SAMSUNG Modeling Guide

for Trace 700

V1_102017A
Disclaimer

The information contained in this Trace 700 Modeling Guide and in the
DVM S library file ("Information”) is for informational purposes only and
should not be construed as engineering or other technical advice.
Samsung is under no obligation to update or keep current the
information or to correct any inaccuracies therein. Samsung and its
affiliates, directors, employees and agents expressly disclaim any liability
or responsibility for any loss or damage arising out of the content,
accuracy or appropriateness of the Information or from the use of all or
any part of the Information by any person. You should obtain your own
professional advice and conduct your own independent evaluation with
respect to the subject matter herein. Samsung is not responsible for,
and does not make any assurances regarding, the function or suitability
of Trace 700 Building Energy Analysis Software.

V1_102017A 2
Contents

1. Introduction
2. Program Installation
3. Importing SAMSUNG DVM S Library File
4. System Modeling – Air cooled DVM S

Appendix A Outdoor Unit Specifications


Appendix B Indoor Unit Specifications

V1_102017A 3
1. Introduction

This document aims to provide guidance for building a simulation model when
analyzing annual energy consumption and conservation standard for energy and
environmental design at the design stage of a HVAC system.
It guides through the process of 1) installation of the library file for Samsung DVM
S units and 2) building a DVM S system on Trace 700, which is a building energy
analysis software. Please visit the Trane website
(http://www.trane.com/commercial/north-america/us/en.html) for information
about purchasing a copy of Trace 700 (including instructions).
The library file can be downloaded at https://www.dvmdownload.com/. The
library file includes 181 models of air-cooled heat pump/heat recovery outdoor
units (North American models) and 126 models of the following indoor unit types:
duct, AHU, 1way/4way cassette, wall-mount, ceiling, and floor standing. Each
model was built on the basis of the cooling and heating performance curves
(capacity ratio modifier function of temperature, energy input ratio modifier
function of temperature, part-load ratio correction factors, and piping correction
factors). The rated specifications of the outdoor and indoor units are shown in
Appendix A and Appendix B, respectively.
The results of any simulation are only a guideline and actual system performance
will depend on conditions in addition to the relevant units’ rated specifications. In
order to increase the accuracy of a simulation, it is critical to use measured data
from an actual building and HVAC system. Even if the DVM S system modeling is
carried out per these instructions, Samsung HVAC does not represent or warrant
that system performance will match the simulation results.

V1_102017A 4
2. Program Installation

▪ Download Trace 700 S/W from the web address below:


http://www.trane.com/commercial/north-america/us/en.html
(from the webpage, go to PRODUCTS AND SYSTEMS → Design & Analysis
Tools → Download Center → Software Download Center)

V1_102017A 5
3. Importing SAMSUNG DVM S Library File

1) Run Trace 700, then select “Libraries” tab → “Equipment” → “Cooling”.


2) From "Library / Template Editors" window, select “File” → “Import Custom Library”,
and open the downloaded "Samsung_DVM S_Lib.EXP" file.
3) Close "Library / Template Editors" window.

1)

2)

V1_102017A 6
3. Importing SAMSUNG DVM S Library File

4) Select “Libraries” → “Equipment” → “Cooling” to re-open "Library / Template


Editors" window.
5) Select “Air-cooled unitary” from "Cooling category” drop-down list, and select
"Samsung_DVM S" from "Equipment type” drop-down list.

5)

V1_102017A 7
4. System Modeling – Air cooled DVM S

1) Click "Create Systems” icon in “Project Navigator” window.


2) Select "Selection” tab in "Create Systems" window.
3) Select “All” in “System category” and select “Variable Refrigerant Flow” in System
type.
4) Click Apply.

