Professional Documents
Culture Documents
Example: If a symmetrically loaded construction grade 6¿12 in. nom. Douglas fir Larch
beam has a maximum end reaction of 30,000 lb, what is its unit stress in vertical
shear? Is the beam safe?
3D1a 1 Rectangular sections: Vv = 0.67 fv b d … ½
2 Circular sections: Vv = 0.59 fv d
Vv = end reaction (total vertical shear), lb. V=30,000 lb.
fv = max. unit stress in vert. shear for species and grade of wood, ? lb/in 2 .
From Table 3-10, fv for const. D.F. Larch=900 lb/in 2 .
b = minimum width or diameter of vertical shear plane, in. From Table 3-
11, actual width of 6 in. nom. timber=5.5 in.
d = min. depth of vert. shear plane, in. This includes notches.
From Table 3-11, actual depth of 12 in. nom. timber=11.5 in.
30,000 = 0.67 fv x5.5¿11.5 …
fv = 708 lb/in 2
708 fv = 900 ã OK
Example 1. If a uniformly loaded 6¿12 in. nom. construction grade Douglas fir Larch
beam has an end reaction of 30,000 lb. and is 12'-6" long, what is its unit stress in
horizontal shear? Is the beam safe?
3D1b 1
Rectangular sections: Vh = 0.5 fh b Lh … ½
2 Circular sections: Vh = 0.5 fh d Lh
3 Connections: Vh = fh b Lh
Vh = vertical shear end reaction, lb. Vh =30,000 lb.
fh = max. unit stress in horizontal shear for species and grade of wood, ? lb/in 2 . From
Table 3-10, fh for const. D.F. Larch=95 lb/in 2 .
b = width or dia. of horiz. shear plane, in. Nom. beam width=5.5 in.
Lh = length of horizontal shear plane, in. In symmetrically loaded beams,
Lh =0.5 L. 0.5 L=0.5x12'-6"=75 in.
30,000 = 0.67xfh x5.5x75 …
fh = 109 lb/in 2
109 >fv = 95 NG
5,400 = 95 x 5.5 Lh …
Lh = 10.3 in.
Example 1. What is the maximum bending moment for a beam of unseasoned No. 2
grade Douglas Fir South if its span is 16 feet and supports 3,600 lb? What is the beams
optima width and depth?
Step 1. Find the beam’s maximum moment, then its section modulus.
3D1c1 Ä= Mmax = fb Sx
Ä= applicable moment formula from Table 3-5. For uniform load, single span, supports
free (assumed), use M1
Mmax =0.125 W L.
Mmax =maximum moment of applied load, ? in-lb
W = weight of uniform load, if any, lb. W=3,600 lb.
P = weight of each point load, if any, lb. Not applicable.
L = length of span, in. 16'-0"¿12 in/ft=192 in.
fb = safe unit stress in bending for species and grade of wood, lb/in 2 . From Table 3-10,
fb for Douglas fir South=1,150
lb/in 2 ¿1.38 for No. 2 grade¿0.85 for unseasoned (seasoned in place). Ú fb
=1,150¿1.38¿0.85=1,350 lb/in 2 .
Sx = section modulus of beam section, ? in 3
(two equations, two unknowns ã first find Mmax , then Sx )
1. Mmax = 0.125 W L = 0.125¿3,600¿192 = 86,400 in-lb
2. Mmax = fb Sx ã 86,400 = 1,350 Sx … Sx = 64.0 in 3
Step 2. From Table 3-11 select the section moduli of standard lumber sizes that³64.0 in
3 , then list their sectional areas. The beam with the smallest area is the economical
section.
Nom. size, in¿in. Section modulus, in 3 C-S area, in 2
4¿12 ...................................... 73.8 .................. 39.4 ... ½
6¿10 ..................................... 82.7 .................. 52.3
8¿8 ....................................... 70.3 .................. 56.3
Economical section is 4¿12
3.D.1.d. Deflection
Deflection is often a more serious consideration in wood beams than steel or concrete
because today’s wood joists, beams, and girders commonly have sheetrock finishes
applied directly to their undersides, which can easily develop cracks along their taped
seams if the structure above is subjected to excessive deflection. In cantilevered wood
beams, maximum deflection on top of the structural members directly above their
supports can inflict similar cracking in the finished floors in the rooms directly above.
Example 1. What is the maximum deflection of a 4x10 Douglas Fir Larch beam with a
uniform load of 180 lb/lf on a 16 feet span? If the beams ubnderside is a plaster ceiling,
id the deflection allowable?
Example 2. What is the maximum span for 3-inch nominal double tongue and groove
Douglas Fir decking if it supports 55 lb/ft2 and the decking span pattern is alternating
spans (see figure 3.29)?
