5320

DEEP SEA ELECT RONICS J1939 ENABLED


AUTO MAINS
FAILURE MODULE
UL508 Issue 1
pending 02/12/03 AM
F EAT URES DESCRIPT ION
The Model 5320 is an Automatic Mains
Failure Control Module. The module is
 CANBus option to connect used to monitor a mains supply and
to the industry standard SAE automatically start a standby generator set.
J1939‘ Ecofr i
endl y’engine The module also provides indication of
management systems providing operational status and fault conditions,
engine protection and automatically shutting down the genset and
instrumentation without requiring indicating failures by means of an LCD
additional senders. display, and appropriate flashing LED on
 Comprehensive remote the front panel.
communication via optional Selected timers and alarms can be altered
RS232 port. Provides RS232 by the customer from the front panel.
Modem link to PC via either PSTN Alterations to the system are made using SPECIFICATION
line or GSM network (using a the 810 interface and a PC. This interface
suitable modem). The module can also provides real time diagnostic facilities. DC Supply:
also signal Engineers via their cell 8 to 35 V Continuous.
It is also possible to monitor the operation
phones using the GSM SMS Cranking Dropouts:
of the system either locally or remotely.
messaging system to advise of
(Optional: Remote Communications output Able to survive 0 V for 50 mS, providing
system alarms.
versions only). supply was at least 10 V before dropout
 Opt i
onalRS485‘ Modbus’out put. and supply recovers to 5V. This is
Easy push button control
Using industry standard achieved without the need for internal
Operation of the module is via pushbutton
communication protocol allows batteries.
controls (with security locking facility)
full system integration into new
mounted on the front panel with Max. Operating Current:
and existing building
STOP/RESET, AUTO, MANUAL and 12V–400mA
management and control
START pushbuttons. The first three 24V–200mA
schemes.
pus hbuttons f eat ure LED ‘ selec ted’
 Engine diagnostic information indications. Further pushbuttons provide Sleep Mode Current:
removes the need for both service LCD DISPLAY SCROLL, LAMP TEST and 12V–70mA
equipment and cryptic diagnostic MUTE functions. 24V–45mA
lamp (when using J1939 option Microprocessor control Standby Current (when in auto):
with J1939 engines). The module features 16-Bit microprocessor 12V–230mA
 LCD 4-line text based display to control and a comprehensive list of timers 24V–120mA
provi de‘at-a-glance’di agnosisof and pre-configured sequences. This
fault conditions, instrumentation allows demanding specifications to be Auxiliary Outputs 1-3:
and operating state. achieved. Relay outputs -5A DC at supply voltage.
Switches to battery negative when active.
 Comprehensive PC configuration The 5320 module provides a four-line text
and status monitoring using 5xxx LCD display with the following Auxiliary Outputs 4 & 5:
PC software. instrumentation displays, accessed via the 8 Amp AC rated volts-free relay
LCD DISPLAY SCROLL push-buttons:
 PIN number protected front panel Dimensions:
programming of selected trip Generator Instruments: 220mm x 160mm x 49mm
points and timers, allows field Volts, Hz, Amps, kW, kVA, cosθ (8.
7’’x6.
3’’x2’

)
changes to be made to the Engine Instruments: Operating Temperature Range:
module settings. RPM, Oil Pressure, Coolant Temperature, -30 to +70°C
 Built in exercise timer. Hours Run, Charging voltage, battery
Volts. Engine ECU interface:
 ‘
Sleepmode’t oensurever yl ow
SAE J1939: Enhanced instrumentation
battery power usage when in SAE J1939 CANbus
and Engine ECU diagnostics via industry
“Off”mode.
standard SAE J1939 interface when used
 Multiple LCD languages (English, in conjunction with J1939 engine ECU.
French, Spanish, German etc.) Mains/Utility Instruments:
possible. Volts, Frequency.
 Automatic and Manual operation
modes. Deep Sea Electronics reserve the right
to change specification without notice.
 Six configurable auxiliary inputs
for connection to external fault Deep Sea Electronics Plc. Deep Sea Electronics inc.
detection equipment. Highfield House, Hunmanby Industrial Estate, 5301E.St ateSt .–Sui te202
North Yorkshire. YO14 0PH. Rockford, Illinois 61108
 Three configurable outputs to
ENGLAND U.S.A.
help produce complex Tel:+44 (0)1723 890099. Phone: +1 (815) 316-8706
applications. Fax: +44 (0)1723 893303. Fax: +1 (815) 316-8708
 Integral load switch control Email: sales@deepseaplc.com Email: dsesales@deepseausa.com
Web: www.deepseaplc.com Web: www.deepseausa.com
capability.
DIMENSIONS

172mm [6 3/4"]
57mm [2 1/4"] 240mm [9 1/2"]

Panel cut
out220mm x160mm (
8.7”x6.
3”)
T YPICAL CONNECT IONS