1)

4)

3)

2)

V1_102017A 8
4. System Modeling – Air cooled DVM S

5) Select "Fans” tab from “Create Systems” window, and select the target system
name from “System description” drop-down list.
6) Select "Samsung Indoor Unit" from “Type” drop-down list, and refer to Appendix B
Indoor Unit Specifications to input “Static Pressure” and “Full Load Energy Rate” of
the target indoor unit. In Trace 700, only one indoor unit can be modeled in one
system. If the target system includes multiple indoor units, the average of full load
energy rate is calculated and input. The calculation method is as follows.

- Target indoor units : AM007FNLDCH X 1ea, AM012FNLDCH X 2ea, AM024FNLDCH X 3ea


- Cooling Capacity : (7500 X 1) + (12000 X 2) + (24000 X 3) = 103500 [BTU/h]
- Average Full Load Energy : {(7500 X 1 X 0.0001664) + (12000 X 2 X 0.0002124) + (24000 X 3 X
0.0002488)} / (103500) = 0.000234 [kW/CFM]

7) Click “Apply” and close the window.

7)

6)

5)

V1_102017A 9
4. System Modeling – Air cooled DVM S

8) Click "Assign Rooms to Systems" icon in “Project Navigator” window.


9) Select target room(s) from “Unassigned Rooms” list, and drag to an appropriate
VRF system to the right.

8)

9)

Drag & Drop

V1_102017A 10
4. System Modeling – Air cooled DVM S

10) Click “Create Plants” icon in "Project Navigator“ window.


11) Drag” Air-cooled Unitary” icon from “Equipment Category” to “Cooling Plants”,
and drag “Electric resistance” icon from “Equipment Category” to “Heating
Plants”.
12) Select a cooling/heating plants and click “Edit” to change the plant name.

10)

11) Drag & Drop

Drag & Drop 12)

V1_102017A 11
4. System Modeling – Air cooled DVM S

13) Select “Cooling Equipment” tab from “Create Plants” window.


14) From “Equipment type” drop-down list, select “Samsung_DVM S”, and, from
“Heat Rejection”’s “Type” drop-down list, select “Included in Compressor Power”.
15) Input “Capacity” and “Energy rate” for cooling mode in the fields for “Cooling”.
Input the values for heating mode in the fields for “Heat recovery”. If “capacity”
value is left blank, the calculated peak load determines the capacity.
16) Click Apply and Close the window.

16)

14)

15)

13)

Note : The VRF Heat Recovery option is able to recover heat from one VRF indoor Unit and share it
with other indoor units that are connected to the same refrigerant circuit. TRACE assumes
that heat can be recovered between all zones that are assigned to the system. However, heat
recovery outdoor units are available only up to a certain capacity (20 tons, as of this writing).
To accurately model VRF heat recovery, the design capacity of all the indoor units (zones)
assigned to the system should be no larger than the available capacity of the VRF heat
Recovery outdoor unit. This might require the creation of several systems and several cooling
plants.
(Refer to “Trace 700 User’s Manual, Building Energy and Economic Analysis version 6.3”)

V1_102017A 12
4. System Modeling – Air cooled DVM S

17) Select “Assign System” icon in "Project Navigator“ window.


18) Drag the cooling system(s) and heating system(s) from “Unassigned system/coils”
box to a respective plant in “Systems and Plants”.

17)

18)
Drag & Drop

V1_102017A 13
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM216KXVGJH/AA 243 15.41 216 17.37 N

AM072FXVAFH2AA 81 4.80 72 4.34 N

AM096FXVAFH2AA 108 6.28 96 5.64 N

AM120FXVAFH2AA 135 8.92 120 8.10 N

AM144FXVAFH2AA 162 11.14 144 10.79 N

AM168HXVAFH2AA 189 13.64 168 13.86 N

AM192HXVAFH2AA 216 16.33 192 16.44 N

AM072FXVAJH2AA 81 4.80 72 4.34 N

AM096FXVAJH2AA 108 6.64 96 6.13 N

AM120FXVAJH2AA 135 8.92 120 8.59 N

AM144FXVAJH2AA 162 11.14 144 10.79 N

AM168HXVAJH2AA 189 13.64 168 13.86 N

AM192HXVAJH2AA 216 16.33 192 16.44 N

AM072KXVTFH/AA 81 4.63 72 4.08 N

AM096KXVTFH/AA 108 6.00 96 5.45 N

AM072KXVTJH/AA 81 4.63 72 4.08 N

AM096KXVTJH/AA 108 6.00 96 5.45 N

V1_102017A 14
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM072FXVAFR2AA 81 4.80 72 4.34 Y