3D1d3 ðsp W L 3 = E t 3
ðsp = span pattern coefficient, as shown in Fig. 3-32. ð sp =0.13 for simple spans, 0.156
for random spans, 0.046 for alternate spans, and 0.054 for double spans. Here ð sp
=0.13.
W = total weight of load, 55 lb/ft 2
L = maximum length of span, ? in.
E = modulus of elasticity for species and grade of wood. From Table 3-10, E for Douglas
fir=1,100,000.
t = thickness of decking, in. t=3 in. nom.=2.5 in. 24 x 13 x 55 L 3 ² 1,100,000 x 2.5 3 …
L ² 46.4 in.
Note: This equation is for Îmax =1/240 L
3D1e P = ba bb fc sin â
These are lightweight wood I-beams with webs of usually 3 /8 to ™ in. plywood and
flanges of 1™ in. thick laminated lumber that are 1™ to 3™ in. wide. They are lighter
and more structurally uniform than solid wood joists, usually have no camber, and are
best for sloping and flat roofs. Typical live load deflection limit is L/480, connectors are
usually metal fasteners, web stiffeners are required under point loads and over
supports, they cannot support load-bearing walls, and they are usually uneconomical at
depths exceeding 18 in.
Lightweight I-joists are typically used in residential and light commercial construction,
and they are really the only economical roof framing for super insulated homes. The
design sequence below may also be used for the total design of any wood beam.
These trusses have parallel (or nearly so) top and bottom chords of wood separated by
webs of dimension lumber, plywood, or diagonal struts of tubular steel. Popularly used
for floors and flat roofs in small commercial buildings, they are feasible where depths
exceed 12 in., spans exceed 17 ft, extensive utility networks are run through their
depths, possibility of renovation exists, and where live loads are uniform and fairly
light. Typical spans range to 50 ft, depths to 22 in. for floors and 48 in. for roofs,
optimal depth-to-span ratios are 0.07 to 0.09, and typical spacing is 12, 13.7, 16, 19.2,
and 24 in. o.c. Maximum duct dimensions run about 0.6 depth, live load deflection is
usually limited to 1/240 span, and lateral bracing is required over all supports, under
point loads, and at uniform intervals along spans. Gluelams make good girders for
interior supports of continuous flat trusses.
The chief advantages of flat wood trusses are quick construction, nailable struts and
chords, large open spans, and flexible planning above and below the span. The
architect typically sizes these members by using tables in manufacturers’ catalogues,
or by specifying their out-line details and sending the specs to the manufacturer.
do so.
Example: a 5-1/8 in Douglas fir 24F gluelam of 1-1/2 inch lamination carries 960 lb/lf
on a 28 feet span. What is its depth for wet conditions of use?
3.D.3. Columns
Example: A timber post shown in Figure 3-37 has a load of 16.6 kips arriving
from above the beams; the end reactions of the four beams intersecting the
column are 7.2, 2.4, 7.2 and 4.2 kips; and the post absorbs a maximum wind
load of 0.6 kips through any one beam at a time. If the post id 10 feet- 8 inch
high and is no. 1 Fouglas Fir Larch, what is its economical section?
3D3 ax
X axis: dex = dx_min +0.33 (dx_max –dx_min )
dex = equivalent dimension of tapered column in X axis, ? in. For square and round
columns, X axis=Y axis.
dx_min = minimum dimension of tapered column in X axis, in. In X
axis, minimum dimension of 6 and 10=6 in.
dx_max = maximum dimension of tapered column in X axis, in. In X
axis, maximum dimension of 6 and 10=10 in.
dex = 6+0.33 (10–6) = 7.32 in.
3D3ay Y axis: similarly, dey = 8+0.33 (12–8) = 9.32 in.
Two kinds of bracing are commonly used in wood construction today: plywood
sheathing for light wood framing (discussed in Sec. 3.D.3.b. above), and diagonal wood
bracing for timber construction. In the latter, short wood members are usually placed
at 30-60° angles near the ends of beams and the tops of their post supports. Such
bracing eliminates rotation in the joint, which increases the support’s K factor and
shortens the effective length of both beam and support.
For example, if a 20 ft barn beam is connected to 45° braces only 2 ft in from each end,
the beam’s maximum moment decreases by 36%. Where wind and/or torsion loads are
severe in wood framing, shear walls may be required. These may be located at the
periphery of the plan where torsion moments of inertia are greatest, or at interior
locations where they can gather loads from both sides. Such walls must be built as
follows:
Ø The angle between the wall’s base and a diagonal from opposite
corners in each floor-to-ceiling height must not exceed 60°.
Ø Framing must be sheathed with minimum £ in. C-C (plugged) structural
grade plywood (1 1 /8 in. is better).
Ø All sheathing must be glued-and-screwed to all studs and plates.
There are many methods of bracing wood structure, both with sheathing on light wood
framing and diagonal bracing of timbers as well as combinations of the two. Some
conceptual possibilities are suggested in Sec. 3. C.3., Bracing.
