ROUTINE TEST RESULTS/REPORT


FOR 5 KVA 3 PHASE 415V / 190V DRY TYPEDISTRIBUTION TRANSFORMER Spec. No. EDTS-366, REV-NIL.

1. Visual inspection &Dimensional Checks: (as per Clause 10.12&10.10.1 SN 1);


TXR. Sr. Nos.: _________________________

a) Visual inspection:
Description Specified Value Observation
Marking Data As per Clause 9.1
Danger Notice plate As per IS :2551-1962

Connection Diagram Plate As per Clause 9.1.6 Anodized aluminum plate showing
connection diagram
Bill of material As per Annexure-A of RCF Specification
Compliance of other clauses of As per clause 10.12.1
Specification

b) Dimensional Checks
Description Specified value as
per Drg. No.
CC71510 (in mm)
Dimensions Length 600
Width 527
Height 480
Sheet Thickness 2mm
Mounting Length 490
Holes Pitch Breadth 350
Elliptical hole Front 14 x 20
Back 20 x 14
Cable Entry Dia/ Nos. Ø 22.3 /2 Nos.
Holes Suitable for PG16
Crimping Primary & Secondary EDTS200+
Socket or EDTS-201
Approved make
Connecting size 4mm/6mm
Lead Cable BS 6195
FRP/SMC Board Terminal Arrangements, Terminal Strips metric fasteners and tightness, their sizes and placements have been
checked as per drawing no. CC71510 and found OK

2) Measurement of Winding Resistance: (as per Clause 10.10.1.SN.2/ & 16.2of IS 2026 Pt-I)
Ambient Temp.(t):
Winding. Resistance P Delta & S Star Connected (mili-ohms)
Sr. No.
Primary
Coil 1U-1V Δ Connected
Primary
Coil 1V-1W Δ Connected
Primary
Coil 1W-1U Δ Connected
Secondary
Coil 2U-2N Υ Connected
Secondary
Coil 2V-2N Υ Connected
Secondary
Coil 2W-2N Υ Connected

-1-
`

3) Measurement of voltage ratio and check of voltage vector relationship: (as per Clause 10.10.1/SN.3/ & 16.3 of IS: 2026 Pt-I)

S. Nos.
Primary
Voltage
Average
Secondary
Voltage
Average
Voltage
Ratio (P/S)
Specified:
2.1842 + 0.5%

Voltage vector relationship: Checked for DY11 and found okay.

4) Measurement of Load Loss and No Load Loss at 75oC

Full Load Loss (W)


Full Load Loss At 75° (W)
No Load Loss At 75° (W)

5) Measurement of and current at 75℃: Ambient Temp.: °C (as per clause 10.10.1/SN 5/& 16.5 of IS: 2026 PT-I)

Average Input
Voltage (V)
Average Input
Current (A)

6) Measurement of Insulation Resistance Test: (as per Clause 10.10.1/SN 6/& 16.6 of IS: 2026 PT-I)
Checked between Primary to Ground, Secondary to ground, and Primary to Secondary and found greater than 500MΩ

7) Dielectric Test: (as per Clause 10.10.1/SN 7/& 16.7 of IS: 2026(PT-I) and clause 10.13)
Applied 5KV for 1 minute between Primary & ground, Secondary & ground, and Primary & Secondary AND WITHSTOOD

8) Induced over voltage withstand test: (as per Clause 10.10.1/SN 8/& 11.1 & 11.2 of IS: 2026 (PT-III)
a) Applied 415-830V/100Hz for 0-15 seconds between Primary Terminals and WITHSTOOD
b) Applied 190-380V/100Hz for 0-15 seconds between Secondary Terminals and WITHSTOOD

10) Measurement of zero sequence Impedance (ZS) In Y sec. RYB shortened, V applied between RYB & N and A measured
S.no S.no S.no S.no S.no
A V ZS* A V ZS* A V ZS* A V ZS* A V ZS*

*ZS = 3×V/A

15) Efficiency test at one forth, half, three forth and full load at 75℃: (to be computed from load loss test at Sr. No. 4)
Output = 5000 VA
T.Losses= No Load Loss + Load Loss Input = output+ losses Efficiency(%) = OP/IP × 100
S.no.
T. L.
¾
½
¼

Tested By_____________ Checked By_________