AM096FXVAFR2AA 108 6.28 96 5.64 Y

AM120FXVAFR2AA 135 8.92 120 8.10 Y

AM144FXVAFR2AA 162 11.14 144 10.79 Y

AM168HXVAFR2AA 189 13.64 168 13.86 Y

AM192HXVAFR2AA 216 16.33 192 16.44 Y

AM072FXVAJR2AA 81 4.80 72 4.34 Y

AM096FXVAJR2AA 108 6.64 96 6.13 Y

AM120FXVAJR2AA 135 8.92 120 8.59 Y

AM144FXVAJR2AA 162 11.14 144 10.79 Y

AM168HXVAJR2AA 189 13.64 168 13.86 Y

AM192HXVAJR2AA 216 16.33 192 16.44 Y

AM072KXVTFR/AA 81 4.63 72 4.08 Y

AM096KXVTFR/AA 108 6.00 96 5.45 Y

AM072KXVTJR/AA 81 4.63 72 4.08 Y

AM096KXVTJR/AA 108 6.00 96 5.45 Y

V1_102017A 15
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM038KXWDCH 42600 2.41 38200 2.62 N

AM048KXWDCH 54600 3.1 47800 3.1 N

AM055KXWDCH 61400 3.57 54600 3.76 N

AM072HXWAFR 81000 3.52 72000 3.15 N

AM072HXWAJR 81000 3.52 72000 3.15 N

AM072KXVTFH 81000 5.01 72000 4.45 N

AM072KXVTFR 81000 5.01 72000 4.45 Y

AM072KXVTJH 81000 5.01 72000 4.45 N

AM072KXVTJR 81000 5.01 72000 4.45 Y

AM096HXWAFR 108000 4.79 96000 4.27 N

AM096HXWAJR 108000 4.79 96000 4.27 N

AM096KXVTFH 108000 6.49 96000 5.94 N

AM096KXVTFR 108000 6.49 96000 5.94 Y

AM096KXVTJH 108000 6.49 96000 5.94 N

AM096KXVTJR 108000 6.49 96000 5.94 Y

AM120HXWAFR 135000 8.92 120000 8.1 Y

AM120HXWAJR 135000 8.92 120000 8.59 Y

V1_102017A 16
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM144HXWAFR 162000 11.14 144000 10.79 Y

AM144HXWAJR 162000 11.14 144000 10.79 Y

AM144KXVTFH 162000 10.02 144000 8.9 N

AM144KXVTFR 162000 10.02 144000 8.9 Y

AM144KXVTJH 162000 10.02 144000 8.9 N

AM144KXVTJR 162000 10.02 144000 8.9 Y

AM168HXVAFH 189000 13.64 168000 13.86 N

AM168HXVAFR 189000 13.64 168000 13.86 Y

AM168HXVAJH 189000 13.64 168000 13.86 N

AM168HXVAJR 189000 13.64 168000 13.86 Y

AM168HXWAFR 189000 8.31 168000 7.42 Y

AM168HXWAJR 189000 8.31 168000 7.42 N

AM168KXVTFH 189000 11.5 168000 10.39 N

AM168KXVTFR 189000 11.5 168000 10.39 Y

AM168KXVTJH 189000 11.5 168000 10.39 N

AM168KXVTJR 189000 11.5 168000 10.39 Y

AM192HXVAFH 216000 16.33 192000 16.44 N

V1_102017A 17
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM192HXVAFR 216000 16.33 192000 16.44 Y

