You are on page 1of 16

ISA Transactions xxx (xxxx) xxx–xxx

Contents lists available at ScienceDirect

ISA Transactions
journal homepage: www.elsevier.com/locate/isatrans

Practice article

Output-only modal analysis of wind turbine tower based on vibration


response under emergency stop
Aijun Hu, Jun Zhao, Ling Xiang∗
Department of Mechanical Engineering, North China Electric Power University, Baoding 071003, Hebei Province, China

A R T I C LE I N FO A B S T R A C T

Keywords: The identification technique of output-only modal parameters is proposed for the large wind turbine tower under
Output-only modal analysis emergency stop. Compared with the response of regular operating conditions, the immediate tower structural
Vibration response response under emergency stop much more resembles a state of free vibration, which is more appropriate for the
Wind turbine tower modal identification of the wind turbine tower. The vibration response is measured in the nacelle, which is easy
Emergency stop
to perform in the field modal test. The variational mode decomposition (VMD) is applied to decompose the
VMD
vibration response into several band-limited intrinsic mode functions. The free responses of decomposed func-
tions are extracted by applying the random decrement technique (RDT). Finally, the modal damping ratio and
natural frequency are identified from each free modal response by using the Hilbert transform method.
Simulations and a 1.5 MW wind turbine field modal test results verify the effectiveness of the proposed iden-
tification method. The main modal parameters of wind turbine, including weak modes, are effectively extracted
by using output-only vibration responses under emergency stop. The modal parameter identification method is
provided for the large wind turbine structure under the engineering condition.

1. Introduction hard work to perform excitation in field testing of large wind turbines.
It is a substantial challenge to carrying out modal tests on large
Over the decades, wind energy has recently gained much attention wind turbine structures. The operational modal analysis (OMA) is re-
from researchers [1]. With the sizes of modern wind turbines in- garded as a key technique for the large and flexible structures. The
creasing, their dynamic behaviors get more complicated. Analyzing and approach was formally documented for modal testing in 1986 [5]. The
experimentally measuring the modal parameters, natural frequency and OMA of structures subject to environment and natural excitations under
modal damping, for instance, of wind turbine structures became more operational states has attracted a lot of attention in engineering since
important to successful design and operation. The traditional Experi- 1990s [6]. The OMA method extracts modal parameters from me-
mental Modal Analysis (EMA) techniques have been widely developed chanical system responses only, so it is also called output-only modal
and employed in wind turbine structures, which extract modal para- analysis [7]. Several ambient excitations are considered in OMA test of
meters from input and output data. The different methods such as im- the wind turbine. Carne et al. have a series of study on modal parameter
pact hammer modal testing, single-input multiple-output (SIMO) and extraction from operating turbines with wind excitation, for example,
multiple-input multiple-output (MIMO) measurement were used to the cross spectra analysis for a 110 m Darrieus bladed vertical axis wind
extract modal parameters of the wind turbine [2]. A 600 kW wind turbine (VAWT) [5], the natural excitation technique (NExT) for a 34 m
turbine with 40 m hub-height is excited by shakers connected with Darrieus VAWT [8] and a two-bladed upwind horizontal axis wind
cables in EMA [3]. Structural response characteristics and modal turbine (HAWT) [9]. Wind excitation is also adopted in the OMA of a
parameters are reported using shake table test on a full-scale 65-kW 600 kW wind turbine with 40 m tall hub [3], a two blade 11 kW down-
wind turbine with 22.6-m hub height [4]. Step-relaxation excitation wind turbine with 18 m tubular steel tower [10], a 40 kW wind turbine
method is used by Carne [5] in the field modal test of a 110 m Darrieus with 21 m steel tower height [11]. Human power is also utilized to pull
bladed vertical axis wind turbine (VAWT). The step-relaxation forces the structure and excite the free vibration response of a 21 m tall steel
are applied to the wind turbine with a high strength cable and a diesel tower [11]. It is reported that sometimes a few modes cannot be well
winch, which is located on the ground 100 m from the base of the excited by the wind [3]. Ambient excitation (wave and wind) and
turbine. As the sizes of modern wind turbines increase, it is usually a overspeed stop test are performed in the modal analysis for a 3 MW


Corresponding author.
E-mail address: ncepuxl@163.com (L. Xiang).

https://doi.org/10.1016/j.isatra.2018.07.035
Received 30 November 2017; Received in revised form 24 July 2018; Accepted 26 July 2018
0019-0578/ © 2018 ISA. Published by Elsevier Ltd. All rights reserved.

Please cite this article as: Hu, A., ISA Transactions (2018), https://doi.org/10.1016/j.isatra.2018.07.035
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

