.4) .88 (1.31) 1.42 (2.11)
 (40) 1.625 (41.3) .060 (1.5) 1.14 (1.69) 1.91 (2.83)
 (50) 2.125 (54.0) .070 (1.8) 1.75 (2.60) 3.09 (4.59)
 (65) 2.625 (66.7) .080 (2.0) 2.48 (3.69) 4.54 (6.75)
 (80) 3.125 (79.4) .090 (2.3) 3.33 (4.95) 6.28 (9.34)
 (90) 3.625 (92.1) .100 (2.5) 4.29 (6.38) 8.28 (12.32)
 (100) 4.125 (104.8) .110 (2.8) 5.38 (8.00) 10.57 (15.72)
 (125) 5.125 (130.2) .125 (3.2) 7.61 (11.32) 15.69 (23.34)
 (150) 6.125 (155.6) .140 (3.5) 10.20 (15.18) 21.81 (32.46)
 (200) 8.125 (206.4) .200 (5.1) 19.29 (28.70) 39.49 (58.89)
Dimensions taken from ASTM B88-83.

Copper Tubing (Type K) Data


Weight of Pipe
Nominal Tubing Size O.D. Size Wall Thickness Weight of Tubing Filled with Water
In. mm In. mm In. mm Lbs./Ft. kg/m Lbs./Ft. kg/m
 (6) .375 (9.5) .035 (.9) .14 (.21) .17 (.25)
 (10) .500 (12.7) .049 (1.2) .27 (.40) .32 (.47)
 (15) .625 (15.9) .049 (1.2) .34 (.50) .43 (.63)
 (17) .750 (19.0) .049 (1.2) .42 (.62) .56 (.83)
 (20) .875 (22.2) .065 (1.6) .64 (.95) .83 (1.23)
 (25) 1.125 (28.6) .065 (1.6) .84 (1.25) 1.18 (1.75)
 (32) 1.375 (34.9) .065 (1.6) 1.04 (1.55) 1.57 (2.34)
 (40) 1.625 (41.3) .072 (1.8) 1.36 (2.02) 2.10 (3.12)
 (50) 2.125 (54.0) .083 (2.1) 2.06 (3.06) 3.37 (5.01)
 (65) 2.625 (66.7) .095 (2.4) 2.92 (4.34) 4.92 (7.31)
 (80) 3.125 (79.4) .109 (2.8) 4.00 (5.95) 6.96 (10.35)
 (90) 3.625 (92.1) .120 (3.0) 5.12 (7.62) 9.02 (13.42)
 (100) 4.125 (104.8) .134 (3.4) 6.51 (9.69) 11.57 (17.22)
 (125) 5.125 (130.2) .160 (4.0) 9.67 (14.39) 17.67 (26.29)
 (150) 6.125 (155.6) .192 (4.9) 13.87 (20.60) 25.07 (37.27)
 (200) 8.125 (206.4) .271 (6.9) 25.90 (38.50) 45.40 (67.52)
Dimensions taken from ASTM B88-83.
1 cubic ft. of water weighs 62.41 lbs.
1 cubic meter of water weighs 999.97 kg.
1 gallon (U.S.) weighs 8.335 lbs.
1 liter weighs .999 kg

132 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

6.0 Reference Charts

Schedule 40 PVC Plastic Pipe Data


Weight of Pipe
Nominal Tubing Size O.D. Size Wall Thickness Weight of Tubing Filled with Water
In. mm In. mm In. mm Lbs./Ft. kg/m Lbs./Ft. kg/m
 (3) .405 (10.3) .068 (1.7) .04 (.06) .06 (.09)
 (6) .540 (13.7) .088 (2.2) .07 (.11) .11 (.17)
 (10) .675 (17.1) .091 (2.3) .10 (.14) .18 (.26)
 (15) .840 (21.3) .109 (2.7) .15 (.20) .25 (.40)
 (20) 1.050 (26.7) .113 (2.9) .20 (.30) .40 (.60)
 (25) 1.315 (33.4) .133 (3.4) .30 (.40) .70 (.90)
 (32) 1.660 (42.1) .140 (3.5) .40 (.60) 1.00 (1.50)
 (40) 1.900 (48.2) .145 (3.7) .50 (.70) 1.40 (2.00)
 (50) 2.375 (60.3) .154 (3.9) .60 (.90) 2.00 (3.00)
 (65) 2.875 (73.0) .203 (5.1) 1.00 (1.50) 3.10 (4.51)
 (80) 3.500 (88.9) .216 (5.5) 1.30 (2.00) 4.50 (6.70)
 (90) 4.000 (101.6) .226 (5.7) 1.60 (2.40) 5.90 (8.70)
 (100) 4.500 (114.3) .237 (6.0) 1.90 (2.80) 7.40 (11.00)
 (125) 5.563 (141.3) .258 (6.5) 2.80 (4.10) 11.40 (17.00)
 (150) 6.625 (168.3) .280 (7.1) 3.30 (4.90) 15.40 (23.00)
 (200) 8.625 (219.1) .322 (8.2) 5.30 (7.80) 26.90 (39.90)
 (250) 10.750 (273.0) .366 (9.3) 7.50 (11.10) 41.60 (61.80)
 (300) 12.750 (323.8) .406 (10.3) 10.00 (14.90) 58.50 (87.00)
Dimensions taken from ASTM B88-83.