Example 1: A two-Storey timber frame building near Boston has a shop with a two-car
garage door on the first floor and an office on the second. The 44x24 feet building is 20
Step 1. Determine the location and number of braces to resist the load in each floor.
One solution: install 45° compression No. 1 grade Douglas fir braces in each end wall at
corners B, C, E, and F, as shown in Fig. 3-38. The total number of braces is 8, with 1
brace resisting the wind from each side at each end of each ceiling.
Step 2. Compute the wind load resisted by each brace on each floor.
Here this load is calculated only for the upper floor braces. The equation below includes
forces due to wind moment and wind shear.
3D41 Vw h = vw ww (h+hp ) (1.5 h+0.5 hp )
Vw = lateral wind load resisted by each brace, ? lb
h = height of floor in which brace is installed, 10 ft
vw = max. unit wind load for local area. For Boston, vw =35 lb/ft 2 .
ww = width of wind load area resisted by brace, ft. Here ww =half
the length of building=44/2=22 ft.
hp = height of any part of building (parapet, roof, etc.) projecting vertically above upper
end of brace, ft. As peak of roof projects 6 ft above second floor, hp =6 ft.
Vw x10 = 35x22 (10+6) (1.5x10+0.5x6) = 22,200 lb
Step 3. Size each brace. Say the ends of each brace are located 3'-0" from each
corner, as shown in Fig. 3-39.
Vw = fc A cos â
Vw = lateral wind load resisted by brace, from Step 2, 22,200 lb
Step 1. Compute the maximum wind load against each shear wall.
3D42 Vw = 0.004 A× 2
Vw = max. wind load against end of each shear wall, ? lb
A = area of wind load surface (vertical projection), ft 2 . A=shear wall
spacing¿maximum story height=20'-0"x(9.0+11.5 in.
floor thickness=9.96 ft)=199 ft 2 .
× = maximum wind speed, mph. ×=100 mph.
Vw = 0.004 x 199 x 100 2 = 7,960 lb
Step 2. Compute the compressive strength of the shear wall, then compare this value
with the maximum wind load found in Step 1.
Vc = 2 fct (I H t 3 ) 0.25 cos 2 (tanÚ H /L )
Vc = compressive strength of shear wall, ? lb
Step 3. According to the Rule of Redundancy, braces are required at each corner of the
boundary framing. A good design is flat A36 steel angles on each side of each corner,
at least 2 bolts in each leg plus one at the corner or fulcrum, the bolts and legs
centered on the axes of the intersecting members, the angles on each side acting as
one brace, and the bolts acting in double shear, as shown in Fig. 3-40d.
As the wind load creates a shear force between the top member of the frame and the
tops of the vertical members at each end (a similar resisting force exists at the
bottom), the force resisted by each corner brace equals half the wind load, or
8,000/2=4,000 lb.
Step 4. Find the force resisted by each bolt in each leg. Try 2 bolts of equal dia. 6 in.
and 12 in. from fulcrum A, with a bolt at A.
Vc = ˜ Vb
Vc = lateral load resisted by each brace, from Step 3, 4,000 lb ˜ = no. of braces in wall,
2 units
Vb = lateral load resisted by each bolt in each brace leg, ? lb
4,000 = 2 Vb … Vb = 2,000 lb
Step 5. Size the bolts. From Table 3-17 find the smallest bolt at 7™ in. length (the
thickness of the boundary frame) and double shear íto frame that resists a load of
2,000 lb. ã 5 /8 in. dia.
Step 6. Size the angles. Each leg is a cantilever whose ‘support’ is the other leg at
fulcrum A, whose width is the angle’s thickness, whose depth is the angle’s width, and
whose loads are the bolts along its span (see Fig. 3-40d). By trying an angle thickness,
find its width
by the moment formula
Vb L1 +Vb L2 +…+Vb Lz = 0.167 fb b d 2
Vb = lateral load resisted by each bolt, from Step 4, 2,000 lb
L1 = length of angle leg from fulcrum to bolt 1, 6 in.
L2 = length of angle leg from fulcrum to bolt 2, 12 in.
… Lz = length of angle leg from fulcrum to each subsequent bolt, in.
Only two bolts ã not applicable.
fb = safe unit stress in bending for type of steel, lb/in 2 . From Table 3-19, fb for A36
steel=24,000 lb/in 2 .