offshore wind turbine with 72 m with hub height [12]. The first natural
frequency and modal damping are obtained in the condition measure-
ment [12]. The damping ratios at different tower level are identified
[13]. “Rotor-stop” tests are also used to obtain the natural frequency
and modal damping of offshore wind turbines at four offshore wind
parks [14]. Rotor-stop condition can cause obvious decay process of the
wind turbine.
Emergency stop is an ambient operating condition of wind turbine.
It is can be triggered by many events, a fault within the control system,
high grid loading or manually triggered by the emergency stop buttons
[15], for instance. The global motion and dynamic structural response
of the wind turbine can be activated during emergency stop. Compared
with the response of regular operating conditions, the emergency stop
can be treated as a step-relaxation. The large amount energy can be
input to the wind turbine. The immediate tower responses represent a
wider frequency range of high signal energy. So the response data can
be used to identify the wind turbine structures. In this paper, the
output-only responses under emergency stops are proposed for the
modal parameters identification of a 1.5 MW onshore wind turbine with Fig. 1. Schematic diagram of the proposed method.
70 m tower height.
Frequency domain and time domain technique still are the critical
organized as follow: Section 2 introduces the VMD algorithm, random
groups of output-only system identification methods. For example,
decrement technique (RDT) and Hilbert transform. Section 3 presents
Brincker et al. [16] used frequency domain decomposition (FDD) to
the numerical analysis results of two responses, which are damped free
practice modal identification from ambient responses. In next year,
vibration response without noise and with white Gaussian noise of a
Brincker et al. [17] enhanced frequency domain decomposition to
MDOF system. Section 4 dedicates the implementation procedure of the
identify damping. However, frequency domain methods are based on
proposed identification routine of the wind turbine tower, and the
Fourier transform, which is adapted to the time-period vibration sig-
modal analysis results are showed in this section. In the end, in section
nals, so the local characteristics for identification of time-varying
5, the conclusions are demonstrated and some further study direction
system may be erased. Because of the limitation, the time domain
proposals are discussed.
methods have further progressed. Some classical methods such as
Ibrahim time domain (ITD) method, its upgrade method and other
methods are illustrated and applied in literature [18–25]. The time 2. Identification algorithms
domain methods can directly use the measured vibration responses
from time-varying system, therefore, the disadvantages of the frequency Fig. 1 illustrates the schematic diagram for the modal parameter
domain methods, such as errors caused by aliasing, leakage and other identification using VMD-RDT method under emergency stop. The
reasons could be avoided. Yang et al. [26,27] performed the modal method consists of four main steps: 1) The vibration signal under
identification of linear structures through adopting Hilbert-huang emergency stop is acquired by accelerometers mounted in the nacelle.
transform (HHT) method. Subsequently, the identification method of 2) VMD is used to decompose the measured responses in time domain.
the instantaneous characteristics of the nonlinear multi-degree of 3) The random decrement technique (RDT) is used to obtain the free
freedom (MDOF) structures based on the Hilbert transform (HT) and responses from each modal response. Finally, the natural frequency and
the empirical mode decomposition (EMD) was presented by Huang and the modal damping ratio can be recognized from each modal free re-
Lou [28]. On the basis of EMD, Pines and Salvino [29] extracted phase sponse by using the Hilbert transform (HT) method. Each of these steps
information from transient signals in structural health monitoring. is described in the following sub-sections.
However, some deficiencies related to the EMD process is found in Ref.
[30]. Bao et al. [31] provided a novel improved Hilbert-Huang trans- 2.1. Variational mode decomposition (VMD) method
form (HHT) algorithm for identification of time-varying systems and
analysis of nonlinear structural response with closely spaced modes. EMD is widely used in non-stationary signal process. However, as a
The RDT-AMD (analytical mode decomposition, AMD) is reported for recursive decomposition model, EMD is known for limitations like
building system identification [32]. The effectiveness of variational mode mixing, end effect and sensitivity to sampling and noise.
mode decomposition (VMD) is validated by Abdollah et al. for shear Recently, Dragomiretskiy and Zosso proposed a novel and non-recur-
frame and footbridge system identification [33]. sively adaptive time-frequency analysis method, the variational mode
Based on the researches, this paper presents a new system identifi- decomposition (VMD). VMD can decompose a complex and real valued
cation routine that uses output-only vibration responses under emer- multi-component signal into a discrete number of sub-signals whose
gency stop to identify the parameters of the wind turbine tower. The bandwidths are estimated using the H1 Gaussian smoothness of the
VMD [34] is used to decompose the measured responses in time do- demodulation signal.
main, which consists of a series of modal responses. Then, the random The decomposition process of VMD is the process of solving varia-
decrement technique (RDT) is used to acquire the free responses from tional problems, which makes the sum of estimation bandwidth of each
each modal response. Finally, the natural frequency and the modal mode minimum. The resulting constrained variational problem for any
damping ratio can be recognized from each modal free response by given non-stationary input signal x(t) in VMD is written as
using the Hilbert transform (HT) method. The field modal test can ea-
2
sily be performed using accelerometer in the nacelle under emergency ⎧ min ⎧∑ ∂ δ (t ) +
stop condition. The large amount energy can be supplied by the

{uk },{ωk }⎨

k(t⎡

j
πt ) ∗u (t ) ⎤⎦ e
k
−jωk t
2⎬



emergency stop, which makes it suitable for the field test of large wind ⎪ s.t. ∑k uk = f
⎩ (1)
turbine structure with low modal frequencies. The modal parameters of
the dominant mode and weak modes of the wind turbine tower are Where ωk = {ω1, ω2, ⋯, ωK } is the center frequency of each intrinsic
identified by VMD-RDT method. The remainder of this paper is mode components, uk = {u1, u2, ⋯, uK } is the corresponding all intrinsic

2
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 2. The simulated signal (a) time waveform of the exponentially decayed components, (b) time waveform and amplitude spectrum of the simulated MDOF
response.