Schedule 80 PVC Plastic Pipe Data


Weight of Pipe
Nominal Tubing Size O.D. Size Wall Thickness Weight of Tubing Filled with Water
In. mm In. mm In. mm Lbs./Ft. kg/m Lbs./Ft. kg/m
 (3) .405 (10.3) .095 (2.4) .05 (.08) .06 (.10)
 (6) .540 (13.7) .119 (3.0) .09 (.14) .12 (.18)
 (10) .675 (17.1) .126 (3.2) .10 (.19) .16 (.28)
 (15) .840 (21.3) .147 (3.7) .10 (.20) .20 (.30)
 (20) 1.050 (26.7) .154 (3.9) .20 (.40) .40 (.70)
 (25) 1.315 (33.4) .179 (4.5) .40 (.50) .70 (.90)
 (32) 1.660 (42.1) .191 (4.8) .50 (.80) 1.00 (1.60)
 (40) 1.900 (48.2) .200 (5.1) .60 (.90) 1.30 (2.00)
 (50) 2.375 (60.3) .218 (5.5) .90 (1.30) 2.20 (3.20)
 (65) 2.875 (73.0) .276 (7.0) 1.30 (2.00) 3.10 (4.70)
 (80) 3.500 (88.9) .300 (7.6) 1.80 (2.70) 4.60 (6.90)
 (90) 4.000 (101.6) .318 (8.1) 2.20 (3.20) 6.00 (8.90)
 (100) 4.500 (114.3) .337 (8.5) 2.60 (3.90) 7.60 (11.30)
 (125) 5.563 (141.3) .375 (9.5) 4.10 (6.10) 12.00 (17.80)
 (150) 6.625 (168.3) .432 (11.0) 5.00 (7.50) 16.30 (24.30)
 (200) 8.625 (219.1) .500 (12.7) 8.00 (11.90) 27.80 (41.30)
 (250) 10.750 (273.0) .593 (15.0) 11.90 (17.70) 43.20 (77.60)
 (300) 12.750 (323.8) .687 (17.4) 16.30 (24.30) 60.30 (89.80)
1 cubic ft. of water weighs 62.41 lbs.
1 cubic meter of water weighs 999.97 kg.
1 gallon (U.S.) weighs 8.335 lbs.
1 liter weighs .999 kg.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 133
Hilti MI/MQ Technical Guide

6.0 Reference Charts

6.2 Metric Conversions


and Equivalents
The Metric Conversion Act of 1975, as amended by the 5BCMF%JBNFUFST
Omnibus Trade and Competitiveness Act of 1988, establishes
Inch-Pound System Hard Metric Conversion Use for Soft Metric
the SI (System International) metric system as the preferred Inch mm Conversion mm
system of measurement in the United States. 1/4 6.35 6
5/16 7.94 8
Many products are currently manufactured and supplied in
3/8 9.52 10
SI or “hard” metric sizes such as MI and anchor bolts of 10
mm, 12 mm, 26 mm, etc. diameter. Where the Imperial sizes 1/2 12.70 12

are given, “soft” metric conversion can sometimes be used 5/8 15.88 16

CVUTQFDJՐDBMMZOPUXIFOTFMFDUJOHBESJMMCJUGPSJOTUBMMJOH 3/4 19.05 20

mechanical anchors, where it is critical to only use the 1 25.40 25

TQFDJՐFE*NQFSJBMPSNFUSJDEJBNFUFSCJU
5IFTPGUDPOWFSTJPO 1-1/4 31.75 32
diameters for anchor bolts is given by Table 1. Standard metric
conversion factors commonly used for modular support and
fastening products are given in Tables 2 and 3.

