SIPROTEC SIP · 2004
Numerical Protection Relays
Editorial

SIPROTEC –
more than just protection
ONE bay, ONE IED (Intel- This is the latest edition of the printed SIPROTEC Catalog. This
ligent Electronic Device) edition - which is now available - contains many suggestions by our
Siemens is the world mar-
ket leader in delivering readers, along with information regarding innovations and supple-
combined protection & mentary products. The SIPROTEC Catalog is also available on
control relays. We provide
CD ROM.
control functionality with
the CFC (Continuous func-
tion chart), which is ac-
One of the new highlights is the SIPROTEC protection relays with
cepted as state-of-art in IEC 61850 communication. IEC 61850 was created by relay experts
industrial automation and manufacturers alike. The goal of this standard is to achieve an
(SIMATIC STEP 7) and
makes the life for the pro- object-oriented communication structure within substations.
tection engineers easier. SIPROTEC protection relays and bay control units are the first to
ONE DIGSI feature the IEC 61850 standard. With the substation configurator, a
Parameterisation - Software part of DIGSI 4, SIPROTEC units as well as other makes can be
serves all products
Siemens is the first supplier configured in accordance with IEC 61850.
to meet this strong
customer demand to have
one software for all
protection products. DIGSI
can handle previous
versions and the bus-bar This SIPROTEC Catalog is supplemented by multimedia computer
protection while providing animation tools.
unrivalled functionality.
+ CD-ROM “SIPROTEC 4 you – Features, Applications, Relays”
ONE single source for all
products and services + CD-ROM “SIPROTEC 4 you – Start Up”.
Siemens provides a full
product range for all mar- + CD-ROM “SIPROTEC 4 you – IEC 61850 & ETHERNET”.
ket segments. In order to
provide optimal services You can order the printed SIPROTEC Catalog (and all the CD
we have concentrated re- ROMs) via the Internet free of charge. Please fill in a form at
sources for important func-
www.siprotec.com/catalog. You may also consult your Siemens
tions, e.g. one product
management, one product representative or send us an e-mail (support@ptd.siemens.de).
development, one factory,
etc. We will support you in This catalog will assist you by increasing your understanding of our
planning, engineering, products and therefore help you to optimally and conveniently
commissioning, relay
co-ordination, type test, utilize the available features and functionality. We wish you a pleas-
etc. all over the world. ant and productive experience with SIPROTEC.

Bernhard W. Niessing
Vice President
Protection and Power Quality
Contents
Product Selection 1

Overview 2

Operating Programs 3
SIPROTEC Communication 4
Numerical Protection Relays
Overcurrent Protection 5