K
mode components, ∑k uk = ∑k = 1 uk represents the summation of whole
intrinsic mode components, and K is the number of the achieved in-
trinsic mode components. By using the Lagrangian multipliers λ (t ) and
quadratic penalty term α the variational model can be obtained. The
augmented Lagrange can be calculated as
2 2
j ⎤
L ({uk }, {ωk }, λ ) = α ∑ ∂t ⎡ ⎛δ (t ) + ⎞ ∗uk (t ) + f (t ) − ∑ uk (t )
k

⎣ ⎝ πt ⎥
⎠⎦ k
2 2

+ λ (t ), f (t ) − ∑ uk (t )
k (2)

Where α is the balancing parameter, f (t ) is the original signal and δ (t )


is the Dirac function. Because of the sensitivity of α for decomposition
results of VMD, the selection of value of α needs to consult the mor-
Fig. 3. Center frequency at different K of the simulated signal decomposition. phology of the vibration signal. Selecting reasonably value of α is cru-
cial in the practical application. In addition, the alternate direction
method of multipliers (ADMM) is used to describe the saddle point. In
other words, the constraint variational model (see Eq. (1)) could be

Fig. 4. Decompositions of numerical signal x(t) by VMD and EMD: (a) VMD of signal x(t), (b) EMD of signal x(t).

3
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 5. RDT and HT of BLIMF1 from VMD: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

Fig. 6. RDT and HT of IMF3 by EMD: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

Table 1
The theoretical and identified values of natural frequency and damping ratio.
Madal Parameters Theoretical value Identified results by VMD Identified results by EMD

Frequency/Hz Damping ratio/% Frequency/Hz Damping ratio/% Frequency/Hz Damping ratio/%

First mode 0.5 3.00 0.514 2.894 0.273 8.420


Second mode 1.8 1.00 1.796 0.921 0.794 2.262
Third mode 3.5 0.68 3.516 0.663 1.795 0.917


obtained by using ADMM. Hence, in the spectral domain, the all band- ∫0 ω uˆ k (ω) 2 dω
limited intrinsic mode functions (BLIMFs) gained from solutions can ωkn + 1 = ∞ .
∫0 uˆ k (ω) 2 dω (4)
calculated in Eq. (3), as shown below.

λˆ (ω) In literature [34] and [35], the VMD method is completely illu-
fˆ (ω) − ∑i ≠ k uˆ i (ω) + 2 strated. The VMD method is proved to have the amazing performance in
uˆkn + 1 (ω) = .
1 + 2α (ω − ωk )2 (3) regard to existing mode decomposition models. This method still can
accurately process vibration response data even from the strong back-
Eq. (4) is the description of center frequency ωk . The wiener filter is ground noise.
embedded in the VMD method because of owning some optimality for
decreasing the noise.

4
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 7. RDT and HT of BLIMF2 from VMD: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

Fig. 8. RDT and HT of BLIMF3 from VMD: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

2.2. Random decrement technique (RDT) Where tk is the starting time for each segment, M is an integer with
MΔt = T being the duration of each segment Δt is the time interval of
Random decrement technique (RDT), is a kind of method used to the modal response time history and x¨ jf (t ) is the jth free modal re-
extract the free response signal of structure. RDT is based on the su- sponse. Once the x¨ jf (t ) is obtained, the modal damping ratio and natural
perposition principle of linear system, using the statistical average frequency can be adopted by using the HT for the single-degree-of-
method to eliminate the random part, and filter out the deterministic freedom (SDOF) system.
free attenuation signal. RDT is simple to achieve and can realize the
real-time data analysis in the actual condition, so it has become a very
2.3. Hilbert transform (HT) modal parameters identification
mature technology of signal attenuation in structure extraction and has
been widely used in the analysis of the vibration mode and structure
The response of the system under ambient excitation is decomposed
damage detection.
Using the RDT, the free modal response from each BLIMF modal by VMD, and each band-limited intrinsic mode functions (BLIMF) after
RDT can be expressed as
acceleration response x¨j (t ) is gained. It should be noted that in order to
obtain L segments the threshold level should be definition, where L is n

the number of segments which have relation to the threshold level ẍs . BLIMFi (t ) = ∑ Ai0 e−ξi ωi t cos(ωdi t + θi0)
The jth free modal response x¨ jf (iΔt ) can be calculated from the en- i=1 (6)
semble average of all segments as
Where A0 and θi are constants which depend on the intensity of im-
L pulsive loading and the mass of the system. ωdi , ωi are the damped
1
x¨ jf (iΔt ) = ∑ x¨j (tk + iΔt ), i = 1,2, ⋯, M circular frequency and the undamped natural circular frequency, re-
L k=1 (5) spectively. ξi is the damping ratio. The analytical signal can be

5
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 9. Center frequency at different K with (a) SNR = 1 (b) SNR = 4/3 (c) SNR = 2 (d) SNR = 4.

differential operator to instantaneous phase, the modal parameters can


be solved as Eq. (9). At the end, the linear least-square fit procedures
could be applied to estimate natural frequency and damping ratio.

⎧ ln Ai (t ) = −ξi ωi t + ln Ai0
dθ (t )
⎨ ω (t ) = ωdi = dti (9)

3. Numerical simulation

In this section, VMD-RDT based method is used to recognize the


modal parameters of a simulated MDOF system. For a no-load linear
MDOF system, each of the damped free vibration response of the system
should be considered. All the modal responses are set according to as-
sumed to the real wind turbine tower parameters in the simulation. The
free vibration response comprises three exponentially decayed compo-
nents in the system, and the equation is shown below
−0.0942t sin(3.1397t + 0.314)
⎧ x1 (t ) = e
x2 (t ) = 2e−0.1131t sin(11.3091t )
⎨ −0.1495t sin(21.9905t + 0.628)
Fig. 10. Decompositions of numerical signal x(t) with Gaussian noise by VMD. ⎩ x3 (t ) = e (10)

