You are on page 1of 6

Worldwide

www.tyco-fire.com
Contacts

Resilient-Seated Gate Valves


Outside Screw and Yoke

General NOTICE
Never remove any piping component
Description nor correct or modify any piping defi-
ciencies without first de-pressurizing
TYCO Resilient-Seated Gate Valves and draining the system. Failure to do
are used in Fire Protection Systems so may result in serious personal inju-
for on/off operation. End connection ry, property damage, and/or impaired
configurations including Flange by device performance.
Flange, Flange by Groove, and Groove
by Groove are available. It is the designer’s responsibility to se-
lect products suitable for the intended
The ductile Iron body weighs approxi- service and to ensure that pressure
mately 50% less than conventional ratings and performance data are not
cast iron valves, which allows easier exceeded. Material and gasket selec-
handling on site and reduced shipping tion should be verified for compatibili-
costs. ty with the specific application. Always
The fully encapsulated EPDM duc- read and understand the installation
tile iron Wedge ensures bubble-tight instructions.
sealing.
Valve components are either inher-
TYCO Gate Valves described here-
in must be installed and maintained Technical
ently corrosion-resistant or protected
with fusion-bonded epoxy resin coat-
in compliance with this document, in
addition to the standards of any other
Data
ing for a long, dependable service life authorities having jurisdiction. Failure Sizes
and enhanced UV protection in ex- to do so may result in serious person- 2˝ (DN50), 2-1/2˝ (DN65), 3˝ (DN80),
posed installations. al injury or impair the performance of 4˝ (DN100), 6˝ (DN150), 8˝ (DN200),
these devices. 10˝ (DN250), and 12˝ (DN300)
This valve is one of the lightest, most
durable gate valves on the market to- The owner is responsible for maintain- Approvals
day. Its design features and material ing their mechanical system and de-
selection criteria fulfill the need for a vices in proper operating condition. UL Listed
dependable, long life and easy to op- The installing contractor or device FM Approved
erate gate valve. manufacturer should be contacted Maximum Working Pressure
with any questions.
UL - 300 psi (20,87 bar)
FM - 232 psi (16 bar)
Flanges
ASME B16.1/ASME B16.42
EN 1092-2/ISO 7005-2
Drilled to ANSI 125/150 or PN10/PN16
Materials of Construction
See valve parts list, Figure 1.

Page 1 of 6 NOVEMBER 2012 TFP1540


TFP1540
Page 2 of 6

15
14
16
17
12
9
NO. DESCRIPTION QTY. MATERIAL
10 1 Wedge . . . . . . . . . . . . . 1 EPDM Coated Ductile Iron
22
2 Wedge Nut . . . . . . . . . . 1 Bronze
11 3 Stem Pin . . . . . . . . . . . 1 Stainless Steel
17
4 Sealing Gasket . . . . . . 1 EPDM
13 5 Sealing O-Ring . . . . . . 3 NBR
13
6 Stem Guide . . . . . . . . . 1 Bronze
9 7 Stem O-Ring . . . . . . . . 2 NBR
8
8 Compression Washer . . 1 Stainless Steel
19 9 Top Gland . . . . . . . . . . 1 FBE Coated Ductile Iron
7 10 Washers . . . . . . . . . . . 2 Bronze
20 11 Top Nut . . . . . . . . . . . . 2 Bronze
6
12 Handwheel . . . . . . . . . . 1 FBE Coated Ductile Iron
18 18 13 Yoke . . . . . . . . . . . . . . 1 FBE Coated Ductile Iron
4 5 14 Stem . . . . . . . . . . . . . . 1 Stainless Steel
14 15 Gland Stud . . . . . . . . . . 2 Zinc Coated Carbon Steel
21
16 Gland Hex Nut . . . . . . . 2 Zinc Coated Carbon Steel
3 17 Flat Washer . . . . . . . . . 4 Zinc Coated Carbon Steel
18 Bonnet . . . . . . . . . . . . . 1 FBE Coated Ductile Iron
2 19 Screw Grouting . . . . . . 1 Activated Resin
20 Bonnet Screw . . . . . . . 4 Black Oxide Carbon Steel
1 21 Body . . . . . . . . . . . . . . . 1 FBE Coated Ductile Iron
22 Yoke Hex Nut . . . . . . . . 2 Zinc Coated Carbon Steel