AM192HXVAJH 216000 16.33 192000 16.44 N

AM192HXVAJR 216000 16.33 192000 16.44 Y

AM192HXWAFR 216000 13.39 192000 15.2 N

AM192HXWAJR 216000 13.39 192000 15.2 N

AM192KXVTFH 216000 12.98 192000 11.88 N

AM192KXVTFR 216000 12.98 192000 11.88 Y

AM192KXVTJH 216000 12.98 192000 11.88 N

AM192KXVTJR 216000 12.98 192000 11.88 Y

AM216HXWAFR 243000 12.98 216000 12.77 N

AM216HXWAJR 243000 12.28 216000 11.26 N

AM216JXVAFH 243000 15.94 216000 15.13 N

AM216JXVAFR 243000 15.94 216000 15.13 Y

AM216JXVAJH 243000 15.94 216000 15.13 N

AM216JXVAJR 243000 15.94 216000 15.13 Y

AM216KXVGJH 243000 16.44 216000 18.4 N

AM216KXVTFH 243000 15.03 216000 13.35 N

V1_102017A 18
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM216KXVTFR 243000 15.03 216000 13.35 Y

AM216KXVTJH 243000 15.03 216000 13.35 N

AM216KXVTJR 243000 15.03 216000 13.35 Y

AM240HXWAFR 270000 18.44 240000 18.2 Y

AM240HXWAJR 270000 18.44 240000 18.2 Y

AM240JXVAFH 270000 18.44 240000 18.2 N

AM240JXVAFR 270000 18.44 240000 18.2 Y

AM240JXVAJH 270000 18.44 240000 18.2 N

AM240JXVAJR 270000 18.44 240000 18.2 Y

AM240KXVTFH 270000 16.51 240000 14.84 N

AM240KXVTFR 270000 16.51 240000 14.84 Y

AM240KXVTJH 270000 16.51 240000 14.84 N

AM240KXVTJR 270000 16.51 240000 14.84 Y

AM240KXWAFR 270000 13.3 240000 17.56 N

AM240KXWAJR 270000 13.3 240000 17.56 N

AM264HXWAFR 297000 16.91 264000 18.35 Y

AM264HXWAJR 297000 16.91 264000 18.35 N

V1_102017A 19
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM264JXVAFH 297000 21.13 264000 20.78 N

AM264JXVAFR 297000 21.13 264000 20.78 Y

AM264JXVAJH 297000 21.13 264000 20.78 N

AM264JXVAJR 297000 21.13 264000 20.78 Y

AM264KXVTFH 297000 17.99 264000 16.33 N

AM264KXVTFR 297000 17.99 264000 16.33 Y

AM264KXVTJH 297000 17.99 264000 16.33 N

AM264KXVTJR 297000 17.99 264000 16.33 Y

AM288HXWAFR 324000 18.18 288000 19.47 N

AM288HXWAJR 324000 18.18 288000 19.47 N

AM288JXVAFH 324000 22.28 288000 21.58 N

AM288JXVAFR 324000 22.28 288000 21.58 Y

AM288JXVAJH 324000 22.28 288000 21.58 N

AM288JXVAJR 324000 22.28 288000 21.58 Y

AM288KXVTFH 324000 19.47 288000 17.82 N

AM288KXVTFR 324000 19.47 288000 17.82 Y

AM288KXVTJH 324000 19.47 288000 17.82 N

V1_102017A 20
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM288KXVTJR 324000 19.47 288000 17.82 Y

AM312HXWAFR 351000 21.58 312000 23.7 Y

AM312HXWAJR 351000 13.39 312000 15.2 N

AM312JXVAFH 351000 24.78 312000 24.65 N

AM312JXVAFR 351000 24.78 312000 24.65 Y

AM312JXVAJH 351000 24.78 312000 24.65 N

AM312JXVAJR 351000 24.78 312000 24.65 Y

AM336HXWAFR 378000 20.43 336000 21.5 Y

AM336HXWAJR 378000 20.43 336000 21.5 N

AM336JXVAFH 378000 27.28 336000 27.72 N

AM336JXVAFR 378000 27.28 336000 27.72 Y

AM336JXVAJH 378000 27.28 336000 27.72 N

AM336JXVAJR 378000 27.28 336000 27.72 Y

AM360HXWAFR 405000 21.7 360000 22.62 Y

AM360HXWAJR 405000 21.7 360000 22.62 N

AM360JXVAFH 405000 29.97 360000 30.3 N

AM360JXVAFR 405000 29.97 360000 30.3 Y

V1_102017A 21
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM360JXVAFR 405000 29.97 360000 30.3 Y