The simulated signal is


calculated as below by using HT to each BLIMF.
x (t ) = x1 (t ) + x2 (t ) + x3 (t ) (11)
Zi (t ) = BLIMFi (t ) + jH (BLIMFi (t )) = Ai (t ) e−jθi (t ) (7) Fig. 2 shows time waveform and amplitude spectrum of the simu-
When the damping is relatively small, the instantaneous amplitude lated signal. Considering the existing of noises in the engineering test,
and the instantaneous phase can be written as the simulation is divided into two parts, response with and without
noise.
−ξ ω t
⎧ Ai (t ) = Ai0 e i i
⎨ 3.1. Free vibration response without noise of a MDOF system
⎩ θi (t ) = ωdi t + θi0 (8)

Introducing logarithmic operator to instantaneous amplitude and VMD is applied for decomposing the simulated MDOF response

6
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 11. RDT and HT of BLIMF1 from VMD: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

Fig. 12. RDT and HT of BLIMF2 from VMD: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

Fig. 13. RDT and HT of BLIMF3 from VMD: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

7
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Table 2
The identified results with different SNR value.
SNR 4 (K = 4) 2 (K = 4) 4/3 (K = 4) 1 (K = 5)

Modal parameters Frequency/Hz Damping ratio/% Frequency/Hz Damping ratio/% Frequency/Hz Damping ratio% frequency/Hz Damping ratio/%

1st mode 0.475 2.907 0.475 2.736 0.475 2.646 0.475 2.608
2nd mode 1.796 0.946 1.796 0.922 1.796 0.918 1.795 0.913
3rd mode 3.515 0.371 3.515 0.307 3.514 0.283 3.515 0.290

Fig. 14. The sensor placement of the wind turbine (a) schematic diagram (b) picture of the tail of the bed plate in the nacelle.

Fig. 15. The signals during emergency stop condition (a) the operation parameters, (b) vibration in the tail and middle bed plate.

signal into an ensemble of band-limited intrinsic mode functions removed in value K selection [38]. The detrended fluctuation analysis
(BLIMFs). For comparison, the EMD results are also supplied. (DFA) was adopted as an indicator for defining the number K in Ref.
In application, the parameters in VMD have significant effect on the [35]. Based on References [34,39], we analyze the center frequency to
decomposition results. Dragomiretskiy and Zosso [34] indicated that select the number of modes K in this paper. As the quadratic penalty
the number of modes K should be predefined, and the K could be tested term α, Reference [39] demonstrated that VMD could well retrieve all
by checking the spectral overlap between modes. The number K was the components when α was fixed to 2000. The value of α is varied from
selected based on experience in literature, for example, rotor-to-stator 1000 to 10000, and it can be calculated in the simulation. According to
rubbing [36] and seismic signal [37] analysis. The low and high fre- the results, α = 2000 is selected in this research.
quency vibrations that were not due to the structural vibration were The simulated signal (Eq. (11)) is decomposed by VMD with

8
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

different K value. The relationship between the center frequency and K


is shown in Fig. 3. It shows that the center frequencies of the first three
modes are the same value when K≥ 3. Since the center frequency is
estimated as the center-of-gravity of the mode's power spectrum [34],
the number K = 3 is selected in the VMD decompositions of the simu-
lated signal. Fig. 4 (a) shows the extracted BLIMFs by VMD. The red
dash lines depicts the original simulated signal in Eq. (10) and blue line
indicates the decomposed components. The BLIMF1, BLIMF2 and
BLIMF3 in Fig. 4 (a), which are decomposed by VMD are identical with
the original components x1 (t ) , x2 (t ) and x3 (t ) . Fig. 4 (b) shows the three
of six IMFs resulting from EMD. It can be seen that IMF1 and IMF2
cover more than one frequency components, and other IMFs are also
generated. Only IMF3 recovers the original component x1 (t ) approxi-
mately. Moreover, the endpoint effect of EMD method is apparently
obvious. It is verified that VMD is better than EMD in such signal de-
composing.
Further, the RDT and HT are applied to identify the modal para-
meters of the signal. What should be paid attention to is that low order
IMFs represent high frequency modes, and high order IMFs represent
low frequency modes in EMD. While in VMD, which is exactly the
Fig. 16. The vibration response of wind turbine tower from X1 sensor. opposite. Fig. 5 shows the recognition results of the first mode from
VMD, and Fig. 6 presents the results of IMF3 from EMD. The wave of
BLIMF1 after RDT is shown in Fig. 5 (a). Fig. 5 (b) shows that the in-
stantaneous frequency, amplitude of the mode and the corresponding
linear least-squares fit. It is found that the modal information is suc-
cessfully identified by applying the VMD. The first frequency is com-
puted to 0.514 Hz and the damping ratio is 2.894%. The results are
close to theoretical values which is shown in Table 1. But in Fig. 6 (b) it
is shown that the extracted mode from IMF3 decomposed by EMD come
into distortion phenomenon after 10 s, leading to the recognition errors.
Using this method, the first frequency is computed to 0.273 Hz and the
damping ratio is 8.420%, which have differences with theoretical va-
lues.
The second and third order modal parameters are further identified
using the VMD. Fig. 7 shows the recognition results of the second mode
from VMD. The wave of BLIMF2 after RDT is shown in Fig. 7 (a). Fig. 7
(b) shows the instantaneous frequency of the mode and the corre-
sponding linear least-squares fit. It can be also seen that the modal
information is successfully identified. The second frequency is com-
puted to 1.796 Hz and the damping ratio is 0.921%. The recognition
results of the third mode from VMD are shown in Fig. 8. The wave of
BLIMF3 after RDT is shown in Fig. 8 (a). The amplitude of the mode,
Fig. 17. Decompositions of the vibration signal from X1 sensor using VMD.
instantaneous frequency and the corresponding linear least-squares fit

