EMERG1W User Instructions

Emergency Lighting Discharge Test solutions


EMERG2W have been developed to meet the needs
EMERG3W of the electrical industry. In accordance to
AS2293.1 and AS/NZS2293.2 ‘Emergency
EMERG4W Evacuation Lighting for Buildings’, a
discharge test circuit MUST be installed
in both existing and new installations.
EMERG.a1

Emergency lighting discharge test kits


Operation
Upon engaging the Green push button for The timer, to be set at 2 hours (2hrs for In accordance with AS2293.1 the test
1 second, the timer starts its operation initial commissioning, 90mins thereafter, facility is capable of being manually reset.
and energizes the contactor coil. The four completes its operation, de-energising If the red push button is pressed the
normally closed contacts open, initiating the contactor coil returning the contacts timer resets & is ready for the green push
operation of the emergency lights. to the normally closed position. button to start the timing cycle again.

These breakers are not supplied as


part of the standard test package.

GENERAL LIGHTING
FROM 6A MCB
CONTROL N
CIRCUIT 1
EM1-1
1 2
EMERGENCY LIGHTING
PUSH BUTTON
SVN391M
Red
1 2
GENERAL LIGHTING

CIRCUIT 2
EM1-2
3 4
EMERGENCY LIGHTING
A1
Green
3 4 B1 EET A2

EZN004 GENERAL LIGHTING


TIMER

CIRCUIT 3
EM1-3
5 6
EET EMERGENCY LIGHTING
15 18 A1 A2
EM1

ESC226 / ESC441
CONTACTOR
GENERAL LIGHTING

CIRCUIT 4
EM1-4
7 8
EMERGENCY LIGHTING

Kit contents in relation to product purchased


1 - Standalone solutions prewired in plastic enclosures
EMERG1W - Suitable for up to 4 separate test circuits EMERG2W - Suitable for up to 2 separate test circuits
QTY Cat.Ref Description Module width QTY Cat.Ref Description Module width
1 ESC441 Contactor - 4NC contacts, 40A 3 1 ESC226 Contactor - 2NC contacts, 25A 1
1 SVN391M Push button - 1NO (green) + 1NO (red) 1 1 SVN391M Push button - 1NO (green) + 1NO (red) 1
1 EZN004 Delay timer - 0.1sec to 10hrs 1 1 EZN004 Delay timer - 0.1sec to 10hrs 1
1 GD106T Enclosure - Plastic, 6 module 6 1 GD104T Enclosure - Plastic, 4 module 4
1 GP106T Door - suits GD106T, transparent - 1 GP104T Door - suits GD104T, transparent -
1 VZ313 Lock - suits GD106T - 1 VZ313 Lock - suits GD104T -

2 - Wired kit without enclosure for PERFORMA panelboards (Classic, Apex, Apex PLUS, Elite)
EMERG3W - Suitable for up to 4 separate test circuits EMERG4W - Suitable for up to 2 separate test circuits
QTY Cat.Ref Description Module width QTY Cat.Ref Description Module width
1 ESC441 Contactor - 4NC contacts, 40A 3 1 ESC226 Contactor - 2NC contacts, 25A 1
1 SVN391M Push button - 1NO (green) + 1NO (red) 1 1 SVN391M Push button - 1NO (green) + 1NO (red) 1
1 EZN004 Delay timer - 0.1sec to 10hrs 1 1 EZN004 Delay timer - 0.1sec to 10hrs 1