5BCMF*NQFSJBM6OJUTUP4*6OJUT 5BCMF4*6OJUTUP*NQFSJBM6OJUT
To Convert Into Multiply By To Convert Into Multiply By

Length Length

inch (in.) millimeter (mm) 25.4 millimeter (mm) inch (in.) 0.0394
foot (ft) meter (m) 0.3048 meter (m) foot (ft) 3.2808
Area Area

square inch (in. ) 2


square millimeter (mm )2
645.16 square millimeter (mm2) square inch (in2) 0.0016
square inch (in.2) square centimeter (cm2) 6.4516 square centimeter (cm2) square inch (in2) 0.155
square foot (ft ) 2
square meter (m ) 2
0.0929 square meter (m ) 2
square foot (ft ) 2
10.7639
Volume Volume

cubic inch (in.3) cubic centimeter (cm3) 16.3871 cubic centimeter (cm3) cubic inch (in3) 0.061
cubic foot (ft )
3
cubic meter (m )
3
0.0283 cubic meter (m ) 3
cubic foot (ft3) 35.3147
gallon (US gal) liter (L) 3.7854 liter (L) gallon (US gal) 0.2642
Force Force

pound force (lbf) newton (N) 4.4482 newton (N) pound force (lbf) 0.2248
pound force (lbf) kilonewton (kN) 0.0044 kilonewton (kN) pound force (lbf) 224.8089
Pressure Pressure

pound/square inch (psi) newton/square millimeter 0.0069 newton/square millimeter pound/square inch (psi) 145.04
(N/mm2)
mega pascal (MPa) pound/square inch (psi) 145.04
pound/square inch (psi) mega pascal (MPa)
mega pascal (MPa) KIP/square inch (ksi) 0.145
KIP/square inch (ksi) mega pascal (MPa) 6.8946
newton/square meter (N/m ) 2
pounds/square foot (psf) 0.0209
pounds/square foot (psf) newton/square meter (N/m2) 47.8801
Torque or Bending Moment
Torque or Bending Moment
OFXUPONFUFS /ɎN
foot pound (ft-lb) 0.7376
foot pound (ft-lb) OFXUPONFUFS /ɎN
1.3558
OFXUPONFUFS /ɎN
inch pound (in-lb) 8.8496
inch pound (in-lb) OFXUPONFUFS /ɎN
0.113
Diaphragm Shear
Diaphragm Shear
newton/meter (N/m) pounds/lineal foot (plf) 0.0685
pounds/foot (plf) newton/meter (N/m) 14.5939

134 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

7.0 Terms and Conditions of Sales

Terms and Conditions of Sale (U.S.)