Fig. 18. RDT and HT of BLIMF1 from X1: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

9
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 19. RDT and HT of BLIMF2 from X1: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

Fig. 20. RDT and HT of BLIMF3 from X1: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

are represented as shown in Fig. 8 (b). The third frequency is computed SNR = 2 Gaussian noise. When the number K is set to 4, the BLIMF1,
to 3.516 Hz and the damping ratio is 0.663%. Table 1 shows the BLIMF2 and BLIMF3 recover the original components x1 (t ) , x2 (t ) and
identified modal parameters of the signal x(t), so it is demonstrated that x3 (t ) . Further, the RDT and HT are applied to identify the modal
the VMD can effectively identify a MDOF system without noise. parameters of the signal. Fig. 11 shows the recognition results of the
first mode from VMD. The wave of BLIMF1 after RDT is shown in
Fig. 11 (a). The instantaneous frequency, amplitude of the mode and
3.2. Damped vibration response with white Gaussian noise of a MDOF the corresponding linear least-squares fit are shown in Fig. 11 (b). It can
system be seen the modal information is successfully identified. The first fre-
quency is computed to 0.475 Hz and the damping ratio is 2.736%.
The decomposition performance of VMD was better than that of Fig. 12 shows the recognition results of the second mode from VMD.
EMD in signal denoising [34]. In order to study the robustness of the The second frequency is computed to 1.796 Hz and the damping ratio is
proposed method, the white Gaussian noise with different SNR value is 0.922%. Fig. 13 shows the recognition results of the third mode from
added to the simulated signal as shown in Eq. (11). VMD. The third frequency is computed to 3.515 Hz and the damping
The simulated signal with different SNR value is decomposed by ratio is 0.307%.
VMD. The relationship between the center frequency and K is shown in The identification results in different SNR are shown in Table 2. It
Fig. 9. It shows that the center frequencies of the first three modes are can be seen the SNR affects the results of system identification. The
the same value when K≥ 5 (Fig. 9 (a)). Therefore, the number K = 5 is natural frequencies are well identified for different SNR value. But in
selected under SNR = 1. For other SNR signals, the number K = 4 is the third modal information, the damping ratios have differences with
selected from the Fig. 9 (b)-(d). theoretical values due to the influence of noise.
Fig. 10 depicts the VMD decompositions of the signal x(t) with

10
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

4. Modal identification of wind turbine tower

In working process of wind turbine, when the driving frequency


from engine or wind turbine blade is closed to the natural frequency of
wind turbine tower, the turbine tower will produce large vibration,
even resonance. The resonance will cause unimaginable harm, so it is
necessary to recognize the modal parameters of the wind turbine tower.
The operating field tests of a 1.5 MW onshore wind turbine with 70 m
hub height are explored by using accelerometer, and the vibration re-
sponses under emergency stop condition are analyzed by applying VMD
and RDT method to identify the modal parameters.
In the test, four ENDEVCO 7290A variable capacitance accel-
erometers are mounted in the middle and end of the bed plate in the
wind turbine nacelle. Fig. 14 shows the schematic diagram and the
picture of sensors placement. X is the wind direction (fore-aft (FA) di-
rection), Y is perpendicular to the nose direction (side-to-side (SS) di-
rection). The emergency stop is artificially triggered through the con-
trol system. The operation parameters and the vibration signals are
recorded with a sampling ratio of 1280 Hz. Fig. 15 shows the recorded
signals during the complete emergency stop process. The recorded
Fig. 21. The vibration response of wind turbine tower from X2 sensor. operation parameters (pitch angle, generator shaft rotating speed,
torque and yaw angle Fig. 15 (a)) are collected from the analog term-
inals of the control system in the test. During this test, the emergency
stop is triggered at about 26 s and the hydraulic brake is applied to stop
the generator shaft immediately. The pitch angle is changed from −1.2
to 88.8°and the rotating speed is decreased from about 1500 to 0 rpm in
a couple of seconds. Because of this sudden collective pitch variation,
the thrust dramatic change excites the tower mainly in the wind (FA)
direction. The vibration response of the SS direction accelerometer is
fainter than that of the FA direction (Fig. 15 (b)). Therefore the vi-
bration signals of the two FA direction accelerometers are used to
further analysis. At 39 s, the brake process is completed and the gen-
erator shaft rotating speed is decreased to 0 rpm. The rotor-gearbox-
generator system is at rest, so only the response of tower arousing by
emergency shutdown process and noise are included in the measured
vibration signal. The recorded data after 39 s of the two FA direction
accelerometers are selected to identify the modal information of the
tower.
The FA direction sensor in the middle of wind turbine's bed plate is
named X1, and the FA direction sensor in the tail is named X2. Fig. 16
shows the time waveform and amplitude spectrum of the vibration
Fig. 22. Decompositions of the vibration signal from X2 sensor using VMD.
response of the wind turbine tower from X1 sensor. The first three peaks
are marked in the amplitude spectrum. It can be seen the dominant
frequency of the dynamic response is clear, which is 0.3875 Hz, in

Fig. 23. RDT and HT of BLIMF1 from X2: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

11
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 24. RDT and HT of BLIMF2 from X2: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

Fig. 25. RDT and HT of BLIMF3 from X2: (a) mode wave by RDT, (b) the corresponding linear least-squares fit.