1 EMERG.a1
Lighting applications

2
Modern lighting systems generate high inrush currents. Therefore we recommend to use the table below to calculate the The information given should be considered as indicative and is provided on an “as is” basis. Considerable variations may occur
maximum number of lamps (or dual fittings) which can be connected to each pole of a Hager contactor on 230V 50Hz depending on the electrical installation and equipment used. Only experienced professionals with the expertise to determine the
characteristics of the electrical installation (value and duration of inrush currents, general characterics of the installation, types of loads,
circuits. etc.) may approve and implement a configuration, in accordance with the currently applicable installation standards. Hager accepts no
- From June 2014, Hager has improved the performance of 1 and 2 module contactors. The products identified on the liability for the use made of this information.
front face with the pictogram can accept a higher number of lamps.
Lamp wattage Rated output (per pole)
- For the 1 and 2 module contactors without the pictogram , divide the results given by 2. Type
(W) 25A ‘+’ 40A 63A
Discharge lamps
Lamp wattage Rated output (per pole) 50 28 32 50
Type
(W) 25A ‘+’ 40A 63A 80 18 24 37
High pressure mercury
Compact Fluorescent Lamps (CFL’s) 125 10 18 28
vapour lamps
5-7 27 49 76 250 6 10 15
(Low power factor <0.9)
CFL with external electronic ballast 9 - 11 26 40 63 400 2 6 9
15 - 26 22 36 57 700 0 4 5
5 - 15 54 86 135 50 22 26 40
CFL with integrated electronic ballast
18 - 26 40 63 100 80 16 22 34
Incandescent lamps High pressure mercury 125 10 15 23
40 57 76 120 vapour lamps 250 6 9 14
60 45 67 105 (High power factor >0.9) 400 2 5 8
75 38 63 100 700 0 3 5
100 28 41 65 1000 0 2 3
Tungsten Halogen Lamps 230V 150 18 29 45 18 20 18 21
Low pressure sodium
200 14 22 35 35 - 55 9 14 20
vapour lamps
300 10 15 23 90 6 9 14
(Low power factor <0.9)
500 6 9 14 135 - 180 4 6 8
1000 2 4 7 18 8 12 24
20 40 139 218 35 7 10 23
Low pressure sodium
35 26 82 129 55 5 10 19
vapour lamps
Halogen ELV (12 or 24V) 50 18 60 94 90 4 8 16
(High power factor >0.9)
with electronic transformer 75 12 52 82 135 2 5 7
100 6 35 55 180 2 5 6
150 4 20 31 35 24 30 50
Fluorescent tubes (T5) 50 15 22 34
15 - 20 30 70 100 70 12 18 28
36 28 60 90 High Pressure sodium lamps 110 10 14 22
40 26 60 90 (Low power factor <0.9) 150 8 10 16
Single - with starter 42 24 55 83 250 5 6 10
(Low power factor <0.9) 58-65 17 35 56 400 2 4 6
80 15 30 48 1000 1 2 3
115 10 20 32 35 18 31 50
140 10 16 26 50 18 22 35
15 - 20 20 36 57 70 12 16 25
36 20 34 53 High Pressure sodium lamps 110 8 13 21
Single - with starter
40 - 42 20 29 45 (High power factor >0.9) 150 6 8 13
(High power factor >0.9)
58 - 80 15 27 42 250 4 7 11
115 15 25 39 400 2 5 8
2 x 18 40 50 78 1000 1 2 3
2 x 20 38 50 78 35 30 42 55
2 x 36 30 44 69 70 17 26 36
2 x 40 26 40 63 Metal - Halide Lamp 150 12 14 20
Double - with starter
2 x 42 24 40 63 (Low power factor <0.9) 250 8 9 14
(Low power factor <0.9)
2 x 58 18 27 42 400 4 6 9
2 x 65 16 27 42 1000 0 3 5
2 x 80 14 22 35 35 18 22 39
2 x 115 10 16 25 70 13 22 39
2 x 18 22 34 53 Metal - Halide Lamp 150 8 12 22
2 x 20 22 29 45 (High power factor >0.9) 250 7 9 16
2 x 36 - 42 20 27 42 400 2 5 7
Double - with starter

Hager Electro Pty. Ltd. - Unit 1/170 Power St. Glendenning NSW 2761 - Tel. 1300 850 253 - www.hagerelectro.com.au
2 x 58 20 25 39 1000 1 2 3
(High power factor >0.9)
2 x 65 14 23 36 LED’s
2 x 80 14 20 31 4 - 12 54 86 135
2 x 115 10 17 25 17 - 22 40 63 101
LED 230V integrated Driver, Non dimmable, E27 / GU10
15 - 20 22 36 57 30 - 40 28 44 70
36 22 34 53 50 22 35 55
Single with electronic ballast nic 40 - 42 22 29 45 4 - 12 120 159 250
Electro LED
58 - 80 20 27 42 17 - 22 88 118 185
230V integrated driver
115 20 25 39 30 - 40 62 82 130
Dimmable, GU 10
2 x 18 22 34 53 50 48 65 102
2 x 20 22 29 45 100 5 6 9
LED high bay lighting
2 x 36 - 42 20 27 42 150 3 4 6
nic 230V integrated driver
Double with electronic ballast Electro 2 x 58 20 25 39 200 2 4 6
2 x 65 14 23 36 1-5 120 180 220
LED
2 x 80 14 20 31 7 - 10 120 160 200
12V external driver Dimmable
2 x 115 10 17 25 15 88 160 200

EMERG.a2