Distance Protection 6

Line Differential Protection 7

Transformer Differential Protection 8

Busbar Differential Protection 9

Relays for Various Protection Applications 10

Generator Protection 11

Motor Protection 12

Bay Units and Power Quality 13

Relay Communication Equipment 14

Test Equipment and Accessories 15

Catalog SIP · 2004 Appendix 16


Supersedes Catalog SIP · 2003

© Siemens AG 2004
1

Product Selection Page

Relay Functions 1/2


1 Product Selection

Relay Functions

1 –

Pilot wire differential


Line differential

Overcurrent

Differential
Distance

7SD600

7SD610

7UT512
7UT513
7UT612
7UT613
7SA513
7SA522

7SJ600
7SJ602

7VH60

7UT63
7SS60
7SS52
7SJ45
7SJ46

7SJ61
7SJ62
7SJ63
7SJ64
7SD5
7SA6

Protection functions Type


ANSI No.* Description –
14 Locked rotor protection – – – – – – – – – – l l l l – – – – – – – –
21 Distance protection, phase n n n – l – – – – – – – – – – – – – – – – –
21N Distance protection, earth (ground) n n n – l – – – – – – – – – – – – – – – – –
21FL Fault locator n n n – l – – – – – – l l l – – – – – – – –
24 Overfluxing (V/f protection) – – – – – – – – – – – – – – – – – – l l – –
25 Synchronizing, synchronism check l l l – l – – – – – – – – l – – – – – – – –
27 Undervoltage – l l – l – – – – – – l l l – – – – – – – –
27/34 Stator earth fault 3rd harmonic – – – – – – – – – – – – – – – – – – – – – –
32 Directional power – – – – – – – – – – – – – l – – – – – – – –
32F Forward power – – – – – – – – – – – – – l – – – – – – – –
32R Reverse power – – – – – – – – – – – – – l – – – – – – – –
37 Undercurrent or underpower – – – – – – – – – l n n n n – – – – – – – –
40 Loss of field – – – – – – – – – – – – – – – – – – – – – –
46 Load unbalance, negative phase- – – – – – – – – n n n n n n – – – l – l – –
sequence overcurrent
47 Phase-sequence voltage n n n – n – – – – – – n n n – – – – – – – –
48 Motor starting protection – – – – – – – – n l l l l l – – – – – – – –
49 Thermal overload – – l – n n – – n n n n n n – n n n n n – –
49R Rotor thermal protection – – – – – – – – n n n n n n – – – – – – – –
49S Stator thermal protection – – – – – – – – n n n n n n – – – – – – – –
50 Instantaneous overcurrent n n n n n n n n n n n n n n – n n n n n – l

50N Instantaneous earth n n n – n n – – n n n n n n – – l n n n – l

fault overcurrent
50BF Breaker failure n l l – n l – – – n n n n n – – – l l l – n

51GN Zero speed and underspeed device – – – – – – – – – – – – – – – – – – – – – –


51 Overcurrent-time relay, phase n n n n n n n n n n n n n n – n n n n n – l

51N Overcurrent-time relay, earth n n n – n n n n n n n n n n – – – n n n – l

51V Overcurrent-time relay, – – – – – – – – – – – – – – – – – – – – – –


voltage controlled
59 Overvoltage n l l – l – – – – – – l l l – – – – – – – –
59N Residual voltage earth l l l – l – – – – n – n n n – – – – – – – –
fault protection
59GN Stator earth-fault protection – – – – – – – – – – – – – – – – – – – – – –
64 100 % Stator earth-fault protection – – – – – – – – – – – – – – – – – – – – – –
(20 Hz)
64R Rotor earth fault – – – – – – – – – – – – – – – – – – – – – –

n Standard function
l Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers

1/2 Siemens SIP · 2004


1 Product Selection

Breaker management
Generator protection

synchronism check

Voltage, frequency
motor protection

Auto-reclosure +
Generator and

Breaker failure
Synchronizing
7UM511
7UM512
7UM515
7UM516

7RW600
7VK512

7SV512
7SV600
7UM61
7UM62

7VK61

7VE51
7VE6
Protection functions Type
ANSI No.* Description –
14 Locked rotor protection – – – – n n – – – – – – –
21 Distance protection, phase – – – n n n – – – – – – –
21N Distance protection, earth – – – – – – – – – – – – –
21FL Fault locator – – – – – – – – – – – – –
24 Overfluxing (V/f protection) – – n – n n – – – – – – n

25 Synchronizing, synchronism check – – – – – – n n n n – – –


27 Undervoltage n – n – n n l – – l – – n

27/34 Stator earth fault 3rd harmonic – n – – n n – – – – – – –


32 Directional power n n – – – n – – – – – – –
32F Forward power – – – n l n – – – – – – –
32R Reverse power – – – n n n – – – – – – –
37 Undercurrent or underpower – n – – – n – – – – – – –
40 Loss of field n n – n l n – – – – – – –
46 Load unbalance, negative phase- n n – n l l – – – – – – –
sequence overcurrent
47 Phase-sequence voltage – – – – n n – – – – – – –
48 Incomplete sequence, locked rotor – – – – l l – – – – – – –
49 Thermal overload n – – – n n – – – – – –
49R Rotor thermal protection – – – – – – – – – – – – –
49S Stator thermal protection n – – – n n – – – – – – –
50 Instantaneous overcurrent – – – – n n – – – – – – –
50N Instantaneous earth-fault – – – – n n – – – – – – –
overcurrent
50BF Breaker failure – – – – n n – – – – n n –
51GN Zero speed and underspeed dev. – – – – – n – – – – – – –
51 Overcurrent-time relay, phase n n – – n n – – – – – – –
51N Overcurrent-time relay, earth – – – – n n – – – – – – –
51V Overcurrent-time relay, n n – – n n – – – – – – –
voltage controlled
59 Overvoltage n n n – n n l – – l – – n