Table 3
The identified results of the vibration responses from X1 and X2.
Sensor X1 X2

Modal Frequency/Hz Damping Frequency/Hz Damping


parameters ratio/% ratio/%

1st mode 0.40 0.69 0.40 0.68


2nd mode 1.70 0.49 1.70 0.24
3rd mode 3.13 1.41 3.49 1.15

agreement with the first mode natural frequency. However, the other
order modal frequencies are faint and difficult to be recognized in ex-
periments. The proposed modal identification method above is applied
to obtain the modal parameters from the vibration responses.
Fig. 26. Decomposed result of EMD.
Fig. 17 shows the decompositions of vibration signal from X1 sensor
using VMD. The K value is set to 4 according to the selecting method in
simulation part. The original vibration signal from X1 is decomposed parameters of the signal. According to the principle of RDT, the selec-
into four modes. Fig. 18 shows the recognition results of the first mode tion of sample segments should contain the entire stationary modal
from VMD. Further, the RDT and HT are applied to identify the modal response for obtaining good estimation accuracy [40,41]. The duration
of the free decay response is chosen corresponding to frequency of the

12
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 27. EMD-RDT identification: (a) the first mode wave by RDT (b) the linear least-squares fit of the first mode (c)the second mode wave by RDT (d) the linear least-
squares fit of the second mode (c)the third mode wave by RDT (d) the linear least-squares fit of the third mode.

modal. The wave of BLIMF1 after RDT is shown in Fig. 18 (a). The shown in Fig. 19 (a). The amplitude of the mode, instantaneous fre-
amplitude of the mode, instantaneous frequency and the corresponding quency and the corresponding linear least-squares fit are exhibited in
linear least-squares fit are exhibited in Fig. 18 (b). It shows that the first Fig. 19 (b). The second frequency is computed to 1.70 Hz and the
modal information is identified. The first frequency is computed to damping ratio is 0.49%. Fig. 17 shows the recognition results of the
0.40 Hz and the damping ratio is 0.69%. Fig. 19 shows the recognition third mode. The wave of BLIMF3 after RDT is shown in Fig. 20 (a). The
results of the second mode from VMD. The wave of BLIMF2 after RDT is amplitude of the mode, instantaneous frequency and the corresponding

13
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Fig. 28. VMD identification: (a) the wave of BLIMF1 (b) the linear least-squares fit of BLIMF1 (c) the wave of BLIMF2 (d) the linear least-squares fit of BLIMF2 (c) the
wave of BLIMF3 (d) the linear least-squares fit of the wave of BLIMF3.

linear least-squares fit are exhibited in Fig. 20 (b). The third frequency 0.3875 Hz which is same as Fig. 16. Likewise, the other order modal
is computed to 3.13 Hz and the damping ratio is 1.41%. frequencies are faint and cannot be recognized, so the proposed modal
X2 FA direction sensor is mounted in the tail of wind turbine's bed identification method is applied to obtain the modal parameters from
plate. Fig. 21 shows the time waveform and amplitude spectrum of the the vibration responses. Fig. 22 shows the decompositions of vibration
vibration response from X2 sensor. It indicates that the dominant nat- signal from X2 sensor using VMD, where the original signal from X2 is
ural frequency of the dynamic response is clear, and the value is decomposed into four modes. Fig. 23 shows the recognition results of