Payment Terms: Net 30 days from date of invoice. Customer agrees to pay all costs incurred by Hilti in collecting any
EFMJORVFOUBNPVOUT JODMVEJOHBUUPSOFZȵTGFFT
Freight: All sales are F.O.B. Destination with transportation allowed via Hilti designated mode. Delivery dates are
estimates only. Additional charges for expedited shipments, special handling requirements, and orders
below certain dollar amounts shall be the responsibility of Customer. Fuel surcharges may apply depending
on market conditions.
Credit: "MMPSEFSTTPMEPODSFEJUBSFTVCKFDUUP$SFEJU%FQBSUNFOUBQQSPWBM
Return Policy: Products must be in saleable condition to qualify for return. Saleable condition is defined as unused items
JOPSJHJOBMVOEBNBHFEQBDLBHJOHBOEVOCSPLFORVBOUJUJFTBOEJOBTOFXDPOEJUJPO"MMSFUVSOTBSFTVCKFDU
to Hilti inspection and acceptance, and a $125 restocking charge if returned more than 90 days after
invoice date. Proof of purchase is required for all returned materials.
Ineligible Return: Special order products and discontinued items are not eligible for return or credit. Dated materials
are only returnable in case quantity and within 14 days after invoice date. In no event shall any
product be returnable or qualify for credit after 1 year from invoice date.
Warranty: Hilti warrants that for a period of 12 months from the date it sells a product it will, at its sole option and
discretion, refund the purchase price, repair, or replace such product if it contains a defect in material or
XPSLNBOTIJQ"CTFODFPG)JMUJȵTSFDFJQUPGOPUJGJDBUJPOPGBOZTVDIEFGFDUXJUIJOUIJTNPOUIQFSJPETIBMM
constitute a waiver of all claims with regard to such product.
THE FOREGOING WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED,
INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE. Hilti shall in no event be liable for, and Customer hereby agrees
to indemnify Hilti against, all claims related to special, direct, indirect, incidental, consequential, and any
other damages arising out of or related to the sale, use, or inability to use the product, including costs and
BUUPSOFZȵTGFFT
Order "DDFQUBODFJTMJNJUFEUPUIFFYQSFTTUFSNTDPOUBJOFEIFSFJO BOEUFSNTBSFTVCKFDUUPDIBOHFCZ)JMUJ
Acceptance: XJUIPVUOPUJDF"EEJUJPOBMPSEJGGFSFOUUFSNTQSPQPTFECZ$VTUPNFSBSFEFFNFENBUFSJBMBOEBSFPCKFDUFE
UPBOESFKFDUFE CVUTVDISFKFDUJPOTIBMMOPUPQFSBUFBTBSFKFDUJPOPGUIFPGGFSVOMFTTJUDPOUBJOTWBSJBODFT
in the terms of the description, quantity, price or delivery schedule of the goods. Orders are not deemed
“accepted” by Hilti unless and until it ships the associated items.
Domestic Origin: Origin information may be obtained by written request to Hilti, Inc., Contract Compliance, P. O. Box 21148,
5VMTB 0LMBIPNB)JMUJȵT2VBMJUZ%FQBSUNFOUQFSTPOOFMBSFUIFPOMZJOEJWJEVBMTBVUIPSJ[FEUPXBSSBOU
the country of origin of Hilti products.
Business Size: Hilti is a large business.
Prices: Prices are those stated on the order, and unless otherwise noted are based on purchasing all items on the
order — pricing for individual products may vary for purchases of different quantities or item combinations.
Hilti does not maintain most favored customer records, makes no representation with respect to same, and
SFKFDUTBOZQSJDFXBSSBOUZUFSNTQSPQPTFECZ$VTUPNFS)JMUJTQVCMJTIFEOFUQSJDFMJTUJTTVCKFDUUPDIBOHF
without notice.
Consent to All transactions made pursuant hereto shall be deemed to have been made and entered into in Tulsa,
Jurisdiction: Oklahoma. Any and all disputes arising directly or indirectly from such transactions shall be resolved in
the courts of the County of Tulsa, State of Oklahoma, to the exclusion of any other court, and any resulting
KVEHNFOUNBZCFFOGPSDFECZBOZDPVSUIBWJOHKVSJTEJDUJPOPGTVDIBOBDUJPO"MMUSBOTBDUJPOTTIBMMCF
governed by and construed in accordance with the laws of the State of Oklahoma.
Indemnification: $VTUPNFSIFSFCZBHSFFTUPJOEFNOJGZ)JMUJGPSBOZDPTUT JODMVEJOHBUUPSOFZȵTGFFT JODVSSFECZ)JMUJBTB
result, in whole or in part, of any violation by Customer of any Federal, State or Local statute or regulation,
PSPGBOZOBUJPOBMMZBDDFQUFETUBOEBSE*UTIBMMCF$VTUPNFSȵTTPMFSFTQPOTJCJMJUZUPDPNQMZXJUIBMM
applicable laws and regulations regarding the handling, use, transportation, or disposal of products upon
taking possession of same.
Convert Check to When you provide a check as payment, you authorize Hilti to use information from your check to make
Eft: a one time electronic fund transfer from your checking account or to process the payment as a check
transaction. When we use information from your check to make an electronic fund transfer, funds may be
withdrawn from your account as soon as the same day we receive your payment, and you will not receive
your check back from your financial institution.
Authorization: HILTI LEGAL DEPARTMENT PERSONNEL ARE THE ONLY INDIVIDUALS AUTHORIZED TO MODIFY THESE
TERMS AND CONDITIONS, WARRANT PRODUCT SUITABILITY FOR SPECIFIC APPLICATIONS, ACCEPT
INFORMATION ON THE POTENTIAL FOR CONSEQUENTIAL DAMAGES, OR EXECUTE CUSTOMER
DOCUMENTS, AND ANY SUCH ACTION IS NULL AND VOID UNLESS IN WRITTEN FORM SIGNED BY
SUCH INDIVIDUAL. HILTI SALES REPRESENTATIVES (INCLUDING ACCOUNT MANAGERS, REGIONAL
MANAGERS, AND CUSTOMER SERVICE REPRESENTATIVES) HAVE NO SUCH AUTHORITY.