AM360JXVAJH 405000 29.97 360000 30.3 N

AM360JXVAJR 405000 29.97 360000 30.3 Y

AM384HXWAFR 432000 26.78 384000 30.4 N

AM384HXWAJR 432000 26.78 384000 30.4 N

AM384JXVAFH 432000 32.66 384000 32.88 N

AM384JXVAFR 432000 32.66 384000 32.88 Y

AM384JXVAJH 432000 32.66 384000 32.88 N

AM384JXVAJR 432000 32.66 384000 32.88 Y

AM408HXWAFR 459000 26.37 408000 27.97 N

AM408HXWAJR 459000 25.67 408000 26.46 N

AM408JXVAFH 459000 32.27 408000 31.57 N

AM408JXVAFR 459000 32.27 408000 31.57 Y

AM408JXVAJH 459000 32.27 408000 31.57 N

AM408JXVAJR 459000 32.27 408000 31.57 Y

AM408KXVGJH 459000 32.77 408000 34.84 N

AM432HXWAFR 486000 29.77 432000 32.2 N

V1_102017A 22
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM432JXVAFH 486000 33.42 432000 32.37 N

AM432JXVAFR 486000 33.42 432000 32.37 Y

AM432JXVAJH 486000 33.42 432000 32.37 N

AM432JXVAJR 486000 33.42 432000 32.37 Y

AM432KXVGJH 486000 32.88 432000 36.8 N

AM456HXWAFR 513000 30.3 456000 33.55 N

AM456HXWAJR 513000 30.3 456000 33.55 N

AM456JXVAFH 513000 36.2 456000 35.82 N

AM456JXVAFR 513000 36.2 456000 35.82 Y

AM456JXVAJH 513000 36.2 456000 36.31 N

AM456JXVAJR 513000 36.2 456000 36.31 Y

AM480HXWAFR 540000 31.57 480000 34.67 N

AM480HXWAJR 540000 31.57 480000 34.67 N

AM480JXVAFH 540000 38.42 480000 38.51 N

AM480JXVAFR 540000 38.42 480000 38.51 Y

AM480JXVAJH 540000 38.42 480000 38.51 N

AM480JXVAJR 540000 38.42 480000 38.51 Y

V1_102017A 23
Appendix A Outdoor Unit Specifications

Heating Capacity Heating Cooling Capacity Cooling Heat Recovery


Model
[MBH] [kW] [MBH] [kW] (Y/N)

AM504HXWAFR 567000 34.97 504000 38.9 N

AM504HXWAJR 567000 34.27 504000 37.39 N

AM504JXVAFH 567000 40.92 504000 41.58 N

AM504JXVAFR 567000 40.92 504000 41.58 Y

AM504JXVAJH 567000 40.92 504000 41.58 N

AM504JXVAJR 567000 40.92 504000 41.58 Y

AM528JXVAFH 594000 43.61 528000 44.16 N

AM528JXVAFR 594000 43.61 528000 44.16 Y

AM528JXVAJH 594000 43.61 528000 44.16 N

AM528JXVAJR 594000 43.61 528000 44.16 Y

AM576HXWAFR 648000 40.17 576000 45.6 N

AM576HXWAJR 648000 40.17 576000 45.6 N

V1_102017A 24
Appendix B Indoor Unit Specifications

Cooling Capacity Heating Capacity Max Airflow Fan Power Energy Rate Units Static Pressure
Model
[Btu/h] [Btu/h] [CFM] [W] [kW / CFM] [in. wg]