59N Residual voltage earth- n – – – n n – – – – – – –


fault protection
59GN Stator earth-fault protection – n n – n n – – – – – – –
64 100 % Stator earth-fault protection – n n – – l – – – – – – –
(20 Hz)
64R Rotor earth fault – n n – n n – – – – – – –

n Standard function
l Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers

Siemens SIP · 2004 1/3


1 Product Selection

Relay Functions

Pilot wire differential


Line differential

Overcurrent

Differential
Distance

7SD600

7SD610

7UT512
7UT513
7UT612
7UT613
7SA513
7SA522

7SJ600
7SJ602

7VH60

7UT63
7SS60
7SS52
7SJ45
7SJ46

7SJ61
7SJ62
7SJ63
7SJ64
7SD5
7SA6

Protection functions Type


ANSI No.* Description –
67 Directional overcurrent – – – – – – – – – – – n n n – – – – – – – –
67N Directional earth-fault overcurrent l l l – l – – – – n – n n n – – – – – – – –
67G Stator earth-fault – – – – – – – – – – – – – – – – – – – – – –
directional overcurrent
68 Out-of-step protection n l l – l – – – – – – – – – – – – – – – – –
74TC Trip circuit supervision – n n – n n – – n n n n n n – – – l l l – –
78 Out-of-step protection – – – – – – – – – – – – – – – – – – – – – –
79 Auto-reclosure l l l – l l – – l l l l l l – – – – – – – –
81 Frequency protection – n n – l – – – – – – l l l – – – – – – – –
81R Rate of frequency change protection – – – – – – – – – – – – – – – – – – – – – –
Vector jump supervision – – – – – – – – – – – – – – – – – – – – – –
85 Carrier interface/remote trip n n n l n n – – – – – – – – – – – – – – – n

86 Lockout function – n n n n n – – – – n n n n – – – n n n n –
87G Differential protection generator – – – – – – – – – – – – – – – n n n n n – –
87T Differential protection transformer – – – n l l – – – – – – – – n n n n n n – –
87BB Differential protection busbar – – – – – – – – – – – – – – – – – n n n n n

87M Differential protection motor – – – – – – – – – – – – – – – n n n n n – –


87L Differential protection line – – – n n n – – – – – – – – – – – n n n – –
87N Restricted earth-fault protection – – – – – – – – – – n n n n n – n l l l – –

n Standard function
l Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers
1/4 Siemens SIP · 2004
1 Product Selection

Breaker management
Generator protection

synchronism check

Voltage, frequency
motor protection

Auto-reclosure +
Generator and

Breaker failure
Synchronizing
7UM511
7UM512
7UM515
7UM516

7RW600
7VK512

7SV512
7SV600
7UM61
7UM62

7VK61

7VE51
7VE6
Protection functions Type
ANSI No.* Description –
67 Directional overcurrent – – – – n n – – – – – – –
67N Directional earth-fault overcurrent – – – – n n – – – – – – –
67G Stator earth-fault – – – – n n – – – – – – –
directional overcurrent
68 Out-of-step protection – – – n – l – – – – – – –
74TC Trip circuit supervision – – – – n n n – – – – – –
78 Out-of-step protection – – – n – n – – – – – – –
79 Auto-reclosure – – – – – – n n – – – – –
81 Frequency protection n n n – n n – – – l – – n

81R Rate of frequency change protection – – – – l l – – – l – – l

Vector jump supervision – – – – l l – – – l – – –


85 Carrier interface/remote trip – – – – – – – – – – – – –
86 Lockout function – – – – n n n – – l – – –
87G Differential protection generator – – – – – n – – – – – – –
87T Differential protection transformer – – – – – n – – – – – – –
87BB Differential protection busbar – – – – – – – – – – – – –
87M Differential protection motor – – – – – n – – – – – – –
87L Differential protection line – – – – – – – – – – – – –
87N Restricted earth-fault protection – – – – – l – – – – – – –

n Standard function
l Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers

Siemens SIP · 2004 1/5