COMPRESSOR MOTOR
AND COMPONENT
INFORMATION
Start Winding
of single phase motors, each distinctly different from Line 2
Main Winding
Identified Conductor
the others. Each type of motor may have two to four (115 Volt Only - Neutral) S
different configurations depending on the compres-
Ground
sor components.
Compressor - Unit
Ground R
A. Resistance Start—Induction Run (RSIR) PTC Relay
This motor, also known as a split-phase motor, is
Figure 3-2. RSIR motor diagram with wired-in
used on many small hermetic compressors up PTC relay.
through 1/3 HP. The motor has low starting torque
and must be applied to completely self-equalizing
capillary tube systems such as household refrigera- B. Capacitor Start—Induction Run (CSIR)
tors, freezers, small water coolers, and dehumidifi-
The CSIR motor is similar to RSIR except a start
ers. This motor has a high resistance start winding
capacitor is included in series with start winding to
which is not designed to remain in the circuit after
produce a higher starting torque. This is commonly
the motor has come up to speed. A relay is necessary
used on commercial refrigeration systems through
to perform the function of disconnecting the start
3/4 HP. Two types of relays are used with this
winding as the motor comes up to design speed.
motor:
Three types of relays are used with this motor:
• a current relay, or
• a current relay,
• a potential relay.
• a wired-in Positive Temperature Coefficient
(PTC) relay, or
External Thermal
• a module Positive Temperature Coefficient Control
Protector
Line 1 C
(PTC).
Start Winding
Main Winding
External Thermal
Protector
Control C
Relay - Current
Start Winding
S
Main Winding
Line 2
Line 1
Relay - Current R
S
Ground
Line 2
Compressor - Unit
R Ground
Ground
Figure 3-3. CSIR motor diagram.
Compressor - Unit
Ground
16 Chapter 3
A LOOK AT SERVICE SAFETY
C. Capacitor Start and Run (CSR) This motor may use either:
This motor arrangement uses a start capacitor and a • an external thermal protector, or
run capacitor in parallel with each other and in
series with the motor start winding. This motor has • an internal thermal protector.
high starting torque, runs efficiently, and is used on PSC motors are basically air conditioning compres-
many refrigeration and air conditioning applications sor motors and are very common up through 5 HP.
through 5 HP. A potential relay removes the start
External or Internal
capacitor from the circuit after the motor is up to Thermal Protector
speed. This motor may use either: Control
Line 1 C
Start Winding
Main Winding
• an external thermal protector, or Line 2
• an internal thermal protector. S
Ground
Potential
Ground
Compressor -
Unit Ground S
R
Thermal Protector
Line 1 C
Plug-In C
Start Winding
Main Winding
Figure 3-4. CSR motor diagram. Run Capacitor
C2 S
PTC
C1 Relay
Main Winding
Line 2 • Unequalized system pressure: Head and suc-
S tion pressures must be equal and not more than
Ground 170 psig. Refrigeration metering device (cap
Compressor - R tube or TX valve) should equalize system pres-
Unit Ground sures within 3 minutes. Unequal system pres-
Run Capacitor
sure may be caused by excessive refrigerant
Figure 3-7. Circuit diagram for PSC compressors. charge, short cycling thermostat, or system
restriction.
• Circuit breaker or fuse trips: Branch circuit
To fully realize the capabilities of this simplified type fuses or circuit breakers sized too small will
of compressor motor, it is necessary to understand cause nuisance tripping (see “Fuse and Circuit
its starting and operating characteristics and the Breaker Sizing” on page 36). If the fuse or cir-
field conditions which can affect it. cuit breaker trips, see “Identifying Compressor
Electrical Problems” on page 47 for electrical
The following conditions affect PSC motor starting: troubleshooting techniques.
• Low voltage: Reduces motor starting and run- • Electrical components: A failed run capacitor
ning torque. A 10% voltage drop reduces a will not allow the compressor to start, and it
motor’s starting ability by 19%. Low voltage will trip the thermal protector. See “Identifying
can cause no start, hard start, light flicker, and Compressor Electrical Problems” on page 47
TV screen flip flop. for electrical troubleshooting techniques.