FIGURE 1
OUTSIDE SCREW AND YOKE GATE VALVE
ASSEMBLY

Installation The owner is responsible for the in-


spection, testing, and maintenance of
The valve should never be forced to
seat by applying a wrench or exten-
In piping systems, TYCO Resilient- their fire protection system and devic- sion to the Handwheel (12), as it may
Seated Gate Valves should be locat- es in compliance with this document, distort the valve components or score
ed where operation, inspection, and as well as with the applicable stan- the sealing surfaces. All replacement
maintenance are readily accessible. dards of the National Fire Protection parts must be obtained from the man-
Association (e.g., NFPA 25), in addition ufacturer to assure proper operation
Care and to the standards of any authority hav-
ing jurisdiction. The installing contrac-
of the valve.
At initial valve installation the Gland
Maintenance tor or product manufacturer should be
contacted relative to any questions.
Hex Nuts (16) should be left only fin-
ger tight to allow the Gland (9) to re-
The TYCO Resilient-Seated Gate Any impairments must be immediately main in a relaxed state during nor-
Valves must be maintained and ser- corrected. mal valve operation. For applications
viced in accordance with this section.
Automatic sprinkler systems are rec- where the valve is subject to vibration,
Before closing a fire protection system ommended to be inspected, tested, a non-hardening thread sealant may
main control valve for maintenance and maintained by a qualified Inspec- be applied to the Gland Hex Nuts (16)
work on the fire protection system that tion Service in accordance with local to prevent self-loosening and subse-
it controls, obtain permission to shut requirements and/or national codes. quent disengagement of the Gland (9).
down the affected fire protection sys-
See Figure 1 for valve components If leakage past the Sealing O-Rings (5)
tem from the proper authorities and
referenced in this section. occurs, evenly tighten the Gland Hex
notify all personnel who may be af-
Nuts (16) until the leakage ceases.
fected by this decision. Debris lodged in the sealing area of
the Wedge (1) may cause the valve
After placing a fire protection system
to close hard. Backing off the Hand-
in service, notify the proper authorities
wheel (12) and closing it again, sever-
and advise those responsible for mon-
al times if necessary, can correct this
itoring proprietary and/or central sta-
problem.
tion alarms.
TFP1540
Page 3 of 6

OPEN

SHUT

CL1

CL2

L L L
FLANGE x FLANGE FLANGE x GROOVE GROOVE x GROOVE

Nominal Nominal
Nominal Nominal Dimensions
Valve Handwheel Approx. Approx. Approx.
Pipe Size Inches (mm)
Size Turns Weight Weight Weight
to Fully FxF FxG GxG
ANSI O.D. Operate Lbs. Lbs. Lbs.
Inches Inches L CL1 CL2 (Open or (kg) (kg) (kg)
DN (mm) Shut)
2 2.375 7.00 15.55 13.07 29.8 27.6 25.4
13
DN50 (60,3) (178) (395) (332) (13,5) (12,5) (11,5)
2-1/2 2.875 7.50 16.14 13.31 35.3 30.9 26.5
16
DN65 (73,0) (190) (410) (338) (16) (14) (12)
– 3.000 7.50 16.14 13.31 30.9 26.5
16 —
DN65 (76,1) (190) (410) (338) (14) (12)
3 3.500 8.00 18.9 14.96 41.9 36.4 30.9
20
DN80 (88,9) (203) (480) (380) (19) (16.5) (14)
4 4.500 9.00 22.56 17.72 57.3 50.7 44.1
20
DN100 (114,3) (229) (573) (450) (26) (23) (20)
– 6.500 10.50 29.53 23.31 88.2 79.4
25 —
DN150 (165,1) (267) (750) (592) (40) (36)
6 6.625 10.50 29.53 23.31 97.0 88.2 79.4
25
DN150 (168,3) (267) (750) (592) (44) (40) (36)
8 8.625 11.50 37.64 29.45 154.4 143.3 110.3
34
DN200 (219,1) (292) (956) (748) (70) (65) (50)
10 10.750 13.00 46.26 34.96 264.6 242.6 220.5
42
DN250 (273,1) (330) (1175) (888) (120) (110) (100)
12 12.750 14.00 51.89 39.57 330.8 297.7 275.6
50
DN300 (323,9) (356) (1318) (1005) (150) (135) (125)
FIGURE 2
OUTSIDE SCREW AND YOKE GATE VALVE
NOMINAL DIMENSIONS
TFP1540
Page 4 of 6

Nominal Nominal Dimensions in Inches (mm)