14
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

Table 4 VMD-RDT-HT method except the third modal damping ratio. Thus, the
Identification results of EMD-RDT-HT and VMD-HT. validity of the proposed method is proved by the comparison result. At
method EMD-RDT-HT VMD-HT the same time, the large fluctuation is presented in the amplitude of the
first modal response of VMD-HT (left in Fig. 28 (b)) and the attenuation
Modal Frequency/Hz Damping Frequency/Hz Damping trend of the second and third modal response is not significant in
parameters ratio/% ratio/% Fig. 28 (c) and (e).
1st mode 0.40 0.61 0.40 0.53 The spectrum of the vibration responses (Figs. 16 and 21) indicates
2nd mode 1.64 0.32 1.69 0.21 that the first mode frequency is dominant. The amplitude of the second
3rd mode failed failed 3.45 0.14 and third mode is very small. However, the second modal response is
extracted after EMD (Fig. 27(c)) and the second and third modal re-
sponses are also extracted by VMD (Fig. 28 (c) and (e)). The results
the first mode from VMD. The wave of BLIMF1 after RDT is shown in indicate the existence of the weak modes. The identification results
Fig. 23 (a). The instantaneous frequency and amplitude of the mode show that the third modal parameters are failed to be identified by
and the corresponding linear least-squares fit are shown in Fig. 23 (b). It EMD-RDT-HT method and the attenuation trend of the second and third
is found that the first modal information is identified applying the VMD. modal response is not significant in the VMD-HT result. In fact, the
The first frequency is computed to 0.40 Hz and the damping ratio is purpose of RDT is to eliminate the random part and extract the de-
0.68%. Fig. 24 shows the recognition results of the second mode from terministic free attenuation signal from the response. Therefore, the
VMD. The wave of BLIMF2 after RDT is shown in Fig. 24 (a). The identification accuracy of the decomposed responses by VMD can be
amplitude of the mode, instantaneous frequency and the corresponding improved after RDT process.
linear least-squares fit are exhibited in Fig. 24 (b). The second fre-
quency is computed to 1.70 Hz and the damping ratio is 0.24%. Fig. 25 5. Conclusions
shows the recognition results of the third mode from VMD. The wave of
BLIMF3 after RDT is shown in Fig. 25 (a). The amplitude of the mode, Emergency stop is utilized to excite the response of large wind
instantaneous frequency and the corresponding linear least-squares fit turbine in field modal testing. The global motion and dynamic struc-
are exhibited in Fig. 25 (b). The third frequency is computed to 3.49 Hz tural response of the wind turbine are activated during emergency stop.
and the damping ratio is 1.15%. The output-only response under emergency stop is adopted for the
The identification results of X1 and X2 sensors are shown in Table 3. operational modal parameter identification of large wind turbine tower.
It can be seen that the first two modal frequencies and the first mode The VMD-RDT modal parameter identification method is proposed in
damping ratio identified from two sensors in same order are consistent this paper. The output-only vibration responses under emergency stop
exactly, and the third mode frequency and the last two modal damping are analyzed. In simulations, it is shown that the VMD scheme clearly
ratios have a little difference between the two sensors. Combining the outperforms EMD with regards to sampling and noise robustness. The
spectrum of the two response signals, it can be seen that the first mode field test shows that the first mode of the wind turbine tower is domi-
is dominant in the spectrum. The amplitude of the first mode frequency nant and other modes are weak. The main modal parameters, including
is much higher than that of the second and third mode. Due to the two weak modes of a 1.5 MW onshore wind turbine with 70 m hub
environment noise, small difference occurs in the modal parameters height are obtained through the proposed identification procedure. It
identification of the low amplitude mode. It can be concluded that the indicates that field modal test can easily be performed using accel-
first three mode parameters, including two weak modes (second and erometer in the nacelle under emergency stop condition. The effec-
third) are identified by the proposed VMD-RDT method through two tiveness is verified through comparison analysis. The proposed identi-
accelerometers located on the different position and the results are fication technique can be applied to the large and flexible structures.
coincident approximately. The sensors are commonly mounted on the The more veracious mode parameter identification method of the very
turbine tower at different level in modal parameter test [12,13]. Con- low energy mode is necessary to be further investigated.
sidering the large wind turbine with 70 m tower height, it is a hard
work in sensor mounting and long signal cable locating. With the Acknowledgements
proposed method, the operational mode parameters of the wind turbine
tower can be identified using only one accelerometer in the nacelle This work was supported by the National Natural Science
under emergency stop condition. It can be easily performed in the field Foundation of China (Grant No. 51475164 and No. 51675178).
modal test.
The EMD-RDT-HT and VMD-HT are used to identify the structure References
parameters. The measured vibration responses of X2 are processed in
the two methods for comparison. Fig. 26 shows the three components of [1] Liu WY, Tang BP, Jiang YH. Status and problems of wind turbine structural health
eight IMFs decomposition resulting from EMD. The identified results of monitoring techniques in China. Renew Energy 2010;35:1414–8.
EMD-RDT-HT are presented in Fig. 27. The first frequency is computed [2] Baqersad J, Poozesh P, Niezrecki C, et al. Comparison of modal parameters ex-
tracted using MIMO, SIMO, and impact hammer tests on a three-bladed wind tur-
to 0.40 Hz and the damping ratio is 0.61%. It can be seen the first modal bine. Conference proceedings of the society for experimental mechanics series, to-
frequency is in accordance with the result in Table 3. And the damping pics in modal analysis II. vol. 8. 2014. p. 185–97. [Orlando, Florida USA].
ratio is close to 0.68% which is identified by the proposed method. The [3] Osgood R, Bir G, Mutha H, et al. Full-scale modal wind turbine tests: comparing
shaker excitation with wind excitation. Structural Dynamics and Renewable Energy
first modal parameter is identified by the EMD-RDT-HT. The second 2011;1:113–24. Springer New York.
frequency and damping ratio is computed to 1.64 Hz and 0.32% by the [4] Prowell I, Uang CM, Elgamal A, et al. Shake table testing of a utility-scale wind
EMD-RDT-HT (Fig. 26 (c) and (d)), respectively. The results are ap- turbine. J Eng Mech 2012;138(7):900–9.
[5] Carne TG, Lauffer JP, Gomez AJ. Modal testing of a very flexible 110m wind turbine
proximate to the values in Table 3. However, the third modal para-
structure. Proceedings of the sixth international modal analysis conference. 1988. p.
meters are failed to be identified by EMD-RDT-HT method. 848–55. Kissimmee, Florida, USA.
According to the VMD-HT method [33], the BLIMFs decomposed by [6] Zhang L, Wang T, Tamura Y. A frequency–spatial domain decomposition (FSDD)
VMD (Fig. 22) were directly used to parameter identification. The method for operational modal analysis. Mech Syst Signal Process
2010;24(5):1227–39.
amplitude of the mode, instantaneous frequency and the corresponding [7] Richardson M, Schwarz B. Modal parameter estimation from operating data. Sound
linear least-squares fit are exhibited in Fig. 28. The identification results Vib 2003:28–36.
of EMD-RDT-HT and VMD-HT are listed in Table 4. It can be seen the [8] James GH, Carne TG, Lauffer JP. The natural excitation technique (NExT) for modal
parameter extraction from operating structures. Int J Anal Exp Modal Anal
identified modal parameters by VMD-HT are very close to those of the 1995;10(4):260–77.

