You are on page 1of 10

ISCHEBECK TITAN (me) L.L.C.

Scaffolding & Formwork Solutions


P.O. Box No. 22385
New Industrial Area - Ajman (United Arab Emirates)
Telephone (06) 74 83 101
Telefax (06) 74 83 102

STATICAL CALCULATION

First Floor - 550mm Thick Slab


4.2mx 5.4m Titan Table 7.450m Height
Project: Deira Mall

Contractor: United Engineering Construction

Ischebeck Titan Reference Drawing: 0001-00

Summary of Calculations

Drawing Sketch Page 2

Summary Page 3

T150 Beam Design Calculations Page 4

T150 Beam Results Page 5

T225 Beam Design Calculations Page 6

T225 Beam Results Page 7

Plywood Design Calculation Page 8

Titan Loadings Data Page 9

Components Properties Page 10

Total Pages: 1 of 10 ( Including Of This Page )

Reference No.:- DU18 032 Cal /102-0

Revision 0

Calculation Sheet Revisions:


Revision Description:- By Date
. . . .
. . . .
Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-2018 Page : 2 of 11 Revision .
. .
Drawing Sketch
Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-2018 Page : 3 of 10 By .
0 23-07-2018 .

Construction Loads:-

Maximum depth of slab ds = 550 mm

Density of concrete D = 25.0 kN/m3

Construction live load LL = 2.125 kN/m2

Dead load from decking DL = 0.50 kN/m2

Maximum construction Load Pmax = ( ds * D ) + LL + DL

Maximum construction Load Pmax = 16.375 kN/m2

Load Details

Load Applied On T150 Secondary Beam = Max. Construction Load x Secondary Beam Spacing

= 16.38 kN/m2 x 0.400 m

= 6.55 kN/m

Load Applied On T255 Primary Beam = Load per m2 x Influence Width on Main T225 Beam

= 16.38 Influence Width on Main T225 Beam

= 16.375 x 2.10 m = 34.39 kN/m

Leg Load:
Maximum Allowable Leg Load :

SWL- Titan Leg Floor To Soffit Ht.


With 3 Ledger Frame 7.450 m = 100.00 kN

Maximum Permissible Jack Extension


With Leg Load of 92.50 kN = 800 mm

Actual Jack Extension = 780 mm


Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-2018 Page : 4 of 10 By .
.

T150 Beam Design Calculations

Beam Properties
Beam Length 4.20 m Resistance Moment Bm = 11.9 kNm
4
Moment of Inertia 596.9 cm Max Shear Force = 30kN
2
Elastic Modulus 68900 N/mm

APPLIED LOADING
Consider Uniformly Distributed Load On = 4.20 m
Distributed Loads ; w = P x S = 7.99 kN/m

Maximun Span = 2.10 m x 7.99 kN/m = 16.78 kN/m

Maximum Reaction On Secondary Beam (In Software) = 16.80 kN/m

MAXIMUM LOADS & DEFLECTIONS ON BEAMS

Max. Sag BM 2.52 kNm @ 2.100 m < Allow. BM = 11.9 kNm ok!
Max. Hog BM -3.21 kNm @ 1.200 m < Allow. BM = 11.9 kNm ok!
Max. Sag Shear Force 9.57 kN @ 1.200 m
Max. Hog Shear Force -9.57 kN @ 4.200 m < Allow. Shear = 30.0 kN ok!
Max. Sag Deflection 2.70 mm @ 2.100 m
< Allow. δ = L/270 = 8.88 mm ok!
Max. Hog Deflection -0.20 mm @ 0.600 m
Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-18 Page : 5 of 10 By .
. . .
T150 BEAM RESULTS (Based On Beam Pal Software)
Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-18 Page : 6 of 10 By .
. . .