AM007MNMDCH 7500 8500 318.0 27 0.0000849 0.039

AM009MNMDCH 9500 10500 318.0 27 0.0000849 0.039

AM012MNMDCH 12000 13500 353.0 31 0.0000878 0.039

AM015MNMDCH 15000 17000 388.0 38 0.0000979 0.039

AM018MNMDCH 18000 20000 600.0 80 0.0001333 0.039

AM024MNHDCH 24000 27000 777.0 114 0.0001467 0.205

AM027MNHDCH 27000 30000 812.0 125 0.0001539 0.205

AM030MNHDCH 30000 34000 848.0 132 0.0001557 0.205

AM036MNHDCH 36000 40000 1024.0 165 0.0001611 0.205

AM048MNHDCH 48000 54000 1377.0 272 0.0001975 0.205

AM009FN4DCH 9000 10000 547.4 32 0.0000585 0

AM012FN4DCH 12000 13500 547.4 32 0.0000585 0

AM018FN4DCH 18000 20000 547.4 32 0.0000585 0

AM024FN4DCH 24000 27000 618.0 40 0.0000647 0

AM030FN4DCH 30000 34000 777.0 65 0.0000837 0

AM036FN4DCH 36000 40000 847.6 75 0.0000885 0

AM048FN4DCH 48000 54000 1024.2 95 0.0000928 0

V1_102017A 25
Appendix B Indoor Unit Specifications

Cooling Capacity Heating Capacity Max Airflow Fan Power Energy Rate Units Static Pressure
Model
[Btu/h] [Btu/h] [CFM] [W] [kW / CFM] [in. wg]

AM007FNLDCH 7500 8500 282.5 47 0.0001664 0.04

AM009FNLDCH 9500 10500 317.8 60 0.0001888 0.04

AM012FNLDCH 12000 13500 353.2 75 0.0002124 0.04

AM018FNLDCH 18000 20000 547.4 140 0.0002558 0.04

AM024FNLDCH 24000 27000 582.7 145 0.0002488 0.04

AM030FNLDCH 30000 34000 1094.8 95 0.0000868 0.04

AM036FNLDCH 36000 40000 1200.7 120 0.0000999 0.12

AM048FNLDCH 48000 54000 1342.0 180 0.0001341 0.12

AM024JNHDCH 24000 27000 653.0 82 0.0001256 0.20

AM027JNHDCH 27000 30000 742 91 0.0001226 0.20

AM030JNHDCH 30000 34000 883.0 108 0.0001223 0.20

AM036JNHDCH 36000 40000 954.0 140 0.0001468 0.20

AM048JNHDCH 48000 54000 1236.0 200 0.0001618 0.20

AM054JNHDCH 54000 61400 1413.0 280 0.0001982 0.20

AM036FNHDCH 36000 40,000 988.9 210 0.0002124 0.39

AM048FNHDCH 48000 54,000 1377.3 330 0.0002396 0.39

AM076FNHDCH 76000 85200 2048.3 530 0.0002587 0.59

V1_102017A 26
Appendix B Indoor Unit Specifications

Cooling Capacity Heating Capacity Max Airflow Fan Power Energy Rate Units Static Pressure
Model
[Btu/h] [Btu/h] [CFM] [W] [kW / CFM] [in. wg]