15
A. Hu et al. ISA Transactions xxx (xxxx) xxx–xxx

[9] Carne TG, James GH. The inception of OMA in the development of modal testing 2001;123(4):659–67.
technology for wind turbines. Mech Syst Signal Process 2010;24:1213–26. [26] Yang JN, Lei Y, Pan SW, Huang N. System identification of linear structures based
[10] Molinari M, Pozzi M, Zonta D, et al. In-field testing of a steel wind turbine tower. on Hilbert–Huang spectral analysis. Part I: normal modes. Earthq Eng Struct Dynam
Structural Dynamics and Renewable Energy 2011;1:103–12. 2003;32(9):1443–67.
[11] Fujiyama C, Yonetsu K, Maeshima T, et al. Identifiable stress state of wind turbine [27] Yang JN, Lei Y, Pan SW, Huang N. System identification of linear structures based
tower-foundation system based on field measurement and FE analysis. Procedia on Hilbert–Huang spectral analysis. Part II: complex modes. Earthq Eng Struct
Engineering 2014;95:279–89. Dynam 2003;32(10):1533–54.
[12] Shirzadeh R, Devriendt C, Bidakhvidi MA, et al. Experimental and computational [28] Huang TL, Lou ML. System identification of nonlinear structures based on HHT.
damping estimation of an offshore wind turbine on a monopile foundation. J Wind Earthq Eng Eng Vib 2006;26(3):80–3.
Eng Ind Aerod 2013;120(120):96–106. [29] Pines DJ, Salvino LW. Structural health monitoring using empirical mode decom-
[13] Devriendt C, Jordaens PJ, Sitter GD, et al. Damping estimation of an offshore wind position and the Hilbert phase. J Sound Vib 2006;294(1–2):97–124.
turbine on a monopile foundation. Renewable Power Generation 2013;7(4):401–12. [30] Peng ZK, Peter WT, Chu FL. An improved Hilbert–Huang transform and its appli-
[14] Damgaard M, Ibsen LB, Andersen LV, et al. Cross-wind modal properties of offshore cation in vibration signal analysis. J Sound Vib 2004;286:187–205.
wind turbines identified by full scale testing. J Wind Eng Ind Aerod [31] Bao CX, Hao H, Li ZX, et al. Time-varying system identification using a newly im-
2013;116(5):94–108. proved HHT algorithm. Comput Struct 2009;87(23–24):1611–23.
[15] Bas J, Smith J, Carriveau R, et al. Structural response of a commercial wind turbine [32] Wang Z, Chen G. Analytical mode decomposition with Hilbert transform for modal
to various stopping events. Wind Eengineering 2012;36(5):553–69. parameter identification of buildings under ambient vibration. Eng Struct
[16] Brincker R, Zhang L, Andersen P. Modal identification from ambient responses 2014;59(2):173–84.
using frequency domain decomposition. Proceedings of the 18th IMAC. 2000. San [33] Bagheri Abdollah, Ozbulut Osman E, Harris Devin K. Structural system identifica-
Antonio, Texas, USA. tion based on variational mode decomposition. J Sound Vib 2018;417:182–97.
[17] Brincker R, Ventura C, Andersen P. Damping estimation by frequency domain [34] Dragomiretskiy K, Zosso D. Variational mode decomposition. IEEE Trans Signal
Decomposition. Proceedings of IMAC XIX. 2001. Kissimmee, USA. Process 2014;62(3):531–44.
[18] Ibrahim SR, Mikulcik EC. A method for the direct identification of vibration para- [35] Liu YY, Yang GL, Li M, et al. Variational mode decomposition denoising combined
meters from the free response. Shock Vib Bull 1977;47(4):35–42. the detrended fluctuation analysis. Signal Process 2016;125:349–64.
[19] Fukuzono K. Investigation of multiple-reference Ibrahim time domain modal [36] Wang YX, Markert R, Xiang JW, et al. Research on variational mode decomposition
parameter estimation technique MS. thesis University of Cincinnati; 1986. and its application in detecting rub-impact fault of the rotor system. Mech Syst
[20] Ku CJ, Cermak JE, Chou LS. Random decrement based method for modal parameter Signal Process 2015;60–61:243–51.
identification of a dynamic system using acceleration responses. J Wind Eng Ind [37] Xue YJ, Cao JX, Wang DX, et al. Application of the variational-mode decomposition
Aerod 2007;95(6):389–410. for seismic time-frequency analysis. IEEE Journal of Selected Topics in Applied
[21] Juang JN, Pappa RS. An eigensystem realization algorithm for modal parameters Earth Observations and Remote Sensing 2016;9(8):3821–31.
identification and model reduction. J Guid Contr Dynam 1985;8(5):620–7. [38] Zhang YC, Liu KP, Qin L, et al. An Deterministic and probabilistic interval predic-
[22] Brown DL, Allemang RJ, Zimmerman R, Mergeay M. Parameters estimation tech- tion for short-term wind power generation based on variational mode decomposi-
niques for modal analysis. Society of Automotive Engineers Technique Paper tion and machine learning methods. Energy Convers Manag 2016;112:208–19.
790221 1979. [39] Wang Y, Markert R. Filter bank property of variational mode decomposition and its
[23] Vold H, Kundrat J, Rocklin GT, Russel RA. Multi-input modal estimation algorithm applications. Signal Process 2015;120:509–21.
for mini-computers SAE Technical Paper Series, No. 820194 1982. [40] Yang JN, Lei Y, Lin S, et al. Identification of natural frequencies and dampings of in
[24] Gautier PE, Gontier C, Smail M. Robustness of an ARMA identification method for situ tall buildings using ambient wind vibration data. J Eng Mech
modal analysis of mechanical systems in the presence of noise. J Sound Vib 2004;130(5):570–7.
1995;179(179):227–42. [41] Perez-Ramirez CA, Amezquita-Sanchez JP, Adeli H, et al. New methodology for
[25] Peeters B, De Roeck G. The Identification of Mechanical Systems:stochastic system modal parameters identification of smart civil structures using ambient vibrations
identification for operational modal analysis: a review. J Dyn Syst Meas Contr and synchrosqueezed wavelet transform. Eng Appl Artif Intell 2016;48:1–12.

16

You might also like