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 135
Hilti MI/MQ Technical Guide

7.0 Terms and Conditions of Sales

Terms and Conditions of Sale (Canada)


Payment Terms: Net 30 days from date of invoice. Customer agrees to pay all costs incurred by Hilti in collecting any
EFMJORVFOUBNPVOUT JGBOZ JODMVEJOHSFBTPOBCMFBUUPSOFZȵTGFFT

Freight: Sales are F.O.B. Destination Point with transportation allowed via Hilti designated mode. Additional charges
may apply for expedited delivery, special handling requirements, and orders under certain dollar limits. Fuel
surcharges may apply depending on market conditions.

Credit: "MMPSEFSTTPMEPODSFEJUBSFTVCKFDUUP$SFEJU%FQBSUNFOUBQQSPWBM BOE$VTUPNFSBHSFFNFOUUPUIFTF


Terms and Conditions of Sale.

Return Policy: Products must be in saleable condition to qualify for return. Saleable condition is defined as unused items
JOPSJHJOBMVOEBNBHFEQBDLBHJOHBOEVOCSPLFORVBOUJUJFTBOEJOBTOFXDPOEJUJPO"MMSFUVSOTBSFTVCKFDU
to Hilti inspection and acceptance, and a $150 restocking charge if returned more than 90 days after invoice
date. Proof of purchase is required for all returned materials.

Ineligible Returns: Special order products and discontinued items are not eligible for return or credit. Dated materials are
only returnable in case quantity and within 14 days after invoice date. In no event shall any product be
returnable or qualify for credit after 1 year from invoice date.

Warranty: Hilti warrants that for a period of 12 months from the date it sells a product it will, at its sole option and
discretion, refund the purchase price, repair, or replace such product if it contains a defect in material or
XPSLNBOTIJQ"CTFODFPG)JMUJȵTSFDFJQUPGOPUJGJDBUJPOPGBOZTVDIEFGFDUXJUIJOUIJTNPOUIQFSJPETIBMM
constitute a waiver of all claims with regard to such product.

THE FOREGOING WARRANTY IS IN LIEU OF AND CUSTOMER WAIVES ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF
MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, AND THE SALE OF GOODS ACT AND
ANY SIMILAR STATUTE OF ANY PROVINCE.

Title to Product: Title to product remains with Hilti until the total invoiced price of product is paid.

Prices: $VTUPNFSBHSFFTUP1BZ)JMUJUIFQSJDFTTFUPVUPO)JMUJȵTJOWPJDF$VTUPNFSBHSFFTUPQBZUBYFTBT
indicated on the invoice unless Customer provides acceptable exemption certificates.

Indemnification: Customer agrees to use product at its own risk and to indemnify Hilti against all liabilities, including legal
fees, to third parties arising out of the use, inability to use, or possession thereof. Hilti shall in no event be
liable for special, incidental, consequential, or any other damages, regardless of fault.

Changes: Only Hilti legal department personnel are authorized to modify these Terms and Conditions of Sale or
NPEJGZDSFEJUUFSNT5FSNTBSFTVCKFDUUPDIBOHFCZ)JMUJXJUIPVUOPUJDF

Cash Sales: Payment in full is due prior to goods being released.

Quotations: These Terms and Conditions of Sale apply once Customer agrees to purchase product. Quotations
on special promotion products are only valid until end of promotion period. Quotations are based on
purchasing all items listed — pricing for individual products may vary for purchases of different quantities or
item combinations.

Convert check to When Customer provides a check as payment, it authorizes Hilti to use information from its check to make a
ETF: POFUJNFFMFDUSPOJDGVOEUSBOTGFSGSPN$VTUPNFSȵTDIFDLJOHBDDPVOUPSUPQSPDFTTUIFQBZNFOUBTBDIFDL
transaction. When Hilti uses information from the check to make an electronic fund transfer, funds may be
XJUIESBXOGSPN$VTUPNFSȵTBDDPVOUBTTPPOBTUIFTBNFEBZ)JMUJSFDFJWFTUIFDIFDLBOE$VTUPNFSXJMM
not receive its check back from the financial institution.

136 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

Notes

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 137
Hilti MI/MQ Technical Guide

Notes

138 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

Notes

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 139
Hilti MI/MQ Technical Guide

Notes

140 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

Notes

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 141
Hilti MI/MQ Technical Guide

Notes

142 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012
Hilti MI/MQ Technical Guide

Notes

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012 143
Hilti MI/MQ Technical Guide

Notes

144 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I MI/MQ Technical Guide 2012

You might also like