AM096FNHDCH 96000 108000 2542.8 790 0.0003107 0.59

AM012JNZDCH 12000 13500 373.0 64 0.0001716 0.40

AM018JNZDCH 18000 22000 531.0 94 0.0001770 0.40

AM024JNZDCH 24000 27000 706.0 144 0.0002040 0.40

AM030JNZDCH 30000 34000 1053.0 218 0.0002070 0.40

AM036JNZDCH 36000 40000 1053.0 218 0.0002070 0.40

AM048JNZDCH 48000 54000 1410.0 290 0.0002057 0.40

AM054JNZDCH 54000 60000 1603.0 341 0.0002127 0.40

AM060JNZDCH 60000 64000 1768.0 380 0.0002149 0.40

AM072JNZDCH 72000 80000 2110.0 620 0.0002938 0.40

AM007FN1DCH 7500 8500 247.2 40 0.0001618 0

AM009FN1DCH 9500 10500 247.2 45 0.0001820 0

AM012FN1DCH 12000 13500 282.5 50 0.0001770 0

AM005KNNDCH 5000 6000 300.0 18 0.0000600 0

AM007KNNDCH 7500 8700 300.0 18 0.0000600 0

AM009FNNDCH 9500 10500 353.0 24 0.0000680 0

AM012FNNDCH 12000 13500 371.0 28 0.0000755 0

V1_102017A 27
Appendix B Indoor Unit Specifications

Cooling Capacity Heating Capacity Max Airflow Fan Power Energy Rate Units Static Pressure
Model
[Btu/h] [Btu/h] [CFM] [W] [kW / CFM] [in. wg]

AM018FNNDCH 18000 20000 459.0 36 0.0000784 0

AM020FNNDCH 20000 23000 477.0 38 0.0000797 0

AM009KN4DCH 9000 10000 565.1 26 0.0000460 0

AM012KN4DCH 12000 13500 565.1 26 0.0000460 0

AM018KN4DCH 18000 20000 565.1 26 0.0000460 0

AM024KN4DCH 24000 27000 671.0 38 0.0000566 0

AM030KN4DCH 30000 34000 900.6 54 0.0000600 0

AM036KN4DCH 36000 40000 988.9 71 0.0000718 0

AM048KN4DCH 48000 54000 1112.5 91 0.0000818 0

AM007HNQDCH 7500 8500 275.5 37 0.0001343 0

AM009HNQDCH 9500 10500 275.5 37 0.0001343 0

AM012HNQDCH 12000 13500 328.4 45 0.0001370 0

AM018HNQDCH 18000 20000 423.8 55 0.0001298 0

AM020HNQDCH 20000 23000 494.4 57 0.0001153 0

AM024HNQDCH 23200 23800 494.4 60 0.0001214 0

AM018FNCDCH 18000 20000 494.4 72 0.0001456 0

AM024FNCDCH 24000 27000 635.7 80 0.0001258 0

V1_102017A 28
Appendix B Indoor Unit Specifications

Cooling Capacity Heating Capacity Max Airflow Fan Power Energy Rate Units Static Pressure
Model
[Btu/h] [Btu/h] [CFM] [W] [kW / CFM] [in. wg]

AM036JNCDCH 36000 40000 1035.0 92 0.0000889 0

AM048JNCDCH 48000 54000 1286.0 160 0.0001244 0

AM006JNFDCH 6000 6700 175.0 35 0.0002000 0

AM009JNFDCH 9500 10500 250.0 40 0.0001600 0

AM012JNFDCH 12000 13500 350 50 0.0001429 0

AM018JNFDCH 18000 20000 550 110 0.0002000 0

AM024JNFDCH 24000 27000 550.0 110 0.0002000 0

AM006JNGDCH 6000 6700 175.0 35 0.0002000 0

AM009JNGDCH 9500 10500 250.0 40 0.0001600 0

AM012JNGDCH 12000 13500 350 50 0.0001429 0

AM018JNGDCH 18000 20000 550.0 110 0.0002000 0

AM024JNGDCH 24000 27000 550.0 110 0.0002000 0

V1_102017A 29
Appendix B Indoor Unit Specifications

Cooling Capacity Heating Capacity Max Airflow Fan Power Energy Rate Units Static Pressure
Model
[Btu/h] [Btu/h] [CFM] [W] [kW / CFM] [in. wg]