18 Chapter 3
A LOOK AT SERVICE SAFETY
Open Closed
• Currently used on all AH, AB, AV, AG, AW, and most AN and SF
models
• Sense motor current and motor winding temperature or
combination thereof
Internal Line-Break Thermal
• Break line current when tripped
Protectors
• Generally protect against loss of charge
• Will not protect motor if compressor is operated outside its
evaporator temperature range
• Not repairable or replaceable
• Currently used on some AN and SF models
• Employs use of solid state temperature sensors in motor
windings and compressor discharge muffler
• Sensor resistance values change with temperature variations
• Module will interrupt power to the contactor coil when resistance
Line Voltage-Electronic Protection values of sensors exceed the specified range. This power
Module interruption thus stops the compressor motor
(NOTE: For more specific details • Module provides protection against:
consult the authorized wholesaler.) • Abnormal locked rotor conditions
• Loss of refrigerant
• High compressor discharge temperatures
• Excessive current conditions
• Time delays of 3 to 5 minutes occur on power interruption or
sensor trip
20 Chapter 3
A LOOK AT SERVICE SAFETY
B. “AN” Wiring on Typical 230/200 Volt • Terminals M1 and M2 are a normally closed
System with Electronic Protection switch actuated by the motor sensor circuit.
Module Switch contacts are rated at 2.5 amps at 265
The Model AN compressors are available with an volts maximum.
advanced solid state protection system. Sensors are • Do not expose the protection module to pro-
provided in each leg of the compressor motor wind- longed ambient temperature higher then
ings to guard against overloading and single phasing. 150°F.
Additionally, a sensor is in the internal discharge line
to detect excessive discharge gas temperatures. • Module has built-in time delay. Power inter-
ruption or sensor trip will cause 3 to 5 minute
Notes on the compressor electronic protection sys- delay before restart.
tem:
• If sensor circuit trips and motor feels cool,
• The compressor will not run if a jumper is check the return gas temperature. It should not
placed across terminals S and S1. be more than 65°F entering the compressor.
B. “AN” Wiring on Typical 230/200 Volt System with Electronic Protection Module - Continued
24 Volt
Compressor Line Voltage Compressor 2 Speed Motor
Sensors C'Case Heaters Power Connections
Chapter 3
S1 S C1 C2 L1 L2 L3 R1 R2 R3
# 14 Min.
# 14 Min.
Electronic Protection Module
M1
Contactor T1 T2 T3
Coil
Control Line
M2
15AA1104C
S S1
L1 L2 L3
T1 T2
To
Control
Circuit
Contactor
# 14 Min. 230/200-60-3
Figure 3-12. “AN” wiring on typical 230/200 volt system with electronic protection module.
C. “AN” Wiring on Typical 460 Volt System with Electronic Protection Module
To Contactor Coil
M1
T1 T2 T3
Control Line
M2 T1
15AA1104C
S S1
230V
L1 L2 L3
T2
To
Control
Circuit
230V 460V *Contactor
23
Min. Min.
Capacity
Model Voltage RLA LRA Cond. Cont.*
BTU/HR Size Size
T1 T2 T3
AN5590G/H 230/200-60-3 92,500 27 172 #8 TW 40 A
Black Tie
Contactor
Compressor Motor and Component Information
T1 T2 T3
Crankcase Heaters
L1 L2 L3
To Control Circuit
Figure 3-15. Small terminal block wiring on typical system with thermal protector.
26
Texas Line
Instruments Tecumseh Circuit Control Circuit
Parts Part T1, T2, M1, M2,
Number Number V.A.C., V.A.C., 1-PH
1-PH
Ground 15AA1104A 90613 24 V.A.C. 24 or 115 or 230 V.A.C.
Contactor Coil
Electronic Protection Module
T1 T2 T3
15AA1104 (See Table 3-6)
M1
24/115/230 V.A.C.
L1 L2 L3
Control Line
M2
2.5A. Max.
S1 S2
T1
To Control Circuit
24 or 120 or 240 V.A.C.
T2
Figure 3-16. Small terminal block wiring on typical system with electronic protection module.