T225 Beam Design Calculations

T225 Beam Properties


Beam Length 5.40 m Resistance Moment Bm = 28.5 kNm
4
Moment of Inertia 2241 cm Max Shear Force = 71.3 kN
2
Elastic Modulus 68900 N/mm

APPLIED LOADING

Distributed Loads ;
w = 34.3875 kN/m

BEAM REACTIONS (+ve Up)

92.80 kN @ 0.000 m
92.80 kN @ 3.000 m Max Leg Load

MAXIMUM LOADS & DEFLECTIONS

Value Position
Max. Sag BM 14.20 kNm @ 2.700 m < Allow. BM = 28.50 kNm ok!
Max. Hog BM -24.60 kNm @ 1.200 m < Allow. BM = 28.50 kNm ok!
Max. Sag Shear Force 51.70 kN @ 1.200 m
Max. Hog Shear Force -51.40 kN @ 4.200 m < Allow. Shear = 71.30 kN ok!
Max. Sag Deflection 5.70 mm @ 2.700 m
< Allow. δ = L/270 = 11.11 mm ok!
Max. Hog Deflection 0.00 mm @ 1.200 m

Max Reaction = Max Leg Load = 92.80 kN


Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-18 Page : 7 of 10 By .
. . . .

T225 BEAM RESULTS (Based On Beam Pal Software)


Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-18 Page : 8 of 10 Revision .
. .

ISCHEBECK TITAN IS NOT SUPPLYING AND IS NOT RESPOSIBLE FOR


PLYWOOD. THIS IS ONLY FOR CLIENT'S REFERENCE.

Plywood Design Calculations


Assuming use of 18mm Wisaform Special Birch 13 Ply Plywood overlaid
Or other plywood of similar structural properties.

Bending stiffness EI = 3.28 kNm2/m


Moment of resistance fZ = 0.782 kNm/m
Shear capacity qA = 16.55 kN/m

(Properties taken from Formwork - a guide to good practice 2nd edition, Appendix G, Table G-W)

Width of waler greater than 38mm = B = 80 mm

Thickness of Plywood = t = 18 mm

For waling width greater than ply thickness t x 2, use loading case 58.
(Ref.: Formwork - a guide to good practice 3rd edition, Appendix B)

Maximum bending moment = 0.095 x Pmax x L2

Hence, 0.489 = 0.095 x 15.250 x L2

= 0.345 kN/m < 0.489 kN/m OK

Therefore, L = 735 mm

Use: L = 488 mm ; to limit deflection

Check shear of plywood: S = 0.525 x (L - B - t ) x (Pmax x L)


L
S = 3.12 kN/m < 16.55 kN/m OK

Check deflection of plywood: δ = 0.0066 x Pmax x L4


EI

δ = 1.74 mm < Span / 270 = 1.81 mm OK


Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-2018 Page : 9 of 10 By .
. .

Titan Loading Data:-


Client: United Engg. Construction Project: DU18 032 Calculation Sht. Revision
Site: Deira Mall Dwg No. 0001-00 Revision .
Area: First Floor Slab & Beam Support Tables By : J. I. Date: -
Date: 23-Jul-2018 Page : 10 of 10 By .
. . .

Titan Beam Properties:-

Titan S150, Titan T150 & T225 Aluminium Beams Properties:-

S150 Beam T150 Beam T225 Beam


2 2 2
Area 12.48 cm 18.6 cm 32.63 cm
4 4 4
Ixx Moment of Interia 364.0 cm 596.9 cm 2241 cm
3 3 3
Zxx Section Modulus 47.25 cm 77.31 cm 199.2 cm
2 2 2
E Modulus of Elasticity 68900 N/mm 68900 N/mm 68900 N/mm
2 2 2
E.I Bending Stiffness 251.0 kNm 411 kNm 1544 kNm
W Weight 3.36 kg/m 5.63 kg/m 8.87 kg/m
M Resistent Moment 6.8 kNm 11.9 kNm 28.5 kNm
S Allowable Shear Force 30 kN 30 kN 71.3 kN

You might also like