3D5a1 V = ˜ fv
V = total load transmitted from member to support, ? lb/lf
˜ = no. of nails carrying load, 4
fv = safe strength of each nail carrying load, lb. From Table 3-15, safe strength of 16d
common nail into cedar=48 lb; then:
As nail is driven into end grain ................. multiply 48x0.67
As nail is driven at angle ..................... multiply abovex0.83
As nail is withdrawal .... multiply abovex0.33/in. penetration
Assume 2 in. penetration ......................... multiply abovex2
fv =48x0.67x0.83x0.33x2=18 lb
V = 18x4 = 72 lb
Example 2: A row of 2¿8 in. nom. deck joists are nailed to a 3x12 girder as shown in
Fig. 3-41. If the 2¿4 sill plate supports each joist’s end load of 420 lb at 16 in. o.c., what
is the required spacing for 16d common nails holding the sill plate to the girder? All
lumber is pressure-treated No. 1 grade Southern pine.
3D5a2 12 fv = V S
fv = safe strength of each nail carrying load, lb. From Table 3-15, safe lateral strength of
16d common nail into pressure-treated No.1 Southern pine=107¿1.20=128 lb.
V = total load transmitted from member to support, lb/lf.
V=4 lb per 16 in. o.c.=420x12/16=315 lb/lf.
S = maximum spacing between nails carrying load, ? in. o.c.
12x128 = Sx315 …
S = 4.87 in. o.c.
Example 1: A 40 in. railing is connected to a wood deck by 2x3 in. nom. balusters 10
in. o.c. as shown in Fig. 3-43. If the rail resists a horizontal force of 125 lb/lf and the
balusters are fastened by lag bolts to a 3¿12 in. nom. girder 1™ in. from its top, what
size bolts should be used? All lumber is const. grade Southern pine.
Example 2. A 3¡ in. long hook for holding a hanging potted plant is screwed 2 in. into
the bottom edge of a 2¿10 in. nom. red cedar greenhouse rafter. If the hook’s shank
has a similar diameter and threads as a standard no. 10 wood screw, what load will it
support?
What load will the hook support if it is screwed into the rafter’s side?
Solution. From Table 3-16, find ‘cedar’ in wood species group A, then in column A read
down to the withdrawal strength alongside “wood screw, no. 10.” The answer is 63
lb/in. penetrationx2 in. penetration= 126 lb. If the connector is screwed into the rafter’s
side, from
Table 3-16 multiply the above value by 1.40 ã 126x1.40=176 lb.
Example: If a 4¿10 girder of Douglas fir is connected to headers at each end by 18 ga.
face-mounted joist hangers, what load can each hanger carry if it has 10 nail holes in
its flanges and N10 nails are used?
3D5d V = ð f + fv ˜
V = joist end reaction on stamped metal hanger, ? lb
ðf = flange factor, lb. If face flanges fit over top of header, ðf for 18 ga. steel=580 lb, 16
ga.=840 lb, 14 ga.=1,230 lb, 12 ga.= 2,020 lb. As face-mounted hangers have no top
flanges, ðf =0.
fv = safe shear strength of each nail or screw, lb. fv for N10 nail (1 in.¿9 ga.)= 92 lb; N16
nail (2™ in.x8 ga.)=134 lb; N20 nail (2™ in.x6 ga.)=145 lb; #8x1¡ in. screw=76 lb.
Here fv =92 lb.
˜ = no. of nail holes in part of fastener attached to support or part attached to member,
whichever is less. Here ˜=10 units.
V Å 0+92x10 = 920 lb
3.D.5.e. Hinges
The size of a hinge is measured by its pin length, flange thick-ness and width, and
length of its screws. With heavy or much-used doors, use larger sizes than computed
below. With heavy-duty hinges (ones with thicker flanges and longer screws), slightly
smaller than
computed sizes may be installed.
3D5e 1
Hollow core doors: L Å 0.04 (h w t)0.63
2 Solid core doors: L Å 0.06 (h w t)0.63
L = total pin length of hinges, whether 2 or 3 per door, ? in.
h = height of door, in. h =96 in.
w = width of door, in. w =42 in.
t = thickness of door, in. t =1£ in.=1.75 in.
L Å 0.06 (96x42x1.75)0.63 Å 15.9 in.
2 or 3 hinges: If L ³ 7 in. ã 2 hinges
If L ³ 7 in, ³ 10 in. ã 2 or 3 hinges
If L ³ 10 in. ã 3 hinges … ½
15.9/3 hinges = 5.32 ã 5™ in. standard or 5 in. heavy duty hinge
As this is a much-used door, consider using 6 in. std. hinges
Example: The base of a 4 in. nom. Douglas fir Larch construction grade rafter sloping at
a pitch of 5 in 12 meets a tie beam of similar lumber as shown in Fig. 3-46. If the rafter
supports 6,600 lb, intersects the tie beam 2'-0" from each end, and the 4 in. nom. tie
beam is 16'-0" long, what is the beam’s minimum depth? How should the rafter and tie
beam be connected?
Step 2. Compute the allowable stress at the face of the notch. The equation below is
Hankinson’s formula.
fc fp = fa (fc sin 2 â+fp cos 2 â)