DETERMINACIÓN DEL REFUERZO TRANSVERSAL

Pu = 20.00 Ton f'c = 210.00 kg/cm2 SECCIÓN


Vu = 17.00 Ton As = 95.28 cm2
Ag = 1350.00 cm2
r libre = 4.00 cm Estribos 3
H= 3.30 m ∅= 0.95 cm (3/8") 30 cm
Fy = 4200 kg/cm2 A est = 0.71 cm2
#Varilla: 4 Y
∅= 1.27 cm (1/2") 45 cm
X
A varilla: 7.94 cm2
r= 5.59 cm

�_𝑢<2𝐹_𝑅 𝑏𝑑√(𝑓_𝑐^∗ ) �_𝑢>𝐴_𝑔 𝑓_𝑐^′/10

Vu < 27.88 Ton Ok Pu > 28.35 Ton No aplica

Columna de primer nivel


Zona de confinamiento Separación de Estribos
b máx 0.45 m bmin/4 7.50 cm
Superior H/6 0.55 m Ss 6db 25.00 cm
600 mm 0.60 m 100 mm 10.00 cm
850 db/√fy 16.66 cm Zs
ss
Central Zona Central 1.05 m Sc 48∅ estribo 45.60 cm
b mín/2 15.00 cm
Inferior L/2 1.65 m Si bmin/4 7.50 cm

sc
S < 15 cm 135°

Zc

min > 6Ø estr


> 80 mm S < 35cm

si
Zi
Sx = 11.28 cm Ok
Sy = 6.28 cm Ok
gancho = 8.00 cm

REVISIÓN DEL CORTANTE

�_𝑢<𝐹_𝑅 (0.7𝑓_𝑐^∗ 𝐴_𝑔+2000𝐴_𝑠)


�_𝑢<𝐹_𝑅 (0.7𝑓_𝑐^∗ 𝐴_𝑔+2000𝐴_𝑠) Vu = 50.00 Ton

Fr = 0.7
Pu = 244.52 T Ok

ρ= 0.024
𝑠𝑖 �<0.015 𝑠𝑖 �≥0.015
VCR = 5.70 Ton
�_𝐶𝑅= 𝐹_𝑅 𝑏𝑑(0.2+20�) √(𝑓_𝑐^∗ ) �_𝐶𝑅=0.5𝐹_𝑅
𝑏𝑑√(𝑓_𝑐^∗ )

1+0.007∗�_𝑢/
Factor = 1.1037037037 𝐴_𝑔

VCR = 6.29 Ton


VSR = 43.71 Ton
Fyh = 4200.00 kg/cm2
Ash = 2.84
𝑠=(𝐹_𝑅 𝐴_𝑣 𝑓_𝑦
𝑑(𝑆𝑒𝑛𝜃+𝑐𝑜𝑠𝜃))/�_𝑆𝑅

s= 5.33 cm

17.00 Ton

Zs 7.50 cm
ss

15.00 cm
sc

Zc

si
7.50 cm
Zi
17.00 Ton
Zs
ss

sc

Zc

si
Zi
17.00 Ton

17.00 Ton
N° Varilla Diámetro Área Peso
pulg cm cm2 kg/m
2 1/ 4 0.64 0.32 0.248
2.5 5/16 0.79 0.49 0.388
3 3/ 8 0.95 0.71 0.56 Grado 30
4 1/ 2 1.27 1.27 0.994 Grado 42
5 5/ 8 1.59 1.99 1.552 Grado 52
6 3/ 4 1.91 2.85 2.235
8 1 2.54 5.07 3.973
10 1 1/ 4 3.18 7.94 6.225
12 1 1/ 2 3.81 11.40 8.938

Tabla 4.5 Recubrimiento mínimo requerido (mm)


N° Varilla 150 200 250 300 400 500 600 700
A1 30 25 25 20 20 20 15 15 2
A2 50 40 35 30 25 25 20 20 3
B1 65 50 40 35 30 30 25 25 4
B2 - - 50 45 40 35 30 30 5
c - - - - - 70 65 60 6
Fuente: Reglamento de Construcciones para el distrito federal