AM005KNNDCH 5,000 6,000 300 18 0.0000600 0

AM006JNFDCH 6000 6700 175.0 35 0.0002000 0

AM006JNGDCH 6000 6700 175.0 35 0.0002000 0

AM007HNQDCH 7500 8500 275.5 37 0.0001343 0

AM007KNNDCH 7500 8700 300.0 18 0.0000600 0

AM009HNQDCH 9500 10500 275.5 37 0.0001343 0

AM009JNFDCH 9500 10500 250.0 40 0.0001600 0

AM009JNGDCH 9500 10500 250.0 40 0.0001600 0

AM009KN4DCH 9000 10000 565.1 26 0.0000460 0

AM012FN4DCH 12000 13500 547.4 32 0.0000585 0

AM012HNQDCH 12000 13500 328.4 45 0.0001370 0

AM012JNFDCH 12000 13500 350.0 50 0.0001429 0

AM012JNGDCH 12000 13500 350.0 50 0.0001429 0

AM012JNZDCH 12000 13500 373.0 64 0.0001716 0.5

AM012KN4DCH 12000 13500 565.1 26 0.0000460 0

AM018HNQDCH 18000 20000 423.8 55 0.0001298 0

AM018JNFDCH 18000 20000 550.0 110 0.0002000 0

V1_102017A 30
Appendix B Indoor Unit Specifications

Cooling Capacity Heating Capacity Max Airflow Fan Power Energy Rate Units Static Pressure
Model
[Btu/h] [Btu/h] [CFM] [W] [kW / CFM] [in. wg]

AM018JNGDCH 18000 20000 550.0 110 0.0002000 0

AM018JNZDCH 18000 22000 531.0 94 0.0001770 0.7

AM018KN4DCH 18000 20000 565.1 26 0.0000460 0

AM020HNQDCH 20000 23000 494.4 57 0.0001153 0

AM024HNQDCH 23200 23800 494.4 60 0.0001214 0

AM024JNFDCH 24000 27000 550.0 110 0.0002000 0

AM024JNGDCH 24000 27000 550.0 110 0.0002000 0

AM024JNHDCH 24,000 27,000 653 82 0.0001256 0.8

AM024JNZDCH 24000 27000 706.0 144 0.0002040 0.7

AM024KN4DCH 24000 27000 671 38 0.0000566 0

AM027JNHDCH 27,000 30,000 742 91 0.0001226 0.8

AM030JNHDCH 30,000 34,000 883.0 108 0.0001223 0.8

AM030JNZDCH 30000 34000 1053.0 218 0.0002070 1

AM030KN4DCH 30000 34000 900.6 54 0.0000600 0

AM036JNCDCH 36000 40,000 1035.0 92 0.0000889 0

AM036JNHDCH 36,000 40,000 954 140 0.0001468 0.8

AM036JNZDCH 36000 40000 1053.0 218 0.0002070 1

V1_102017A 31
Appendix B Indoor Unit Specifications

Cooling Capacity Heating Capacity Max Airflow Fan Power Energy Rate Units Static Pressure
Model
[Btu/h] [Btu/h] [CFM] [W] [kW / CFM] [in. wg]

AM036KN4DCH 36000 40000 988.9 71 0.0000718 0

AM048JNCDCH 48000 54000 1286.0 160 0.0001244 0

AM048JNHDCH 48,000 54,000 1,236 200 0.0001618 0.8

AM048JNZDCH 48000 54000 1410.0 290 0.0002057 1

AM048KN4DCH 48000 54000 1112.5 91 0.0000818 0

AM054JNZDCH 54000 60000 1603.0 341 0.0002127 1

AM060JNZDCH 60000 64000 1768.0 380 0.0002149 1

AM072JNESCH 72000 47000 988.9 360 0.0003641 1.18

AM072JNZDCH 72000 80000 2110.0 620 0.0002938 1

AM076FNHDCH 76800 85200 2048 530 0.0002587 0.98

AM096FNHDCH 96000 108000 2543 790 0.0003107 1.10

AM096JNESCH 96000 59000 1236.1 450 0.0003640 1.18

V1_102017A 32
2017.09
Ver.1.0

Samsung Electronics Co., LTD.