Valve Size
ANSI ISO 7005-2
ANSI Class 150 PN16
Inches
DN Dim. Dim. Qty. Dim. Dim. Qty.
A B N A B N
2 4.75 0.75 4.92 0.75 Dim. A
4 4 Bolt Circle
DN50 (120,5) (19) (125,0) (19)
Diameter
2-1/2 5.50 0.75 5.71 0.75
4 4
DN65 (139,5) (19) (145,0) (19)
Dim. B
3 6.00 0.75 6.30 0.75 Bolt Hole
4 8
DN80 (152,5) (19) (160,0) (19) Diameter
4 7.50 0.75 7.09 0.75
8 8 Qty. N
DN100 (190,5) (19) (180,0) (19)
Number of
6 9.50 0.88 9.45 0.88 Bolt Holes
8 8
DN150 (241,5) (22) (240,0) (23)
8 11.75 0.88 11.61 0.88
8 12
DN200 (298,5) (22) (295,0) (23)
10 14.25 1.00 13.98 1.13
12 12
DN250 (362,0) (25) (355,0) (28)
12 17.00 1.00 16.14 1.13
12 12
DN300 (432,0) (25) (410,0) (28)

FIGURE 3
GATE VALVE FLANGE
NOMINAL DIMENSIONS

FLOW RATE IN LITRES PER MINUTE (LPM)


(1 GPM = 3.785 LPM)
400 600 800 1000 2000 3000 4000 6000 10000 20000 30000
0.30 0,020
IN POUNDS PER SQUARE INCH (PSI)

NOMINAL PRESSURE DROP IN BAR


NOMINAL PRESSURE DROP

0.20

(1 PSI = 0.06895 BAR)


65)

)
250

300
)

)
100

150

200
50)

80)

0,010
(DN
(DN

(DN

(DN

(DN
(DN

(DN

(DN

0,009
CH

0,008
CH

CH

CH

CH
CH

CH

CH
2 IN

0,007
2 IN

3 IN

IN

IN

0.10
4 IN

6 IN

8 IN
/
2-1

10

12

0.09 0,006
0.08
0.07 0,005

0.06 0,004
0.05
100 200 300 400 600 800 1000 2000 3000 4000 6000 10000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
GATE VALVE FRICTION LOSS
TFP1540
Page 5 of 6

Nominal Nominal Part Number


Valve Size Pipe Size
ANSI O.D. Flange x Flange Flange x Flange Flange x Groove Flange x Groove
Inches Inches Groove x Groove
ANSI Class 150 ISO 7005-2 PN16 ANSI Class 150 ISO 7005-2 PN16
DN (mm)
2 2.375 TMRX-050-000-3 TMRX-050-000-1 TMRT-050-060-3 TMRT-050-060-1 TMRG-050-060-4
DN50 (60,3)
2-1/2 2.875 TMRX-065-000-3 TMRX-065-000-1 TMRT-065-073-3 TMRT-065-073-1 TMRG-065-073-4
DN65 (73,0)
– 3.000 — — TMRT-065-076-3 TMRT-065-076-1 TMRG-065-076-4
DN65 (76,1)
3 3.500 TMRX-080-000-3 TMRX-080-000-1 TMRT-080-089-3 TMRT-080-089-1 TMRG-080-089-4
DN80 (88,9)
4 4.500 TMRX-100-000-3 TMRX-100-000-1 TMRT-100-114-3 TMRT-100-114-1 TMRG-100-114-4
DN100 (114,3)
– 6.500 — — TMRT-150-165-3 TMRT-150-165-1 TMRG-150-165-4
DN150 (165,1)
6 6.625 TMRX-150-000-3 TMRX-150-000-1 TMRT-150-168-3 TMRT-150-168-1 TMRG-150-168-4
DN150 (168,3)
8 8.625 TMRX-200-000-3 TMRX-200-000-1 TMRT-200-219-3 TMRT-200-219-1 TMRG-200-219-4
DN200 (219,1)
10 10.750 TMRX-250-000-3 TMRX-250-000-1 TMRT-250-273-3 TMRT-250-273-1 TMRG-250-273-4
DN250 (273,1)
12 12.750 TMRX-300-000-3 TMRX-300-000-1 TMRT-300-324-3 TMRT-300-324-1 TMRG-300-324-4
DN300 (323,9)
TABLE A
OUTSIDE SCREW AND YOKE GATE VALVE
PART NUMBERS

Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name and Part
Number (P/N). Refer to Table A for a
complete list of part numbers.
TFP1540
Page 6 of 6

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright © 2012 Tyco Fire Products, LP. All rights reserved.

You might also like