A LOOK AT SERVICE SAFETY
Compressor
Relay Type Characteristics
Motor Type
• Sense starting current to main (run) windings
• Contacts normally open
• Contacts close and then release in less than 1 second
Current Relay RSIR and CSIR as motor starts
• Must be installed vertically since contacts open by
gravity
28 Chapter 3
A LOOK AT SERVICE SAFETY
Potential Type Relay Supplier Code Designations tion, an explanation of the code numbers should be
In recent years, Tecumseh has used an increasing useful in the field.
number of potential relays with hermetic compres- Tecumseh has two major suppliers of potential
sors. A large number of these have been used on air relays: the General Electric Company and the sup-
conditioning applications, but there are also many plier of White Rodgers relays. An explanation of the
other applications. Since there are many variations code designation for relays manufactured by each of
with regard to these relays such as number of termi- these companies is provided in Figures 3-20 and 3-
nals, coil group, hot pick up, and mounting posi- 21.
Example: 3ARR3-A5C3
3ARR3- A 5 C 3
Number of Coil Group Calibration
Potential Relay Mounting
Terminals and (Continuous (Hot Pickup)
Type Position
Bracket Voltage) (Volts)
Example: 128-122-1335CA
Chapter 3
128- 12 2- 13 3 5 C A
Potential Terminals, Coil Group Calibration Customer's
Type of Contact Mounting
Relay Type and (Continuous (Hot Pick Up) Part Number
Bracket Structure Position
Type Location Voltage) (Volts) (To be stamped on relay)
A = 260-280
1 = 130 B = 280-300
2 = 170 C = 300-320
2 = SPNC - less than 1 1/2 HP
3 = 256 D = 320-340
6 = SPNC - 1 1/2 HP and Larger
4 = 336 E = 340-360
5 = 395 F = 350-370
6 = 420 G = 360-380
11 = 3 screw terminal 7 = 495 H = 365-395
12 = 4 screw terminal (seldom used) J = 120-130
13 = 5 screw terminal K = 130-140
23 = 5 quick connect terminals L = 140-150
M = 150-160
P = 170-180
R = 180-190
See note on page 31. S = 190-200
1 = Face down T = 200-220
2 = Face up U = 220-240
3 = Face out - horizontal - numbers upside down V = 240-260
4 = Face out - 90 clockwise from number 3 position W = 210-230
5 = Face out - horizontal - numbers right side up
11 = Flat Bracket remote (Tecumseh) 6 = Face out - 90 counterclockwise from number 3 position
12 = "L" Bracket (Tecumseh)
16 = "L" Bracket for "FB" model compressors
Note: Room temperature calibratio
20 = "L" Bracket for Tecumseh Twins = 1 1/2 HP and larger n is 5 to 7% lower than these values.
21 = "L" Bracket for capacitor box mounting
29 = Flat Bracket (Marion) was "14" (under cover)
NOTE: As noted above, the 4th digit in the code tion.Mounting in any other position can change the
number of G.E. relays and the 7th digit for White relay’s operating characteristics enough so that the
Rodgers relays indicates the position in which the compressor will not start properly. This can result in
relay is to be mounted. It is of utmost importance compressor motor failure.
that the relay be mounted in the required posi-
5 2
4 6 1
1 6 4
1
4
2
5
6
6
5
2
2 5
4
1
20 to 50 MFD + 5 MFD
32 Chapter 3
A LOOK AT SERVICE SAFETY
Compressor
Capacitor Type Characteristics
Motor Type
• Designed to operate for only a few seconds
during start
• Taken out of start winding circuit by relay
• Excessive start capacitor MFD increases
start winding current, increases start winding
temperature, and may reduce start torque
Start Capacitor CSIR and CSR • Capacitors in CSR motors should have
15,000 ohm, 2 watt bleed resistor across
terminals
• Capacitor rated voltage must be equal to or
more than that specified
• Capacitor MFD should not be more than that
specified
Common Common
Start
Run
Run
Spade Type Terminal Pins Spade Type Terminal Pins
S & C Models (1955 to phaseout) AV Models
AK Models
Internal Thermostat
Terminal Pins
Many CL Models
34
A LOOK AT SERVICE SAFETY
Common Start
Common Start
1 Phase 1 Phase
L1 L2
C T1 T2 S 3 Phase 3 Phase
Run L3
1 Phase 3 Phase
R T3
Run
Screw-On Type Terminal Pins Screw-On Type Terminal Pins
AG, AN & SF Models CL Models
24 Volt
Compressor Line Voltage Compressor 2 Speed Motor
Sensors Crankcase Heaters Power Connections
S1 S C1 C2 L1 L2 L3 R1 R2 R3
36 Chapter 3